Professional Documents
Culture Documents
Disinfection
50 psi 15 minutes
Standing time is 3
hours or 24 hours
Flush with potable water until clear, fill with water/chlorine solution, stand for (depending upon
designated time, flush with potable water water/chlorine
solution
concentration)
10-foot head of water 15 minutes
5 psi 15 minutes
Record static pressure on hydrant A, then open hydrant B and use pitot tube to
Until pressure
measure flow pressure from hydrant B, measure residual pressure at hydrant A while stabilizes
flowing hydrant B
200 psi or 50 psi above working pressure in excess of 150 psi (whichever is larger) 2 hours
CODE
LEAKAGE PERMITTED OR SECTION
RESULT
REFERENCE
None OPC 312.2
OBC 901.5,
Record residual pressure NFPA 13:
15.2.1.2
OBC 901.5,
N/A NFPA 13:
10.10.2.1
OBC 901.5,
2 quarts per hour per 100
gaskets or joints NFPA 13:
10.10.2.2
List of abbreviations used in this table:
IFGC-International Fuel Gas Code
NFPA-National Fire Protection Association
OBC-Ohio Building Code
OMC-Ohio Mechanical Code
OPC-Ohio Plumbing Code
TBD-To be determined
TYPE OF PIPING SYSTEM TEST OR PROCEDURE REQUIRED TEST PRESSURE OR METHOD TEST DURATION
Ground Source Heat Pump Loops Hydrostatic test (water) 100 psi 30 minutes
Hydrostatic test 1.5 times the max working pressure, not less
than 5 psi. Not to impose a pressure >10 psi on 30 minutes
(water) a connected tank
or
1.5 times the max working pressure, not less
Fuel Oil Pneumatic test (air) than 5 psi. Not to impose a pressure >10 psi on 30 minutes
a connected tank
or
OBC 901.5,
Record residual pressure
NFPA 13: 15.2.1.2
OBC 901.5,
N/A
NFPA 13: 10.10.2.1
2 quarts per hour per 100 gaskets or OBC 901.5,
joints NFPA 13: 10.10.2.2
OBC 901.5,
None
NFPA 13: 16.2.1.10
OBC 901.5,
Alarm received
NFPA 13: 16.2.3.1
OBC 901.5,
Record residual pressures
NFPA 13: 16.2.3.4
OBC 901.5,
1.5 psi
NFPA 13: 16.2.2.1
OBC 901.5,
Record elapsed time & pressure for the
valve to trip and time for water to reach NFPA 13: 16.2.3.2.3
test outlet; ensure alarm received and 7.2.3.3
OMC 1308,
None
NFPA 31: 8.8
OMC 1308,
None
NFPA 31: 8.8
OMC 1308,
None
NFPA 31: 8.8
OMC 301.3,
None
IFGC 406.4
OMC 301.3,
None
IFGC 406.6