Relay Menu Database Introduction
Page 1 of 163

RELAY MENU DATABASE

The MiCOM P340 family covers the following:


P341, P342, P343, P344 & P345 Range of Relays

For more information on the relays covered by this document see the P34x/EN M/I96 and P341/EN M/F74 technical manuals

This version of the Relay Menu Database is specific to the following models

Model number Software number


P341 0360J and 0700J
P342 0360J
P343 0360K
P344 0360K
P345 0360K

For other models / software versions, please contact


Schneider Electric for the relevant information.

Page 1
470234511.xls
Relay Menu Database Introduction
Page 2 of 163

This chapter is split into several sections, these are as follows:


Introduction
Courier & Modbus Database
Data Types
G32_DDB_Lists
G155 Meas. Range
DDB Signals
Events
IEC 60870-5-103

Courier & Modbus Database


This database defines the structure of the relay menu for the courier interface and the front panel user interface. This includes all of the relay
settings and measurements. Datatypes for indexed strings for Courier and the user interface are cross-referenced to the Menu Datatype
Definition section (using a G Number). For all settable cells the setting limits and default value are also defined within this database.

Note: The following labels are used within the database

Label Description Value


V1 Main VT Rating 1 (100/110 V)
V2 Checksynch VT Rating 1 (100/110 V)
V3 NVD VT Rating 1 (100/110 V)
I1 Phase CT Rating 1 or 5 (Setting 0A08)
I2 Earth Fault CT Rating 1 or 5 (Setting 0A0A)
I3 Sensitive CT Rating 1 or 5 (Setting 0A0C)
I4 Mutual CT Rating 1 or 5 (Setting 0A0E)

Data Types
This table defines the datatypes used for Courier and user interface. This section also defines the indexed string setting options for all
interfaces. The datatypes defined within this section are cross-referenced to from the menu Database using a G number.

DDB Signals
This table defines all of the relay internal digital signals (opto inputs, output contacts and protection inputs and outputs). A relay may have up
to 512 internal signals each referenced by a numeric index as shown in this table. This numeric index is used to select a signal for the
commissioning monitor port. It is also used to explicitly define protection events produced by the relay (see the Event Data section of this
Appendix).

Events
This section of the appendix specifies all the event information that can be produced by the relay. It details exactly how each event will be
presented via the Courier and User interfaces.

Page 2
470234511.xls
Relay Menu Database Introduction
Page 3 of 163

IEC 870 Monitor, IEC 870 Control, IEC 870 Generic Measurements & Extended Fault Data
These sections fully define the operation of the IEC 60870-5-103 (VDEW) interface for the relay. They should be read in conjunction with the
relevant section of the SCADA Communications chapter (Px4x/EN SC).

References
Px4x/EN IT - Introduction: User Interface operation and connections to the relay
Px4x/EN SC - Communications: Overview of communication interfaces
Courier User Guide R6512
IEC 60870-5-103 Telecontrol Equipment and Systems – Transmission Protocols –
Companion Standard for the informative interface of Protection Equipment.

Page 3
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 4 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
00 00 SYSTEM DATA * * * * * * *
00 01 Language Indexed String G19 1 English Setting English, Français, Deutsch, Español, Русский 0 3 1 2 * * * * * * *
00 02 Password ASCII Password(4 chars) 4x00001 4x00002 G20 G20 2 AAAA Setting **** 65 90 1 0 * * * * * * *
00 03 Sys Fn Links Binary Flag (8 bits); Indexed Strings 4x00003 G95 G95 1 Setting 0 = latched, 1 = self-reset 1 1 1 2 * * * * * * *
00 04 Description ASCII Text(16 chars) 4x00004 4x00011 G3 G3 8 MiCOM P34* Setting MiCOM P34x 32 163 1 2 * * * * * * * * = 1 for Model 1, 2 for Model 2, 3 for Model 3, 4 for Model 4, 5 for Model 5
00 05 Plant Reference ASCII Text(16 chars) 4x00012 4x00019 G3 G3 8 MiCOM Setting MiCOM 32 163 1 2 * * * * * * *
00 06 Model Number ASCII Text(32 chars) 3x00020 3x00035 G3 G3 16 Model Number Data <Model number> * * * * * * *
00 08 Serial Number ASCII Text(7 chars) 3x00044 3x00051 G3 G3 8 Serial Number Data <Serial number> * * * * * * *
00 09 Frequency Unsigned Integer(8 bits) 4x00020 G1 1 1 50 Setting 50Hz, 60Hz 50 60 10 2 * * * * * * *
00 0A Comms Level Unsigned Integer(16 bits) 2 Data <conformance level displayed> * * * * * * *
00 0B Relay Address Unsigned Integer(16 bits) 255 Setting <Relay address> 0 255 1 1 * * * * * * *
00 0C Plant Status Binary Flag(16 bits) 3x00002 G4 G4 1 Data 16-bit binary setting * * * * * * *
00 0D Control Status Binary Flag(16 bits) 3x00004 G5 G5 1 Data Not used * * * * * * *
00 0E Active Group Unsigned Integer(16 bits) 3x00006 G1 1 Data 1 * * * * * * *
00 0F UNUSED Not used
00 10 CB Trip/Close Indexed String(2) G55 No Operation Command 0 = No Operation, 1 = Trip, 2 = Close 0 2 1 1 * * * * * * * Visible to LCD+Front Port
00 10 CB Trip/Close Indexed String(2) N/A 4x00021 G55 G55 1 No Operation Command 0 = No Operation, 1 = Trip, 2 = Close 0 2 1 1 * * * * * * * Visible to Rear Port
00 11 Software Ref. 1 ASCII Text(16 chars) 3x00052 3x00059 G3 8 Data <Software Ref. 1> * * * * * * *
00 12 Software Ref 2 ASCII Text(16 chars) Data <Software Ref. 1> * * * * * * * Ethernet Card Software Reference, if fitted.
00 20 Opto I/P Status Binary Flag; Indexed String 3x11025 3x11026 G8 G8 2 Data 16-bit binary setting: 0 = energised, 1= de-energised * * * * * * * The original register 30007 is available for opto inputs #1 to #16
00 21 Relay O/P Status Binary Flag; Indexed String 3x00008 3x00009 G9 G9 2 Data 16-bit binary setting: 0 = operated state, 1= non-operated state * * * * * * *
00 22 Alarm Status 1 Binary Flag; Indexed String 3x00011 3x00012 G96 G96 2 Data 32-bit binary setting: 0 = Off, 1 = On * * * * * * *
00 23 UNUSED Not used
00 30 Opto I/P Status Binary Flag; Indexed String 3x11025 3x11026 G8 G8 2 Data 16-bit binary setting: 0 = energised, 1= de-energised * * * * * * * The original register 30007 is available for opto inputs #1 to #16
00 40 Relay O/P Status Binary Flag; Indexed String 3x00008 3x00009 G9 G9 2 Data 16-bit binary setting: 0 = operated state, 1= non-operated state * * * * * * *
00 50 Alarm Status 1 Binary Flag; Indexed String 3x00011 3x00012 G96 G96 2 Data 32-bit binary setting: 0 = Off, 1 = On * * * * * * *
00 51 Alarm Status 2 Binary Flag; Indexed String 3x00013 3x00014 G128 G128 2 Data 32-bit binary setting: 0 = Off, 1 = On * * * * * * *
00 52 Alarm Status 3 Binary Flag(32 bits); Indexed String 3x00015 3x00016 G228 G228 2 Data 32-bit binary setting: 0 = Off, 1 = On * * * * * * *
00 D0 Access Level Unsigned Integer(16 bits) 3x00010 G1 1 Data 0 = Read only, 1 = Read + Execute, 2 = Read + Execute + Edit * * * * * * *
00 D1 Password Control Indexed String 4x00022 G22 G22 1 2 Setting 0 = level 1&2, 1 = level 2, 2 = No passwords required 0 2 1 2 * * * * * * *
00 D2 Password Level 1 ASCII Password(4 chars) 4x00023 4x00024 G20 G20 2 AAAA Setting 4 characters 65 90 1 1 * * * * * * *
00 D3 Password Level 2 ASCII Password(4 chars) 4x00025 4x00026 G20 G20 2 AAAA Setting 4 characters 65 90 1 2 * * * * * * *
01 00 VIEW RECORDS * * * * * * * Previous Modbus addresses in the event and fault records are retained for backward compatibility.
01 01 Select Event Unsigned Integer(16 bits) 4x00100 G1 249 1 0 Setting 0 to 249 step 1 0 249 1 0 Max value is oldest record
01 02 Menu Cell Ref Cell Reference N/A 3x10007 G13 1 (From Record) Data Latched alarm active, Latched alarm inactive, Self reset alarm active, Self reset alarm inactive, Relay contact event, Opto-isolated input event, * * * * * * * Indicates type of event. Previous Modbus address - 3x00107; See Event sheet
01 03 Time & Date IEC870 Time & Date 3x10003 3x10006 G12 4 (From Record) Data From record * * * * * * * Previous Modbus address - 3x00103 to 3x00106
01 04 Event Text Ascii String (32 chars) Data 32 character string * * * * * * * See Event sheet
01 05 Event Value Unsigned Int / Binary Flag (32 bits) 3x10008 3x10009 G27 2 Data 32-bit binary string * * * * * * * Previous addresses - 3x00108 to 3x00109 binary flag for contact, opto, alarm & protection events. Unsigned integers for
maintenance records. Details see Event sheet.
01 06 Select Fault Unsigned Integer (16 bits) 4x00101 G1 4 1 Setting 0 to 4 step 1 0 20 1 2 * * * * * * * Allows Fault Record to be selected
01 40 Faulted Phase Binary Flag (8 Bits) N/A 3x10020 G16 G16 1 Data 8-bit binary string * * * * * * * Previous Modbus address 3x00113. For fault record use only.
01 42 Start Elements1 Binary Flag (32 Bits) N/A 3x10022 3x10023 G84 G84 2 Data 32-bit binary string * * * * * * * Previous Modbus address 3x00114 to 3x00115. For fault record use only.
01 43 Start Elements2 Binary Flag (32 Bits) N/A 3x10024 3x10025 G107 G107 2 Data 32-bit binary string * * * * * * * Previous Modbus address 3x00116 to 3x00117. For fault record use only.
01 44 Start Elements3 Binary Flag (32 Bits) N/A 3x10026 3x10027 G129 G129 2 Data 32-bit binary string * * * * * * * For fault record use only.
01 45 Start Elements4 Binary Flag (32 Bits) N/A 3x10028 3x10029 G131 G131 2 Data 32-bit binary string * * * * * For fault record use only.
01 49 Trip Elements1 Binary Flag (32 Bits) N/A 3x10030 3x10031 G85 G85 2 Data 32-bit binary string * * * * * * * Previous Modbus address 3x00118 to 3x00119. For fault record use only.
01 4A Trip Elements2 Binary Flag (32 Bits) N/A 3x10032 3x10033 G86 G86 2 Data 32-bit binary string * * * * * * * Previous Modbus address 3x00120 to 3x00121. For fault record use only.
01 4B Trip Elements3 Binary Flag (32 Bits) N/A 3x10034 3x10035 G130 G130 2 Data 32-bit binary string * * * * * * * For fault record use only.
01 4C Trip Elements4 Binary Flag (32 Bits) N/A 3x10036 3x10037 G132 G132 2 Data 32-bit binary string * * * * * * *
01 50 Fault Alarms Binary Flag (32 Bits) N/A 3x10038 3x10039 G87 G87 2 Data 32-bit binary string * * * * * * * Previous Modbus address 3x00122 to 3x00123. For fault record use only.
01 51 Fault Alarms 2 Binary Flag (32 Bits) N/A 3x10040 3x10041 G89 G89 2 Data 32-bit binary string * * * * * * *
01 55 Fault Time IEC870 Time & Date 3x10042 3x10045 G12 4 (From Record) Data From record * * * * * * * Previous Modbus address 3x00124 to 3x00127. For fault record use only.
01 57 Active Group Unsigned Integer 3x10046 G1 1 Data <Active group> * * * * * * * Previous Modbus address 3x00128. For fault record use only.
01 59 System Frequency Courier Number (frequency) 3x10047 G30 1 Data <System frequency> * * * * * * * Previous Modbus address 3x00129. For fault record use only.
01 5B Fault Duration Courier Number (time) 3x10048 3x10049 G24 2 Data <Fault duration> * * * * * * * Previous Modbus addresses 3x00130 to 3x00131. For fault record use only.
01 5E CB Operate Time Courier Number (time) 3x10050 G25 1 Data <CB Operate time> * * * * * * * Previous Modbus address 3x00132. For fault record use only.
01 60 Relay Trip Time Courier Number (time) 3x10051 3x10052 G24 2 Data <relay trip time> * * * * * * * Previous Modbus addresses 3x00133 to 3x00134. For fault record use only.
01 62 IA Courier Number (current) 3x10053 3x10054 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00135 to 3x00136. For fault record use only.
IA-1
01 63 IB Courier Number (current) 3x10055 3x10056 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00137 to 3x00138. For fault record use only.
IB-1
01 64 IC Courier Number (current) 3x10057 3x10058 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00139 to 3x00140. For fault record use only.
IC-1
01 65 VAB Courier Number (voltage) 3x10059 3x10060 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00141 to 3x00142. For fault record use only.
01 66 VBC Courier Number (voltage) 3x10061 3x10062 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00143 to 3x00144. For fault record use only.
01 67 VCA Courier Number (voltage) 3x10063 3x10064 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00145 to 3x00146. For fault record use only.
01 68 VAN Courier Number (voltage) 3x10065 3x10066 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00147 to 3x00148. For fault record use only.
01 69 VBN Courier Number (voltage) 3x10067 3x10068 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00149 to 3x00150. For fault record use only.
01 6A VCN Courier Number (voltage) 3x10069 3x10070 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00151 to 3x00152. For fault record use only.
01 70 IA-2 Courier Number (current) 3x10071 3x10072 G24 2 Data Not settable * * * * Previous Modbus addresses 3x00153 to 3x00154. For fault record use only.
01 71 IB-2 Courier Number (current) 3x10073 3x10074 G24 2 Data Not settable * * * * Previous Modbus addresses 3x00155 to 3x00156. For fault record use only.
01 72 IC-2 Courier Number (current) 3x10075 3x10076 G24 2 Data Not settable * * * * Previous Modbus addresses 3x00157 to 3x00158. For fault record use only.
01 80 IA Differential Courier Number (current) 3x10077 3x10078 G24 2 Data Not settable * * * * Previous Modbus addresses 3x00159 to 3x00160. For fault record use only.
01 81 IB Differential Courier Number (current) 3x10079 3x10080 G24 2 Data Not settable * * * * Previous Modbus addresses 3x00161 to 3x00162. For fault record use only.
01 82 IC Differential Courier Number (current) 3x10081 3x10082 G24 2 Data Not settable * * * * Previous Modbus addresses 3x00163 to 3x00164. For fault record use only.
01 83 IA Diff PU Courier Number (current) 3x10164 3x10165 G24 2 Data Not settable * * * *
01 84 IB Diff PU Courier Number (current) 3x10166 3x10167 G24 2 Data Not settable * * * *
01 85 IC Diff PU Courier Number (current) 3x10168 3x10169 G24 2 Data Not settable * * * *
01 86 IA Diff 2H Courier Number (current) 3x10170 3x10171 G24 2 Data Not settable * * * *
01 87 IB Diff 2H Courier Number (current) 3x10172 3x10173 G24 2 Data Not settable * * * *
01 88 IC Diff 2H Courier Number (current) 3x10174 3x10175 G24 2 Data Not settable * * * *
01 89 IA Diff 5H Courier Number (current) 3x10176 3x10177 G24 2 Data Not settable * * * *
01 8A IB Diff 5H Courier Number (current) 3x10178 3x10179 G24 2 Data Not settable * * * *
01 8B IC Diff 5H Courier Number (current) 3x10180 3x10181 G24 2 Data Not settable * * * *
01 90 VN Measured Courier Number (voltage) 3x10083 3x10084 G24 2 Data Not settable * * * * * Previous Modbus addresses 3x00165 to 3x00166. For fault record use only.
VN1 Measured * *
01 92 VN2 Measured Courier Number (voltage) 3x10085 3x10086 G24 2 Data Not settable * * For fault record use only.
01 94 VN Derived Courier Number (voltage) 3x10087 3x10088 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00167 to 3x00168. For fault record use only.
01 96 IN Measured Courier Number (current) 3x10089 3x10090 G24 2 Data Not settable * * * * * * Previous Modbus addresses 3x00169 to 3x00170. For fault record use only.
IN Derived *
01 99 I Sensitive Courier Number (current) 3x10091 3x10092 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00171 to 3x00172. For fault record use only.
01 9C IREF Diff Courier Number (current) 3x10093 3x10094 G24 2 Data Not settable * * * * * Previous Modbus addresses 3x00173 to 3x00174. For fault record use only.
01 9D IREF Bias Courier Number (current) 3x10095 3x10096 G24 2 Data Not settable * * * * * Previous Modbus addresses 3x00175 to 3x00176. For fault record use only.
01 A0 I2 Courier Number (current) 3x10097 3x10098 G24 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00177 to 3x00178. For fault record use only.
01 A2 V2 Courier Number (voltage) 3x10099 3x10100 G24 2 Data Not settable * * * * * * * For fault record use only.
01 A6 3 Phase Watts Courier Number (Power) 3x10101 3x10102 G125 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00179 to 3x00180. For fault record use only.
01 A8 3 Phase VArs Courier Number (VAr) 3x10103 3x10104 G125 2 Data Not settable * * * * * * * Previous Modbus addresses 3x00181 to 3x00182. For fault record use only.
01 AA 3Ph Power Factor Courier Number (Decimal) 3x10105 G30 1 Data Not settable * * * * * * * Previous Modbus address 3x00183. For fault record use only.
01 B0 RTD 1 Courier Number (Temperature) 3x10106 G10 1 Data Not settable * * * * * Previous Modbus address 3x00184. For fault record use only. Courier text = RTD Label setting
01 B1 RTD 2 Courier Number (Temperature) 3x10107 G10 1 Data Not settable * * * * * Previous Modbus address 3x00185. For fault record use only. Courier text = RTD Label setting
01 B2 RTD 3 Courier Number (Temperature) 3x10108 G10 1 Data Not settable * * * * * Previous Modbus address 3x00186. For fault record use only. Courier text = RTD Label setting
01 B3 RTD 4 Courier Number (Temperature) 3x10109 G10 1 Data Not settable * * * * * Previous Modbus address 3x00187. For fault record use only. Courier text = RTD Label setting
01 B4 RTD 5 Courier Number (Temperature) 3x10110 G10 1 Data Not settable * * * * * Previous Modbus address 3x00188. For fault record use only. Courier text = RTD Label setting
01 B5 RTD 6 Courier Number (Temperature) 3x10111 G10 1 Data Not settable * * * * * Previous Modbus address 3x00189. For fault record use only. Courier text = RTD Label setting
01 B6 RTD 7 Courier Number (Temperature) 3x10112 G10 1 Data Not settable * * * * * Previous Modbus address 3x00190. For fault record use only. Courier text = RTD Label setting
01 B7 RTD 8 Courier Number (Temperature) 3x10113 G10 1 Data Not settable * * * * * Previous Modbus address 3x00191. For fault record use only. Courier text = RTD Label setting
01 B8 RTD 9 Courier Number (Temperature) 3x10114 G10 1 Data Not settable * * * * * Previous Modbus address 3x00192. For fault record use only. Courier text = RTD Label setting
01 B9 RTD 10 Courier Number (Temperature) 3x10115 G10 1 Data Not settable * * * * * Previous Modbus address 3x00193. For fault record use only. Courier text = RTD Label setting
01 C2 df/dt Courier Number (Hz/s) 3x10116 G25 1 Data Not settable * * * * * * * Previous Modbus address 3x00194. For fault record use only.
01 C4 V Vector Shift Courier Number (Angle) 3x10117 G30 1 Data Not settable * * Previous Modbus address 3x00195. For fault record use only.
01 C6 CLIO Input 1 Courier Number (Decimal) 3x10118 3x10119 G125 2 Data Not settable * * * * * * * Previous Modbus address 3x00490. For fault record use only. Courier text = RTD Label setting
01 C7 CLIO Input 2 Courier Number (Decimal) 3x10120 3x10121 G125 2 Data Not settable * * * * * * * Previous Modbus address 3x00492. For fault record use only. Courier text = RTD Label setting
01 C8 CLIO Input 3 Courier Number (Decimal) 3x10122 3x10123 G125 2 Data Not settable * * * * * * * Previous Modbus address 3x00494. For fault record use only. Courier text = RTD Label setting
01 C9 CLIO Input 4 Courier Number (Decimal) 3x10124 3x10125 G125 2 Data Not settable * * * * * * * Previous Modbus address 3x00496. For fault record use only. Courier text = RTD Label setting
01 CA 64S V Magnitude Courier Number (voltage) 3x10126 3x10127 G24 2 Data Not settable * For fault record use only.
01 CB 64S I Magnitude Courier Number (current) 3x10128 3x10129 G24 2 Data Not settable * For fault record use only.
01 CC 64S R primary Courier Number (resistance) 3x10130 3x10131 G125 2 Data Not settable * For fault record use only.
01 CD 64R CL Input Courier Number (current) 3x10132 3x10133 G125 2 Data Not settable * * * * * For fault record use only.
01 CE 64R R Fault Courier Number (resistance) 3x10134 3x10135 G125 2 Data Not settable * * * * * For fault record use only.
01 D0 DLR Ambient Temp Courier Number (Temperature) 3x10136 3x10137 G125 2 Data Not settable *
01 D1 Wind Velocity Courier Number (Velocity) 3x10138 3x10139 G125 2 Data Not settable *
01 D2 Wind Direction Courier Number (Decimal) 3x10140 3x10141 G125 2 Data Not settable *
01 D3 Solar Radiation Courier Number (Power) 3x10142 3x10143 G125 2 Data Not settable *
01 D4 DLR Ampacity Courier Number (Current) 3x10144 3x10145 G125 2 Data Not settable *
01 D5 DLR CurrentRatio Courier Number (Percentage) 3x10146 3x10147 G125 2 Data Not settable *
01 D6 Dyn Conduct Temp Courier Number (Temperature) 3x10148 3x10149 G125 2 Data Not settable *
01 E4 IA Peak Mag Courier Number (Current) 3x10182 3x10183 G24 2 Data Not settable * * * * * IA Peak Magnitude
01 E5 IB Peak Mag Courier Number (Current) 3x10184 3x10185 G24 2 Data Not settable * * * * * IB Peak Magnitude
01 E6 IC Peak Mag Courier Number (Current) 3x10186 3x10187 G24 2 Data Not settable * * * * * IC Peak Magnitude
01 E7 I2t Phase A-1 Courier Number (I2t) 3x10188 3x10189 G24 2 Data Not settable * * * * * I2t Phase A
01 E8 I2t Phase B-1 Courier Number (I2t) 3x10190 3x10191 G24 2 Data Not settable * * * * * I2t Phase B
01 E9 I2t Phase C-1 Courier Number (I2t) 3x10192 3x10193 G24 2 Data Not settable * * * * * I2t Phase C
01 EA IA-2 Peak Mag Courier Number (Current) 3x10150 3x10151 G24 2 Data Not settable * * * * IA Peak Magnitude
01 EB IB-2 Peak Mag Courier Number (Current) 3x10152 3x10153 G24 2 Data Not settable * * * * IB Peak Magnitude
01 EC IC-2 Peak Mag Courier Number (Current) 3x10154 3x10155 G24 2 Data Not settable * * * * IC Peak Magnitude
01 ED I2t Phase A-2 Courier Number (I2t) 3x10156 3x10157 G24 2 Data Not settable * * * * I2t Phase A
01 EE I2t Phase B-2 Courier Number (I2t) 3x10158 3x10159 G24 2 Data Not settable * * * * I2t Phase B
01 EF I2t Phase C-2 Courier Number (I2t) 3x10160 3x10161 G24 2 Data Not settable * * * * I2t Phase C
01 F0 Select Maint Unsigned Integer (16 bits) 4x00102 G1 9 1 Manual override toSetting 0 to 9, step 1 0 9 1 0 * * * * * * * Allows Self Test Report to be selected
01 F1 Maint Text Ascii Text (32 chars) 1 Data 32 character string * * * * * * *
01 F2 Maint Type Unsigned integer (32 bits) 3x00036 3x00037 G27 2 Data 32-bit binary string * * * * * * *
01 F3 Maint Data Unsigned integer (32 bits) 3x00038 3x00039 G27 2 Data 32-bit binary string * * * * * * *
01 FF Reset Indication Indexed String G11 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
02 00 MEASUREMENTS 1 * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 5 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
02 01 IA Magnitude Courier Number (current) 3x00200 3x00201 G24 2 Data Not settable * * * * * * *
IA-1 Magnitude
02 02 IA Phase Angle Courier Number (angle) 3x00202 G30 1 Data Not settable * * * * * * *
IA-1 Phase Angle
02 03 IB Magnitude Courier Number (current) 3x00203 3x00204 G24 2 Data Not settable * * * * * * *
IB-1 Magnitude
02 04 IB Phase Angle Courier Number (angle) 3x00205 G30 1 Data Not settable * * * * * * *
IB-1 Phase Angle
02 05 IC Magnitude Courier Number (current) 3x00206 3x00207 G24 2 Data Not settable * * * * * * *
IC-1 Magnitude
02 06 IC Phase Angle Courier Number (angle) 3x00208 G30 1 Data Not settable * * * * * * *
IC-1 Phase Angle
02 07 IN Measured Mag Courier Number (current) 3x00209 3x00210 G24 2 Data Not settable * * * * *
02 08 IN Measured Ang Courier Number (angle) 3x00211 G30 1 Data Not settable * * * * *
02 09 IN Derived Mag Courier Number (current) 3x00212 3x00213 G24 2 Data Not settable * * * * * * *
IN-1 Derived Mag
02 0A IN Derived Angle Courier Number (angle) 3x00214 G30 1 Data Not settable * *
02 0B Isen Magnitude Courier Number (current) 3x00215 3x00216 G24 2 Data Not settable * * * * * * *
02 0C Isen Angle Courier Number (degrees) 3x00217 G30 1 Data Not settable * * * * * * *
02 0D I1 Magnitude Courier Number (current) 3x00218 3x00219 G24 2 Data Not settable * * * * * * *
02 0E I2 Magnitude Courier Number (current) 3x00220 3x00221 G24 2 Data Not settable * * * * * * *
02 0F I0 Magnitude Courier Number (current) 3x00222 3x00223 G24 2 Data Not settable * * * * * * *
02 10 IA RMS Courier Number (current) 3x00224 3x00225 G24 2 Data Not settable * * * * * * *
02 11 IB RMS Courier Number (current) 3x00226 3x00227 G24 2 Data Not settable * * * * * * *
02 12 IC RMS Courier Number (current) 3x00228 3x00229 G24 2 Data Not settable * * * * * * *
02 13 IN-2 Derived Mag Courier Number (current) 3x00273 3x00274 G24 2 Data Not settable * * * *
02 14 VAB Magnitude Courier Number (voltage) 3x00230 3x00231 G24 2 Data Not settable * * * * * * *
02 15 VAB Phase Angle Courier Number (angle) 3x00232 G30 1 Data Not settable * * * * * * *
02 16 VBC Magnitude Courier Number (voltage) 3x00233 3x00234 G24 2 Data Not settable * * * * * * *
02 17 VBC Phase Angle Courier Number (angle) 3x00235 G30 1 Data Not settable * * * * * * *
02 18 VCA Magnitude Courier Number (voltage) 3x00236 3x00237 G24 2 Data Not settable * * * * * * *
02 19 VCA Phase Angle Courier Number (angle) 3x00238 G30 1 Data Not settable * * * * * * *
02 1A VAN Magnitude Courier Number (voltage) 3x00239 3x00240 G24 2 Data Not settable * * * * * * *
02 1B VAN Phase Angle Courier Number (angle) 3x00241 G30 1 Data Not settable * * * * * * *
02 1C VBN Magnitude Courier Number (voltage) 3x00242 3x00243 G24 2 Data Not settable * * * * * * *
02 1D VBN Phase Angle Courier Number (angle) 3x00244 G30 1 Data Not settable * * * * * * *
02 1E VCN Magnitude Courier Number (voltage) 3x00245 3x00246 G24 2 Data Not settable * * * * * * *
02 1F VCN Phase Angle Courier Number (angle) 3x00247 G30 1 Data Not settable * * * * * * *
02 20 VN Measured Mag Courier Number (voltage) 3x00248 3x00249 G24 2 Data Not settable * * * * * * *
VN1 Measured Mag
02 21 VN Measured Ang Courier Number (angle) 3x00250 G30 1 Data Not settable * * * * * * *
VN1 Measured Ang
02 22 VN Derived Mag Courier Number (voltage) 3x00251 3x00252 G24 2 Data Not settable * * * * * * *
02 23 VN Derived Ang Courier Number (angle) 3x00272 G30 1 Data Not settable * * * * * * *
02 24 V1 Magnitude Courier Number (voltage) 3x00253 3x00254 G24 2 Data Not settable * * * * * * *
02 25 V2 Magnitude Courier Number (voltage) 3x00255 3x00256 G24 2 Data Not settable * * * * * * *
02 26 V0 Magnitude Courier Number (voltage) 3x00257 3x00258 G24 2 Data Not settable * * * * * * *
02 27 VAN RMS Courier Number (voltage) 3x00259 3x00260 G24 2 Data Not settable * * * * * * *
02 28 VBN RMS Courier Number (voltage) 3x00261 3x00262 G24 2 Data Not settable * * * * * * *
02 29 VCN RMS Courier Number (voltage) 3x00263 3x00264 G24 2 Data Not settable * * * * * * *
02 2D Frequency Courier Number (frequency) 3x00265 G30 1 Data Not settable * * * * * * *
02 40 I1 Magnitude Courier Number (current) 3x00218 3x00219 G24 2 Data Not settable * * * * * * *
02 41 I1 Phase Angle Courier Number (angle) 3x00266 G30 1 Data Not settable * * * * * * *
02 42 I2 Magnitude Courier Number (current) 3x00220 3x00221 G24 2 Data Not settable * * * * * * *
02 43 I2 Phase Angle Courier Number (angle) 3x00267 G30 1 Data Not settable * * * * * * *
02 44 I0 Magnitude Courier Number (current) 3x00222 3x00223 G24 2 Data Not settable * * * * * * *
02 45 I0 Phase Angle Courier Number (angle) 3x00268 G30 1 Data Not settable * * * * * * *
02 46 V1 Magnitude Courier Number (voltage) 3x00253 3x00254 G24 2 Data Not settable * * * * * * *
02 47 V1 Phase Angle Courier Number (angle) 3x00269 G30 1 Data Not settable * * * * * * *
02 48 V2 Magnitude Courier Number (voltage) 3x00255 3x00256 G24 2 Data Not settable * * * * * * *
02 49 V2 Phase Angle Courier Number (angle) 3x00270 G30 1 Data Not settable * * * * * * *
02 4A V0 Magnitude Courier Number (voltage) 3x00257 3x00258 G24 2 Data Not settable * * * * * * *
02 4B V0 Phase Angle Courier Number (angle) 3x00271 G30 1 Data Not settable * * * * * * *
02 50 VN2 Measured Mag Courier Number (voltage) 3x00275 3x00276 G24 2 Data Not settable * *
02 51 VN2 Measured Ang Courier Number (angle) 3x00277 G30 1 Data Not settable * *
02 70 C/S Voltage Mag Courier Number (voltage) 3x00281 3x00282 G24 2 Data Not settable * * * * * * *
02 71 C/S Voltage Ang Courier Number (angle) 3x00283 G30 1 Data Not settable * * * * * * *
02 72 CS Gen-Bus Mag Courier Number (angle) 3x00284 3x00285 G24 1 Data Not settable * * * * * * * Visible if System Checks enabled
02 73 CS Gen-Bus Angle Courier Number (angle) 3x00286 G30 1 Data Not settable * * * * * * * Visible if System Checks enabled
02 74 Slip Frequency Courier Number (frequency) 3x00287 G30 1 Data Not settable * * * * * * * Visible if System Checks enabled
02 75 CS Frequency Courier Number (frequency) 3x00288 G30 1 Data Not settable * * * * * * *
03 00 MEASUREMENTS 2 * * * * * * *
03 01 A Phase Watts Courier Number (Power) 3x00300 3x00302 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30391 and 30392 available with improved G125 floating point data type
03 02 B Phase Watts Courier Number (Power) 3x00303 3x00305 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30393 and 30394 available with improved G125 floating point data type
03 03 C Phase Watts Courier Number (Power) 3x00306 3x00308 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30395 and 30396 available with improved G125 floating point data type
03 04 A Phase VArs Courier Number (VAr) 3x00309 3x00311 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30397 and 30398 available with improved G125 floating point data type
03 05 B Phase VArs Courier Number (VAr) 3x00312 3x00314 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30399 and 30400 available with improved G125 floating point data type
03 06 C Phase VArs Courier Number (VAr) 3x00315 3x00317 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30401 and 30402 available with improved G125 floating point data type
03 07 A Phase VA Courier Number (VA) 3x00318 3x00320 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30403 and 30404 available with improved G125 floating point data type
03 08 B Phase VA Courier Number (VA) 3x00321 3x00323 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30405 and 30406 available with improved G125 floating point data type
03 09 C Phase VA Courier Number (VA) 3x00324 3x00326 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30407 and 30408 available with improved G125 floating point data type
03 0A 3 Phase Watts Courier Number (Power) 3x00327 3x00329 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30409 and 30410 available with improved G125 floating point data type
03 0B 3 Phase VArs Courier Number (VAr) 3x00330 3x00332 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30411 and 30412 available with improved G125 floating point data type
03 0C 3 Phase VA Courier Number (VA) 3x00333 3x00335 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30413 and 30414 available with improved G125 floating point data type
03 0D NPS Power S2 Courier Number (VA) 3x00336 3x00338 G29 3 Data Not settable * * * * * Alternative Modbus register pairs 30500 and 30501 available with improved G125 floating point data type
03 0E 3Ph Power Factor Courier Number (decimal) 3x00339 G30 1 Data Not settable * * * * * * *
03 0F APh Power Factor Courier Number (decimal) 3x00340 G30 1 Data Not settable * * * * * * *
03 10 BPh Power Factor Courier Number (decimal) 3x00341 G30 1 Data Not settable * * * * * * *
03 11 CPh Power Factor Courier Number (decimal) 3x00342 G30 1 Data Not settable * * * * * * *
03 12 3Ph WHours Fwd Courier Number (Wh) 3x00343 3x00345 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30415 and 30416 available with improved G125 floating point data type
03 13 3Ph WHours Rev Courier Number (Wh) 3x00346 3x00348 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30417 and 30418 available with improved G125 floating point data type
03 14 3Ph VArHours Fwd Courier Number (VArh) 3x00349 3x00351 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30419 and 30420 available with improved G125 floating point data type
03 15 3Ph VArHours Rev Courier Number (VArh) 3x00352 3x00354 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30421 and 30422 available with improved G125 floating point data type
03 16 3Ph W Fix Demand Courier Number (Power) 3x00355 3x00357 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30423 and 30424 available with improved G125 floating point data type
03 17 3Ph VArs Fix Dem Courier Number (Vars) 3x00358 3x00360 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30425 and 30426 available with improved G125 floating point data type
03 18 IA Fixed Demand Courier Number (Current) 3x00361 3x00362 G24 2 Data Not settable * * * * * * *
03 19 IB Fixed Demand Courier Number (Current) 3x00363 3x00364 G24 2 Data Not settable * * * * * * *
03 1A IC Fixed Demand Courier Number (Current) 3x00365 3x00366 G24 2 Data Not settable * * * * * * *
03 1B 3 Ph W Roll Dem Courier Number (Power) 3x00367 3x00369 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30427 and 30428 available with improved G125 floating point data type
03 1C 3Ph VArs RollDem Courier Number (VAr) 3x00370 3x00372 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30429 and 30430 available with improved G125 floating point data type
03 1D IA Roll Demand Courier Number (Current) 3x00373 3x00374 G24 2 Data Not settable * * * * * * *
03 1E IB Roll Demand Courier Number (Current) 3x00375 3x00376 G24 2 Data Not settable * * * * * * *
03 1F IC Roll Demand Courier Number (Current) 3x00377 3x00378 G24 2 Data Not settable * * * * * * *
03 20 3Ph W Peak Dem Courier Number (Power) 3x00379 3x00381 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30431 and 30432 available with improved G125 floating point data type
03 21 3Ph VAr Peak Dem Courier Number (VAr) 3x00382 3x00384 G29 3 Data Not settable * * * * * * * Alternative Modbus register pairs 30433 and 30434 available with improved G125 floating point data type
03 22 IA Peak Demand Courier Number (Current) 3x00385 3x00386 G24 2 Data Not settable * * * * * * *
03 23 IB Peak Demand Courier Number (Current) 3x00387 3x00388 G24 2 Data Not settable * * * * * * *
03 24 IC Peak Demand Courier Number (Current) 3x00389 3x00390 G24 2 Data Not settable * * * * * * *
03 25 Reset Demand Indexed String 4x00103 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
03 26 NPS Power S2 CT2 Courier Number (VA) 3x00593 3x00595 G29 3 Data Not settable * * * * Alternative Modbus register pairs 30596 and 30597 available with improved G125 floating point data type
04 00 MEASUREMENTS 3 * * * *
04 01 IA-2 Magnitude Courier Number (Current) 3x00435 3x00436 G24 2 Data Not settable * * * *
04 02 IA-2 Phase Angle Courier Number (Angle) 3x00437 G30 1 Data Not settable * * * *
04 03 IB-2 Magnitude Courier Number (Current) 3x00438 3x00439 G24 2 Data Not settable * * * *
04 04 IB-2 Phase Angle Courier Number (Angle) 3x00440 G30 1 Data Not settable * * * *
04 05 IC-2 Magnitude Courier Number (Current) 3x00441 3x00442 G24 2 Data Not settable * * * *
04 06 IC-2 Phase Angle Courier Number (Angle) 3x00443 G30 1 Data Not settable * * * *
04 07 IA Differential Courier Number (Current) 3x00444 3x00445 G24 2 Data Not settable * * * *
04 08 IB Differential Courier Number (Current) 3x00446 3x00447 G24 2 Data Not settable * * * *
04 09 IC Differential Courier Number (Current) 3x00448 3x00449 G24 2 Data Not settable * * * *
04 0A IA Bias Courier Number (Current) 3x00450 3x00451 G24 2 Data Not settable * * * *
04 0B IB Bias Courier Number (Current) 3x00452 3x00453 G24 2 Data Not settable * * * *
04 0C IC Bias Courier Number (Current) 3x00454 3x00455 G24 2 Data Not settable * * * *
04 0D IREF Diff Courier Number (Current) 3x00456 3x00457 G24 2 Data Not settable * * * * *
04 0E IREF Bias Courier Number (Current) 3x00458 3x00459 G24 2 Data Not settable * * * * *
04 0F VN 3rd Harmonic Courier Number (Voltage) 3x00460 3x00461 G24 2 Data Not settable * * *
04 10 NPS Thermal Courier Number (Percentage) 3x00462 G1 1 Data Not settable * * * * *
04 11 Reset NPSThermal Indexed String 4x00104 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * *
04 12 RTD 1 Courier Number (Temperature) 3x00463 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 13 RTD 2 Courier Number (Temperature) 3x00464 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 14 RTD 3 Courier Number (Temperature) 3x00465 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 15 RTD 4 Courier Number (Temperature) 3x00466 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 16 RTD 5 Courier Number (Temperature) 3x00467 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 17 RTD 6 Courier Number (Temperature) 3x00468 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 18 RTD 7 Courier Number (Temperature) 3x00469 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 19 RTD 8 Courier Number (Temperature) 3x00470 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 1A RTD 9 Courier Number (Temperature) 3x00471 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 1B RTD 10 Courier Number (Temperature) 3x00472 G10 1 Data Not settable * * * * * Courier text = RTD label setting
04 1C RTD Open Cct Binary Flag (10 bits); Indexed String 3x00473 G108 G108 1 Data Not settable * * * * *
04 1D RTD Short Cct Binary Flag (10 bits); Indexed String 3x00474 G109 G109 1 Data Not settable * * * * *
04 1E RTD Data Error Binary Flag (10 bits); Indexed String 3x00475 G110 G110 1 Data Not settable * * * * *
04 1F Reset RTD Flags Indexed string 4x00105 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * *
04 20 APh Sen Watts Courier Number (Power) 3x00476 3x00477 G125 2 Data Not settable * * * * * * *
04 21 APh Sen Vars Courier Number (Var) 3x00478 3x00479 G125 2 Data Not settable * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 6 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
04 22 APh Power Angle Courier Number (angle) 3x00480 G30 1 Data Not settable * * * * * * *
04 23 Thermal Overload Courier Number (Percentage) 3x00481 G1 1 Data Not settable * * * * * * *
04 24 Reset ThermalO/L Indexed String 4x00106 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
04 25 CLIO Input 1 Courier Number (Decimal) 3x00482 3x00483 G125 2 Data Not settable * * * * * * * Courier Text = CLIO label setting
04 26 CLIO Input 2 Courier Number (Decimal) 3x00484 3x00485 G125 2 Data Not settable * * * * * * * Courier Text = CLIO label setting
04 27 CLIO Input 3 Courier Number (Decimal) 3x00486 3x00487 G125 2 Data Not settable * * * * * * * Courier Text = CLIO label setting
04 28 CLIO Input 4 Courier Number (Decimal) 3x00488 3x00489 G125 2 Data Not settable * * * * * * * Courier Text = CLIO label setting
04 30 F Band1 Time (s) Unsigned Integer (32 bits) 3x00502 3x00503 G27 2 Data Not settable * * * * * Turbine Abnormal Frequency (TAF). Band 1 Accumulated Time
04 32 Reset Freq Band1 Indexed String 4x00107 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * Reset TAF Band 1 Time
04 34 F Band2 Time (s) Unsigned Integer (32 bits) 3x00504 3x00505 G27 2 Data Not settable * * * * * Turbine Abnormal Frequency (TAF). Band 2 Accumulated Time
04 36 Reset Freq Band2 Indexed String 4x00108 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * Reset TAF Band 2 Time
04 38 F Band3 Time (s) Unsigned Integer (32 bits) 3x00506 3x00507 G27 2 Data Not settable * * * * * Turbine Abnormal Frequency (TAF). Band 3 Accumulated Time
04 3A Reset Freq Band3 Indexed String 4x00109 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * Reset TAF Band 3 Time
04 3C F Band4 Time (s) Unsigned Integer (32 bits) 3x00508 3x00509 G27 2 Data Not settable * * * * * Turbine Abnormal Frequency (TAF). Band 4 Accumulated Time
04 3E Reset Freq Band4 Indexed String 4x00110 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * Reset TAF Band 4 Time
04 40 F Band5 Time (s) Unsigned Integer (32 bits) 3x00510 3x00511 G27 2 Data Not settable * * * * * Turbine Abnormal Frequency (TAF). Band 5 Accumulated Time
04 42 Reset Freq Band5 Indexed String 4x00111 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * Reset TAF Band 5 Time
04 44 F Band6 Time (s) Unsigned Integer (32 bits) 3x00512 3x00513 G27 2 Data Not settable * * * * * Turbine Abnormal Frequency (TAF). Band 6 Accumulated Time
04 46 Reset Freq Band6 Indexed String 4x00112 G11 G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * Reset TAF Band 6 Time
04 48 df/dt Courier Number (Hz/sec) 3x00525 3x00526 G125 2 Data Not settable * * * * * * * dep on df/dt setting in configuration collumn
04 50 Volts/Hz Courier Number (Volts/Hz) 3x00514 3x00515 G24 2 Data Not settable * * * * * Vab/Frequency
04 52 64S V Magnitude Courier Number (voltage) 3x00516 3x00517 G24 2 Data Not settable * Low frequency injection St EF Voltage magnitude measured at the relay terminal
04 54 64S I Magnitude Courier Number (current) 3x00518 3x00519 G24 2 Data Not settable * Low frequency injection St EF Current magnitude measured at the relay terminal
04 55 64S I Angle Courier Number (angle) 3x00520 G30 1 Data Not settable * St EF current angle measurement, affected by Comp Angle setting when St EF is enabled. I64S phase angle relative to V64S
vector.
04 57 64S R secondary Courier Number (resistance) 3x00521 3x00522 G125 2 Data Not settable * St EF secondary resistance measurement at the relay terminal, affected by Series R and Parallel G settings
04 58 64S R primary Courier Number (resistance) 3x00523 3x00524 G125 2 Data Not settable * St EF primary resistance, converted from secondary resistance using the R Factor setting
04 71 64R CL Input Courier Number (current) 3x00539 3x00540 G125 2 Data Not settable * * * * *
04 72 64R R Fault Courier Number (resistance) 3x00541 3x00542 G125 2 Data Not settable * * * * *
04 91 IA Diff PU Courier Number (current) 3x11300 3x11301 G24 2 Data Not settable * * * *
04 92 IB Diff PU Courier Number (current) 3x11302 3x11303 G24 2 Data Not settable * * * *
04 93 IC Diff PU Courier Number (current) 3x11304 3x11305 G24 2 Data Not settable * * * *
04 94 IA Bias PU Courier Number (current) 3x11306 3x11307 G24 2 Data Not settable * * * *
04 95 IB Bias PU Courier Number (current) 3x11308 3x11309 G24 2 Data Not settable * * * *
04 96 IC Bias PU Courier Number (current) 3x11310 3x11311 G24 2 Data Not settable * * * *
04 97 IA Diff 2H Courier Number (current) 3x11312 3x11313 G24 2 Data Not settable * * * *
04 98 IB Diff 2H Courier Number (current) 3x11314 3x11315 G24 2 Data Not settable * * * *
04 99 IC Diff 2H Courier Number (current) 3x11316 3x11317 G24 2 Data Not settable * * * *
04 9A IA Diff 5H Courier Number (current) 3x11318 3x11319 G24 2 Data Not settable * * * *
04 9B IB Diff 5H Courier Number (current) 3x11320 3x11321 G24 2 Data Not settable * * * *
04 9C IC Diff 5H Courier Number (current) 3x11322 3x11323 G24 2 Data Not settable * * * *
04 9D CT2 I1 Mag Courier Number (current) 3x11324 3x11325 G24 2 Data Not settable * * * *
04 9E CT2 I1 Angle Courier Number (angle) 3x11351 G30 1 Data Not settable * * * *
04 9F CT2 I2 Mag Courier Number (current) 3x11326 3x11327 G24 2 Data Not settable * * * *
04 A0 CT2 I2 Angle Courier Number (angle) 3x11352 G30 1 Data Not settable * * * *
04 A1 CT2 I0 Mag Courier Number (current) 3x11328 3x11329 G24 2 Data Not settable * * * *
04 A2 CT2 I0 Angle Courier Number (angle) 3x11353 G30 1 Data Not settable * * * *
04 A3 CT1 I2/I1 Courier Number (Percentage) 3x11330 3x11331 G24 2 Data Not settable * * * *
04 A4 CT2 I2/I1 Courier Number (Percentage) 3x11332 3x11333 G24 2 Data Not settable * * * *
05 00 MEASUREMENTS 4
05 01 Hot Spot T Courier Number (°C) 3x11334 G10 1 Data Not settable * * * * *
05 02 Top Oil T Courier Number (°C) 3x11335 G10 1 No Data Not settable * * * * *
05 03 Reset Xthermal Indexed String 4x00113 G11 G11 1 No Command Not settable 0 1 1 1 * * * * *
05 04 Ambient T Courier Number (°C) 3x11336 G10 1 Data Not settable * * * * *
05 05 TOL Pretrip left Courier Number (decimal) 3x11337 3x11338 G24 2 Data Not settable * * * * *
05 06 LOL status Courier Number (decimal) 3x11339 3x11340 G24 2 Data Not settable * * * * *
05 07 Reset LOL Indexed String 4x00114 G11 G11 1 No Command Not settable 0 1 1 1 * * * * *
05 08 Rate of LOL Courier Number (decimal) 3x11341 3x11342 G24 2 No Data Not settable * * * * *
05 09 LOL Ageing Fact Courier Number (decimal) 3x11343 3x11344 G24 2 Data Not settable * * * * *
05 0A Lres at Design T Courier Number (decimal) 3x11345 3x11346 G24 2 No Data Not settable * * * * *
05 0B FAA,m Courier Number (decimal) 3x11347 3x11348 G24 2 Data Not settable * * * * *
05 0C Lres at FAA,m Courier Number (decimal) 3x11349 3x11350 G24 2 No Data Not settable * * * * *
05 20 Max Iac Courier Number (Current) 3x00543 3x00544 G125 2 Data *
05 22 DLR Ambient Temp Courier Number (Temperature) 3x00545 3x00546 G125 2 Data *
05 24 Wind Velocity Courier Number (Velocity) 3x00547 3x00548 G125 2 Data *
05 26 Wind Direction Courier Number (Decimal) 3x00549 3x00550 G125 2 Data *
05 28 Solar Radiation Courier Number (Current) 3x00551 3x00552 G125 2 Data *
05 32 Effct wind angle Courier Number (Angle) 3x00553 3x00554 G125 2 Data *
05 34 Pc Courier Number (Power) 3x00555 3x00556 G125 2 Data *
05 36 Pc, natural Courier Number (Power) 3x00557 3x00558 G125 2 Data *
05 38 Pc1, forced Courier Number (Power) 3x00559 3x00560 G125 2 Data *
05 3A Pc2, forced Courier Number (Power) 3x00561 3x00562 G125 2 Data *
05 3C DLR Ampacity Courier Number (Current) 3x00563 3x00564 G125 2 Data *
05 3E DLR CurrentRatio Courier Number (Percentage) 3x00565 3x00566 G125 2 Data *
05 40 Dyn Conduct Temp Courier Number (Temperature) 3x00567 3x00568 G125 2 Data *
05 42 Steady Conduct T Courier Number (Temperature) 3x00569 3x00570 G125 2 Data *
05 44 Time Constant Courier Number (Time) 3x00571 3x00572 G125 2 Data *
06 00 CB CONDITION
06 01 CB Operations Unsigned Integer 3x00600 G1 1 Data * * * * * * *
06 02 Total IA Broken Courier Number (current) 3x00601 3x00602 G24 2 Data * * * * * * *
06 03 Total IB Broken Courier Number (current) 3x00603 3x00604 G24 2 Data * * * * * * *
06 04 Total IC Broken Courier Number (current) 3x00605 3x00606 G24 2 Data * * * * * * *
06 05 CB Operate Time Courier Number (time) 3x00607 G25 1 Data * * * * * * *
06 06 CB Close Time Courier Number (time) 3x00608 G25 1 Data * * * * * * *
06 07 Reset CB Data Indexed String 4x00150 G11 G11 1 No Command 0 1 1 1 * * * * * * *
07 00 CB CONTROL * * * * * * *
07 01 CB Control by Indexed String 4x00200 G99 G99 1 Disabled Setting Disabled, Local, Remote, Local + Remote, Opto, Opto + Local, Opto + Remote, Opto 0 7 1 2 * * * * * * *
07 02 Close Pulse Time Courier Number (Time) 4x00201 G2 49 1 0.5 Setting 0.1s to 10s step 0.01s 0.1 10 0.01 2 * * * * * * *
07 03 Trip Pulse Time Courier Number (Time) 4x00202 G2 49 1 0.5 Setting 0.1s to 5s step 0.01s 0.1 5 0.01 2 * * * * * * *
07 05 Man Close Delay Courier Number (Time) 4x00203 G2 59999 1 10 Setting 0.01s to 600s step 0.01s 0.01 600 0.01 2 * * * * * * * Manual Close Delay
07 06 CB Healthy Time Courier Number (Time) 4x00204 4x00205 G35 1000000 2 5 Setting 0.01s to 9999s step 0.01s 0.01 9999 0.01 2 * * * * * * *
07 07 Sys Check Time Courier Number (Time) 4x00210 4x00211 G35 1000000 2 5 Setting 0.01s to 9999s step 0.01s 0.01 9999 0.01 2 * * * * * * *
07 08 Lockout Reset Indexed String 4x00206 G11 G11 59999 1 No Command 0 = No, 1 = Yes 0 1 1 2 * * * * * * *
07 09 Reset Lockout by Indexed String 4x00207 G81 G81 59999 1 CB Close Setting 0 = User Interface, 1 = CB Close 0 1 1 2 * * * * * * *
07 0A Man Close RstDly Courier Number (Time) 4x00208 G2 59999 1 5 Setting 0.01 to 600 step 0.01 0.01 600 0.01 2 * * * * * * * Manual Close Reset Delay
07 11 CB Status Input Indexed String 4x00209 G118 G118 1 None Setting 0 = None, 1 = 52A, 2 = 52B, 3 = Both 52A and 52B 0 3 1 2 * * * * * * *
08 00 DATE AND TIME * * * * * * *
08 01 Date/Time IEC870 Time & Date N/A 4x00300 4x00303 G12 4 Setting 0 * * * * * * *
N/A N/A Date 12/01/1998 <Date> * * * * * * * Front Panel Menu only
N/A N/A Time 12:00:00 <Time> * * * * * * * Front Panel Menu only
08 04 IRIG-B Sync Indexed String 4x00304 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
08 05 IRIG-B Status Indexed String 3x00090 G17 G17 1 Data Card not fitted, Card failed, signal healthy, No signal * * * * * * *
08 06 Battery Status Indexed String 3x00091 G59 G59 1 Data Dead, Healthy * * * * * * *
08 07 Battery Alarm Indexed String 4x00305 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
08 13 SNTP Status Indexed String G247 Data Disabled, Trying Server1, Trying Server 2, Server 1 OK, Server 2 OK, No response, No Valid Clock * * * * * * *
08 20 LocalTime Enable Indexed String G254 Fixed Setting Disabled, Fixed, Flexible 0 2 1 2 * * * * * * *
08 21 LocalTime Offset Courier Number (Time Minutes) 0 Setting -720 mins to +720 mins step 15 mins -720 720 15 2 * * * * * * *
08 22 DST Enable Indexed String G37 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
08 23 DST Offset Courier Number (Time Minutes) 60 Setting 30 mins, 60 mins 30 60 30 2 * * * * * * *
08 24 DST Start Indexed String G252 Last Setting First, Second, Third, Fourth, Last 0 4 1 2 * * * * * * *
08 25 DST Start Day Indexed String G250 Sunday Setting Monday, Tuesday, Wednesday, Thursday, Friday, Saturday 0 6 1 2 * * * * * * *
08 26 DST Start Month Indexed String G251 March Setting Any of the 12 months 0 11 1 2 * * * * * * *
08 27 DST Start Mins Courier Number (Time Minutes) 60 Setting 0 mins to 1425 mins step 15 mins 0 1425 15 2 * * * * * * *
08 28 DST End Indexed String G252 Last Setting First, Second, Third, Fourth, Last 0 4 1 2 * * * * * * *
08 29 DST End Day Indexed String G250 Sunday Setting Monday, Tuesday, Wednesday, Thursday, Friday, Saturday 0 6 1 2 * * * * * * *
08 2A DST End Month Indexed String G251 October Setting Any of the 12 months 0 11 1 2 * * * * * * *
08 2B DST End Mins Courier Number (Time Minutes) 60 Setting 0 mins to 1425 mins step 15 mins 0 1425 15 2 * * * * * * *
08 30 RP1 Time Zone Indexed String G253 Local Setting UTC, Local 0 1 1 2 * * * * * * *
08 31 RP2 Time Zone Indexed String G253 Local Setting UTC, Local 0 1 1 2 * * * * * * *
08 32 DNPOE Time Zone Indexed String G253 Local Setting UTC, Local 0 1 1 2 * * * * * * *
08 33 Tunnel Time Zone Indexed String G253 Local Setting UTC, Local 0 1 1 2 * * * * * * *
09 00 CONFIGURATION * * * * * * *
09 01 Restore Defaults Indexed String 4x00402 G53 G53 1 No Operation Command No operation, All settings, Setting Group 1, Setting Group 2, Setting Group 3, Setting 0 5 1 2 * * * * * * *
09 02 Setting Group Indexed String 4x00403 G61 G61 1 Select via Menu Setting Select from Menu, Select from PSL 0 1 1 2 * * * * * * *
09 03 Active Settings Indexed String 4x00404 G90 G90 1 Group 1 Setting Group 1, Group 2, Group 3, Group 4 0 3 1 1 * * * * * * *
09 04 Save Changes Indexed String 4x00405 G62 G62 1 No Operation Command No Operation, Save, Abort 0 2 1 2 * * * * * * *
09 05 Copy From Indexed String 4x00406 G90 G90 1 Group 1 Setting Group 1, Group 2, Group 3, Group 4 0 3 1 2 * * * * * * *
09 06 Copy To Indexed String 4x00407 G98 G98 1 No Operation Command No Operation, Group 1, Group 2, Group 3, Group 4 0 3 1 2 * * * * * * *
09 07 Setting Group 1 Indexed String 4x00408 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 08 Setting Group 2 Indexed String 4x00409 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 09 Setting Group 3 Indexed String 4x00410 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 0A Setting Group 4 Indexed String 4x00411 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 0B System Config Indexed String 4x00437 G80 1 Visible Setting Invisible, Visible 0 1 1 2 * * * * * * *
09 0C Power Indexed String 4x00413 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 0D Field Failure Indexed String 4x00414 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * *
09 0E NPS Thermal Indexed String 4x00415 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * *
09 0F System Backup Indexed String 4x00416 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * *
09 10 Overcurrent Indexed String 4x00417 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 11 Thermal Overload Indexed String 4x00433 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 12 Differential Indexed String 4x00412 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * *
09 13 Earth Fault Indexed String 4x00418 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 14 Rotor EF Indexed String 4x00438 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * *
09 15 SEF/REF/SPower Indexed String 4x00419 G114 G114 1 Disabled Setting 0 = Disabled, 1 = SEF/REF, 2 = Sensitive Power 0 2 1 2 * * * * * * *
SEF/REF
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 7 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
09 16 Residual O/V NVD Indexed String 4x00420 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * * Residual Overvoltage
09 17 100% Stator EF Indexed String 4x00421 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * *
Enabled
09 18 V/Hz Indexed String 4x00422 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * *
09 19 df/dt Indexed String 4x00423 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 1A V Vector Shift Indexed String 4x00424 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * *
09 1B Dead Machine Indexed String 4x00425 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * *
09 1C Reconnect Delay Indexed String 4x00426 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * *
09 1D Volt Protection Indexed String 4x00427 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 1E Freq Protection Indexed String 4x00428 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 1F RTD Inputs Indexed String 4x00429 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * *
09 20 CB Fail Indexed String 4x00430 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 21 Supervision Indexed String 4x00431 G37 G37 1 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 22 NOT USED Not used
09 23 Dynamic Rating Indexed String 4x00439 G37 G1 1 Enabled Setting Enabled, Disabled 0 1 1 2 *
09 24 Pole Slipping Indexed String 4x00436 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * *
09 25 Input Labels Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 26 Output Labels Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 27 RTD Labels Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * *
09 28 CT & VT Ratios Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 29 Record Control Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 2A Disturb Recorder Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * * Disturbance recorder
09 2B Measure't Setup Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 2C Comms Settings Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 2D Commission Tests Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 2E Setting Values Indexed String G54 Primary Setting 0 = Primary, 1 = Secondary 0 1 1 1 * * * * * * *
09 2F Control Inputs Indexed String G80 Visible Setting Invisible, Visible 0 1 1 2 * * * * * * *
09 30 CLIO Inputs Indexed String 4x00434 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 31 CLIO Outputs Indexed String 4x00435 G37 G37 1 Enabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 32 CLIO status (Hidden)
(Note: No Courier text)
09 33 System Checks Indexed String 4x00443 G37 G37 1 Disabled Setting 0 1 1 2 * * * * * * *
09 35 Ctrl I/P Config Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 36 Ctrl I/P Labels Indexed String G80 Visible Setting Invisible, Visible 0 1 1 1 * * * * * * *
09 39 Direct Access Indexed String G231 Enabled Setting 0 = Disabled, 1 = Enabled, 2 = Hotkey Only, 3 = CB Ctrl Only 0 3 1 1 * * * * * * *
0 1 1 1
09 50 Function Key Indexed String 4x00432 G80 Visible Setting Invisible, Visible 0 1 1 1 *
09 FB RP1 Read Only Indexed String 4x00440 G37 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 FC RP2 Read Only Indexed String 4x00441 G37 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 FD NIC Read Only Indexed String 4x00442 G37 Disabled Setting Enabled, Disabled 0 1 1 2 * * * * * * *
09 FF LCD Contrast Unsigned Integer (16 bits) 11 Setting 0 to 31 step 1 0 31 1 1 * * * * * * *
0A 00 CT AND VT RATIOS * * * * * * * Values for multipliers used else where
0A 12 Main VT Primary Courier Number (Voltage) 4x00500 4x00501 G35 999900 2 110 Setting 100V to 1MV step 1V 100 1000000 1 2 * * * * * * * Label V1=Main VT Rating/110
0A 13 Main VT Sec'y Courier Number (Voltage) 4x00502 G2 60 1 110 Setting 80V to 140V step 1V 80*V1 140*V1 1*V1 2 * * * * * * * Label M1=[0A12]/[0A13]
0A 16 C/S VT Primary Courier Number (Voltage) 4x00516 4x00517 G2 G35 29999 2 110 Setting 100V to 1MV step 1V 100 1000000 1 2 *(60-TE) * Label Vcs=C/S VT Rating/110
0A 17 C/S VT Sec'y Courier Number (Voltage) 4x00518 G2 G2 60 1 110 Setting 80V to 140V step 1V 80 140 1 2 *(60-TE) * Label Mcs=[0A16]/[0A17]
0A 22 VN1 VT Primary Courier Number (Voltage) 4x00503 4x00504 G35 999900 2 110 Setting 100V to 1MV step 1V 100 1000000 1 2 * * * * * * * Neutral Displacement VT Primary. Label V3=Neutral Disp VT Rating/110
0A 23 VN1 VT Secondary Courier Number (Voltage) 4x00505 G2 60 1 110 Setting 80V to 140V step 1V 80*V3 140*V3 1*V3 2 * * * * * * * Neutral Displacement VT Secondary. Label M3=[0A22]/[0A23]
0A 27 VN2 VT Primary Courier Number (Voltage) 4x00506 4x00507 G35 999900 2 110 Setting 100V to 1MV step 1V 100 1000000 1 2 * * Second NVD VT. Label V2=VN2 VT Rating/110
0A 28 VN2 VT Secondary Courier Number (Voltage) 4x00508 G2 60 1 110 Setting 80V to 140V step 1V 80*V2 140*V2 1*V2 2 * * Second NVD VT. Label M2=[0A27]/[0A28]
0A 31 Ph CT Polarity Indexed String 4x00519 G165 G165 1 Standard Setting Standard, Inverted 0 1 1 2 * * * * * * * Polarity of phase CT group (3 phase)
Ph CT1 Polarity
0A 32 Phase CT Primary Courier Number (Current) 4x00509 G2 59999 1 300 Setting 1A to 60kA step 1A 1 60000 1 2 * * * * * * * I1=Phase CT1 secondary rating
Phase CT1 Primary
0A 33 Phase CT Sec'y Courier Number (Current) 4x00510 G2 1 1 Setting 1A, 5A 1 5 4 2 * * * * * * * Label M4=[0A32]/[0A33]
Phase CT1 Sec'y
0A 36 Ph CT2 Polarity Indexed String 4x00520 G165 G165 1 Standard Setting Standard, Inverted 0 1 1 2 * * * * Polarity of phase CT2 group (3 phase)
0A 37 Phase CT2 Prim'y Courier Number (Current) 4x00521 G2 59999 1 300 Setting 1A to 60kA step 1A 1 60000 1 2 * * * * I4=Phase CT2 secondary rating
0A 38 Phase CT2 Sec'y Courier Number (Current) 4x00522 G2 1 1 Setting 1A, 5A 1 5 4 2 * * * * Label M7=[0A37]/[0A38]
0A 51 E/F CT Polarity Indexed String 4x00523 G165 G165 1 Standard Setting Standard, Inverted 0 1 1 2 * * * * * Polarity of E/F (IN1) CT
0A 52 E/F CT Primary Courier Number (Current) 4x00511 G2 59999 1 1 Setting 1A to 60kA step 1A 1 60000 1 2 * * * * * Label I2=E/F CT secondary rating
0A 53 E/F CT Secondary Courier Number (Current) 4x00512 G2 1 1 Setting 1A, 5A 1 5 4 2 * * * * * Label M5=[0A52]/[0A53]
0A 61 Isen CT Polarity Indexed String 4x00524 G165 G165 1 Standard Setting Standard, Inverted 0 1 1 2 * * * * * * * Polarity of SEF (Isen) CT
0A 62 Isen CT Primary Courier Number (Current) 4x00513 G2 59999 1 1 Setting 1A to 60kA step 1A 1 60000 1 2 * * * * * * * Label I3=SEF CT secondary rating
0A 63 Isen CT Sec'y Courier Number (Current) 4x00514 G2 1 1 1 Setting 1A, 5A 1 5 4 2 * * * * * * * Label M6=[0A62]/[0A63]
0B 00 RECORD CONTROL * * * * * * *
0B 01 Clear Events Indexed String G11 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
0B 02 Clear Faults Indexed String G11 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
0B 03 Clear Maint Indexed String G11 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
0B 04 Alarm Event Indexed String 4x10400 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 05 Relay O/P Event Indexed String 4x10401 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 06 Opto Input Event Indexed String 4x10402 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 07 General Event Indexed String 4x10403 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 08 Fault Rec Event Indexed String 4x10404 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 09 Maint Rec Event Indexed String 4x10405 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 0A Protection Event Indexed String 4x10406 G37 G37 1 Enabled Setting Enabled, disabled 0 1 1 2 * * * * * * *
0B 30 Clear Dist Recs Indexed String G11 1 No Command 0 = No, 1 = Yes 0 1 1 1 * * * * * * *
0B 40 DDB 31 - 0 Binary Flag (32 bits) 4x10407 4x10408 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 41 DDB 63 - 32 Binary Flag (32 bits) 4x10409 4x10410 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 42 DDB 95 - 64 Binary Flag (32 bits) 4x10411 4x10412 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 43 DDB 127 - 96 Binary Flag (32 bits) 4x10413 4x10414 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 44 DDB 159 - 128 Binary Flag (32 bits) 4x10415 4x10416 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 45 DDB 191 - 160 Binary Flag (32 bits) 4x10417 4x10418 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 46 DDB 223 - 192 Binary Flag (32 bits) 4x10419 4x10420 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 47 DDB 255 - 224 Binary Flag (32 bits) 4x10421 4x10422 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 48 DDB 287 - 256 Binary Flag (32 bits) 4x10423 4x10424 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 49 DDB 319 - 288 Binary Flag (32 bits) 4x10425 4x10426 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 4A DDB 351 - 320 Binary Flag (32 bits) 4x10427 4x10428 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 4B DDB 383 - 352 Binary Flag (32 bits) 4x10429 4x10430 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 4C DDB 415 - 384 Binary Flag (32 bits) 4x10431 4x10432 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 4D DDB 447 - 416 Binary Flag (32 bits) 4x10433 4x10434 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 4E DDB 479 - 448 Binary Flag (32 bits) 4x10435 4x10436 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 4F DDB 511 - 480 Binary Flag (32 bits) 4x10437 4x10438 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 50 DDB 543 - 512 Binary Flag (32 bits) 4x10439 4x10440 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 51 DDB 575 - 544 Binary Flag (32 bits) 4x10441 4x10442 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 52 DDB 607 - 576 Binary Flag (32 bits) 4x10443 4x10444 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 53 DDB 639 - 608 Binary Flag (32 bits) 4x10445 4x10446 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 54 DDB 671 - 640 Binary Flag (32 bits) 4x10447 4x10448 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 55 DDB 703 - 672 Binary Flag (32 bits) 4x10449 4x10450 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 56 DDB 735 - 704 Binary Flag (32 bits) 4x10451 4x10452 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 57 DDB 767 - 736 Binary Flag (32 bits) 4x10453 4x10454 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 58 DDB 799 - 768 Binary Flag (32 bits) 4x10455 4x10456 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 59 DDB 831 - 800 Binary Flag (32 bits) 4x10457 4x10458 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 5A DDB 863 - 832 Binary Flag (32 bits) 4x10459 4x10460 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 5B DDB 895 - 864 Binary Flag (32 bits) 4x10461 4x10462 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 5C DDB 927 - 896 Binary Flag (32 bits) 4x10463 4x10464 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 5D DDB 959 - 928 Binary Flag (32 bits) 4x10465 4x10466 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 5E DDB 991 - 960 Binary Flag (32 bits) 4x10467 4x10468 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 5F DDB 1023 - 992 Binary Flag (32 bits) 4x10469 4x10470 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 60 DDB 1055-1024 Binary Flag (32 bits) 4x10471 4x10472 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 8 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
0B 61 DDB 1087-1056 Binary Flag (32 bits) 4x10473 4x10474 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 62 DDB 1119-1088 Binary Flag (32 bits) 4x10475 4x10476 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 63 DDB 1151-1120 Binary Flag (32 bits) 4x10477 4x10478 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 64 DDB 1183-1152 Binary Flag (32 bits) 4x10479 4x10480 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 65 DDB 1215-1184 Binary Flag (32 bits) 4x10481 4x10482 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 66 DDB 1247-1216 Binary Flag (32 bits) 4x10483 4x10484 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 67 DDB 1279-1248 Binary Flag (32 bits) 4x10485 4x10486 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 68 DDB 1311-1280 Binary Flag (32 bits) 4x10487 4x10488 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 69 DDB 1343-1312 Binary Flag (32 bits) 4x10489 4x10490 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 6A DDB 1375-1344 Binary Flag (32 bits) 4x10491 4x10492 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 6B DDB 1407-1376 Binary Flag (32 bits) 4x10493 4x10494 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 6C DDB 1439-1408 Binary Flag (32 bits) N/A 4x10495 4x10496 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 6D DDB 1471-1440 Binary Flag (32 bits) N/A 4x10497 4x10498 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 6E DDB 1503-1472 Binary Flag (32 bits) N/A 4x10499 4x10500 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 6F DDB 1535-1504 Binary Flag (32 bits) N/A 4x10501 4x10502 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 70 DDB 1567-1536 Binary Flag (32 bits) N/A 4x10503 4x10504 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 71 DDB 1599-1568 Binary Flag (32 bits) N/A 4x10505 4x10506 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 72 DDB 1631-1600 Binary Flag (32 bits) N/A 4x10507 4x10508 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 73 DDB 1663-1632 Binary Flag (32 bits) N/A 4x10509 4x10510 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 74 DDB 1695-1664 Binary Flag (32 bits) N/A 4x10511 4x10512 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 75 DDB 1727-1696 Binary Flag (32 bits) N/A 4x10513 4x10514 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 76 DDB 1759-1728 Binary Flag (32 bits) N/A 4x10515 4x10516 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 77 DDB 1791-1760 Binary Flag (32 bits) N/A 4x10517 4x10518 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 78 DDB 1823-1792 Binary Flag (32 bits) N/A 4x10519 4x10520 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 79 DDB 1855-1824 Binary Flag (32 bits) N/A 4x10521 4x10522 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 7A DDB 1887-1856 Binary Flag (32 bits) N/A 4x10523 4x10524 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 7B DDB 1919-1888 Binary Flag (32 bits) N/A 4x10525 4x10526 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 7C DDB 1951-1920 Binary Flag (32 bits) N/A 4x10527 4x10528 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 7D DDB 1983-1952 Binary Flag (32 bits) N/A 4x10529 4x10530 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 7E DDB 2015-1984 Binary Flag (32 bits) N/A 4x10531 4x10532 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0B 7F DDB 2047-2016 Binary Flag (32 bits) N/A 4x10533 4x10534 G27 2 0xFFFFFFFF Setting 32-bit binary setting: 1 = event recording Enabled, 0 = event recording Disabled 0xFFFFFFFF 32 1 2 * * * * * * *

0C 00 DISTURB RECORDER * * * * * * * DISTURBANCE RECORDER


0C 52 Duration Courier Number (Time) 4x00600 G2 1050 1 1.5 Setting 0.1s to 10.5s step 0.01s 0.1 10.5 0.01 2 * * * * * * *
0C 54 Trigger Position Courier Number (%) 4x00601 G2 1050 1 33.3 Setting 0% to 100% step 0.1% 0 100 0.1 2 * * * * * * *
0C 56 Trigger Mode Indexed String 4x00602 G34 G34 1 Single Single, Extended 0 1 1 2 * * * * * * *
0C 58 Analog Channel 1 Indexed String 4x00603 G31 G31 1 VAN Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * * ** Max = 7 for P341, 8 for P342; 11 for P343, 12 for P344, 14 for P345

0C 59 Analog Channel 2 Indexed String 4x00604 G31 G31 1 VBN Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 5A Analog Channel 3 Indexed String 4x00605 G31 G31 1 VCN Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 5B Analog Channel 4 Indexed String 4x00606 G31 G31 1 VN1 Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 5C Analog Channel 5 Indexed String 4x00607 G31 G31 1 IA (IA-1) Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 5D Analog Channel 6 Indexed String 4x00608 G31 G31 1 IB (IB-1) Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 5E Analog Channel 7 Indexed String 4x00609 G31 G31 1 IC (IC-1) Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 5F Analog Channel 8 Indexed String 4x00610 G31 G31 1 I Sensitive Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * * * *

0C 60 Analog Channel 9 Indexed String 4x00675 G31 G31 1 IN Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * * *

0C 61 AnalogChannel 10 Indexed String 4x00676 G31 G31 1 IA-2 Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * *

0C 62 AnalogChannel 11 Indexed String 4x00677 G31 G31 1 IB-2 Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * *

0C 63 AnalogChannel 12 Indexed String 4x00678 G31 G31 1 IC-2 Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * * * *

0C 64 AnalogChannel 13 Indexed String 4x00679 G31 G31 1 VN2 Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 * *

0C 65 AnalogChannel 14 Indexed String 4x00680 G31 G31 1 V64S Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 *

0C 66 AnalogChannel 15 Indexed String 4x00681 G31 G31 1 I64S Setting VAN, VBN, VCN, VN1, IA, IB, IC, IN, I Sensitive, IA-2, IB-2, IC-2,VN2, V64S, I64S 0 ** 1 2 *

0C 80 Digital Input 1 Indexed String 4x00611 G32 G32 1 Output R1 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 81 Input 1 Trigger Indexed String 4x00612 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 82 Digital Input 2 Indexed String 4x00613 G32 G32 1 Output R2 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 83 Input 2 Trigger Indexed String 4x00614 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 84 Digital Input 3 Indexed String 4x00615 G32 G32 1 Output R3 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 85 Input 3 Trigger Indexed String 4x00616 G66 G66 1 Trigger L/H Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 86 Digital Input 4 Indexed String 4x00617 G32 G32 1 Output R4 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 87 Input 4 Trigger Indexed String 4x00618 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 88 Digital Input 5 Indexed String 4x00619 G32 G32 1 Output R5 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 89 Input 5 Trigger Indexed String 4x00620 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 8A Digital Input 6 Indexed String 4x00621 G32 G32 1 Output R6 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 8B Input 6 Trigger Indexed String 4x00622 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 8C Digital Input 7 Indexed String 4x00623 G32 G32 1 Output R7 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C 8D Input 7 Trigger Indexed String 4x00624 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 8E Digital Input 8 Indexed String 4x00625 G32 G32 1 Input L1 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R8
0C 8F Input 8 Trigger Indexed String 4x00626 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 90 Digital Input 9 Indexed String 4x00627 G32 G32 1 Input L2 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R9
0C 91 Input 9 Trigger Indexed String 4x00628 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 92 Digital Input 10 Indexed String 4x00629 G32 G32 1 Input L3 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R10
0C 93 Input 10 Trigger Indexed String 4x00630 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 94 Digital Input 11 Indexed String 4x00631 G32 G32 1 Input L4 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R11
0C 95 Input 11 Trigger Indexed String 4x00632 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 96 Digital Input 12 Indexed String 4x00633 G32 G32 1 Input L5 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R12
0C 97 Input 12 Trigger Indexed String 4x00634 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 98 Digital Input 13 Indexed String 4x00635 G32 G32 1 Input L6 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R13
0C 99 Input 13 Trigger Indexed String 4x00636 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 9A Digital Input 14 Indexed String 4x00637 G32 G32 1 Input L7 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Output R14
0C 9B Input 14 Trigger Indexed String 4x00638 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 9C Digital Input 15 Indexed String 4x00639 G32 G32 1 Input L8 Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L1
0C 9D Input 15 Trigger Indexed String 4x00640 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C 9E Digital Input 16 Indexed String 4x00641 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L2
0C 9F Input 16 Trigger Indexed String 4x00642 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C A0 Digital Input 17 Indexed String 4x00643 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L3
0C A1 Input 17 Trigger Indexed String 4x00644 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C A2 Digital Input 18 Indexed String 4x00645 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L4
0C A3 Input 18 Trigger Indexed String 4x00646 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 9 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
0C A4 Digital Input 19 Indexed String 4x00647 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L5
0C A5 Input 19 Trigger Indexed String 4x00648 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C A6 Digital Input 20 Indexed String 4x00649 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L6
0C A7 Input 20 Trigger Indexed String 4x00650 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C A8 Digital Input 21 Indexed String 4x00651 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L7
0C A9 Input 21 Trigger Indexed String 4x00652 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C AA Digital Input 22 Indexed String 4x00653 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L8
0C AB Input 22 Trigger Indexed String 4x00654 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C AC Digital Input 23 Indexed String 4x00655 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L9
0C AD Input 23 Trigger Indexed String 4x00656 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C AE Digital Input 24 Indexed String 4x00657 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L10
0C AF Input 24 Trigger Indexed String 4x00658 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C B0 Digital Input 25 Indexed String 4x00659 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L11
0C B1 Input 25 Trigger Indexed String 4x00660 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C B2 Digital Input 26 Indexed String 4x00661 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L12
0C B3 Input 26 Trigger Indexed String 4x00662 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C B4 Digital Input 27 Indexed String 4x00663 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L13
0C B5 Input 27 Trigger Indexed String 4x00664 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C B6 Digital Input 28 Indexed String 4x00665 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L14
0C B7 Input 28 Trigger Indexed String 4x00666 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C B8 Digital Input 29 Indexed String 4x00667 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L15
0C B9 Input 29 Trigger Indexed String 4x00668 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C BA Digital Input 30 Indexed String 4x00669 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Input L16
0C BB Input 30 Trigger Indexed String 4x00670 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0C BC Digital Input 31 Indexed String 4x00671 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
Function Key 10
0C BD Input 31 Trigger Indexed String 4x00672 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
Trigger L/H
0C BE Digital Input 32 Indexed String 4x00673 G32 G32 1 Unused Setting Any of 32 O/P Contacts or Any of 32 Opto Inputs or Internal Digital Sig 0 DDB Size 1 2 * * * * * * *
0C BF Input 32 Trigger Indexed String 4x00674 G66 G66 1 No Trigger Setting No trigger, Trigger L/H, trigger H/L 0 2 1 2 * * * * * * *
0D 00 MEASURE'T SETUP * * * * * * * MEASUREMENT SETTINGS
0D 01 Default Display Indexed String 4x00700 G52 G52 1 Description Setting 3Ph + N Current, 3Ph Neutral Voltage, Power, Date and Time, Description, Plant 0 7 1 2 * * * * * * *
Reference, Frequency, Access Level
0D 02 Local Values Indexed String 4x00701 G54 G54 1 Primary Setting Primary, Secondary 0 1 1 1 * * * * * * * Local Measurement Values
0D 03 Remote Values Indexed String 4x00702 G54 G54 1 Primary Setting Primary, Secondary 0 1 1 1 * * * * * * * Remote Measurement Values
0D 04 Measurement Ref Indexed String 4x00703 G56 G56 1 VA Setting 0 = VA, 1 = VB, 2 = VC, 3 = IA, 4 = IB, 5 = IC 0 5 1 1 * * * * * * * Measurement Phase Reference
0D 05 Measurement Mode Unsigned Integer 4x00705 G1 3 1 0 Setting 0, 1, 2, 3 0 3 1 1 * * * * * * *
0D 06 Fix Dem Period Courier Number (time-minutes) 4x00706 G2 1 15 Setting 1 min to 99 mins step 1 min 1 99 1 2 * * * * * * * Fixed Demand Interval
0D 07 Roll Sub Period Courier Number (time-minutes) 4x00707 G2 1 1 Setting 1 min to 99 mins step 1 min 1 99 1 2 * * * * * * * Rolling demand sub period
0D 08 Num Sub Periods Unsigned Integer 4x00708 G1 1 15 Setting 1 to 15 step 1 1 15 1 2 * * * * * * * Number of rolling sub-periods
0D 0B Remote 2 Values Indexed String G54 Primary Setting Primary, Secondary 0 1 1 2 * * * * * * * Remote 2 Measurement Values. Visible when Model no. Hardware option (Field 7) = 7 or 8
0E 00 COMMUNICATIONS * * * * * * *
0E 01 RP1 Protocol Indexed String G71 Data <Protocol> * * * * * * *
0E 02 RP1 Address Unsigned integer (16 bits) 255 Setting 0 to 255 (Courier) 0 255 1 1 * * * * * * * Rear Port 1 Courier Protocol device address
0E 02 RP1 Address Unsigned integer (16 bits) 1 Setting 0 to 247 (Modbus) 1 247 1 1 * * * * * * * Rear Port 1 Modbus Protocol device address
0E 02 RP1 Address Unsigned integer (16 bits) 1 Setting 0 to 255 (IEC60870) 0 254 1 1 * * * * * * * Rear Port 1 IEC60870-5-103 Protocol device address
0E 02 RP1 Address Unsigned integer (16 bits) 1 Setting 0 to 65534 (DNP3.0) 0 65534 1 1 * * * * * * * Rear Port 1 DNP 3.0 Protocol device address
0E 03 RP1 InactivTimer Courier Number (Time-minutes) 15 Setting 1 min to 30 min step 1 min (Courier) 1 30 1 2 * * * * * * * Rear Port 1 Courier Protocol inactivity timer
0E 03 RP1 InactivTimer Courier Number (Time-minutes) 15 Setting 1 min to 30 min step 1 min (Modbus) 1 30 1 2 * * * * * * * Rear Port 1 Modbus Protocol inactivity timer
0E 03 RP1 InactivTimer Courier Number (Time-minutes) 15 Setting 1 min to 30 min step 1 min (IEC60870) 1 30 1 2 * * * * * * * Rear Port 1 IEC60870-5-103 Protocol inactivity timer
0E 04 RP1 Baud Rate Indexed String G38m 19200 bits/s Setting 9600 bps, 19200 bps, 38400 bps (Modbus) 0 2 1 2 * * * * * * * Rear Port 1 Modbus Protcol serial bit/baud rate
0E 04 RP1 Baud Rate Indexed String G38v 19200 bits/s Setting 9600 bps, 19200 bps, 38400 bps (IEC60870) 0 1 1 2 * * * * * * * Rear Port 1 IEC60870-5-103 Protcol serial bit/baud rate
0E 04 RP1 Baud Rate Indexed String G38d 19200 bits/s Setting 9600 bps, 19200 bps, 38400 bps (DNP3.0) 0 5 1 2 * * * * * * * Rear Port 1 DNP 3.0 Protcol serial bit/baud rate
0E 05 RP1 Parity Indexed String G39 None Setting Odd, Even, None (Modbus) 0 2 1 2 * * * * * * * Rear Port 1 Modbus Protocol parity
0E 05 RP1 Parity Indexed String G39 None Setting Odd, Even, None (DNP3.0) 0 2 1 2 * * * * * * * Rear Port 1 DNP 3.0 Protocol parity
0E 06 RP1 Meas Period Courier Number (Time) 15 Setting 1s to 60s step 1s (IEC60870) 1 60 1 2 * * * * * * * Rear Port 1 IEC60870-5-103 Protocol measurment period
0E 07 RP1 PhysicalLink Indexed String G21 Copper Setting Copper, fiber Optic, Kbus 0 1 1 1 * * * * * * * Rear Port 1 Physical link selector. Available when Fibre Optic Comms card is specified by model number
0E 08 RP1 Time Sync Indexed String G37 Disabled Setting Enabled, Disabled (DNP3.0) 0 1 1 2 * * * * * * * Rear Port 1 DNP 3.0 Protocol time sync configuration. NB Not available when IRIG-B option fitted and enabled.
0E 09 Modbus IEC Time Indexed String 4x00306 G238 G238 1 Standard Setting Standard, Reverse (IEC60870) 0 1 1 2 * * * * * * * Controls the format of the time-date G12 data type. Modbus Only.
0E 0A RP1 CS103Blcking Indexed String G210 Disabled Setting Disabled, Monitor blocking, Command Blocking (IEC60870) 0 2 1 2 * * * * * * * Rear Port 1 IEC60870-5-103 Protocol blocking configuration
0E 0B RP1 Card Status Indexed String G208 Data K-Bus OK, EIA485 OK, Fiber Optic OK (Courier) * * * * * * * Rear Port 1 Courier Protocol Status
0E 0C RP1 Port Config Indexed String G207 K-Bus Setting Kbus, EIA485 (Courier) 0 1 1 2 * * * * * * * Rear Port 1 Courier Protocol copper port configuration; K-Bus or EIA485
0E 0D RP1 Comms Mode Indexed String G206 IEC60870 FT1.2 Setting IEC60870 FT1.2 Frame, 10-bit No parity 0 1 1 2 * * * * * * * Rear Port 1 Courier Protocol EIA485 mode
0E 0E RP1 Baud Rate Indexed String G38c 19200 bits/s Setting 9600 bps, 19200 bps, 38400 bps (Courier) 0 2 1 2 * * * * * * * Rear Port 1 Courier Protocol EIA485 bit/baud rate
0E 11 DNP Need Time Courier Number (Time) 10 Setting 1 to 30 step 1 (DNP3.0) 1 30 1 2 * * * * * * *
0E 12 DNP App Fragment Unsigned Integer 2048 Setting 100 to 2048 step 1 (DNP3.0) 100 2048 1 2 * * * * * * *
0E 13 DNP App Timeout Courier Number (Time) 2 Setting 1 to 120 step 1 (DNP3.0) 1 120 1 2 * * * * * * *
0E 14 DNP SBO Timeout Courier Number (Time) 10 Setting 1 to 10 step 1 (DNP3.0) 1 10 1 2 * * * * * * *
0E 15 DNP Link Timeout Courier Number (Time) 0 Setting 0s to 120s step 1s 0 120 1 2 * * * * * * *
0E 1F NIC Protocol Indexed String G235 IEC61850 Data IEC61850 (Ethernet) * * * * * * *
0E 22 NIC MAC Address ASCII Text (17 chars) Ethernet MAC AddData MAC address (Ethernet) * * * * * * *
0E 64 NIC Tunl Timeout Courier Number (time-minutes) 5.00 min Setting 1 min to 30 min step 1 min (Ethernet) 1 30 1 2 * * * * * * *
0E 6A NIC Link Report Indexed String G226 Alarm Setting Alarm, Event, None (Ethernet) 0 2 1 2 * * * * * * *
0E 80 REAR PORT2 (RP2) (Sub Heading) * * * * * * * Visible when Rear Port 2 fitted.
0E 81 RP2 Protocol ASCII Text(16 chars) Courier Data <Protocol> * * * * * * * Rear Port 2 Protocol - "Courier"
0E 84 RP2 Card Status Indexed String G204 Data Unsupported, Card not fitted, EIA232 OK, EIA485 OK, Kbus OK * * * * * * * Rear Port 2 Courier Protocol Status
0E 88 RP2 Port Config Indexed String G205 EIA232 (RS232) Setting EIA232, EIA485, Kbus 0 2 1 2 * * * * * * * Rear Port 2 Courier Protocol port configuration; K-Bus or EIA485
0E 8A RP2 Comms Mode Indexed String G206 IEC60870 FT1.2 Setting IEC60870 FT1.2 Frame, 10-bit No parity 0 1 1 2 * * * * * * * Rear Port 2 Courier Protocol EIA485 mode
0E 90 RP2 Address Unsigned Integer (16 bits) 255 Setting 0 to 255 0 255 1 1 * * * * * * * Rear Port 2 Courier Protocol device address
0E 92 RP2 InactivTimer Courier Number (time-minutes) 15 Setting 1 min to 30 min step 1 min 1 30 1 2 * * * * * * * Rear Port 2 Courier Protocol inactivity timer
0E 94 RP2 Baud Rate Indexed String G38c 19200 bits/s Setting 9600 bps, 19200 bps, 38400 bps 0 2 1 2 * * * * * * * Rear Port 2 Courier Protocol EIA485 bit/baud rate
0E A0 NIC Protocol Indexed String DNP3 Data DNP3(Ethernet) 1 * * * * * * *
0E A1 IP address ASCII Text(16 chars) 0.0.0.0 Data <IP address of relay> 1 * * * * * * *
0E A2 Subnet mask ASCII Text(16 chars) 0.0.0.0 Data <Subnet mask of relay> 1 * * * * * * *
0E A3 NIC MAC Address ASCII Text (17 chars) Ethernet MAC AddData MAC address (Ethernet) 1 * * * * * * *
0E A4 Gateway ASCII Text 0.0.0.0 Data <Gateway address> 1 * * * * * * *
0E A5 DNP Time Sync Indexed String G37 Disabled Setting Disabled, Enabled 0 1 1 1 * * * * * * *
0E A6 Meas Scaling Indexed String G249 Normalised Setting Normalised, Primary, Secondary 0 2 1 1 * * * * * * *
0E A7 NIC Tunl Timeout Courier Number (time-minutes) 5 mins Setting 1 min to 30 min step 1 min 1 30 1 1 * * * * * * *
0E A8 NIC Link Report Indexed String G226 Alarm Setting Alarm, Event, None 0 2 1 1 * * * * * * *
0E AA SNTP PARAMETERS Sub Heading 1 * * * * * * *
0E AB SNTP Server 1 Courier Number (time-minutes) 0.0.0.0 Data <IP address of SNTP server 1> 1 * * * * * * *
0E AC SNTP Server 2 Indexed String 0.0.0.0 Data <IP address of SNTP server 2> 1 * * * * * * *
0E AD SNTP Poll Rate Courier Number (time) 64 s Data 1 * * * * * * *
0E B1 DNP Need Time Courier Number (time) 10 Setting 1 to 30 step 1 1 30 1 1 * * * * * * * The duration of time waited before requesting another time sync from the master
0E B2 DNP App Fragment Unsigned Integer 2048 Setting 100 to 2048 step 1 (DNP3.0) 100 2048 1 1 * * * * * * * The maximum message length (application fragment size) transmitted by the relay
0E B3 DNP App Timeout Courier Number (time) 2 Setting 1 to 120 step 1 (DNP3.0) 1 120 1 1 * * * * * * * Duration of time waited, after sending a message fragment and awaiting a confirmation from the master
0E B4 DNP SBO Timeout Courier Number (time) 10 Setting 1 to 10 step 1 (DNP3.0) 1 10 1 1 * * * * * * * Duration of time waited, after receiving a select command and awaiting an operate confirmation from the master
0F 00 COMMISSION TESTS * * * * * * *
0F 01 Opto I/P Status Binary Flag (32 bits); Indexed String 3x00725 3x00726 G8 G8 2 Data 16-bit binary string * * * * * * * The original register 30007 is available for Opto Inputs #1 to #16.
0F 02 Relay O/P Status Binary Flag (32 bits); Indexed String 3x00008 3x00009 G9 G9 2 Data 16-bit binary string * * * * * * *
0F 03 Test Port Status Binary Flag(8 bits); Indexed String 3x00722 G1 1 Data 8-bit binary string * * * * * * *
0F 04 LED Status Binary Flag(8 bits) Data 8-bit binary string * * * * * *
0F 05 Monitor Bit 1 Unsigned Integer 4x00850 G1 1 64 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 06 Monitor Bit 2 Unsigned Integer 4x00851 G1 1 65 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 07 Monitor Bit 3 Unsigned Integer 4x00852 G1 1 66 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 08 Monitor Bit 4 Unsigned Integer 4x00853 G1 1 67 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 09 Monitor Bit 5 Unsigned Integer 4x00854 G1 1 68 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 0A Monitor Bit 6 Unsigned Integer 4x00855 G1 1 69 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 0B Monitor Bit 7 Unsigned Integer 4x00856 G1 1 70 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 0C Monitor Bit 8 Unsigned Integer 4x00857 G1 1 71 Setting 0, 1 (LED off or on) 0 1022 1 1 * * * * * * *
0F 0D Test Mode Indexed String 4x00858 G119 G119 1 Disabled Setting Disabled, Test Mode, Contacts Blocked 0 2 1 2 * * * * * * * IEC60870 Test Mode Change
0F 0E Test Pattern Binary Flag (32bits) 4x00859 4x00860 G9 G9 2 0 Setting 32 bit binary string 0 20 1 2 * * * * * * * IEC60870 Test Mode Change
0F 0F Contact Test Indexed String 4x00861 G93 G93 1 No Operation Command No Operation, Apply Test, Remove Test 0 2 1 2 * * * * * * * IEC60870 Test Mode Change
0F 10 Test LEDs Indexed String 4x00862 G94 G94 1 No Operation Command No Operation, Apply Test 0 1 1 2 * * * * * * *
0F 15 Red LED Status Binary Flag (32 bits); Indexed String Data 18-bit binary string * * * *
0F 16 Green LED Status Binary Flag (32 bits); Indexed String Data 18-bit binary string * * * *
0F 1A 64S R sec (test) Courier Number (resistance) 3x11200 3x11201 G125 2 Data 32-bit binary string St EFI secondary resistance measurement during commissioning. Used for setting 'Series R' in 64S
0F 1B 64S R pri (test) Courier Number (resistance) 3x11202 3x11203 G125 2 Data 32-bit binary string St EFI primary resistance measurement during commissioning. Used for setting 'Series R' in 64S
0F 1C 64S X sec (test) Courier Number (reactance) 3x11204 3x11205 G125 2 Data 32-bit binary string St EFI secondary reactance measurement during commissioning. Used for setting 'Series X' in 64S
0F 1D 64S X pri (test) Courier Number (reactance) 3x11206 3x11207 G125 2 Data 32-bit binary string St EFI primary reactance measurement during commissioning. Used for setting 'Series X' in 64S
0F 20 DDB 31 - 0 Binary Flag(32) N/A 3x11023 3x11024 G27 2 Data 32-bit binary string * * * * * * * See DDB definition table.
0F 21 DDB 63 - 32 Binary Flag(32) N/A 3x11025 3x11026 G27 2 Data 32-bit binary string * * * * * * *
0F 22 DDB 95 - 64 Binary Flag(32) N/A 3x11027 3x11028 G27 2 Data 32-bit binary string * * * * * * *
0F 23 DDB 127 - 96 Binary Flag(32) N/A 3x11029 3x11030 G27 2 Data 32-bit binary string * * * * * * *
0F 24 DDB 159 - 128 Binary Flag(32) N/A 3x11031 3x11032 G27 2 Data 32-bit binary string * * * * * * *
0F 25 DDB 191 - 160 Binary Flag(32) N/A 3x11033 3x11034 G27 2 Data 32-bit binary string * * * * * * *
0F 26 DDB 223 - 192 Binary Flag(32) N/A 3x11035 3x11036 G27 2 Data 32-bit binary string * * * * * * *
0F 27 DDB 255 - 224 Binary Flag(32) N/A 3x11037 3x11038 G27 2 Data 32-bit binary string * * * * * * *
0F 28 DDB 287 - 256 Binary Flag(32) N/A 3x11039 3x11040 G27 2 Data 32-bit binary string * * * * * * *
0F 29 DDB 319 - 288 Binary Flag(32) N/A 3x11041 3x11042 G27 2 Data 32-bit binary string * * * * * * *
0F 2A DDB 351 - 320 Binary Flag(32) N/A 3x11043 3x11044 G27 2 Data 32-bit binary string * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 10 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
0F 2B DDB 383 - 352 Binary Flag(32) N/A 3x11045 3x11046 G27 2 Data 32-bit binary string * * * * * * *
0F 2C DDB 415 - 384 Binary Flag(32) N/A 3x11047 3x11048 G27 2 Data 32-bit binary string * * * * * * *
0F 2D DDB 447 - 416 Binary Flag(32) N/A 3x11049 3x11050 G27 2 Data 32-bit binary string * * * * * * *
0F 2E DDB 479 - 448 Binary Flag(32) N/A 3x11051 3x11052 G27 2 Data 32-bit binary string * * * * * * *
0F 2F DDB 511 - 480 Binary Flag(32) N/A 3x11053 3x11054 G27 2 Data 32-bit binary string * * * * * * *
0F 30 DDB 543 - 512 Binary Flag(32) N/A 3x11055 3x11056 G27 2 Data 32-bit binary string * * * * * * *
0F 31 DDB 575 - 544 Binary Flag(32) N/A 3x11057 3x11058 G27 2 Data 32-bit binary string * * * * * * *
0F 32 DDB 607 - 576 Binary Flag(32) N/A 3x11059 3x11060 G27 2 Data 32-bit binary string * * * * * * *
0F 33 DDB 639 - 608 Binary Flag(32) N/A 3x11061 3x11062 G27 2 Data 32-bit binary string * * * * * * *
0F 34 DDB 671 - 640 Binary Flag(32) N/A 3x11063 3x11064 G27 2 Data 32-bit binary string * * * * * * *
0F 35 DDB 703 - 672 Binary Flag(32) N/A 3x11065 3x11066 G27 2 Data 32-bit binary string * * * * * * *
0F 36 DDB 735 - 704 Binary Flag(32) N/A 3x11067 3x11068 G27 2 Data 32-bit binary string * * * * * * *
0F 37 DDB 767 - 736 Binary Flag(32) N/A 3x11069 3x11070 G27 2 Data 32-bit binary string * * * * * * *
0F 38 DDB 799 - 768 Binary Flag(32) N/A 3x11071 3x11072 G27 2 Data 32-bit binary string * * * * * * *
0F 39 DDB 831 - 800 Binary Flag(32) N/A 3x11073 3x11074 G27 2 Data 32-bit binary string * * * * * * *
0F 3A DDB 863 - 832 Binary Flag(32) N/A 3x11075 3x11076 G27 2 Data 32-bit binary string * * * * * * *
0F 3B DDB 895 - 864 Binary Flag(32) N/A 3x11077 3x11078 G27 2 Data 32-bit binary string * * * * * * *
0F 3C DDB 927 - 896 Binary Flag(32) N/A 3x11079 3x11080 G27 2 Data 32-bit binary string * * * * * * *
0F 3D DDB 959 - 928 Binary Flag(32) N/A 3x11081 3x11082 G27 2 Data 32-bit binary string * * * * * * *
0F 3E DDB 991 - 960 Binary Flag(32) N/A 3x11083 3x11084 G27 2 Data 32-bit binary string * * * * * * *
0F 3F DDB 1023 - 992 Binary Flag(32) N/A 3x11085 3x11086 G27 2 Data 32-bit binary string * * * * * * *
0F 40 DDB 1055-1024 Binary Flag(32) N/A 3x11087 3x11088 G27 2 Data 32-bit binary string * * * * * * *
0F 41 DDB 1087-1056 Binary Flag(32) N/A 3x11089 3x11090 G27 2 Data 32-bit binary string * * * * * * *
0F 42 DDB 1119-1088 Binary Flag(32) N/A 3x11091 3x11092 G27 2 Data 32-bit binary string * * * * * * *
0F 43 DDB 1151-1120 Binary Flag(32) N/A 3x11093 3x11094 G27 2 Data 32-bit binary string * * * * * * *
0F 44 DDB 1183-1152 Binary Flag(32) N/A 3x11095 3x11096 G27 2 Data 32-bit binary string * * * * * * *
0F 45 DDB 1215-1184 Binary Flag(32) N/A 3x11097 3x11098 G27 2 Data 32-bit binary string * * * * * * *
0F 46 DDB 1247-1216 Binary Flag(32) N/A 3x11099 3x11100 G27 2 Data 32-bit binary string * * * * * * *
0F 47 DDB 1279-1248 Binary Flag(32) N/A 3x11101 3x11102 G27 2 Data 32-bit binary string * * * * * * *
0F 48 DDB 1311-1280 Binary Flag(32) N/A 3x11103 3x11104 G27 2 Data 32-bit binary string * * * * * * *
0F 49 DDB 1343-1312 Binary Flag(32) N/A 3x11105 3x11106 G27 2 Data 32-bit binary string * * * * * * *
0F 4A DDB 1375-1344 Binary Flag(32) N/A 3x11107 3x11108 G27 2 Data 32-bit binary string * * * * * * *
0F 4B DDB 1407-1376 Binary Flag(32) N/A 3x11109 3x11110 G27 2 Data 32-bit binary string * * * * * * *
0F 4C DDB 1439-1408 Binary Flag(32) N/A 3x11111 3x11112 G27 2 Data 32-bit binary string * * * * * * *
0F 4D DDB 1471-1440 Binary Flag(32) N/A 3x11113 3x11114 G27 2 Data 32-bit binary string * * * * * * *
0F 4E DDB 1503-1472 Binary Flag(32) N/A 3x11115 3x11116 G27 2 Data 32-bit binary string * * * * * * *
0F 4F DDB 1535-1504 Binary Flag(32) N/A 3x11117 3x11118 G27 2 Data 32-bit binary string * * * * * * *
0F 50 DDB 1567-1536 Binary Flag(32) N/A 3x11119 3x11120 G27 2 Data 32-bit binary string * * * * * * *
0F 51 DDB 1599-1568 Binary Flag(32) N/A 3x11121 3x11122 G27 2 Data 32-bit binary string * * * * * * *
0F 52 DDB 1631-1600 Binary Flag(32) N/A 3x11123 3x11124 G27 2 Data 32-bit binary string * * * * * * *
0F 53 DDB 1663-1632 Binary Flag(32) N/A 3x11125 3x11126 G27 2 Data 32-bit binary string * * * * * * *
0F 54 DDB 1695-1664 Binary Flag(32) N/A 3x11127 3x11128 G27 2 Data 32-bit binary string * * * * * * *
0F 55 DDB 1727-1696 Binary Flag(32) N/A 3x11129 3x11130 G27 2 Data 32-bit binary string * * * * * * *
0F 56 DDB 1759-1728 Binary Flag(32) N/A 3x11131 3x11132 G27 2 Data 32-bit binary string * * * * * * *
0F 57 DDB 1791-1760 Binary Flag(32) N/A 3x11133 3x11134 G27 2 Data 32-bit binary string * * * * * * *
0F 58 DDB 1823-1792 Binary Flag(32) N/A 3x11135 3x11136 G27 2 Data 32-bit binary string * * * * * * *
0F 59 DDB 1855-1824 Binary Flag(32) N/A 3x11137 3x11138 G27 2 Data 32-bit binary string * * * * * * *
0F 5A DDB 1887-1856 Binary Flag(32) N/A 3x11139 3x11140 G27 2 Data 32-bit binary string * * * * * * *
0F 5B DDB 1919-1888 Binary Flag(32) N/A 3x11141 3x11142 G27 2 Data 32-bit binary string * * * * * * *
0F 5C DDB 1951-1920 Binary Flag(32) N/A 3x11143 3x11144 G27 2 Data 32-bit binary string * * * * * * *
0F 5D DDB 1983-1952 Binary Flag(32) N/A 3x11145 3x11146 G27 2 Data 32-bit binary string * * * * * * *
0F 5E DDB 2015-1984 Binary Flag(32) N/A 3x11147 3x11148 G27 2 Data 32-bit binary string * * * * * * *
0F 5F DDB 2047-2016 Binary Flag(32) N/A 3x11149 3x11150 G27 2 Data 32-bit binary string * * * * * * *
10 00 CB MONITOR SETUP * * * * * * *
10 01 Broken I^ Courier Number (Decimal) 4x00151 G2 10 1 2 Setting 1 to 2 step 0.1 1 2 0.1 2 * * * * * * * Broken Current Index
10 02 I^ Maintenance Indexed String 4x00152 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Broken Current to cause maintenance alarm
10 03 I^ Maintenance Courier Number (Current) 4x00153 4x00154 G35 2500000000 2 1000 Setting 1*In^ to 25000*In^ step 1*In^ 1 25000 1 2 * * * * * * * IX Maintenance Alarm
10 04 I^ Lockout Indexed String 4x00155 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Broken Current to cause lockout alarm
10 05 I^ Lockout Courier Number (Current) 4x00156 4x00157 G35 2500000000 2 2000 Setting 1*In^ to 25000*In^ step 1*In^ 1 25000 1 2 * * * * * * * IX Maintenance Lockout
10 06 No. CB Ops Maint Indexed String 4x00158 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Circuit Breaker Trips to cause maintenance alarm
10 07 No. CB Ops Maint Unsigned Integer 4x00159 G1 250 1 10 Setting 1 to 10000 step 1 1 10000 1 2 * * * * * * * Number of Circuit Breaker Trips for maintenance alarm
10 08 No. CB Ops Lock Indexed String 4x00160 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Circuit Breaker Trips to cause lockout alarm
10 09 No. CB Ops Lock Unsigned Integer 4x00161 G1 250 1 20 Setting 1 to 10000 step 1 1 10000 1 2 * * * * * * * Number of Circuit Breaker Trips for lockout alarm
10 0A CB Time Maint Indexed String 4x00162 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Circuit Breaker Operating Time to cause maintenance alarm
10 0B CB Time Maint Courier Number (Time) 4x00163 4x00164 G35 500000 2 0.1 Setting 0.005s to 0.5s step 0.001s 0.005 0.5 0.001 2 * * * * * * * Circuit Breaker Operating time for maintenance alarm
10 0C CB Time Lockout Indexed String 4x00165 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Circuit Breaker Operating Time to cause lockout alarm
10 0D CB Time Lockout Courier Number (Time) 4x00166 4x00167 G35 500000 2 0.2 Setting 0.005s to 0.5s step 0.001s 0.005 0.5 0.001 2 * * * * * * * Circuit Breaker Operating time for lockout alarm
10 0E Fault Freq Lock Indexed String 4x00168 G88 G88 1 Alarm Disabled Setting Alarm Disabled, Alarm Enabled 0 1 1 2 * * * * * * * Excessive fault frequency
10 0F Fault Freq Count Unsigned Integer 4x00169 G1 9999 1 10 Setting 1 to 9999 step 1 1 9999 1 2 * * * * * * * Excessive Fault Frequency Counter
10 10 Fault Freq Time Courier Number (Time) 4x00170 4x00171 G35 999900 2 3600 Setting 0s to 9999s step 1s 0 9999 1 2 * * * * * * * Excessive Fault Frequency Time
11 00 OPTO CONFIG * * * * * * * Visible for Model Number design suffix 'B' and beyond
11 01 Global Nominal V Indexed String 4x00900 G200 G200 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250, custom 0 5 1 2 * * * * * * * Select Custom to select individual Opto . Threshold Voltages
11 02 Opto Input 1 Indexed String 4x00901 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 03 Opto Input 2 Indexed String 4x00902 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 04 Opto Input 3 Indexed String 4x00903 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 05 Opto Input 4 Indexed String 4x00904 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 06 Opto Input 5 Indexed String 4x00905 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 07 Opto Input 6 Indexed String 4x00906 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 08 Opto Input 7 Indexed String 4x00907 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 09 Opto Input 8 Indexed String 4x00908 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 0A Opto Input 9 Indexed String 4x00909 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 0B Opto Input 10 Indexed String 4x00910 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 0C Opto Input 11 Indexed String 4x00911 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 0D Opto Input 12 Indexed String 4x00912 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 0E Opto Input 13 Indexed String 4x00913 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 0F Opto Input 14 Indexed String 4x00914 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 10 Opto Input 15 Indexed String 4x00915 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 11 Opto Input 16 Indexed String 4x00916 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 12 Opto Input 17 Indexed String 4x00917 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 13 Opto Input 18 Indexed String 4x00918 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 14 Opto Input 19 Indexed String 4x00919 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 15 Opto Input 20 Indexed String 4x00920 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 16 Opto Input 21 Indexed String 4x00921 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 17 Opto Input 22 Indexed String 4x00922 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 18 Opto Input 23 Indexed String 4x00923 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 19 Opto Input 24 Indexed String 4x00924 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * * * * *
11 1A Opto Input 25 Indexed String 4x00925 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 1B Opto Input 26 Indexed String 4x00926 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 1C Opto Input 27 Indexed String 4x00927 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 1D Opto Input 28 Indexed String 4x00928 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 1E Opto Input 29 Indexed String 4x00929 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 1F Opto Input 30 Indexed String 4x00930 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 20 Opto Input 31 Indexed String 4x00931 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 21 Opto Input 32 Indexed String 4x00932 G201 G201 1 48-54V Setting 24-27, 30-34, 48-54, 110-125, 220-250 0 4 1 2 * * * *
11 50 Opto Filter Ctrl Binary Flag (32 bits) 4x00933 4x00934 G8 G8 1 0xFFFFFFFF Setting 16 bit binary string (0 disable filtering, 1 enable filtering) 0xFFFFFFFF 32 1 2 * * * * * * * Opto filter configuration
11 80 Characteristic Indexed String 4x00935 G237 G237 1 Standard 60%-80 Setting 0 = Standard 60%-80%, 1 = 50%-70% 0 1 1 2 * * * * * * * Opto input pickup & drop-off threshold. Applicable to design suffix "J" or better.
12 00 CONTROL INPUTS * * * * * * *
12 01 Ctrl I/P Status Binary Flag (32 bits); Indexed String 4x00950 4x00951 G202 G202 2 Setting 32 bit binary string. (Set = 1, Reset = 0) 2 * * * * * * *
12 02 Control Input 1 Indexed String 4x00952 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 03 Control Input 2 Indexed String 4x00953 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 04 Control Input 3 Indexed String 4x00954 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 05 Control Input 4 Indexed String 4x00955 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 06 Control Input 5 Indexed String 4x00956 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 07 Control Input 6 Indexed String 4x00957 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 08 Control Input 7 Indexed String 4x00958 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 09 Control Input 8 Indexed String 4x00959 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 0A Control Input 9 Indexed String 4x00960 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 0B Control Input 10 Indexed String 4x00961 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 0C Control Input 11 Indexed String 4x00962 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 0D Control Input 12 Indexed String 4x00963 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 0E Control Input 13 Indexed String 4x00964 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 0F Control Input 14 Indexed String 4x00965 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 10 Control Input 15 Indexed String 4x00966 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 11 Control Input 16 Indexed String 4x00967 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 12 Control Input 17 Indexed String 4x00968 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 13 Control Input 18 Indexed String 4x00969 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 14 Control Input 19 Indexed String 4x00970 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 15 Control Input 20 Indexed String 4x00971 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 16 Control Input 21 Indexed String 4x00972 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 17 Control Input 22 Indexed String 4x00973 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 18 Control Input 23 Indexed String 4x00974 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 19 Control Input 24 Indexed String 4x00975 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 1A Control Input 25 Indexed String 4x00976 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 1B Control Input 26 Indexed String 4x00977 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 1C Control Input 27 Indexed String 4x00978 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 1D Control Input 28 Indexed String 4x00979 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 1E Control Input 29 Indexed String 4x00980 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 1F Control Input 30 Indexed String 4x00981 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 20 Control Input 31 Indexed String 4x00982 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
12 21 Control Input 32 Indexed String 4x00983 G203 G203 1 No Operation Command No Operation, Set, Reset 0 2 1 2 * * * * * * *
13 00 CTRL I/P CONFIG * * * * * * *
13 01 Hotkey Enabled Binary Flag (32 bits); Indexed String G233 0xFFFFFFFF Setting 32 bit binary string. (Enabled = 1, Disabled = 0) 0xFFFFFFFF 32 1 2 * * * * * * * Hotkey Menu - Control Input availability
13 10 Control Input 1 Indexed String 4x10002 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 11 Ctrl Command 1 Indexed String 4x10003 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 11 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
13 14 Control Input 2 Indexed String 4x10004 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 15 Ctrl Command 2 Indexed String 4x10005 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 18 Control Input 3 Indexed String 4x10006 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 19 Ctrl Command 3 Indexed String 4x10007 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 1C Control Input 4 Indexed String 4x10008 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 1D Ctrl Command 4 Indexed String 4x10009 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 20 Control Input 5 Indexed String 4x10010 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 21 Ctrl Command 5 Indexed String 4x10011 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 24 Control Input 6 Indexed String 4x10012 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 25 Ctrl Command 6 Indexed String 4x10013 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 28 Control Input 7 Indexed String 4x10014 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 29 Ctrl Command 7 Indexed String 4x10015 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 2C Control Input 8 Indexed String 4x10016 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 2D Ctrl Command 8 Indexed String 4x10017 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 30 Control Input 9 Indexed String 4x10018 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 31 Ctrl Command 9 Indexed String 4x10019 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 34 Control Input 10 Indexed String 4x10020 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 35 Ctrl Command 10 Indexed String 4x10021 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 38 Control Input 11 Indexed String 4x10022 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 39 Ctrl Command 11 Indexed String 4x10023 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 3C Control Input 12 Indexed String 4x10024 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 3D Ctrl Command 12 Indexed String 4x10025 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 40 Control Input 13 Indexed String 4x10026 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 41 Ctrl Command 13 Indexed String 4x10027 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 44 Control Input 14 Indexed String 4x10028 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 45 Ctrl Command 14 Indexed String 4x10029 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 48 Control Input 15 Indexed String 4x10030 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 49 Ctrl Command 15 Indexed String 4x10031 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 4C Control Input 16 Indexed String 4x10032 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 4D Ctrl Command 16 Indexed String 4x10033 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 50 Control Input 17 Indexed String 4x10034 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 51 Ctrl Command 17 Indexed String 4x10035 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 54 Control Input 18 Indexed String 4x10036 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 55 Ctrl Command 18 Indexed String 4x10037 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 58 Control Input 19 Indexed String 4x10038 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 59 Ctrl Command 19 Indexed String 4x10039 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 5C Control Input 20 Indexed String 4x10040 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 5D Ctrl Command 20 Indexed String 4x10041 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 60 Control Input 21 Indexed String 4x10042 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 61 Ctrl Command 21 Indexed String 4x10043 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 64 Control Input 22 Indexed String 4x10044 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 65 Ctrl Command 22 Indexed String 4x10045 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 68 Control Input 23 Indexed String 4x10046 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 69 Ctrl Command 23 Indexed String 4x10047 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 6C Control Input 24 Indexed String 4x10048 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 6D Ctrl Command 24 Indexed String 4x10049 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 70 Control Input 25 Indexed String 4x10050 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 71 Ctrl Command 25 Indexed String 4x10051 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 74 Control Input 26 Indexed String 4x10052 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 75 Ctrl Command 26 Indexed String 4x10053 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 78 Control Input 27 Indexed String 4x10054 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 79 Ctrl Command 27 Indexed String 4x10055 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 7C Control Input 28 Indexed String 4x10056 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 7D Ctrl Command 28 Indexed String 4x10057 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 80 Control Input 29 Indexed String 4x10058 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 81 Ctrl Command 29 Indexed String 4x10059 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 84 Control Input 30 Indexed String 4x10060 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 85 Ctrl Command 30 Indexed String 4x10061 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 88 Control Input 31 Indexed String 4x10062 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 89 Ctrl Command 31 Indexed String 4x10063 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
13 8C Control Input 32 Indexed String 4x10064 G234 G234 1 Latched Setting Latched, Pulsed 0 1 1 2 * * * * * * * Individual Control Input Type
13 8D Ctrl Command 32 Indexed String 4x10065 G232 G232 1 SET/RESET Setting 0 = ON/OFF, 1 = SET/RESET, 2 = IN/OUT, 3 = ENABLED/DISABLED 0 3 1 2 * * * * * * * Individual Control Input Command Text
17 00 FUNCTION KEYS * * * *
17 01 Fn Key Status Binary Flag (10 bits); Indexed String 0 Data 8-bit binary string * * * *
17 02 Fn Key 1 Indexed String 4x10575 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 03 Fn Key 1 Mode Indexed String 4x10576 G243 G243 1 Toggled Setting Toggle, Normal 0 1 1 2 * * * *
17 04 Fn Key 1 Label ASCII Text (16 chars) 4x10577 4x10584 G3 8 Function Key 1 Setting 16 character text string 32 163 1 2 * * * *
17 05 Fn Key 2 Indexed String 4x10585 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 06 Fn Key 2 Mode Indexed String 4x10586 G243 G243 1 Normal Setting Toggle, Normal 0 1 1 2 * * * *
17 07 Fn Key 2 Label ASCII Text (16 chars) 4x10587 4x10594 G3 8 Function Key 2 Setting 16 character text string 32 163 1 2 * * * *
17 08 Fn Key 3 Indexed String 4x10595 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 09 Fn Key 3 Mode Indexed String 4x10596 G243 G243 1 Normal Setting Toggle, Normal 0 1 1 2 * * * *
17 0A Fn Key 3 Label ASCII Text (16 chars) 4x10597 4x10604 G3 8 Function Key 3 Setting 16 character text string 32 163 1 2 * * * *
17 0B Fn Key 4 Indexed String 4x10605 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 0C Fn Key 4 Mode Indexed String 4x10606 G243 G243 1 Toggled Setting Toggle, Normal 0 1 1 2 * * * *
17 0D Fn Key 4 Label ASCII Text (16 chars) 4x10607 4x10614 G3 8 Function Key 4 Setting 16 character text string 32 163 1 2 * * * *
17 0E Fn Key 5 Indexed String 4x10615 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 0F Fn Key 5 Mode Indexed String 4x10616 G243 G243 1 Toggled Setting Toggle, Normal 0 1 1 2 * * * *
17 10 Fn Key 5 Label ASCII Text (16 chars) 4x10617 4x10624 G3 8 Function Key 5 Setting 16 character text string 32 163 1 2 * * * *
17 11 Fn Key 6 Indexed String 4x10625 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 12 Fn Key 6 Mode Indexed String 4x10626 G243 G243 1 Toggled Setting Toggle, Normal 0 1 1 2 * * * *
17 13 Fn Key 6 Label ASCII Text (16 chars) 4x10627 4x10634 G3 8 Function Key 6 Setting 16 character text string 32 163 1 2 * * * *
17 14 Fn Key 7 Indexed String 4x10635 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 15 Fn Key 7 Mode Indexed String 4x10636 G243 G243 1 Normal Setting Toggle, Normal 0 1 1 2 * * * *
17 16 Fn Key 7 Label ASCII Text (16 chars) 4x10637 4x10644 G3 8 Function Key 7 Setting 16 character text string 32 163 1 2 * * * *
17 17 Fn Key 8 Indexed String 4x10645 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 18 Fn Key 8 Mode Indexed String 4x10646 G243 G243 1 Normal Setting Toggle, Normal 0 1 1 2 * * * *
17 19 Fn Key 8 Label ASCII Text (16 chars) 4x10647 4x10654 G3 8 Function Key 8 Setting 16 character text string 32 163 1 2 * * * *
17 1A Fn Key 9 Indexed String 4x10655 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 1B Fn Key 9 Mode Indexed String 4x10656 G243 G243 1 Normal Setting Toggle, Normal 0 1 1 2 * * * *
17 1C Fn Key 9 Label ASCII Text (16 chars) 4x10657 4x10664 G3 8 Function Key 9 Setting 16 character text string 32 163 1 2 * * * *
17 1D Fn Key 10 Indexed String 4x10665 G242 G242 1 Unlocked Setting Disable, Lock, Unlock 0 2 1 2 * * * *
17 1E Fn Key 10 Mode Indexed String 4x10666 G243 G243 1 Normal Setting Toggle, Normal 0 1 1 2 * * * *
17 1F Fn Key 10 Label ASCII Text (16 chars) 4x10667 4x10674 G3 8 Function Key 10 Setting 16 character text string 32 163 1 2 * * * *
19 00 IED CONFIGURATOR * * * * * * *
19 05 Switch Conf.Bank Indexed String G248 No Action Command No action, Switch Banks 0 1 1 2 * * * * * * *
19 0A Restore MCL Indexed String G256 No Action Command No Action, Restore MCL 0 1 1 2 * * * * * * *
19 10 Active Conf.Name ASCII Text Not Available Data <Active configuration name> * * * * * * *
19 11 Active Conf.Rev ASCII Text Not Available Data <Active configuration revision> * * * * * * *
19 20 Inact.Conf.Name ASCII Text Not Available Data <Inactive configuration name * * * * * * *
19 21 Inact.Conf.Rev ASCII Text Not Available Data <Inactive configuration revision> * * * * * * *
19 30 IP PARAMETERS Sub Heading * * * * * * *
19 31 IP Address ASCII Text 0.0.0.0 Data <IP address of relay> * * * * * * *
19 32 Subnet Address ASCII Text 0.0.0.0 Data <Subnet mask of relay> * * * * * * *
19 33 Gateway ASCII Text 0.0.0.0 Data <Gateway address> * * * * * * *
19 40 SNTP PARAMETERS Sub Heading * * * * * * *
19 41 SNTP Server 1 ASCII Text 0.0.0.0 Data <IP address of SNTP server 1> * * * * * * *
19 42 SNTP Server 2 ASCII Text 0.0.0.0 Data <IP address of SNTP server 2> * * * * * * *
19 50 IEC 61850 SCL Sub Heading * * * * * * *
19 51 IED Name ASCII Text Not Available Data <8 character IED name> * * * * * * *
19 60 IEC 61850 GOOSE Sub Heading * * * * * * *
19 70 GoEna Binary Flag (32 bits) 0x00 Setting 8-bit binary string(0 disable goose, 1 enable goose) 0xFF 32 1 2 * * * * * * *
19 71 Test Mode Indexed String 0x00 Setting 8-bit binary string 0xFF 32 1 2 * * * * * * *
19 73 Ignore Test Flag Indexed String G11 No Setting Yes, No 0 1 1 2 * * * * * * *
29 00 CTRL I/P LABELS * * * * * * *
29 01 Control Input 1 ASCII Text (16 chars) 4x10100 4x10107 G3 8 Control Input 1 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 02 Control Input 2 ASCII Text (16 chars) 4x10108 4x10115 G3 8 Control Input 2 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 03 Control Input 3 ASCII Text (16 chars) 4x10116 4x10123 G3 8 Control Input 3 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 04 Control Input 4 ASCII Text (16 chars) 4x10124 4x10131 G3 8 Control Input 4 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 05 Control Input 5 ASCII Text (16 chars) 4x10132 4x10139 G3 8 Control Input 5 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 06 Control Input 6 ASCII Text (16 chars) 4x10140 4x10147 G3 8 Control Input 6 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 07 Control Input 7 ASCII Text (16 chars) 4x10148 4x10155 G3 8 Control Input 7 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 08 Control Input 8 ASCII Text (16 chars) 4x10156 4x10163 G3 8 Control Input 8 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 09 Control Input 9 ASCII Text (16 chars) 4x10164 4x10171 G3 8 Control Input 9 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 0A Control Input 10 ASCII Text (16 chars) 4x10172 4x10179 G3 8 Control Input 10 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 0B Control Input 11 ASCII Text (16 chars) 4x10180 4x10187 G3 8 Control Input 11 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 0C Control Input 12 ASCII Text (16 chars) 4x10188 4x10195 G3 8 Control Input 12 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 0D Control Input 13 ASCII Text (16 chars) 4x10196 4x10203 G3 8 Control Input 13 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 0E Control Input 14 ASCII Text (16 chars) 4x10204 4x10211 G3 8 Control Input 14 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 0F Control Input 15 ASCII Text (16 chars) 4x10212 4x10219 G3 8 Control Input 15 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 10 Control Input 16 ASCII Text (16 chars) 4x10220 4x10227 G3 8 Control Input 16 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 11 Control Input 17 ASCII Text (16 chars) 4x10228 4x10235 G3 8 Control Input 17 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 12 Control Input 18 ASCII Text (16 chars) 4x10236 4x10243 G3 8 Control Input 18 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 13 Control Input 19 ASCII Text (16 chars) 4x10244 4x10251 G3 8 Control Input 19 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 14 Control Input 20 ASCII Text (16 chars) 4x10252 4x10259 G3 8 Control Input 20 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 15 Control Input 21 ASCII Text (16 chars) 4x10260 4x10267 G3 8 Control Input 21 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 16 Control Input 22 ASCII Text (16 chars) 4x10268 4x10275 G3 8 Control Input 22 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 17 Control Input 23 ASCII Text (16 chars) 4x10276 4x10283 G3 8 Control Input 23 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 18 Control Input 24 ASCII Text (16 chars) 4x10284 4x10291 G3 8 Control Input 24 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 19 Control Input 25 ASCII Text (16 chars) 4x10292 4x10299 G3 8 Control Input 25 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 1A Control Input 26 ASCII Text (16 chars) 4x10300 4x10307 G3 8 Control Input 26 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 1B Control Input 27 ASCII Text (16 chars) 4x10308 4x10315 G3 8 Control Input 27 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 1C Control Input 28 ASCII Text (16 chars) 4x10316 4x10323 G3 8 Control Input 28 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 1D Control Input 29 ASCII Text (16 chars) 4x10324 4x10331 G3 8 Control Input 29 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 12 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
29 1E Control Input 30 ASCII Text (16 chars) 4x10332 4x10339 G3 8 Control Input 30 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 1F Control Input 31 ASCII Text (16 chars) 4x10340 4x10347 G3 8 Control Input 31 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
29 20 Control Input 32 ASCII Text (16 chars) 4x10348 4x10355 G3 8 Control Input 32 Setting 16 character text string 32 163 1 2 * * * * * * * Text description for the Control Input.
30 00 GROUP 1 SYSTEM CONFIG * * * * * * *
30 01 Winding Config Indexed String 4x11004 G174 G174 1 Generator Setting 0 1 1 2 * * * * *
30 02 Ref Power S Courier Number (VA) 4x11005 G2 G2 1 100M Setting 0.1M 5000M 0.1 2 * * * *
30 11 HV Connection Indexed String 4x11006 G175 G175 1 Y-Wye Setting 0 2 1 2 * * * *
30 12 HV Grounding Indexed String 4x11007 G176 G176 1 Grounded Setting 0 1 1 2 * * * *
30 13 HV Nominal Courier Number (Voltage) 4x11008 4x11009 G1 G35 999900 2 220 kV Setting 100 1M 1 2 * * * *
30 20 %Reactance Courier Number (Percentage) 4x11011 G2 G2 1 10% Setting 1 100 0.1 * * * *
30 31 LV Vector Group Unsigned Integer 4x11012 G1 G1 1 0 Setting 0 11 1 2 * * * *
30 32 LV Connection Indexed String 4x11013 G175 G175 1 Y-Wye Setting D-Delta Z-Zigzag 2 * * * *
30 33 LV Grounding Indexed String 4x11014 G176 G176 1 Grounded Setting 2 * * * *
30 34 LV Nominal Courier Number (Voltage) 4x11015 4x11016 G1 G35 2 11KV Setting 100 1M 1 2 * * * * *
30 40 Match Factor HV Courier Number (Decimal) G2 G2 1 Data * * * *
30 41 Match Factor LV Courier Number (Decimal) G2 G2 1 Data * * * *
30 42 Phase Sequence Indexed String 4x11000 G163 G163 1 Standard ABC Setting 0= Standard ABC, 1 = Reverse ACB 0 1 1 2 * * * * * * *
30 43 VT Reversal Indexed String 4x11001 G164 G164 1 No Swap Setting 0= No Swap, 1 = A-B Swapped, 2 = B-C Swapped, 3 = C-A Swapped 0 3 1 2 * * * * * * *
30 44 CT1 Reversal Indexed String 4x11002 G164 G164 1 No Swap Setting 0= No Swap, 1 = A-B Swapped, 2 = B-C Swapped, 3 = C-A Swapped 0 3 1 2 * * * * * * *
30 45 CT2 Reversal Indexed String 4x11003 G164 G164 1 No Swap Setting 0= No Swap, 1 = A-B Swapped, 2 = B-C Swapped, 3 = C-A Swapped 0 3 1 2 * *
30 50 C/S Input Indexed String 4x11018 G40 G40 1 A-N Setting 0 5 1 2 * * * * * * * I*=Phase CT secondary rating
30 51 C/S V Ratio Corr Courier Number 4x11019 G2 G2 1 1 Setting 0.1 2 0.001 2 * * * * * * *
30 52 C/S VT Vect Grp Courier Number 4x11020 G2 G2 1 0 Setting 0 11 1 2 * * * * * * *
30 53 Main VT Location Indexed String 4x11021 G177 G177 1 Gen Setting 0 1 1 2 * * * * * * * Neutral Displacement VT Primary
31 00 GROUP 1 POWER * * * * * * *
31 20 Operating Mode Indexed String 4x01064 G115 G115 0 Generating Setting 0 = Generating, 1 = Motoring 0 1 1 2 * * * * * * *
31 24 Power1 Function Indexed String 4x01050 G102 G102 1 Over Setting 0 = Disabled, 1 = Reverse, 2 = Low Forward, 3 = Over 0 3 1 2 * * * * * * *
Reverse
31 28 -P>1 Setting Courier Number (Power) 4x01051 G2 143 1 20 Setting 4*V1*I1 to 300*V1*I1 step 1*V1*I1 4*V1*I1 300*V1*I1 1*V1*I1 2 * * * * * * *
592 1 5 1*V1*I1 to 300*V1*I1 step 0.2*V1*I1 1*V1*I1 300*V1*I1 0.2*V1*I1 2
31 2C P<1 Setting Courier Number (Power) 4x01052 G2 143 1 20 Setting 4*V1*I1 to 300*V1*I1 step 1*V1*I1 4*V1*I1 300*V1*I1 1*V1*I1 2 * * * * * * *
592 1 10 1*V1*I1 to 300*V1*I1 step 0.2*V1*I1 1*V1*I1 300*V1*I1 0.2*V1*I1 2
31 30 P>1 Setting Courier Number (Power) 4x01053 G2 143 1 120 Setting 4*V1*I1 to 300*V1*I1 step 1*V1*I1 4*V1*I1 300*V1*I1 1*V1*I1 2 * * * * * * *
592 1 120 1*V1*I1 to 300*V1*I1 step 0.2*V1*I1 1*V1*I1 300*V1*I1 0.2*V1*I1 2
31 34 Power1 TimeDelay Courier Number (Time) 4x01054 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
31 38 Power1 DO Timer Courier Number (Time) 4x01055 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
31 3C P1 Poledead Inh Indexed String 4x01056 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
31 40 Power2 Function Indexed String 4x01057 G102 G102 1 Disabled Setting 0 = Disabled, 1 = Reverse, 2 = Low Forward, 3 = Over 0 3 1 2 * * * * * * *
Low Forward
31 44 -P>2 Setting Courier Number (Power) 4x01058 G2 143 1 20 Setting 4*V1*I1 to 300*V1*I1 step 1*V1*I1 4*V1*I1 300*V1*I1 1*V1*I1 2 * * * * * * *
592 1 5 1*V1*I1 to 300*V1*I1 step 0.2*V1*I1 1*V1*I1 300*V1*I1 0.2*V1*I1 2
31 48 P<2 Setting Courier Number (Power) 4x01059 G2 143 1 20 Setting 4*V1*I1 to 300*V1*I1 step 1*V1*I1 4*V1*I1 300*V1*I1 1*V1*I1 2 * * * * * * *
592 1 10 1*V1*I1 to 300*V1*I1 step 0.2*V1*I1 1*V1*I1 300*V1*I1 0.2*V1*I1 2
31 4C P>2 Setting Courier Number (Power) 4x01060 G2 143 1 120 Setting 4*V1*I1 to 300*V1*I1 step 1*V1*I1 4*V1*I1 300*V1*I1 1*V1*I1 2 * * * * * * *
592 1 120 1*V1*I1 to 300*V1*I1 step 0.2*V1*I1 1*V1*I1 300*V1*I1 0.2*V1*I1 2
31 50 Power2 TimeDelay Courier Number (Time) 4x01061 G2 10000 1 2 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
31 54 Power2 DO Timer Courier Number (Time) 4x01062 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
31 58 P2 Poledead Inh Indexed String 4x01063 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
31 60 NPS OVERPOWER (Sub Heading) * * * * *
31 61 S2> CT Source Indexed String 4x01068 G116 G116 1 IA1-IB1-IC1 Setting 0 = IA1-IB1-IC1, 1 = IA2-IB2-IC2 0 1 1 2 * * * *
31 62 S2>1 Status Indexed String 4x01065 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * *
31 64 S2>1 Setting Courier Number (VA) 4x01066 G2 2990 1 0.5 Setting 0.1*V1*I1 to 30*V1*I1 step 0.01*V1*I1 0.1*V1*I1 30*V1*I1 0.01*V1*I1 2 * * * * *
0.1*V1*I4 to 30*V1*I4 step 0.01*V1*I4 0.1*V1*I4 30*V1*I4 0.01*V1*I4
31 68 S2>1 Time Delay Courier Number (Time) 4x01067 G2 10000 1 0.1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
32 00 GROUP 1 FIELD FAILURE * * * * *
32 01 FFail Alm Status Indexed String 4x01100 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * *
32 02 FFail Alm Angle Courier Number (Angle) 4x01101 G2 60 1 15 Setting 15 to 75 step 1 15 75 1 2 * * * * *
32 03 FFail Alm Delay Courier Number (Time) 4x01102 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
32 04 FFail1 Status Indexed String 4x01103 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
32 05 FFail1 -Xa1 Courier Number (Impedance) 4x01104 G2 80 1 20 Setting 0 to 40*V1/I1 step 0.05*V1/I1 0 40*V1/I1 0.5*V1/I1 2 * * * * *
32 06 FFail1 Xb1 Courier Number (Impedance) 4x01105 G2 300 1 220 Setting 25*V1/I1 to 325*V1/I1 step 1*V1/I1 25*V1/I1 325*V1/I1 1*V1/I1 2 * * * * *
32 07 FFail1 TimeDelay Courier Number (Time) 4x01106 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
32 08 FFail1 DO Timer Courier Number (Time) 4x01107 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
32 09 FFail2 Status Indexed String 4x01108 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * *
32 0A FFail2 -Xa2 Courier Number (Impedance) 4x01109 G2 80 1 20 Setting 0 to 40*V1/I1 step 0.05*V1/I1 0 40*V1/I1 0.5*V1/I1 2 * * * * *
32 0B FFail2 Xb2 Courier Number (Impedance) 4x01110 G2 300 1 110 Setting 25*V1/I1 to 325*V1/I1 step 1*V1/I1 25*V1/I1 325*V1/I1 1*V1/I1 2 * * * * *
32 0C FFail2 TimeDelay Courier Number (Time) 4x01111 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
32 0D FFail2 DO Timer Courier Number (Time) 4x01112 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
33 00 GROUP 1 NPS THERMAL * * * * *
33 01 I2therm>1 Alarm Indexed String 4x01150 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
33 02 I2therm>1 Set Courier Number (Current) 4x01151 G2 47 1 0.05 Setting 0.03*I1 to 0.5*I1 step 0.01*I1 0.03*I1 0.5*I1 0.01*I1 2 * * * * *
33 03 I2therm>1 Delay Courier Number (Time) 4x01152 G2 10000 1 20s Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
33 04 I2therm>2 Trip Indexed String 4x01153 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
33 05 I2therm>2 Set Courier Number (Current) 4x01154 G2 45 1 0.1 Setting 0.05*I1 to 0.5*I1 step 0.01*I1 0.05*I1 0.5*I1 0.01*I1 2 * * * * *
33 06 I2therm>2 k Courier Number (Time) 4x01155 G2 380 1 15 Setting 2 to 40 step 0.1 2 40 0.1 2 * * * * *
33 07 I2therm>2 kRESET Courier Number (Time) 4x01156 G2 380 1 15 Setting 2 to 40 step 0.1 2 40 0.1 2 * * * * *
33 08 I2therm>2 tMAX Courier Number (Time) 4x01157 G2 1500 1 1000 Setting 500 to 2000 step 1 500 2000 1 2 * * * * *
33 09 I2therm>2 tMIN Courier Number (Time) 4x01158 G2 10000 1 0.25 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
34 00 GROUP 1 SYSTEM BACKUP * * * * *
34 01 Backup Function Indexed String 4x01200 G103 G103 1 Voltage controlled Setting 0 = Disabled, 1 = Underimpedance, 2 = Volt Controlled, 3 = Volt Restrained 0 3 1 2 * * * * *
34 02 Vector Rotation Indexed String 4x01201 G104 G104 1 None Setting 0 = None, 1 = Delta-Star 0 1 1 2 * * * * *
34 20 V Dep OC Char Indexed String 4x01202 G111 G111 1 IEC S Inverse Setting DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, Rectifier, RI, IEEE 0 15 1 2 * * * * *
34 23 V Dep OC I> Set Courier Number (Current) 4x01203 G2 320 1 1 Setting 0.8*I1 to 4*I1 step 0.01*I1 0.8*I1 4*I1 0.01*I1 2 * * * * *
34 25 V Dep OC T Dial Courier Number (Decimal) 4x01204 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * * * * *
34 26 V Dep OC Reset Indexed String 4x01205 G60 G60 10000 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * * * * *
34 27 V Dep OC Delay Courier Number (Time) 4x01206 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
34 28 V Dep OC TMS Courier Number (Decimal) 4x01207 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * * * * *
34 29 V Dep OC K (RI) Courier Number (Decimal) 4x01219 G2 198 1 1 Setting 0.1 to 10 step 0.05 0.1 10 0.05 2 * * * * *
34 2A V Dep OC Usr Rst Indexed String 4x01220 G140 G140 1 DT Setting 0 = DT, 1 = User Curve 1, 2 = User Curve 2, 3 = User Curve 3, 4 = User Curve 4 0 4 1 2 * * * * *

34 2B V Dep OC tRESET Courier Number (Time) 4x01208 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
34 2D V Dep OC V<1 Set Courier Number (Voltage) 4x01209 G2 115 1 80 Setting 5*V1 to 120*V1 step 1*V1 5*V1 120*V1 1*V1 2 * * * * *
34 2E V Dep OC V<2 Set Courier Number (Voltage) 4x01210 G2 115 1 60 Setting 5*V1 to 120*V1 step 1*V1 5*V1 120*V1 1*V1 2 * * * * *
34 2F V Dep OC k Set Courier Number (Decimal) 4x01211 G2 18 1 0.25 Setting 0.1 to 1 step 0.05 0.1 1 0.05 2 * * * * *
34 30 Z<1 Setting Courier Number (Impedance) 4x01212 G2 236 1 70 Setting 2*V1/I1 to 120*V1/I1 step 0.5*V1/I1 2*V1/I1 120*V1/I1 0.5*V1/I1 2 * * * * *
34 31 Z<1 Time Delay Courier Number (Time) 4x01213 G2 1000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
34 32 Z<1 tRESET Courier Number (Time) 4x01214 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
34 33 Z< Stage 2 Indexed String 4x01215 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * *
34 34 Z<2 Setting Courier Number (Impedance) 4x01216 G2 236 1 70 Setting 2*V1/I1 to 120*V1/I1 step 0.5*V1/I1 2*V1/I1 120*V1/I1 0.5*V1/I1 2 * * * * *
34 35 Z<2 Time Delay Courier Number (Time) 4x01217 G2 1000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
34 36 Z<2 tRESET Courier Number (Time) 4x01218 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
35 00 GROUP 1 OVERCURRENT * * * * * * *
35 20 PHASE O/C (Sub Heading) * * * * * * *
35 21 I> CT Source Indexed String 4x01249 G116 G116 1 IA1-IB1-IC1 Setting 0 1 1 2 * * * *
35 23 I>1 Function Indexed String 4x01250 G150 G150 1 IEC S Inverse Setting Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, Rectifier, 0 12 1 2 * * * * * * *
RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse,
User Curve 1, User Curve 2, User Curve 3, User Curve 4
35 24 I>1 Direction Indexed String 4x01251 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 27 I>1 Current Set Courier Number (Current) 4x01252 G2 392 1 1 Setting 0.08*I1 to 4.0*I1 step 0.01*I1 0.08*I1 4.0*I1 0.01*I1 2 * * * * * * *
35 29 I>1 Time Delay Courier Number (Time) 4x01253 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 2A I>1 TMS Courier Number (Decimal) 4x01254 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * * * * * * *
35 2B I>1 Time Dial Courier Number (Decimal) 4x01255 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * * * * * * *
35 2C I>1 K (RI) Courier Number (Decimal) 4x01276 G2 198 1 1 Setting 0.1 to 100 step 0.05 0.1 10 0.05 2 * * * * * * *
35 2E I>1 Reset Char Indexed String 4x01256 G60 G60 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * * * * * * *
35 2F I>1 Usr Rst Char Indexed String 4x01298 G140 G140 1 DT Setting 0= DT, 1 = User Curve 1, 2 = User Curve 2, 3 = User Curve 3, 4 = User Curve 4 0 4 1 2 * * * * * * *

35 30 I>1 tRESET Courier Number (Time) 4x01257 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 32 I>2 Function Indexed String 4x01258 G150 G150 1 Disabled Setting Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, Rectifier, 0 16 1 2 * * * * * * *
RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse,
User Curve 1, User Curve 2, User Curve 3, User Curve 4
35 33 I>2 Direction Indexed String 4x01259 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 36 I>2 Current Set Courier Number (Current) 4x01260 G2 392 1 1 Setting 0.08*I1 to 4.0*I1 step 0.01*I1 0.08*I1 4.0*I1 0.01*I1 2 * * * * * * *
992
35 38 I>2 Time Delay Courier Number (Time) 4x01261 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 39 I>2 TMS Courier Number (Decimal) 4x01262 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * * * * * * *
35 3A I>2 Time Dial Courier Number (Decimal) 4x01263 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * * * * * * *
35 3B I>2 K (RI) Courier Number (Decimal) 4x01277 G2 198 1 1 Setting 0.1 to 100 step 0.05 0.1 10 0.05 2 * * * * * * *
35 3D I>2 Reset Char Indexed String 4x01264 G60 G60 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * * * * * * *
35 3E I>2 Usr Rst Char Indexed String 4x01299 G140 G140 1 DT Setting 0= DT, 1 = User Curve 1, 2 = User Curve 2, 3 = User Curve 3, 4 = User Curve 4 0 4 1 2 * * * * * * *

35 3F I>2 tRESET Courier Number (Time) 4x01265 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 40 I>3 Status Indexed String 4x01266 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
35 41 I>3 Direction Indexed String 4x01267 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 44 I>3 Current Set Courier Number (Current) 4x01268 G2 3192 1 10 Setting 0.08*I1 to 32*I1 step 0.01*I1 0.08*I1 32*I1 0.01*I1 2 * * * * * * *
0.08*I1 to 10*I1 step 0.01*I1 10*I1
35 45 I>3 Time Delay Courier Number (Time) 4x01269 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 47 I>4 Status Indexed String 4x01270 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
35 48 I>4 Direction Indexed String 4x01271 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 4B I>4 Current Set Courier Number (Current) 4x01272 G2 3192 1 10 Setting 0.08*I1 to 32*I1 step 0.01*I1 0.08*I1 32*I1 0.01*I1 2 * * * * * * *
0.08*I1 to 10*I1 step 0.01*I1 10*I1
35 4C I>4 Time Delay Courier Number (Time) 4x01273 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 4E I> Char Angle Courier Number (Angle) 4x01274 G2 190 1 30 Setting -95° to 95° step 1° -95 95 1 2 * * * * * * *
35 4F I> Function Link Binary Flag 4x01275 G14 G14 190 1 15 Setting 4-bit binary setting for I>1 to I>4 VTS blocking respectivley 15 4 1 2 * * * * * * *
35 50 NPS OVERCURRENT (Sub Heading) * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 13 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
35 51 I2> CT Source Indexed String 4x01297 G116 G116 1 IA1-IB1-IC1 Setting 0 1 1 2 * * * *
35 52 I2>1 Status Indexed String 4x01278 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
35 54 I2>1 Direction Indexed String 4x01279 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 56 I2>1 Current Set Courier Number (Current) 4x01280 G2 392 1 0.2 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4*I1 0.01*I1 2 * * * * * * *
35 58 I2>1 Time Delay Courier Number (Time) 4x01281 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 62 I2>2 Status Indexed String 4x01282 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
35 64 I2>2 Direction Indexed String 4x01283 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 66 I2>2 Current Set Courier Number (Current) 4x01284 G2 392 1 0.2 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4*I1 0.01*I1 2 * * * * * * *
35 68 I2>2 Time Delay Courier Number (Time) 4x01285 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 72 I2>3 Status Indexed String 4x01286 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
35 74 I2>3 Direction Indexed String 4x01287 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 76 I2>3 Current Set Courier Number (Current) 4x01288 G2 392 1 0.2 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4*I1 0.01*I1 2 * * * * * * *
35 78 I2>3 Time Delay Courier Number (Time) 4x01289 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 82 I2>4 Status Indexed String 4x01290 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
35 84 I2>4 Direction Indexed String 4x01291 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
35 86 I2>4 Current Set Courier Number (Current) 4x01292 G2 392 1 0.2 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4*I1 0.01*I1 2 * * * * * * *
35 88 I2>4 Time Delay Courier Number (Time) 4x01293 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
35 90 I2> VTS Block Binary Flag 4x01294 G158 G158 190 1 15 Setting 4-bit binary setting for I2>1 to I2>4 VTS blocking respectivley 15 4 1 2 * * * * * * *
35 94 I2> V2pol Set Courier Number (Voltage) 4x01295 G2 49 1 5 Setting 0.5*V1 to 25*V1 step 0.5*V1 0.5*V1 25*V1 0.5*V1 2 * * * * * * *
35 98 I2> Char Angle Courier Number (Angle) 4x01296 G2 190 1 -60 Setting -95° to 95° step 1° -95 95 1 2 * * * * * * *
36 00 GROUP 1 THERMAL OVERLOAD * * * * * * *
36 40 GEN THERMAL (Sub Heading) * * * * *
36 50 Thermal Indexed String 4x01308 G37 G37 1 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
36 55 Thermal I> Courier Number (Current) 4x01309 G2 200 1 1.2 Setting 0.5*I1 to 2.5*I1 step 0.01*I1 0.5*I1 2.5*I1 0.01*I1 2 * * * * * * *
36 5A Thermal Alarm Courier Number (Percentage) 4x01310 G2 80 1 90 Setting 20% to 100% step 1% 20 100 1 2 * * * * * * *
36 5F T-heating Courier Number (Time, minutes) 4x01311 G2 199 1 1min Setting 1min to 200min step 1min 1 200 1 2 * * * * * * *
36 64 T-cooling Courier Number (Time, minutes) 4x01312 G2 199 1 1min Setting 1min to 200min step 1min 1 200 1 2 * * * * * * *
36 69 M Factor Courier Number (Decimal) 4x01313 G2 10 1 0 Setting 0 to 10 step 1 0 10 1 2 * * * * * * *
36 70 XFORMER THERMAL (Sub Heading) * * * * *
36 71 Thermal Indexed String 4x01314 G37 G37 1 1 Enabled Setting 0 1 1 2 * * * * *
36 72 Mn't winding Indexed String 4x01363 G192 G192 1 1 HV Current Setting 0 2 1 2 * * * *
36 73 Ambient T Indexed String 4x01315 G189 G189 1 AVERAGE Setting 0 14 1 2 * * * * *
36 74 Amb CLI Type Indexed String 4x01316 G153 G153 1 4-20mA Setting 0 3 1 2 * * * * *
36 75 Amb CLI Min Courier Number (Decimal) 4x01317 4x01318 G35 2 0 Setting -9999 9999 0.1 2 * * * * *
36 76 Amb CLI Max Courier Number (Decimal) 4x01319 4x01320 G35 2 100 Setting -9999 9999 0.1 2 * * * * *
36 77 Average Amb T Courier Number (Decimal) 4x01321 G2 G2 1 25 Setting -25 75 0.1 2 * * * * *
36 78 Top Oil T Indexed String 4x01322 G190 G190 1 CALCULATED Setting 0 14 1 2 * * * * *
36 79 Top Oil CLI Typ Indexed String 4x01323 G153 G153 1 4-20mA Setting 0 3 1 2 * * * * *
36 7A Top Oil CLI Min Courier Number (Decimal) 4x01324 4x01325 G35 2 0 Setting -9999 9999 0.1 2 * * * * *
36 7B Top Oil CLI Max Courier Number (Decimal) 4x01326 4x01327 G35 2 100 Setting -9999 9999 0.1 2 * * * * *
36 7C IB Courier Number (Decimal) 4x01328 G2 G2 1 1 Setting 0.1 4 0.01 2 * * * * *
36 7D Rated NoLoadLoss Courier Number (Decimal) 4x01329 G2 G2 1 3 Setting 0.1 100 0.1 2 * * * * *
36 7E Hot Spot overtop Courier Number (Decimal) 4x01330 G2 G2 1 25 Setting 0.1 200 0.1 2 * * * * *
36 7F Top Oil overamb Courier Number (Decimal) 4x01331 G2 G2 1 55 Setting 0.1 200 0.1 2 * * * * *
36 80 Cooling Mode Indexed String 4x01364 G191 G191 1 Natural Setting 0 4 1 2 * * * * *
36 81 Cooling Status Indexed String G191 G191 1 Natural data 0 4 1 2 * * * * *
36 82 NATURAL COOL (Sub Heading) 4x01366 * * * * *
36 83 Winding exp m Courier Number (Decimal) 4x01367 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 84 Oil exp n Courier Number (Decimal) 4x01368 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 85 FORCED AIR COOL (Sub Heading) 4x01369 * * * * *
36 86 Winding exp m Courier Number (Decimal) 4x01370 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 87 Oil exp n Courier Number (Decimal) 4x01371 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 88 FORCED OIL COOL (Sub Heading) 4x01372 * * * * *
36 89 Winding exp m Courier Number (Decimal) 4x01373 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 8A Oil exp n Courier Number (Decimal) 4x01374 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 8B FORCED AIR & OIL (Sub Heading) 4x01375 * * * * *
36 8C Winding exp m Courier Number (Decimal) 4x01332 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 8D Oil exp n Courier Number (Decimal) 4x01333 G2 G2 1 0.8 Setting 0.01 2 0.01 2 * * * * *
36 8E Hot spot rise co Courier Number (Decimal) 4x01334 G2 G2 1 1 Setting 0.01 20 0.01 2 * * * * *
36 8F Top oil rise co Courier Number (Decimal) 4x01335 G2 G2 1 120 Setting 1 1000 1 2 * * * * *
36 90 TOL Status Indexed String 4x01336 G37 G37 1 Enabled Setting 2 * * * * *
36 91 Hot Spot>1 Set Courier Number (Decimal) 4x01337 G2 G2 1 110 Setting 1 300 0.1 2 * * * * *
36 92 tHot Spot>1 Set Courier Number (Time) 4x01338 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 93 Hot Spot>2 Set Courier Number (Decimal) 4x01339 G2 G2 1 130 Setting 1 300 0.1 2 * * * * *
36 94 tHot Spot>2 Set Courier Number (Time) 4x01340 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 95 Hot Spot>3 Set Courier Number (Decimal) 4x01341 G2 G2 1 150 Setting 1 300 0.1 2 * * * * *
36 96 tHot Spot>3 Set Courier Number (Time) 4x01342 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 97 Top Oil>1 Set Courier Number (Decimal) 4x01343 G2 G2 1 70 Setting 1 300 0.1 2 * * * * *
36 98 tTop Oil>1 Set Courier Number (Time) 4x01344 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 99 Top Oil>2 Set Courier Number (Decimal) 4x01345 G2 G2 1 80 Setting 1 300 0.1 2 * * * * *
36 9A tTop Oil>2 Set Courier Number (Time) 4x01346 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 9B Top Oil>3 Set Courier Number (Decimal) 4x01347 G2 G2 1 90 Setting 1 300 0.1 2 * * * * *
36 9C tTop Oil>3 Set Courier Number (Time) 4x01348 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 9D tPre-trip Set Courier Number (Time) 4x01349 G2 G2 1 5 Setting 0 60000 1 2 * * * * *
36 A0 LOL Status Indexed String 4x01350 G37 G37 1 Enabled Setting 2 * * * * *
36 A1 Life Hours at HS Courier Number (Decimal) 4x01351 4x01352 G35 G35 2 180000 Setting 1 300000 1 2 * * * * *
36 A2 Design HS temp Courier Number (Decimal) 4x01353 G2 G2 1 110 Setting 1 200 0.1 2 * * * * *
36 A3 Constant B Set Courier Number (Decimal) 4x01354 4x01355 G35 G35 2 15000 Setting 1 100000 1 2 * * * * *
36 A4 FAA> Set Courier Number (Decimal) 4x01356 G2 G2 1 2 Setting 0.1 30 0.01 2 * * * * *
36 A5 tFAA> Set Courier Number (Decimal) 4x01357 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 A6 LOL>1 Set Courier Number (Decimal) 4x01358 4x01359 G35 G35 2 160000 Setting 1 300000 1 2 * * * * *
36 A7 tLOL> Set Courier Number (Decimal) 4x01360 G2 G2 1 10 Setting 0 60000 1 2 * * * * *
36 B0 Reset Life Hours Courier Number (Decimal) 4x01361 4x01362 G35 G35 2 0 Setting 0 300000 1 2 * * * * *
37 00 GROUP 1 DIFFERENTIAL * * * * Was in database column 30, moved in version 32 s/w
37 01 GEN DIFF (Sub Heading) * * * *
37 02 Gen Diff Func Indexed String 4x01000 G101 G101 1 Percentage Bias Setting 0 = Disabled, 1 = Percentage Bia, 2 = High Impedance, 3 = Interturn 0 3 1 2 * * * *
37 03 Gen Diff Is1 Courier Number (Current) 4x01001 G2 45 1 0.1 Setting 0.05*I1 to 0.5*I1 step 0.01*I1 0.05*I1 0.5*I1 0.01*I1 2 * * * *
37 04 Gen Diff k1 Courier Number (Percentage) 4x01002 G2 4 1 0 Setting 0 to 20% step 5% 0 20 5 2 * * * *
37 05 Gen Diff Is2 Courier Number (Current) 4x01003 G2 40 1 1.2 Setting 1*I1 to 5*I1 step 0.1*I1 1*I1 5*I1 0.1*I1 2 * * * *
37 06 Gen Diff k2 Courier Number (Percentage) 4x01004 G2 13 1 150 Setting 20% to 150% step 10% 20 150 10 2 * * * *
37 10 Interturn Is_A Courier Number (Current) 4x01005 G2 195 1 0.1 Setting 0.05*I1 to 2*I1 step 0.01*I1 0.05*I1 2*I1 0.01*I1 2 * * * *
37 14 Interturn Is_B Courier Number (Current) 4x01006 G2 195 1 0.1 Setting 0.05*I1 to 2*I1 step 0.01*I1 0.05*I1 2*I1 0.01*I1 2 * * * *
37 18 Interturn Is_C Courier Number (Current) 4x01007 G2 195 1 0.1 Setting 0.05*I1 to 2*I1 step 0.01*I1 0.05*I1 2*I1 0.01*I1 2 * * * *
37 1C Interturn Delay Courier Number (Time) 4x01008 G2 10000 1 0.1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * *
37 30 XFORMER DIFF (Sub Heading) * * * *
37 31 Xform Diff Func Indexed String 4x01009 G37 G37 1 Disabled Setting 0 1 1 2 * * * *
37 32 Set Mode Indexed String 4x01010 G185 G185 1 Simple Setting 0 1 1 2 * * * *
37 33 Xform Is1 Courier Number (Current) 4x01011 G2 G2 1 0.2 Setting 0.05*PU 2.5*PU 0.01*PU 2 * * * *
37 34 Xform k1 Courier Number (Percentage) 4x01012 G2 G2 1 30 Setting 0 150 1 2 * * * *
37 35 Xform Is2 Courier Number (Current) 4x01013 G2 G2 1 1 Setting 0.1*PU 10*PU 0.1*I1 2 * * * *
37 36 Xform k2 Courier Number (Percentage) 4x01014 G2 G2 1 80 Setting 15 150 1 2 * * * *
37 37 Xform tDiff Courier Number (Time) 4x01015 G2 G2 1 0s Setting 0 10s 10ms * * * *
37 40 Xform Is-CTS Courier Number (Current) 4x01016 G2 G2 1 1.5 Setting 0.1*PU 2.5*PU 0.01*PU * * * *
37 41 Xform HS1 Status Indexed String 4x01017 G37 G37 1 Enabled Setting 0 1 1 2 * * * *
37 42 Xform Is-HS1 Courier Number (Current) 4x01018 G2 G2 1 1/Xt Setting 2.5*PU 16*PU 0.1*PU * * * *
37 43 Xform HS2 Status Indexed String 4x01019 G37 G37 1 Enabled Setting 0 1 1 2 * * * *
37 44 Xform Is-HS2 Courier Number (Current) 4x01020 G2 G2 1 16 Setting 2.5*PU 16*PU 0.1*PU * * * *
37 50 Zero seq filt HV Indexed String 4x01021 G37 G37 1 Enabled Setting 0 1 1 * * * *
37 51 Zero seq filt LV Indexed String 4x01022 G37 G37 1 Enabled Setting 0 1 1 * * * *
37 52 2nd harm blocked Indexed String 4x01023 G37 G37 1 Enabled Setting 0 1 1 * * * *
37 53 Xform Ih(2)%> Courier Number (Percentage) 4x01024 G2 G2 1 20% Setting 0.05 0.5 1 * * * *
37 54 Cross blocking Indexed String 4x01025 G37 G37 1 Disabled Setting 0 1 1 * * * *
37 55 5th harm blocked Indexed String 4x01026 G37 G37 1 Disabled Setting 0 1 1 * * * *
37 56 Xform Ih(5)%> Courier Number (Percentage) 4x01027 G2 G2 1 35% Setting 0 1 0.01 * * * *
37 60 Circuitry Fail Indexed String 4x01028 G37 G37 1 Enabled Setting 0 1 1 * * * *
37 61 Is-cctfail Courier Number (Current) 4x01029 G2 G2 1 0.1 Setting 0.03 1 0.01 * * * *
37 62 K-cctfail Courier Number (Percentage) 4x01030 G2 G2 1 0.1 Setting 0 0.5 0.01 * * * *
37 63 CctFail Delay Courier Number (Time) 4x01031 G2 G2 1 5s Setting 0 10 0.1s * * * *
38 00 GROUP 1 EARTH FAULT * * * * * * *
38 01 IN Input Indexed String G49 G49 Derived Data 0 = Measured, 1 = Derived * * * * * * *
Measured
38 25 IN>1 Function Indexed String 4x01400 G151 G151 1 IEC S Inverse Setting Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, RI, IEEE 0 16 1 2 * * * * * * *
M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse, IDG, User
Curve 1, User Curve 2, User Curve 3, User Curve 4
38 26 IN>1 Direction Indexed String 4x01401 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
38 29 IN>1 Current Courier Number (Current) 4x01402 G2 392 1 0.2 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4.0*I1 0.01*I1 2 * * * * * * *
398 0.1 0.02*I2 to 4*I2 step 0.01*I2 0.02*I2 4.0*I2 0.01*I2
38 2A IN>1 IDG Is Courier Number (Decimal) 4x01431 G2 30 1 1.5 Setting 1 to 4 step 0.1 1 4 0.1 2 * * * * * * *
38 2C IN>1 Time Delay Courier Number (Time) 4x01403 G2 10000 1 1 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * * * *
38 2D IN>1 TMS Courier Number (Decimal) 4x01404 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * * * * * * *
38 2E IN>1 Time Dial Courier Number (Decimal) 4x01405 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * * * * * * *
38 2F IN>1 K (RI) Courier Number (Decimal) 4x01432 G2 198 1 1 Setting 0.1 to 10 step 0.05 0.1 10 0.05 2 * * * * * * *
38 30 IN>1 IDG Time Courier Number (Decimal) 4x01433 G2 100 1 1.2 Setting 1 to 2 step 0.01 1 2 0.01 2 * * * * * * *
38 32 IN>1 Reset Char Indexed String 4x01406 G60 G60 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * * * * * * *
38 33 IN>1 UsrRst Char Indexed String 4x01437 G140 G140 1 DT Setting 0 = DT, 1 = User Curve 1, 2 = User Curve 2, 3 = User Curve 3, 4 = User Curve 4 0 4 1 2 * * * * * * *

38 34 IN>1 tRESET Courier Number (Time) 4x01407 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
38 36 IN>2 Function Indexed String 4x01408 G151 G151 1 Disabled Setting Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, RI, IEEE 0 12 1 2 * * * * * * *
G105 G105 1 Disabled M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse, IDG 0 1 1 2
0 = Disabled, 1 = DT

38 37 IN>2 Direction Indexed String 4x01409 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
38 3A IN>2 Current Courier Number (Current) 4x01410 G2 392 1 0.2 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4.0*I1 0.01*I1 2 * * * * * * *
998 0.45 0.02*I2 to 10*I2 step 0.01*I2 0.02*I2 10.0*I2 0.01*I2
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 14 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
38 3B IN>2 IDG Is Courier Number (Decimal) 4x01434 G2 30 1 1.5 Setting 1 to 4 step 0.1 1 4 0.1 2 * *
38 3D IN>2 Time Delay Courier Number (Time) 4x01411 G2 10000 1 1 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * * * *
0
38 3E IN>2 TMS Courier Number (Decimal) 4x01412 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * *
38 3F IN>2 Time Dial Courier Number (Decimal) 4x01413 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * *
38 40 IN>2 K (RI) Courier Number (Decimal) 4x01435 G2 198 1 1 Setting 0.1 to 10 step 0.05 0.1 10 0.05 2 * *
38 41 IN>2 IDG Time Courier Number (Time) 4x01436 G2 100 1 1.2 Setting 1 to 2 step 0.01 1 2 0.01 2 * *
38 43 IN>2 Reset Char Indexed String 4x01414 G60 G60 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * *
38 44 IN>2 tRESET Courier Number (Time) 4x01415 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
38 46 IN>3 Status Indexed String 4x01416 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
38 47 IN>3 Direction Indexed String 4x01417 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
38 4A IN>3 Current Courier Number (Current) 4x01418 G2 3192 1 0.5 Setting 0.08*I1 to 32*I1 step 0.01*I1 0.08*I1 32*I1 0.01*I1 2 * *
38 4B IN>3 Time Delay Courier Number (Time) 4x01419 G2 10000 1 0 Setting 0 to 200 step 0.01 0 200 0.01 2 * *
38 4D IN>4 Status Indexed String 4x01420 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
38 4E IN>4 Direction Indexed String 4x01421 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
38 51 IN>4 Current Courier Number (Current) 4x01422 G2 3192 1 0.5 Setting 0.08*I1 to 32*I1 step 0.01*I1 0.08*I1 32*I1 0.01*I1 2 * *
38 52 IN>4 Time Delay Courier Number (Time) 4x01423 G2 10000 1 0 Setting 0 to 200 step 0.01 0 200 0.01 2 * *
38 54 IN> Func Link Binary Flags 4x01424 G63 G63 190 1 15 Setting 4-bit binary setting for IN>1 to IN>4 VTS blocking respectivley 15 4 1 2 * *
38 55 IN> DIRECTIONAL (Sub Heading) 2 * *
38 56 IN> Char Angle Courier Number(Angle) 4x01425 G2 190 1 -60 Setting -95° to 95° step 1° -95 95 1 2 * *
38 57 IN> Pol Indexed String 4x01426 G46 G46 1 Zero Sequence Setting 0 = Zero Sequence, 1 = Neg Sequence 0 1 1 2 * *
38 58 IN> VNpol Input Indexed String 4x01427 G49 G49 1 Measured Setting 0 = Measured, 1 = Derived 0 1 1 2 * *
38 59 IN> VNpol Set Courier Number (Voltage) 4x01428 G2 5 Setting 0.5*V1 to 80*V1 step 0.5*V1 0.5*V1 80*V1 0.5*V1 2 * *
0.5*V3 to 80*V3 step 0.5*V3 0.5*V3 80*V3 0.5*V3
38 5A IN> V2pol Set Courier Number (Voltage) 4x01429 G2 49 1 5 Setting 0.5*V1 to 25*V1 step 0.5*V1 0.5*V1 25*V1 0.5*V1 2 * *
38 5B IN> I2pol Set Courier Number (Current) 4x01430 G2 92 1 0.08 Setting 0.08*I1 to 1*I1 step 0.01*I1 0.08*I1 1*I1 0.01*I1 2 * *
39 00 GROUP 1 ROTOR EF * * * * *
39 02 Injection Freq Indexed String 4x01450 G168 G168 1 0.25 Hz Setting 0 = 0.25Hz, 1 = 0.5Hz, 2 = 1.0Hz 0 2 1 2 * * * * *
39 04 CL I/P Select Indexed String 4x01451 G166 G166 1 Current Loop CL1 Setting Current Loop CL1, Current Loop CL2, Current Loop CL3, Current Loop CL4 0 3 1 2 * * * * *
39 08 64R R<1 Alarm Indexed String 4x01452 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
39 0C 64R R<1 Alm Set Courier Number (Resistance) 4x01453 4x01454 G35 79000 2 40000 Setting 1000 to 80000 step 1 1000 80000 1 2 * * * * *
39 10 64R R<1 Alm Dly Courier Number (Time) 4x01455 G2 6000 1 10 Setting 0 to 600 step 0.1 0 600 0.1 2 * * * * *
39 14 64R R<2 Trip Indexed String 4x01456 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
39 18 64R R<2 Trip Set Courier Number (Resistance) 4x01457 4x01458 G35 79000 2 5000 Setting 1000 to 80000 step 1 1000 80000 1 2 * * * * *
39 1C 64R R<2 Trip Dly Courier Number (Time) 4x01459 G2 6000 1 1 Setting 0 to 600 step 0.1 0 600 0.1 2 * * * * *
39 20 R Compensation Courier Number (Resistance) 4x01460 G2 2000 1 0 Setting -1000 to 1000 step 1 -1000 1000 1 2 * * * * *
3A 00 GROUP 1 SEF/REF PROT'N * * * * * * *
3A 01 SEF/REF Options Indexed String 4x01500 G58 G58 1 SEF Setting SEF, SEF cos, SEF sin, Wattmetric, Hi Z REF, Lo Z REF, Lo Z REF+SEF, Lo Z REF+ 0 4 1 2 * * * * * * *
0 7 1 2
3A 2A ISEF>1 Function Indexed String 4x01501 G152 G152 1 DT Setting Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M 0 15 1 2 * * * * * * *
G105 G105 Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse, IDG, User 0 1 1
Curve 1, User Curve 2, User Curve 3, User Curve 4
0 = Disabled, 1 = DT
3A 2B ISEF>1 Direction Indexed String 4x01502 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * * * * * * *
3A 2E ISEF>1 Current Courier Number (Current) 4x01503 G2 380 1 0.05 Setting 0.005*I3 to 0.1*I3 step 0.00025*I3 0.005*I3 0.1*I3 0.00025*I3 2 * * * * * * *
3A 2F ISEF>1 IDG Is Courier Number (Decimal) 4x01535 G2 30 1 1.5 Setting 1 to 4 step 0.1 1 4 0.1 2 * *
3A 31 ISEF>1 Delay Courier Number (Time) 4x01504 G2 20000 1 1 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * * * *
3A 32 ISEF>1 TMS Courier Number (Decimal) 4x01505 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * *
3A 33 ISEF>1 Time Dial Courier Number (Decimal) 4x01506 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * *
3A 34 ISEF>1 IDG Time Courier Number (Time) 4x01536 G2 100 1 1.2 Setting 1 to 2 step 0.01 1 2 0.01 2 * *
3A 36 ISEF>1 Reset Chr Indexed String 4x01507 G60 G60 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * *
3A 37 ISEF>1 Usr Reset Indexed String 4x01540 G140 G140 1 DT Setting 0 = DT, 1 = User Curve 1, 2 = User Curve 2, 3 = User Curve 3, 4 = User Curve 4 0 4 1 2 * *
3A 38 ISEF>1 tRESET Courier Number (Time) 4x01508 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
3A 3A ISEF>2 Function Indexed String 4x01509 G152 G152 1 Disabled Setting Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT 0 11 1 2 * *
Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse,
US ST Inverse, IDG
3A 3B ISEF>2 Direction Indexed String 4x01510 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
3A 3E ISEF>2 Current Courier Number (Current) 4x01511 G2 380 1 0.05 Setting 0.005*I3 to 0.1*I3 step 0.00025*I3 0.005*I3 0.1*I3 0.00025*I3 2 * *
3A 3F ISEF>2 IDG Is Courier Number (Decimal) 4x01537 G2 30 1 1.5 Setting 1 to 4 step 0.1 1 4 0.1 2 * *
3A 41 ISEF>2 Delay Courier Number (Time) 4x01512 G2 20000 1 1 Setting 0 to 200 step 0.01 0 200 0.01 2 * *
3A 42 ISEF>2 TMS Courier Number (Decimal) 4x01513 G2 47 1 1 Setting 0.025 to 1.2 step 0.025 0.025 1.2 0.025 2 * *
3A 43 ISEF>2 Time Dial Courier Number (Decimal) 4x01514 G2 9999 1 1 Setting 0.01 to 100 step 0.01 0.01 100 0.01 2 * *
3A 44 ISEF>2 IDG Time Courier Number (Time) 4x01538 G2 100 1 1.2 Setting 1 to 2 step 0.01 1 2 0.01 2 * *
3A 46 ISEF>2 Reset Chr Indexed String 4x01515 G60 G60 1 DT Setting 0 = DT, 1 = Inverse 0 1 1 2 * *
3A 47 ISEF>2 tRESET Courier Number (Time) 4x01516 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
3A 49 ISEF>3 Status Indexed String 4x01517 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
3A 4A ISEF>3 Direction Indexed String 4x01518 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
3A 4D ISEF>3 Current Courier Number (Current) 4x01519 G2 795 1 0.4 Setting 0.005*I3 to 0.80*I3 step 0.001*I3 0.005*I3 0.80*I3 0.001*I3 2 * *
3A 4E ISEF>3 Delay Courier Number (Time) 4x01520 G2 20000 1 0.5 Setting 0 to 200 step 0.01 0 200 0.01 2 * *
3A 50 ISEF>4 Status Indexed String 4x01521 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
3A 51 ISEF>4 Direction Indexed String 4x01522 G44 G44 1 Non-Directional Setting 0 = Non-Directional, 1 = Directional Fwd, 2 = Directional Rev 0 2 1 2 * *
3A 54 ISEF>4 Current Courier Number (Current) 4x01523 G2 795 1 0.6 Setting 0.005*I3 to 0.80*I3 step 0.001*I3 0.005*I3 0.80*I3 0.001*I3 2 * *
3A 55 ISEF>4 Delay Courier Number (Time) 4x01524 G2 20000 1 0.25 Setting 0 to 200 step 0.01 0 200 0.01 2 * *
3A 57 ISEF> Func Link Binary Flags 4x01525 G64 G64 190 1 15 Setting 4-bit binary setting for ISEF>1 to ISEF>4 VTS blocking respectivley 15 4 1 2 * * * * * * *
1 1 1 2
3A 58 ISEF DIRECTIONAL (Sub Heading) 2 * * * * * * *
3A 59 ISEF> Char Angle Courier Number(Angle) 4x01526 G2 190 1 90 Setting -95° to 95° step 1° -95 95 1 2 * * * * * * *
3A 5A ISEF>VNpol Input Indexed String 4x01527 G49 G49 1 Measured Setting 0 = Measured, 1 = Derived 0 1 1 2 * * * * * * *
3A 5B ISEF> VNpol Set Courier Number (Voltage) 4x01528 G2 43 1 5 Setting 0.5*V1 to 80*V1 step 0.5*V1 0.5*V1 80*V1 0.5*V1 2 * * * * * * *
* * * * * * *
3A 5D WATTMETRIC SEF (Sub Heading) * * * * * * *
3A 5E PN> Setting Courier Number (Power) 4x01529 G2 400 1 9 Setting 0.0*V1*I3 to 20*V1*I3 step 0.05*V1*I3 0.0*V1*I3 20*V1*I3 0.05*V1*I3 2 * * * * * * *
0.0*V3*I3 to 20*V3*I3 step 0.05*V3*I3 0.0*V3*I3 20*V3*I3 0.05*V3*I3 * * * * * * *
3A 60 RESTRICTED E/F (Sub Heading) * * * * * * *
3A 61 IREF> CT Source Indexed String 4x01539 G116 G116 1 IA1-IB1-IC1 Setting 0 1 1 2 * * * *
3A 62 IREF> k1 Courier Number (Percentage) 4x01530 G2 20 1 0 Setting 0 to 20% step 1% 0 20 1 2 * * * * *
3A 63 IREF> k2 Courier Number (Percentage) 4x01531 G2 150 1 150 Setting 0 to 150% step 1% 0 150 1 2 * * * * *
3A 64 IREF> Is1 Courier Number (Current) 4x01532 G2 95 1 0.2 Setting 0.05*I1 to 1.0*I1 step 0.01*I1 0.05*I1 1.0*I1 0.01*I1 2 * * * * *
3A 65 IREF> Is2 Courier Number (Current) 4x01533 G2 140 1 1 Setting 0.1*I1 to 1.5*I1 step 0.01*I1 0.1*I1 1.5*I1 0.01*I1 2 * * * * *
3A 66 IREF> Is Courier Number (Current) 4x01534 G2 95 1 0.2 Setting 0.05*I3 to 1.0*I3 step 0.01*I3 0.05*I3 1.0*I3 0.01*I3 2 * * * * * * *
3B 00 GROUP 1 RESIDUAL O/V NVD * * * * *
3B 10 VN>1 Status Indexed String 4x11550 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
3B 12 VN>1 Input Indexed String G159 G159 Derived Data 0 = Derived, 1 = VN1, 2 = VN2 * * * * * * * VN>1 Input is always the derived VN
3B 14 VN>1 Function Indexed String 4x11551 G161 G161 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 4 1 2 * * * * * * *
4 = User Curve 3, 5 = User Curve 4
3B 16 VN>1 Voltage Set Courier Number (Voltage) 4x11552 G2 49 1 5 Setting 1*V1 to 80*V1 step 1*V1 1*V1 80*V1 1*V1 2 * * * * * * *
1*V3 to 80*V3 step 1*V3 1*V3 80*V3 1*V3 * * * * * * *
1*V2 to 80*V2 step 1*V2 1*V2 80*V2 1*V2 * * * * * * *
3B 18 VN>1 Time Delay Courier Number (Time) 4x11553 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 1A VN>1 TMS Courier Number (Decimal) 4x11554 G2 199 1 1 Setting 0.5 to 100 step 0.5 0.5 100 0.5 2 * * * * * * *
3B 1C VN>1 tReset Courier Number (Time) 4x11555 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 20 VN>2 Status Indexed String 4x11556 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
3B 22 VN>2 Input Indexed String G159 G159 1 Derived Data 0 = Derived, 1 = VN1, 2 = VN2 * * * * * * * VN>2 Input is always the derived VN
3B 24 VN>2 Function Indexed String 4x11557 G161 G161 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 4 1 2 * * * * * * *
4 = User Curve 3, 5 = User Curve 4
3B 26 VN>2 Voltage Set Courier Number (Voltage) 4x11558 G2 49 1 10 Setting 1*V1 to 80*V1 step 1*V1 1*V1 80*V1 1*V1 2 * * * * * * *
1*V3 to 80*V3 step 1*V3 1*V3 80*V3 1*V3 * * * * * * *
1*V2 to 80*V2 step 1*V2 1*V2 80*V2 1*V2 * * * * * * *
3B 28 VN>2 Time Delay Courier Number (Time) 4x11559 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 2A VN>2 TMS Courier Number (Decimal) 4x11560 G2 199 1 1 Setting 0.5 to 100 step 0.5 0.5 100 0.5 2 * * * * * * *
3B 2C VN>2 tReset Courier Number (Time) 4x11561 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 30 VN>3 Status Indexed String 4x11562 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
3B 32 VN>3 Input Indexed String G159 G159 VN1 Data 0 = Derived, 1 = VN1, 2 = VN2 * * * * * * * VN>3 Input is always the measured VN1
3B 34 VN>3 Function Indexed String 4x11563 G161 G161 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 4 1 2 * * * * * * *
4 = User Curve 3, 5 = User Curve 4
3B 36 VN>3 Voltage Set Courier Number (Voltage) 4x11564 G2 49 1 5 Setting 1*V1 to 80*V1 step 1*V1 1*V1 80*V1 1*V1 2 * * * * * * *
1*V3 to 80*V3 step 1*V3 1*V3 80*V3 1*V3 * * * * * * *
1*V2 to 80*V2 step 1*V2 1*V2 80*V2 1*V2 * * * * * * *
3B 38 VN>3 Time Delay Courier Number (Time) 4x11565 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 3A VN>3 TMS Courier Number (Decimal) 4x11566 G2 199 1 1 Setting 0.5 to 100 step 0.5 0.5 100 0.5 2 * * * * * * *
3B 3C VN>3 tReset Courier Number (Time) 4x11567 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 40 VN>4 Status Indexed String 4x11568 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
3B 42 VN>4 Input Indexed String G159 G159 VN1 Data 0 = Derived, 1 = VN1, 2 = VN2 * * * * * * * VN>4 Input is always the measured VN1
3B 44 VN>4 Function Indexed String 4x11569 G161 G161 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 4 1 2 * * * * * * *
4 = User Curve 3, 5 = User Curve 4
3B 46 VN>4 Voltage Set Courier Number (Voltage) 4x11570 G2 49 1 10 Setting 1*V1 to 80*V1 step 1*V1 1*V1 80*V1 1*V1 2 * * * * * * *
1*V3 to 80*V3 step 1*V3 1*V3 80*V3 1*V3 * * * * * * *
1*V2 to 80*V2 step 1*V2 1*V2 80*V2 1*V2 * * * * * * *
3B 48 VN>4 Time Delay Courier Number (Time) 4x11571 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 4A VN>4 TMS Courier Number (Decimal) 4x11572 G2 199 1 1 Setting 0.5 to 100 step 0.5 0.5 100 0.5 2 * * * * * * *
3B 4C VN>4 tReset Courier Number (Time) 4x11573 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3B 50 VN>5 Status Indexed String 4x11574 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * *
3B 52 VN>5 Input Indexed String G159 G159 VN2 Data 0 = Derived, 1 = VN1, 2 = VN2 * * VN>5 Input is always the measured VN2
3B 54 VN>5 Function Indexed String 4x11575 G161 G161 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 4 1 2 * *
4 = User Curve 3, 5 = User Curve 4
3B 56 VN>5 Voltage Set Courier Number (Voltage) 4x11576 G2 49 1 5 Setting 1*V1 to 80*V1 step 1*V1 1*V1 80*V1 1*V1 2 * * * * * * *
1*V3 to 80*V3 step 1*V3 1*V3 80*V3 1*V3 * * * * * * *
1*V2 to 80*V2 step 1*V2 1*V2 80*V2 1*V2 * * * * * * *
3B 58 VN>5 Time Delay Courier Number (Time) 4x11577 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
3B 5A VN>5 TMS Courier Number (Decimal) 4x11578 G2 199 1 1 Setting 0.5 to 100 step 0.5 0.5 100 0.5 2 * *
3B 5C VN>5 tReset Courier Number (Time) 4x11579 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
3B 60 VN>6 Status Indexed String 4x11580 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
3B 62 VN>6 Input Indexed String G159 G159 VN2 Data 0 = Derived, 1 = VN1, 2 = VN2 * * VN>6 Input is always the measured VN2
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 15 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
3B 64 VN>6 Function Indexed String 4x11581 G161 G161 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 4 1 2 * *
4 = User Curve 3, 5 = User Curve 4
3B 66 VN>6 Voltage Set Courier Number (Voltage) 4x11582 G2 49 1 10 Setting 1*V1 to 80*V1 step 1*V1 1*V1 80*V1 1*V1 2 * * * * * * *
1*V3 to 80*V3 step 1*V3 1*V3 80*V3 1*V3 * * * * * * *
1*V2 to 80*V2 step 1*V2 1*V2 80*V2 1*V2 * * * * * * *
3B 68 VN>6 Time Delay Courier Number (Time) 4x11583 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
3B 6A VN>6 TMS Courier Number (Decimal) 4x11584 G2 199 1 1 Setting 0.5 to 100 step 0.5 0.5 100 0.5 2 * *
3B 6C VN>6 tReset Courier Number (Time) 4x11585 G2 10000 1 0 Setting 0 to 100 step 0.01 0 100 0.01 2 * *
3C 00 GROUP 1 100% STATOR EF * * *
3C 01 VN 3rd Harmonic Indexed String 4x01600 G112 G112 2 1 1 (Undervoltage) Setting 0 = Disabled, 1 = VN3H< Enabled, 2 = VN3H> Enabled 0 2 1 2 * * *
3C 02 100% St EF VN3H< Courier Number (Voltage) 4x01601 G2 197 1 1 Setting 0.3*V3 to 20*V3 step 0.1*V3 0.3*V3 20*V3 0.1*V3 2 * * *
3C 03 VN3H< Delay Courier Number (Time) 4x01602 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * *
3C 04 V<Inhibit set Courier Number (Voltage) 4x01603 G2 90 1 80 Setting 30*V1 to 120*V1 step 1*V1 30*V1 120*V1 1*V1 2 * * *
3C 05 P< Inhibit Indexed String 4x01604 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * *
3C 06 P<Inhibit set Courier Number (Power) 4x01605 G2 392 1 4 Setting 4*V1*I1 to 200*V1*I1 step 0.5*V1*I1 4*V1*I1 200*V1*I1 0.5*V1*I1 2 * * *
3C 07 Q< Inhibit Indexed String 4x01606 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * *
3C 08 Q<Inhibit set Courier Number (VAr) 4x01607 G2 392 1 4 Setting 4*V1*I1 to 200*V1*I1 step 0.5*V1*I1 4*V1*I1 200*V1*I1 0.5*V1*I1 2 * * *
3C 09 S< Inhibit Indexed String 4x01608 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * *
3C 0A S<Inhibit set Courier Number (VA) 4x01609 G2 392 1 4 Setting 4*V1*I1 to 200*V1*I1 step 0.5*V1*I1 4*V1*I1 200*V1*I1 0.5*V1*I1 2 * * *
3C 0B 100% St EF VN3H> Courier Number (Voltage) 4x01610 G2 197 1 1 Setting 0.3*V3 to 20*V3 step 0.1*V3 0.3*V3 20*V3 0.1*V3 2 * * *
3C 0C VN3H> Delay Courier Number (Time) 4x01611 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * *
3C 10 64S LF Injection Indexed String 4x01612 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * Available to P345 only
3C 14 64S R Factor Courier Number (Decimal) 4x01613 G2 19999 1 10 Setting 0.01 to 200 step 0.01 0.01 200 0.01 2 * Scaling factor for primary resistance across earthing transformer. Affects the stator resistance settings and measurements only.

3C 18 (Not used) Not used


3C 1C 64S R<1 Alarm Indexed String 4x01614 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 *
3C 20 64S R<1 Alm Set Courier Number (Resistance) 4x01615 G2 6900 1 100 Setting 10 to 700 step 0.1 10 700 0.1 2 *
3C 24 64S R<1 Alm Dly Courier Number (Time) 4x01616 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 *
3C 28 64S R<2 Trip Indexed String 4x01617 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 *
3C 2C 64S R<2 Trip Set Courier Number (Resistance) 4x01618 G2 6900 1 20 Setting 10 to 700 step 0.1 10 700 0.1 2 *
3C 30 64S R<2 Trip Dly Courier Number (Time) 4x01619 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 *
3C 34 64S Angle Comp Courier Number (Angle) 4x01620 G2 1200 1 0 Setting -60° to 60° step 0.1° -60 60 0.1 2 *
3C 38 64S Series R Courier Number (Resistance) 4x01621 G2 7000 1 0 Setting 10 to 700 step 0.1 0 700 0.1 2 *
3C 3A 64S Series X Courier Number (Reactance) 4x01622 G2 7000 1 0 Setting 10 to 700 step 0.1 0 700 0.1 2 *
3C 3C 64S Parallel G Courie Number (Conductance) 4x01623 G35 1000000 2 0 Setting 0 to 0.1 step 0.0000001 0 0.1 1E-07 2 *
3C 40 64S Overcurrent Indexed String 4x01625 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 *
3C 44 64S I>1 Trip Set Courier Number (Current) 4x01626 G2 148 1 0.5 Setting 0.02 to 1.5 step 0.01 0.02 1.5 0.01 2 *
3C 48 64S I>1 Trip Dly Courier Number (Time) 4x01627 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 *
3C 4C 64S Supervision Indexed String 4x01628 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 *
3C 50 64S V<1 Set Courier Number (Voltage) 4x01629 G2 247 1 1 Setting 0.3 to 25 step 0.1 0.3 25 0.1 2 *
3C 54 64S I<1 Set Courier Number (Current) 4x01630 G2 35 1 0.01 Setting 0.005 to 0.04 step 0.001 0.005 0.04 0.001 2 *
3C 58 64S Superv'n Dly Courier Number (Time) 4x01631 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 *
3D 00 GROUP 1 VOLTS/HZ * * * * *
3D 01 V/Hz Alm Status Indexed String 4x01650 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
3D 02 V/Hz Alarm Set Courier Number (Volts/Hz) 4x01651 G2 200 1 2.31 Setting 1.5*V1 to 3.5*V1 step 0.01*V1 1.5*V1 3.5*V1 0.01*V1 2 * * * * *
3D 03 V/Hz Alarm Delay Courier Number (Time) 4x01652 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * *
3D 10 V/Hz>1 Status Indexed String 4x01657 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
3D 13 V/Hz>1 Trip Func Indexed String 4x01658 G160 G160 2 1 DT Setting 0 = DT, 1 = IDMT, 2 = User Curve 1, 3 = User Curve 2, 0 5 1 2 * * * * *
4 = User Curve 3, 5 = User Curve 4
3D 16 V/Hz>1 Trip Set Courier Number (Volts/Hz) 4x01659 G2 200 1 2.42 Setting 1.5*V1 to 3.5*V1 step 0.01*V1 1.5*V1 3.5*V1 0.01*V1 2 * * * * *
3D 19 V/Hz>1 Trip TMS Courier Number (Decimal) 4x01660 G2 1200 1 1 Setting 0.01 to 12 step 0.01 0.01 12 0.01 2 * * * * *
3D 1A V/Hz>1 Delay Courier Number (Time) 4x01661 G2 60000 1 60 Setting 0 to 600 step 0.01 0 600 0.01 2 * * * * *
3D 1B V/Hz>1 Reset Char Indexed String 4x01662 G140 G140 DT Setting 0 = DT, 1 = User Curve 1, 2 = User Curve 2, 3 = User Curve 3, 4 = User Curve 4 0 4 1 2 * * * * *

3D 1C V/Hz>1 tRESET Courier Number (Time) 4x01670 G2 60000 0 Setting 0 to 600 step 0.01 0.01 600 0.01 2 * * * * *
3D 20 V/Hz>2 Status Indexed String 4x01663 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
3D 25 V/Hz>2 Trip Set Courier Number (Volts/Hz) 4x01664 G2 200 1 2.64 Setting 1.5*V1 to 3.5*V1 step 0.01*V1 1.5*V1 3.5*V1 0.01*V1 2 * * * * *
3D 2A V/Hz>2 Delay Courier Number (Time) 4x01665 G2 60000 1 3 Setting 0 to 600 step 0.01 0 600 0.01 2 * * * * *
3D 30 V/Hz>3 Status Indexed String 4x01667 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
3D 35 V/Hz>3 Trip Set Courier Number (Volts/Hz) 4x01668 G2 200 1 2.86 Setting 1.5*V1 to 3.5*V1 step 0.01*V1 1.5*V1 3.5*V1 0.01*V1 2 * * * * *
3D 3A V/Hz>3 Delay Courier Number (Time) 4x01669 G2 60000 1 2 Setting 0 to 600 step 0.01 0 600 0.01 2 * * * * *
3D 40 V/Hz>4 Status Indexed String 4x01671 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
3D 45 V/Hz>4 Trip Set Courier Number (Volts/Hz) 4x01672 G2 200 1 3.08 Setting 1.5*V1 to 3.5*V1 step 0.01*V1 1.5*V1 3.5*V1 0.01*V1 2 * * * * *
3D 4A V/Hz>4 Delay Courier Number (Time) 4x01673 G2 60000 1 1 Setting 0 to 600 step 0.01 0 600 0.01 2 * * * * *
3E 00 GROUP 1 DF/DT * *
3E 10 Operating Mode Indexed String 4x01734 G193 G193 1 Rolling Window Setting 0 1 1 2 * * * * * * *
Fixed Window
3E 11 df/dt Avg Cycles Courier Number 4x01700 G2 G2 1 3 Setting 2 12 1 2 * * * * * * *
3E 12 df/dt Iterations Courier Number 4x01701 G2 G2 1 2 Setting 1 4 1 2 * * * * * * *
3E 20 df/dt>1 Status Indexed String 4x01702 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
3E 21 df/dt>1 Setting Courier Number (Hz/s) 4x01703 G2 G2 99 1 0.2 Setting 0.1Hz/s to 10Hz/s step 0.01Hz/s 0.1 10 0.01 2 * * * * * * *
3E 22 df/dt>1 Dir'n Indexed String 4x01704 G182 G182 1 Both Setting 0 2 1 2 * * * * * * *
3E 23 df/dt>1 Time Courier Number (Time) 4x01705 G2 G2 10000 1 0.5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
3E 24 df/dt>1 f L/H Indexed String 4x01706 G37 G37 8000 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
3E 25 df/dt>1 f Low Courier Number (Frequency) 4x01707 G2 G2 8000 1 49.5 Setting 45Hz to 65Hz step 0.01Hz 45 65 0.01 2 * * * * * * *
3E 26 df/dt>1 f High Courier Number (Frequency) 4x01708 G2 G2 8000 1 50.5 Setting 45Hz to 65Hz step 0.01Hz 45 65 0.01 2 * * * * * * *
3E 30 df/dt>2 Status Indexed String 4x01710 G37 G37 1 Enabled Setting 0 1 1 2 * * * * * * *
3E 31 df/dt>2 Setting Courier Number (Hz/s) 4x01711 G2 G2 99 1 0.2 Setting 0.1 10 0.01 2 * * * * * * *
3E 32 df/dt>2 Dir'n Indexed String 4x01712 G182 G182 1 Positive Setting 0 2 1 2 * * * * * * *
3E 33 df/dt>2 Time Courier Number (Time) 4x01713 G2 G2 10000 1 0.5 Setting 0 100 0.01 2 * * * * * * *
3E 40 df/dt>3 Status Indexed String 4x01720 G37 G37 1 Enabled Setting 0 1 1 2 * * * * * * *
3E 41 df/dt>3 Setting Courier Number (Hz/s) 4x01721 G2 G2 99 1 0.2 Setting 0.1 10 0.01 2 * * * * * * *
3E 42 df/dt>3 Dir'n Indexed String 4x01722 G182 G182 1 Positive Setting 0 2 1 2 * * * * * * *
3E 43 df/dt>3 Time Courier Number (Time) 4x01723 G2 G2 10000 1 0.5 Setting 0 100 0.01 2 * * * * * * *
3E 50 df/dt>4 Status Indexed String 4x01730 G37 G37 1 Enabled Setting 0 1 1 2 * * * * * * *
3E 51 df/dt>4 Setting Courier Number (Hz/s) 4x01731 G2 G2 99 1 0.2 Setting 0.1 10 0.01 2 * * * * * * *
3E 52 df/dt>4 Dir'n Indexed String 4x01732 G182 G182 1 Positive Setting 0 2 1 2 * * * * * * *
3E 53 df/dt>4 Time Courier Number (Time) 4x01733 G2 G2 10000 1 0.5 Setting 0 100 0.01 2 * * * * * * *
3F 00 GROUP 1 V VECTOR SHIFT * *
3F 01 V Shift Status Indexed String 4x01750 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * *
3F 02 V Shift Angle Courier Number (Angle) 4x01751 G2 28 1 10 Setting -2° to 30° step 1° 2 30 1 2 * *
40 00 GROUP 1 DEAD MACHINE * * *
40 01 Dead Mach Status Indexed String 4x01800 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * *
40 02 DM CT Source Indexed String 4x01805 G116 G116 1 IA1-IB1-IC1 Setting 0 1 1 2 * * *
40 03 Dead Mach I> Courier Number (Current) 4x01801 G2 39 1 0.1 Setting 0.08*I1 to 4*I1 step 0.01*I1 0.08*I1 4*I1 0.01*I1 2 * * *
0.08*I4 to 4*I1_2 step 0.01*I4 0.08*I4 4*I4 0.01*I4
40 04 Dead Mach V< Courier Number (Voltage) 4x01802 G2 9000 1 80 Setting 10*V1 to 120*V1 step 1*V1 10*V1 120*V1 1*V1 2 * * *
40 05 Dead Mach tPU Courier Number (Time) 4x01803 G2 100 1 5 Setting 0 to 10 step 0.1 0 10 0.1 2 * * *
40 06 Dead Mach tDO Courier Number (Time) 4x01804 G2 100 1 0.5 Setting 0 to 10 step 0.1 0 10 0.1 2 * * *
41 00 GROUP 1 RECONNECT DELAY * *
41 01 Reconnect Status Indexed String 4x01850 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * *
41 02 Reconnect Delay Courier Number (Time) 4x01852 G2 30000 1 60 Setting 0 to 300 step 0.01 0 300 0.01 2 * *
41 03 Reconnect tPULSE Courier Number (Time) 4x01853 G2 2999 1 1 Setting 0.01 to 30 step 0.01 0.01 30 0.01 2 * *
42 00 GROUP 1 VOLT PROTECTION * * * * * * *
42 01 UNDER VOLTAGE (Sub Heading) * * * * * * *
42 02 V< Measur't Mode Indexed String 4x01950 G47 G47 1 Phase-Neutral Setting 0 = Phase-Phase, 1 = Phase-Neutral 0 1 1 2 * * * * * * *
42 03 V< Operate Mode Indexed String 4x01951 G48 G48 1 Any Phase Setting 0 = Any Phase, 1 = Three Phase 0 1 1 2 * * * * * * *
42 04 V<1 Function Indexed String 4x01952 G23 G23 1 DT Setting 0 = Disabled, 1 = DT, 2 = IDMT,3 = User Curve 1, 4 = User Curve 2, 5 = User Curve 3, 6 = 0 6 1 2 * * * * * * *
User Curve
42 05 V<1 Voltage Set Courier Number (Voltage) 4x01953 G2 60 1 50 Setting 10*V1 to 120*V1 step 1*V1 10*V1 120*V1 1*V1 2 * * * * * * *
42 06 V<1 Time Delay Courier Number (Time) 4x01954 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
42 07 V<1 TMS Courier Number (Decimal) 4x01955 G2 199 1 1 Setting 0.05 to 100 step 0.05 0.05 100 0.05 2 * * * * * * *
42 08 V<1 Poledead Inh Indexed String 4x01956 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
42 09 V<2 Status Indexed String 4x01957 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
42 0A V<2 Voltage Set Courier Number (Voltage) 4x01958 G2 60 1 38 Setting 10*V1 to 120*V1 step 1*V1 10*V1 120*V1 1*V1 2 * * * * * * *
42 0B V<2 Time Delay Courier Number (Time) 4x01959 G2 10000 1 5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
42 0C V<2 Poledead Inh Indexed String 4x01960 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
42 0D OVERVOLTAGE (Sub Heading) * * * * * * *
42 0E V> Measur't Mode Indexed String 4x01961 G47 G47 1 Phase-Phase Setting 0 = Phase-Phase, 1 = Phase-Neutral 0 1 1 2 * * * * * * *
42 0F V> Operate Mode Indexed String 4x01962 G48 G48 1 Any Phase Setting 0 = Any Phase,1 = Three Phase 0 1 1 2 * * * * * * *
42 10 V>1 Function Indexed String 4x01963 G23 G23 1 DT Setting 0 = Disabled, 1 = DT, 2 = IDMT, 3 = User Curve 1, 4 = User Curve 2, 5 = User Curve 3, 6 = 0 6 1 2 * * * * * * *
User Curve 4
42 11 V>1 Voltage Set Courier Number (Voltage) 4x01964 G2 50 1 130 Setting 60*V1 to 185*V1 step 1*V1 60*V1 185*V1 1*V1 2 * * * * * * *
42 12 V>1 Time Delay Courier Number (Time) 4x01965 G2 10000 1 10 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
42 13 V>1 TMS Courier Number (Decimal) 4x01966 G2 199 1 1 Setting 0.05 to 100 step 0.05 0.05 100 0.05 2 * * * * * * *
42 14 V>2 Status Indexed String 4x01967 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
42 15 V>2 Voltage Set Courier Number (Voltage) 4x01968 G2 50 1 150 Setting 60*V1 to 185*V1 step 1*V1 60*V1 185*V1 1*V1 2 * * * * * * *
42 16 V>2 Time Delay Courier Number (Time) 4x01969 G2 10000 1 0.5 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
42 20 NPS OVERVOLTAGE (Sub Heading) * * * * * * *
42 22 V2>1 Status Indexed String 4x01970 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
42 26 V2>1 Voltage Set Courier Number (Voltage) 4x01971 G2 150 1 15 Setting 1*V1 to 150*V1 step 1*V1 1*V1 150*V1 1*V1 2 * * * * * * *
42 28 V2>1 Time Delay Courier Number (Time) 4x01972 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 00 GROUP 1 FREQ PROTECTION * * * * * * *
43 01 UNDER FREQUENCY (Sub Heading) * * * * * * *
43 02 F<1 Status Indexed String 4x02000 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
43 03 F<1 Setting Courier Number (Frequency) 4x02001 G2 2000 1 49.5 Setting 45Hz to 65Hz step 0.01Hz 45 65 0.01 2 * * * * * * *
43 04 F<1 Time Delay Courier Number (Time) 4x02002 G2 10000 1 4 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 05 F<2 Status Indexed String 4x02003 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
43 06 F<2 Setting Courier Number (Frequency) 4x02004 G2 2000 1 49 Setting 45Hz to 65Hz step 0.01Hz 45 65 0.01 2 * * * * * * *
43 07 F<2 Time Delay Courier Number (Time) 4x02005 G2 10000 1 3 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 08 F<3 Status Indexed String 4x02006 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
43 09 F<3 Setting Courier Number (Frequency) 4x02007 G2 2000 1 48.5 Setting 45Hz to 65Hz step 0.01Hz 45 65 0.01 2 * * * * * * *
43 0A F<3 Time Delay Courier Number (Time) 4x02008 G2 10000 1 2 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 0B F<4 Status Indexed String 4x02009 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 16 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
43 0C F<4 Setting Courier Number (Frequency) 4x02010 G2 2000 1 48 Setting 45Hz to 65Hz step 0.01Hz 45 65 0.01 2 * * * * * * *
43 0D F<4 Time Delay Courier Number (Time) 4x02011 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 0E F< Function Link Binary Flag (4 bits) 4x02012 G65 G65 1 16 Setting 4-bit binary setting for F<1 Poledead to F<4 Poledead blocking respectivley 15 4 1 2 * * * * * * *
43 0F OVER FREQUENCY (Sub Heading) * * * * * * *
43 10 F>1 Status Indexed String 4x02013 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
43 11 F>1 Setting Courier Number (Frequency) 4x02014 G2 2000 1 50.5 Setting 45Hz to 68Hz step 0.01Hz 45 68 0.01 2 * * * * * * *
43 12 F>1 Time Delay Courier Number (Time) 4x02015 G2 10000 1 2 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 13 F>2 Status Indexed String 4x02016 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
43 14 F>2 Setting Courier Number (Frequency) 4x02017 G2 2000 1 51 Setting 45Hz to 68Hz step 0.01Hz 45 68 0.01 2 * * * * * * *
43 15 F>2 Time Delay Courier Number (Time) 4x02018 G2 10000 1 1 Setting 0 to 100 step 0.01 0 100 0.01 2 * * * * * * *
43 20 TURBINE F PROT (Sub Heading) * * * * * Turbine Abnormal Frequency Protection
43 22 Turbine F Status Indexed String 4x12000 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 24 Band 1 Status Indexed String 4x12001 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 26 Band 1 Freq Low Courier Number (Frequency) 4x12002 G2 5000 1 46.5 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 28 Band 1 Freq High Courier Number (Frequency) 4x12003 G2 5000 1 47 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 2A Band 1 Duration Courier Number (Time) 4x12004 4x12025 G35 360000000 2 1 Setting 0 to 3600000 step 0.01 0 3600000 0.01 2 * * * * * Band 1 Accumulated Time Threshold
43 2C Band 1 Dead Time Courier Number (Time) 4x12026 G2 20000 1 0.2 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * *
43 34 Band 2 Status Indexed String 4x12027 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 36 Band 2 Freq Low Courier Number (Frequency) 4x12028 G2 5000 1 47 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 38 Band 2 Freq High Courier Number (Frequency) 4x12029 G2 5000 1 47.5 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 3A Band 2 Duration Courier Number (Time) 4x12030 4x12031 G35 360000000 2 2.5 Setting 0 to 3600000 step 0.01 0 3600000 0.01 2 * * * * * Band 2 Accumulated Time Threshold
43 3C Band 2 Dead Time Courier Number (Time) 4x12032 G2 20000 1 0.2 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * *
43 44 Band 3 Status Indexed String 4x12033 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 46 Band 3 Freq Low Courier Number (Frequency) 4x12034 G2 5000 1 47.5 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 48 Band 3 Freq High Courier Number (Frequency) 4x12035 G2 5000 1 48 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 4A Band 3 Duration Courier Number (Time) 4x12036 4x12037 G35 360000000 2 14 Setting 0 to 3600000 step 0.01 0 3600000 0.01 2 * * * * * Band 3 Accumulated Time Threshold
43 4C Band 3 Dead Time Courier Number (Time) 4x12038 G2 20000 1 0.2 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * *
43 54 Band 4 Status Indexed String 4x12039 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 56 Band 4 Freq Low Courier Number (Frequency) 4x12040 G2 5000 1 48 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 58 Band 4 Freq High Courier Number (Frequency) 4x12041 G2 5000 1 48.5 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 5A Band 4 Duration Courier Number (Time) 4x12042 4x12043 G35 360000000 2 100 Setting 0 to 3600000 step 0.01 0 3600000 0.01 2 * * * * * Band 4 Accumulated Time Threshold
43 5C Band 4 Dead Time Courier Number (Time) 4x12044 G2 20000 1 0.2 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * *
43 64 Band 5 Status Indexed String 4x12045 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 66 Band 5 Freq Low Courier Number (Frequency) 4x12046 G2 5000 1 48.5 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 68 Band 5 Freq High Courier Number (Frequency) 4x12047 G2 5000 1 49 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 6A Band 5 Duration Courier Number (Time) 4x12048 4x12049 G35 360000000 2 540 Setting 0 to 3600000 step 0.01 0 3600000 0.01 2 * * * * * Band 5 Accumulated Time Threshold
43 6C Band 5 Dead Time Courier Number (Time) 4x12050 G2 20000 1 0.2 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * *
43 74 Band 6 Status Indexed String 4x12051 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
43 76 Band 6 Freq Low Courier Number (Frequency) 4x12052 G2 5000 1 49 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 78 Band 6 Freq High Courier Number (Frequency) 4x12053 G2 5000 1 49.5 Setting 20Hz to 70Hz step 0.01Hz 20 70 0.01 2 * * * * *
43 7A Band 6 Duration Courier Number (Time) 4x12054 4x12055 G35 360000000 2 3000 Setting 0 to 3600000 step 0.01 0 3600000 0.01 2 * * * * * Band 6 Accumulated Time Threshold
43 7C Band 6 Dead Time Courier Number (Time) 4x12056 G2 20000 1 0.2 Setting 0 to 200 step 0.01 0 200 0.01 2 * * * * *
44 00 GROUP 1 RTD PROTECTION * * * * *
44 01 Select RTD Binary Flags(10 bits)Indexed String 4x02053 G50 G50 1 0 Setting 10-bit binary setting 1023 10 1 2 * * * * *
44 02 RTD 1 Alarm Set Courier Number (Temperature) 4x02054 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 03 RTD 1 Alarm Dly Courier Number (Time) 4x02055 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 04 RTD 1 Trip Set Courier Number (Temperature) 4x02056 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 05 RTD 1 Trip Dly Courier Number (Time) 4x02057 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 06 RTD 2 Alarm Set Courier Number (Temperature) 4x02058 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 07 RTD 2 Alarm Dly Courier Number (Time) 4x02059 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 08 RTD 2 Trip Set Courier Number (Temperature) 4x02060 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 09 RTD 2 Trip Dly Courier Number (Time) 4x02061 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 0A RTD 3 Alarm Set Courier Number (Temperature) 4x02062 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 0B RTD 3 Alarm Dly Courier Number (Time) 4x02063 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 0C RTD 3 Trip Set Courier Number (Temperature) 4x02064 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 0D RTD 3 Trip Dly Courier Number (Time) 4x02065 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 0E RTD 4 Alarm Set Courier Number (Temperature) 4x02066 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 0F RTD 4 Alarm Dly Courier Number (Time) 4x02067 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 10 RTD 4 Trip Set Courier Number (Temperature) 4x02068 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 11 RTD 4 Trip Dly Courier Number (Time) 4x02069 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 12 RTD 5 Alarm Set Courier Number (Temperature) 4x02070 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 13 RTD 5 Alarm Dly Courier Number (Time) 4x02071 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 14 RTD 5 Trip Set Courier Number (Temperature) 4x02072 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 15 RTD 5 Trip Dly Courier Number (Time) 4x02073 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 16 RTD 6 Alarm Set Courier Number (Temperature) 4x02074 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 17 RTD 6 Alarm Dly Courier Number (Time) 4x02075 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 18 RTD 6 Trip Set Courier Number (Temperature) 4x02076 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 19 RTD 6 Trip Dly Courier Number (Time) 4x02077 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 1A RTD 7 Alarm Set Courier Number (Temperature) 4x02078 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 1B RTD 7 Alarm Dly Courier Number (Time) 4x02079 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 1C RTD 7 Trip Set Courier Number (Temperature) 4x02080 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 1D RTD 7 Trip Dly Courier Number (Time) 4x02081 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 1E RTD 8 Alarm Set Courier Number (Temperature) 4x02082 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 1F RTD 8 Alarm Dly Courier Number (Time) 4x02083 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 20 RTD 8 Trip Set Courier Number (Temperature) 4x02084 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 21 RTD 8 Trip Dly Courier Number (Time) 4x02085 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 22 RTD 9 Alarm Set Courier Number (Temperature) 4x02086 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 23 RTD 9 Alarm Dly Courier Number (Time) 4x02087 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 24 RTD 9 Trip Set Courier Number (Temperature) 4x02088 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 25 RTD 9 Trip Dly Courier Number (Time) 4x02089 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 26 RTD 10 Alarm Set Courier Number (Temperature) 4x02090 G1 200 1 80 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 27 RTD 10 Alarm Dly Courier Number (Time) 4x02091 G1 100 1 10 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
44 28 RTD 10 Trip Set Courier Number (Temperature) 4x02092 G1 200 1 85 Setting 0° to 200°C step 1°C 0 200 1 2 * * * * *
44 29 RTD 10 Trip Dly Courier Number (Time) 4x02093 G1 100 1 1 Setting 0s to 100s step 1s 0 100 1 2 * * * * *
45 00 GROUP 1 CB FAIL & I< * * * * * * *
45 01 BREAKER FAIL (Sub Heading) * * * * * * *
45 02 CB Fail 1 Status Indexed String 4x02100 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
45 03 CB Fail 1 Timer Courier Number (Time) 4x02101 G2 1000 1 0.2 Setting 0s to 10s step 0.01s 0 10 0.01 2 * * * * * * *
45 04 CB Fail 2 Status Indexed String 4x02102 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
45 05 CB Fail 2 Timer Courier Number (Time) 4x02103 G2 1000 1 0.4 Setting 0s to 10s step 0.01s 0 10 0.01 2 * * * * * * *
45 06 CBF Non I Reset Indexed String 4x02104 G68 G68 2 1 CB Open & I< Setting 0 = I< Only, 1 = CB Open & I<, 2 = Prot Reset & I< 0 2 1 2 * * * * * * *
45 07 CBF Ext Reset Indexed String 4x02105 G68 G68 2 1 CB Open & I< Setting 0 = I< Only, 1 = CB Open & I<, 2 = Prot Reset & I< 0 2 1 2 * * * * * * *
45 08 UNDER CURRENT (Sub Heading) * * * * * * *
45 09 I< Current Set Courier Number (Current) 4x02106 G2 318 1 0.1 Setting 0.02*I1 to 3.2*I1 step 0.01*I1 0.02*I1 3.2*I1 0.01*I1 2 * * * * * * *
0.02*I4 to 3.2*I4 step 0.01*I4 0.02*I4 3.2*I4 0.01*I4
45 0A IN< Current Set Courier Number (Current) 4x02107 G2 318 1 0.1 Setting 0.02*I2 to 3.2*I2 step 0.01*I2 0.02*I2 3.2*I2 0.01*I2 2 * * * * *
45 0B ISEF< Current Courier Number (Current) 4x02108 G2 320 1 0.02 Setting 0.001*I3 to 0.8*I3 step 0.0005*I3 0.001*I3 0.8*I3 0.0005*I3 2 * * * * * * *
45 0C BLOCKED O/C (Sub Heading) * *
45 0D Remove I> Start Indexed String 4x02109 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
45 0E Remove IN> Start Indexed String 4x02110 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * *
45 15 I< CT Source Indexed String 4x02111 G116 G116 1 IA-1, IB-1, IC-1 Setting 0 = IA-1 IB-1 IC-1, 1 = IA-2 IB-2 IC-2 0 1 1 2 * * * *
46 00 GROUP 1 SUPERVISION * * * * * * *
46 01 VT SUPERVISION (Sub Heading) * * * * * * *
46 02 VTS Status Indexed String 4x02150 G7 G7 1 Blocking Setting Blocking, Indication, disabled 0 1 1 2 * * * * * * *
46 03 VTS Reset Mode Indexed String 4x02151 G69 G69 1 Manual Setting Manual, Auto 0 1 1 2 * * * * * * *
46 04 VTS Time Delay Courier Number (Time) 4x02152 G2 90 1 5 Setting 1s to 10s step 0.1s 1 10 0.1 2 * * * * * * *
46 05 VTS I> Inhibit Courier Number (Current) 4x02153 G2 392 1 10 Setting 0.08pu to 32pu step 0.01pu 0.08*I1 32*I1 0.01*I1 2 * * * * * * *
46 06 VTS I2> Inhibit Courier Number (Current) 4x02154 G2 392 1 0.05 Setting 0.05pu to 0.5pu step 0.01pu 0.05*I1 0.5*I1 0.01*I1 2 * * * * * * *
46 07 CT SUPERVISION (Sub Heading) * * * * * * *
46 08 CTS1 Status Indexed String 4x02155 G37 G37 43 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
46 09 CTS1 VN Input Indexed String 4x02156 G49 G49 1 Derived Setting 0 = Measured, 1 = Derived 0 1 1 2 * * * * * * *
46 0A CTS1 VN< Inhibit Courier Number (Voltage) 4x02157 G2 43 1 5 Setting 0.5*V1 to 22*V1 step 0.5*V1 0.5*V1 22*V1 0.5*V1 2 * * * * * * *
0.5*V3 to 22*V3 step 0.5*V3 0.5*V3 22*V3 0.5*V3
46 0B CTS1 IN> Set Courier Number (Current) 4x02158 G2 392 1 0.2 Setting 0.08pu to 4pu step 0.01pu 0.08*I1 4*I1 0.01*I1 2 * * * * * * *
46 0C CTS1 Time Delay Courier Number (Time) 4x02159 G2 10 1 5 Setting 0s to 10s step 1s 0 10 1 2 * * * * * * *
46 20 CTS2 Status Indexed String 4x02160 G37 G37 43 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * *
46 24 CTS2 VN Input Indexed String 4x02161 G49 G49 1 Derived Setting 0 = Measured, 1 = Derived 0 1 1 2 * * * *
46 28 CTS2 VN< Inhibit Courier Number (Voltage) 4x02162 G2 43 1 5 Setting 0.5*V1 to 22*V1 step 0.5*V1 0.5*V1 22*V1 0.5*V1 2 * * * *
0.5*V3 to 22*V3 step 0.5*V3 0.5*V3 22*V3 0.5*V3
46 2C CTS2 IN> Set Courier Number (Current) 4x02163 G2 392 1 0.2 Setting 0.08pu to 4pu step 0.01pu 0.08*I1 4*I1 0.01*I1 2 * * * *
46 30 CTS2 Time Delay Courier Number (Time) 4x02164 G2 10 1 5 Setting 0s to 10s step 1s 0 10 1 2 * * * *
46 31 DIFF CTS Status Indexed String 4x02165 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * *
46 32 Diff CTS Mode Indexed String 4x02166 G187 G187 1 Restrain Setting 0 = Indication, 1= Restrain 0 1 1 2 * * * *
46 33 CTS Time Delay Courier Number (time) 4x02167 G2 G2 1 2s Setting 0s to 10s step 0.1s 0s 10s 0.1s 2 * * * *
46 34 CTS I1 Courier Number (current) 4x02168 G2 G2 43 1 10% Setting 0% to 100% step 1% 0% 100% 1% 2 * * * *
46 35 CTS I2/I1>1 Courier Number 4x02169 G2 G2 392 1 5% Setting 5% to 100% step 1% 5% 100% 1% 2 * * * *
46 36 CTS I2/I1>2 Courier Number 4x02170 G2 G2 10 1 30% Setting 5% to 100% step 1% 5% 100% 1% 2 * * * *
46 50 THROUGH FAULT (sub heading) * * * *
46 51 Through Fault Indexed String 4x02171 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * *
46 52 Monitored Input Indexed String 4x02172 G186 G186 1 HV 0= HV, 1= LV HV LV 1 2 * * * *
46 53 TF I> Trigger Courier Number (Current) 4x02173 G2 G2 1 1 0.08*In to 16*In step 0.01*In 0.08*In 16*In 0.01 * * * * *
46 54 TF I2t> Alarm Courier Number (I2t) 4x02174 G2 G2 1 800(In * In *t) 0 to 50000A2s step 1 0 50,000 1 * * * * *
47 00 GROUP 1 SENSITIVE POWER * * * * * * *
47 20 Comp Angle Courier Number (Angle) 4x02175 G2 50 1 0 Setting -5° to 5° step 0.1° -5 5 0.1 2 * * * * * * *
47 24 Operating Mode Indexed String 4x02190 G115 G115 0 1 Generating Setting 0 = Generating, 1 = Motoring 0 1 1 2 * * * * * * *
47 28 Sen Power1 Func Indexed String 4x02176 G102 G102 3 1 Reverse Setting 0 = Disabled, 2 = Reverse, 3 = Low Forward, 4 = Over 0 3 1 2 * * * * * * *
47 2C Sen -P>1 Setting Courier Number (Power) 4x02177 G2 997 1 0.5*V1*I3 Setting 0.3*V1*I3 to 100*V1*I3 step 0.1*V1*I3 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * * * *
47 30 Sen P<1 Setting Courier Number (Power) 4x02178 G2 997 1 0.5*V1*I3 Setting 0.3*V1*I3 to 100*V1*I3 step 0.1*V1*I3 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * * * *
47 34 Sen P>1 Setting Courier Number (Power) 4x02179 G2 997 1 50*V1*I3 Setting 0.3*V1*I3 to 100*V1*I3 step 0.1*V1*I3 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * * * *
47 38 Sen Power1 Delay Courier Number (Time) 4x02180 G2 10000 1 5 Setting 0s to 100s step 0.01s 0 100 0.01 2 * * * * * * *
47 3C Power1 DO Timer Courier Number (Time) 4x02181 G2 10000 1 0 Setting 0s to 100s step 0.01s 0 100 0.01 2 * * * * * * *
47 40 P1 PoleDead Inh Indexed String 4x02182 G37 G37 1 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
47 44 Sen Power2 Func Indexed String 4x02183 G102 G102 3 1 Low Forward Setting 0 = Disabled, 2 = Reverse, 3 = Low Forward, 4 = Over 0 3 1 2 * * * * * * *
47 48 Sen -P>2 Setting Courier Number (Power) 4x02184 G2 997 1 0.5*V1*I3 Setting 0.3*V1*I3 to 100*V1*I3 step 0.1*V1*I3 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 17 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
47 4C Sen P<2 Setting Courier Number (Power) 4x02185 G2 997 1 0.5*V1*I3 Setting 0.3*V1*I3 to 100*V1*I3 step 0.1*V1*I3 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * * * *
47 50 Sen P>2 Setting Courier Number (Power) 4x02186 G2 997 1 50*V1*I3 Setting 0.3*V1*I3 to 100*V1*I3 step 0.1*V1*I3 0.3*V1*I3 100*V1*I3 0.1*V1*I3 2 * * * * * * *
47 54 Sen Power2 Delay Courier Number (Time) 4x02187 G2 10000 1 2 Setting 0s to 100s step 0.01s 0 100 0.01 2 * * * * * * *
47 58 Power2 DO Timer Courier Number (Time) 4x02188 G2 10000 1 0 Setting 0s to 100s step 0.01s 0 100 0.01 2 * * * * * * *
47 5C P2 PoleDead Inh Indexed String 4x02189 G37 G37 1 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
48 00 GROUP 1 DYNAMIC RATING *
48 01 Dyn Line Rating Indexed String 4x12200 G171 G1 1 1 1 Setting 0 2 1 2 *
48 02 DLR LINE SETTING (Sub Heading) *
48 03 Conductor Type Indexed String 4x12201 G169 G1 36 1 Lynx Setting 0 36 1 2 *
48 04 NonFerrous layer Courier Number (Integer) 4x12202 G2 2 1 2 Setting 1 3 1 2 *
48 05 DC Resist per km Courier Number (Resistance) 4x12203 G2 19990 1 1 Setting 0.001 2 0.0001 2 *
48 06 Overall Diameter Courier Number (Length) 4x12204 G2 9900 1 0.005 Setting 0.001 0.1 1E-05 2 *
48 07 Outer Layer Diam Courier Number (Length) 4x12205 G2 900 1 0.002 Setting 0.001 0.01 1E-05 2 *
48 08 TotalArea(mm sq) Courier Number (Decimal) 4x12206 4x12207 G35 G27 99000 2 100 Setting 10 1000 0.01 2 *
48 09 TempCoefR x0.001 Courier Number (Decimal) 4x12208 G2 900 1 4 Setting 1 10 0.01 2 *
48 0A mc Courier Number (Decimal) 4x12209 G2 49990 1 500 Setting 1 5000 0.1 2 *
48 0E Solar Absorpt Courier Number (Decimal) 4x12210 G2 72 1 0.5 Setting 0.23 0.95 0.01 2 *
48 0F Line Emissivity Courier Number (Decimal) 4x12211 G2 72 1 0.5 Setting 0.23 0.95 0.01 2 *
48 10 Line Elevation Courier Number (Length) 4x12212 G2 7000 1 0 Setting -1000 6000 1 2 *
48 11 Line Azimuth Min Courier Number (Decimal) 4x12213 G2 3600 1 0 Setting 0 360 0.1 2 *
48 12 Line Azimuth Max Courier Number (Decimal) 4x12214 G2 3600 1 180 Setting 0 360 0.1 2 *
48 13 T Conductor Max Courier Number (Temperature) 4x12215 G2 3000 1 50 Setting 0 300 0.1 2 *
48 14 Ampacity Min Courier Number (Current) 4x12216 G2 1900 1 0.2 Setting 0.1 4 0.001 2 *
48 15 Ampacity Max Courier Number (Current) 4x12217 G2 1900 1 2 Setting 0.1 4 0.001 2 *
48 16 Drop-off Ratio Courier Number (Percentage) 4x12218 G2 100 1 98 Setting 70 99 0.1 2 *
48 17 Line Direction Courier Number (Decimal) 4x12219 G2 3600 1 0 Setting 0 360 0.1 2 *
48 20 DLR CHANNEL SET (Sub Heading) *
48 21 Ambient Temp Indexed String 4x12230 G170 G1 4 1 1 Setting 0 4 1 2 *
48 22 Default AmbientT Courier Number (Temperature) 4x12231 G2 2000 1 20 Setting -100 100 0.1 2 *
48 23 Ambient T Corr Courier Number (Temperature) 4x12232 G2 1000 0 Setting -50 50 0.1 2 *
48 24 Ambient T Min Courier Number (Temperature) 4x12233 G2 2000 1 -40 Setting -100 100 0.1 2 *
48 25 Ambient T Max Courier Number (Temperature) 4x12234 G2 2000 1 50 Setting -100 100 0.1 2 *
48 26 Ambient T AvgSet Indexed String 4x12235 G37 G1 1 1 0 Setting 0 1 1 2 *
48 27 Ambient T AvgDly Courier Number (Time) 4x12236 G2 359 1 100 Setting 10 3600 10 2 *
48 28 Amb T Input Type Indexed String 4x12237 G153 G1 3 1 4-20mA Setting 0 3 1 2 *
48 29 Amb T I/P Min Courier Number (Temperature) 4x12238 G2 2000 1 -40 Setting -100 100 0.1 2 *
48 2A Amb T I/P Max Courier Number (Temperature) 4x12239 G2 2000 1 50 Setting -100 100 0.1 2 *
48 2B Amb T I< Alarm Indexed String 4x12240 G37 G1 1 1 Disabled Setting 0 1 1 2 *
48 2C Amb T I< Alm Set Courier Number (Current) 4x12241 G2 40 1 0.0035 Setting 0 0.004 0.0001 2 *
48 31 Wind Velocity Indexed String 4x12242 G170 G1 4 1 2 Setting 0 4 1 2 *
48 32 Default Wind Vel Courier Number (Velocity) 4x12243 G2 6000 1 0.5 Setting 0 60 0.01 2 *
48 33 Wind Vel Corr Courier Number (Percentage) 4x12244 G2 1500 100 Setting 0 150 0.1 2 *
48 34 Wind Vel Min Courier Number (Velocity) 4x12245 G2 1000 1 0 Setting 0 60 0.01 2 *
48 35 Wind Vel Max Courier Number (Velocity) 4x12246 G2 1000 1 60 Setting 0 60 0.01 2 *
48 36 Wind Vel AvgSet Indexed String 4x12247 G37 G1 1 1 0 Setting 0 1 1 2 *
48 37 Wind Vel AvgDly Courier Number (Time) 4x12248 G2 359 1 100 Setting 10 3600 10 2 *
48 38 WV Input Type Indexed String 4x12249 G153 G1 3 1 4-20mA Setting 0 3 1 2 *
48 39 WV I/P Minimum Courier Number (Velocity) 4x12250 G2 1000 1 0 Setting 0 60 0.01 2 *
48 3A WV I/P Maximum Courier Number (Velocity) 4x12251 G2 1000 1 60 Setting 0 60 0.01 2 *
48 3B WV I< Alarm Indexed String 4x12252 G37 G1 1 1 Disabled Setting 0 1 1 2 *
48 3C WV I< Alarm Set Courier Number (Current) 4x12253 G2 40 1 0.0035 Setting 0 0.004 0.0001 2 *
48 41 Wind Direction Indexed String 4x12254 G170 G1 4 1 3 Setting 0 4 1 2 *
48 42 Default Wind Dir Courier Number (Decimal) 4x12255 G2 3600 1 0 Setting 0 360 0.1 2 *
48 43 Wind Dir Corr Courier Number (Decimal) 4x12256 G2 3600 0 Setting -180 180 0.1 2 *
48 44 Wind Dir Min Courier Number (Decimal) 4x12257 G2 3600 1 0 Setting 0 360 0.1 2 *
48 45 Wind Dir Max Courier Number (Decimal) 4x12258 G2 3600 1 360 Setting 0 360 0.1 2 *
48 46 Wind Dir AvgSet Indexed String 4x12259 G37 G1 1 1 0 Setting 0 1 1 2 *
48 47 Wind Dir AvgDly Courier Number (Time) 4x12260 G2 359 1 100 Setting 10 3600 10 2 *
48 48 WD Input Type Indexed String 4x12261 G153 G1 3 1 4-20mA Setting 0 3 1 2 *
48 49 WD I/P Minimum Courier Number (Decimal) 4x12262 G2 360 1 0 Setting 0 360 0.1 2 *
48 4A WD I/P Maximum Courier Number (Decimal) 4x12263 G2 360 1 360 Setting 0 360 0.1 2 *
48 4B WD I< Alarm Indexed String 4x12264 G37 G1 1 1 Disabled Setting 0 1 1 2 *
48 4C WD I< Alarm Set Courier Number (Current) 4x12265 G2 40 1 0.0035 Setting 0 0.004 0.0001 2 *
48 51 Solar Radiation Indexed String 4x12266 G170 G1 4 1 0 Setting 0 4 1 2 *
48 52 Default Solar R Courier Number (Power) 4x12267 G2 3000 1 0 Setting 0 3000 1 2 * Default Solar Radiation per square meter ( /m2)
48 53 Solar Rad Corr Courier Number (Power) 4x12268 G2 2000 0 Setting -1000 1000 1 2 *
48 54 Solar Rad Min Courier Number (Power) 4x12269 G2 3000 1 0 Setting 0 3000 1 2 *
48 55 Solar Rad Max Courier Number (Power) 4x12270 G2 3000 1 1000 Setting 0 3000 1 2 *
48 56 Solar Rad AvgSet Indexed String 4x12271 G37 G1 1 1 0 Setting 0 1 1 2 *
48 57 Solar Rad AvgDly Courier Number (Time) 4x12272 G2 359 1 100 Setting 10 3600 10 2 *
48 58 SR Input Type Indexed String 4x12273 G153 G1 3 1 4-20mA Setting 0 3 1 2 *
48 59 SR I/P Minimum Courier Number (Power) 4x12274 G2 3000 1 0 Setting 0 3000 1 2 *
48 5A SR I/P Maximum Courier Number (Power) 4x12275 G2 3000 1 1000 Setting 0 3000 1 2 *
48 5B SR I< Alarm Indexed String 4x12276 G37 G1 1 1 Disabled Setting 0 1 1 2 *
48 5C SR I< Alarm Set Courier Number (Current) 4x12277 G2 40 1 0.0035 Setting 0 0.004 0.0001 2 *
48 60 DLR PROT SETTING (Sub Heading) *
48 61 DLR I>1 Trip Indexed String 4x12278 G37 G1 1 1 Enabled Setting 0 1 1 2 * Ampacity protection stage 1 of 6
48 62 DLR I>1 Set Courier Number (Percentage) 4x12279 G2 1800 1 80 Setting 20 200 0.1 2 *
48 63 DLR I>1 Delay Courier Number (Time) 4x12280 G2 30000 1 10 Setting 0 30000 1 2 *
48 64 DLR I>2 Trip Indexed String 4x12281 G37 G1 1 1 Enabled Setting 0 1 1 2 * Ampacity protection stage 2of 6
48 65 DLR I>2 Set Courier Number (Percentage) 4x12282 G2 1800 1 90 Setting 20 200 0.1 2 *
48 66 DLR I>2 Delay Courier Number (Time) 4x12283 G2 30000 1 10 Setting 0 30000 1 2 *
48 67 DLR I>3 Trip Indexed String 4x12284 G37 G1 1 1 Enabled Setting 0 1 1 2 * Ampacity protection stage 3 of 6
48 68 DLR I>3 Set Courier Number (Percentage) 4x12285 G2 1800 1 95 Setting 20 200 0.1 2 *
48 69 DLR I>3 Delay Courier Number (Time) 4x12286 G2 30000 1 10 Setting 0 30000 1 2 *
48 6A DLR I>4 Trip Indexed String 4x12287 G37 G1 1 1 Enabled Setting 0 1 1 2 * Ampacity protection stage 4 of 6
48 6B DLR I>4 Set Courier Number (Percentage) 4x12288 G2 1800 1 97 Setting 20 200 0.1 2 *
48 6C DLR I>4 Delay Courier Number (Time) 4x12289 G2 30000 1 10 Setting 0 30000 1 2 *
48 6D DLR I>5 Trip Indexed String 4x12290 G37 G1 1 1 Enabled Setting 0 1 1 2 * Ampacity protection stage 5 of 6
48 6E DLR I>5 Set Courier Number (Percentage) 4x12291 G2 1800 1 99 Setting 20 200 0.1 2 *
48 6F DLR I>5 Delay Courier Number (Time) 4x12292 G2 30000 1 10 Setting 0 30000 1 2 *
48 70 DLR I>6 Trip Indexed String 4x12293 G37 G1 1 1 Enabled Setting 0 1 1 2 * Ampacity protection stage 6 of 6
48 71 DLR I>6 Set Courier Number (Percentage) 4x12294 G2 1800 1 100 Setting 20 200 0.1 2 *
48 72 DLR I>6 Delay Courier Number (Time) 4x12295 G2 30000 1 10 Setting 0 30000 1 2 *
49 00 GROUP 1 POLE SLIPPING * * *
49 01 PSlip Function Indexed String 4x02250 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * *
49 02 Z Based PoleSlip (Sub Heading) * * *
49 03 Pole Slip Mode Indexed String 4x02251 G113 G113 1 Generating Setting 0 = Generating, 1 = Motoring, 2 = Both 0 2 1 2 * * *
49 04 PSlip Za Forward Courier Number (Impedance) 4x02252 G2 700 1 100*V1/I1 Setting 0.5*V1/I1 to 350*V1/I1 step 0.5*V1/I1 0.5*V1/I1 350*V1/I1 0.5*V1/I1 2 * * *
49 05 PSlip Zb Reverse Courier Number (Impedance) 4x02253 G2 700 1 150*V1/I1 Setting 0.5*V1/I1 to 350*V1/I1 step 0.5*V1/I1 0.5*V1/I1 350*V1/I1 0.5*V1/I1 2 * * *
49 06 Lens Angle Courier Number (Angle) 4x02254 G2 60 1 120 Setting 90° to 150° step 1° 90 150 1 2 * * *
49 07 PSlip Timer T1 Courier Number (Time) 4x02255 G2 200 1 0.015 Setting 0s to 1s step 0.005s 0 1 0.005 2 * * *
49 08 PSlip Timer T2 Courier Number (Time) 4x02256 G2 200 1 0.015 Setting 0s to 1s step 0.005s 0 1 0.005 2 * * *
49 09 Blinder Angle Courier Number (Angle) 4x02257 G2 90 1 75 Setting 20° to 90° step 1° 20 90 1 2 * * *
49 0A PSlip Zc Courier Number (Impedance) 4x02258 G2 700 1 50*V1/I1 Setting 0.5*V1/I1 to 350*V1/I1 step 0.5*V1/I1 0.5*V1/I1 350*V1/I1 0.5*V1/I1 2 * * *
49 0B Zone1 Slip Count Unsigned Integer 4x02259 G1 19 1 1 Setting 1 to 20 step 1 1 20 1 2 * * *
49 0C Zone2 Slip Count Unsigned Integer 4x02260 G1 19 1 2 Setting 1 to 20 step 1 1 20 1 2 * * *
49 0D PSlip Reset Time Courier Number (Time) 4x02261 G2 10000 1 30 Setting 0s to 100s step 0.01s 0 100 0.01 2 * * *
4A 00 GROUP 1 INPUT LABELS * * * * * * *
4A 01 Opto Input 1 ASCII Text (16 chars) 4x02300 4x02307 G3 8 L1 Setting Group Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 02 Opto Input 2 ASCII Text (16 chars) 4x02308 4x02315 G3 8 L2 Setting Group Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 03 Opto Input 3 ASCII Text (16 chars) 4x02316 4x02323 G3 8 L3 Block IN>3&4 Setting Editable 16 character string 32 163 1 2 * * * * * * *
L3 Block IN>2

4A 04 Opto Input 4 ASCII Text (16 chars) 4x02324 4x02331 G3 8 L4 Block I>3&4 Setting Editable 16 character string 32 163 1 2 * * * * * * *
L4 Block I>2
4A 05 Opto Input 5 ASCII Text (16 chars) 4x02332 4x02339 G3 8 L5 Reset Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 06 Opto Input 6 ASCII Text (16 chars) 4x02340 4x02347 G3 8 L6 Ext Prot Trip Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 07 Opto Input 7 ASCII Text (16 chars) 4x02348 4x02355 G3 8 L7 52a Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 08 Opto Input 8 ASCII Text (16 chars) 4x02356 4x02363 G3 8 L8 52b Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 09 Opto Input 9 ASCII Text (16 chars) 4x02364 4x02371 G3 8 L9 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 0A Opto Input 10 ASCII Text (16 chars) 4x02372 4x02379 G3 8 L10 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 0B Opto Input 11 ASCII Text (16 chars) 4x02380 4x02387 G3 8 L11 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 0C Opto Input 12 ASCII Text (16 chars) 4x02388 4x02395 G3 8 L12 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 0D Opto Input 13 ASCII Text (16 chars) 4x02396 4x02403 G3 8 L13 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 0E Opto Input 14 ASCII Text (16 chars) 4x02404 4x02411 G3 8 L14 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 0F Opto Input 15 ASCII Text (16 chars) 4x02412 4x02419 G3 8 L15 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 10 Opto Input 16 ASCII Text (16 chars) 4x02420 4x02427 G3 8 L16 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 11 Opto Input 17 ASCII Text (16 chars) 4x02428 4x02435 G3 8 L17 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 12 Opto Input 18 ASCII Text (16 chars) 4x02436 4x02443 G3 8 L18 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 13 Opto Input 19 ASCII Text (16 chars) 4x02444 4x02451 G3 8 L19 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 14 Opto Input 20 ASCII Text (16 chars) 4x02452 4x02459 G3 8 L20 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 15 Opto Input 21 ASCII Text (16 chars) 4x02460 4x02467 G3 8 L21 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 16 Opto Input 22 ASCII Text (16 chars) 4x02468 4x02475 G3 8 L22 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 17 Opto Input 23 ASCII Text (16 chars) 4x02476 4x02483 G3 8 L23 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 18 Opto Input 24 ASCII Text (16 chars) 4x02484 4x02491 G3 8 L24 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4A 19 Opto Input 25 ASCII Text (16 chars) 4x02492 4x02499 G3 8 L25 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 1A Opto Input 26 ASCII Text (16 chars) 4x02500 4x02507 G3 8 L26 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 1B Opto Input 27 ASCII Text (16 chars) 4x02508 4x02515 G3 8 L27 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 1C Opto Input 28 ASCII Text (16 chars) 4x02516 4x02523 G3 8 L28 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 1D Opto Input 29 ASCII Text (16 chars) 4x02524 4x02531 G3 8 L29 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 1E Opto Input 30 ASCII Text (16 chars) 4x02532 4x02539 G3 8 L30 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 1F Opto Input 31 ASCII Text (16 chars) 4x02540 4x02547 G3 8 L31 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4A 20 Opto Input 32 ASCII Text (16 chars) 4x02548 4x02555 G3 8 L32 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 18 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
4B 00 GROUP 1 OUTPUT LABELS * * * * * * *
4B 01 Relay 1 ASCII Text (16 chars) 4x02556 4x02563 G3 8 R1 IN>1 Start Setting Editable 16 character string 32 163 1 2 * * * * * * *
R1 Trip CB
4B 02 Relay 2 ASCII Text (16 chars) 4x02564 4x02571 G3 8 R2 I>1 Start Setting Editable 16 character string 32 163 1 2 * * * * * * *
R2 Trip
PrimeMov
4B 03 Relay 3 ASCII Text (16 chars) 4x02572 4x02579 G3 8 R3 Any Trip Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 04 Relay 4 ASCII Text (16 chars) 4x02580 4x02587 G3 8 R4 General Alarm Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 05 Relay 5 ASCII Text (16 chars) 4x02588 4x02595 G3 8 R5 CB Fail Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 06 Relay 6 ASCII Text (16 chars) 4x02596 4x02603 G3 8 R6 Control Close Setting Editable 16 character string 32 163 1 2 * * * * * * *
R6 E/F Trip

4B 07 Relay 7 ASCII Text (16 chars) 4x02604 4x02611 G3 8 R7 Control Trip Setting Editable 16 character string 32 163 1 2 * * * * * *
R7 V or F Trip *
R7 Volt Trip
4B 08 Relay 8 ASCII Text (16 chars) 4x02612 4x02619 G3 8 R8 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R8 Freq Trip
4B 09 Relay 9 ASCII Text (16 chars) 4x02620 4x02627 G3 8 R9 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R9 Diff Trip
4B 0A Relay 10 ASCII Text (16 chars) 4x02628 4x02635 G3 8 R10 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R10 SysBack
Trip
4B 0B Relay 11 ASCII Text (16 chars) 4x02636 4x02643 G3 8 R11 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R11 NPS Trip
4B 0C Relay 12 ASCII Text (16 chars) 4x02644 4x02651 G3 8 R12 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R12 Ffail Trip
4B 0D Relay 13 ASCII Text (16 chars) 4x02652 4x02659 G3 8 R13 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R13 Power Trip
4B 0E Relay 14 ASCII Text (16 chars) 4x02660 4x02667 G3 8 R14 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
R14 V/Hz Trip
4B 0F Relay 15 ASCII Text (16 chars) 4x02668 4x02675 G3 8 R15 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 10 Relay 16 ASCII Text (16 chars) 4x02676 4x02683 G3 8 R16 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 11 Relay 17 ASCII Text (16 chars) 4x02684 4x02691 G3 8 R17 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 12 Relay 18 ASCII Text (16 chars) 4x02692 4x02699 G3 8 R18 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 13 Relay 19 ASCII Text (16 chars) 4x02700 4x02707 G3 8 R19 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 14 Relay 20 ASCII Text (16 chars) 4x02708 4x02715 G3 8 R20 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 15 Relay 21 ASCII Text (16 chars) 4x02716 4x02723 G3 8 R21 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 16 Relay 22 ASCII Text (16 chars) 4x02724 4x02731 G3 8 R22 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 17 Relay 23 ASCII Text (16 chars) 4x02732 4x02739 G3 8 R23 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 18 Relay 24 ASCII Text (16 chars) 4x02740 4x02747 G3 8 R24 Not Used Setting Editable 16 character string 32 163 1 2 * * * * * * *
4B 19 Relay 25 ASCII Text (16 chars) 4x02748 4x02755 G3 8 R25 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 1A Relay 26 ASCII Text (16 chars) 4x02756 4x02763 G3 8 R26 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 1B Relay 27 ASCII Text (16 chars) 4x02764 4x02771 G3 8 R27 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 1C Relay 28 ASCII Text (16 chars) 4x02772 4x02779 G3 8 R28 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 1D Relay 29 ASCII Text (16 chars) 4x02780 4x02787 G3 8 R29 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 1E Relay 30 ASCII Text (16 chars) 4x02788 4x02795 G3 8 R30 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 1F Relay 31 ASCII Text (16 chars) 4x02796 4x02803 G3 8 R31 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4B 20 Relay 32 ASCII Text (16 chars) 4x02804 4x02811 G3 8 R32 Not Used Setting Editable 16 character string 32 163 1 2 * * * *
4C 00 GROUP 1 RTD LABELS * * * * *
4C 01 RTD 1 ASCII Text (16 chars) 4x02812 4x02819 G3 8 RTD 1 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 02 RTD 2 ASCII Text (16 chars) 4x02820 4x02827 G3 8 RTD 2 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 03 RTD 3 ASCII Text (16 chars) 4x02828 4x02835 G3 8 RTD 3 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 04 RTD 4 ASCII Text (16 chars) 4x02836 4x02843 G3 8 RTD 4 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 05 RTD 5 ASCII Text (16 chars) 4x02844 4x02851 G3 8 RTD 5 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 06 RTD 6 ASCII Text (16 chars) 4x02852 4x02859 G3 8 RTD 6 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 07 RTD 7 ASCII Text (16 chars) 4x02860 4x02867 G3 8 RTD 7 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 08 RTD 8 ASCII Text (16 chars) 4x02868 4x02875 G3 8 RTD 8 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 09 RTD 9 ASCII Text (16 chars) 4x02876 4x02883 G3 8 RTD 9 Setting Editable 16 character string 32 163 1 2 * * * * *
4C 0A RTD 10 ASCII Text (16 chars) 4x02884 4x02891 G3 8 RTD 10 Setting Editable 16 character string 32 163 1 2 * * * * *
4D 00 GROUP 1 CLIO PROTECTION * * * * * * *
4D 02 CLIO Input 1 Indexed String 4x02895 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 04 CLI1 Input Type Indexed String 4x02896 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 3 1 2 * * * * * * *
4D 06 CLI1 Input Label ASCII Text (16 chars) 4x01900 4x01907 G3 8 CLIO Input 1 Setting Editable 16 character string 32 163 1 2 * * * * * * *
4D 08 CLI1 Minimum Courier Number (Decimal) 4x02897 4x02898 G35 2 0 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 0A CLI1 Maximum Courier Number (Decimal) 4x02899 4x02900 G35 2 100 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 0C CLI1 Alarm Indexed String 4x02901 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 0E CLI1 Alarm Fn Indexed String 4x02902 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 10 CLI1 Alarm Set Courier Number (Decimal) 4x02903 4x02904 G35 2 50 Setting CLI1 Minimum to CLI1 Maximum step 0.1 CLI1 Minimum CLI1 Maximum0.1 2 * * * * * * *
4D 12 CLI1 Alarm Delay Courier Number (Time) 4x02905 G2 1 1 Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 14 CLI1 Trip Indexed String 4x02906 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 16 CLI1 Trip Fn Indexed String 4x02907 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 18 CLI1 Trip Set Courier Number (Decimal) 4x02908 4x02909 G35 2 60 Setting CLI1 Minimum to CLI1 Maximum step 0.1 CLI1 Minimum CLI1 Maximum0.1 2 * * * * * * *
4D 1A CLI1 Trip Delay Courier Number (Time) 4x02910 G2 1 0 Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 1C CLI1 I< Alarm Indexed String 4x02911 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 1E CLI1 I< Alm Set Courier Number (Current) 4x02912 G2 1 0.0035 Setting 0mA to 4mA step 0.1mA 0 0.004 0.0001 2 * * * * * * *
4D 22 CLIO Input 2 Indexed String 4x02913 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 24 CLI2 Input Type Indexed String 4x02914 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 3 1 2 * * * * * * *
4D 26 CLI2 Input Label ASCII Text (16 chars) 4x01908 4x01915 G3 8 CLIO Input 2 Setting Editable 16 character string 32 163 1 2 * * * * * * *
4D 28 CLI2 Minimum Courier Number (Decimal) 4x02915 4x02916 G35 2 0 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 2A CLI2 Maximum Courier Number (Decimal) 4x02917 4x02918 G35 2 100 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 2C CLI2 Alarm Indexed String 4x02919 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 2E CLI2 Alarm Fn Indexed String 4x02920 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 30 CLI2 Alarm Set Courier Number (Decimal) 4x02921 4x02922 G35 2 50 Setting CLI2 Minimum to CLI2 Maximum step 0.1 CLI2 Minimum CLI2 Maximum0.1 2 * * * * * * *
4D 32 CLI2 Alarm Delay Courier Number (Time) 4x02923 G2 1 1s Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 34 CLI2 Trip Indexed String 4x02924 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 36 CLI2 Trip Fn Indexed String 4x02925 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 38 CLI2 Trip Set Courier Number (Decimal) 4x02926 4x02927 G35 2 60 Setting CLI2 Minimum to CLI2 Maximum step 0.1 CLI2 Minimum CLI2 Maximum0.1 2 * * * * * * *
4D 3A CLI2 Trip Delay Courier Number (Time) 4x02928 G2 1 0s Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 3C CLI2 I< Alarm Indexed String 4x02929 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 3E CLI2 I< Alm Set Courier Number (Current) 4x02930 G2 1 0.0035 Setting 0mA to 4mA step 0.1mA 0 0.004 0.0001 2 * * * * * * *
4D 42 CLIO Input 3 Indexed String 4x02931 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 44 CLI3 Input Type Indexed String 4x02932 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 3 1 2 * * * * * * *
4D 46 CLI3 Input Label ASCII Text (16 chars) 4x01916 4x01923 G3 8 CLIO Input 3 Setting Editable 16 character string 32 163 1 2 * * * * * * *
4D 48 CLI3 Minimum Courier Number (Decimal) 4x02933 4x02934 G35 2 0 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 4A CLI3 Maximum Courier Number (Decimal) 4x02935 4x02936 G35 2 100 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 4C CLI3 Alarm Indexed String 4x02937 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 4E CLI3 Alarm Fn Indexed String 4x02938 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 50 CLI3 Alarm Set Courier Number (Decimal) 4x02939 4x02940 G35 2 50 Setting CLI3 Minimum to CLI3 Maximum step 0.1 CLI3 Minimum CLI3 Maximum0.1 2 * * * * * * *
4D 52 CLI3 Alarm Delay Courier Number (Time) 4x02941 G2 1 1s Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 54 CLI3 Trip Indexed String 4x02942 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 56 CLI3 Trip Fn Indexed String 4x02943 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 58 CLI3 Trip Set Courier Number (Decimal) 4x02944 4x02945 G35 2 60 Setting CLI3 Minimum to CLI3 Maximum step 0.1 CLI3 Minimum CLI3 Maximum0.1 2 * * * * * * *
4D 5A CLI3 Trip Delay Courier Number (Time) 4x02946 G2 1 0s Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 5C CLI3 I< Alarm Indexed String 4x02947 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 5E CLI3 I< Alm Set Courier Number (Current) 4x02948 G2 1 0.0035 Setting 0mA to 4mA step 0.1mA 0 0.004 0.0001 2 * * * * * * *
4D 62 CLIO Input 4 Indexed String 4x02949 G37 G37 1 Enabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 64 CLI4 Input Type Indexed String 4x02950 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 3 1 2 * * * * * * *
4D 66 CLI4 Input Label ASCII Text (16 chars) 4x01924 4x01931 G3 8 CLIO Input 4 Setting Editable 16 character string 32 163 1 2 * * * * * * *
4D 68 CLI4 Minimum Courier Number (Decimal) 4x02951 4x02952 G35 2 0 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 6A CLI4 Maximum Courier Number (Decimal) 4x02953 4x02954 G35 2 100 Setting -9999 to 9999 step 0.1 -9999 9999 0.1 2 * * * * * * *
4D 6C CLI4 Alarm Indexed String 4x02955 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 6E CLI4 Alarm Fn Indexed String 4x02956 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 70 CLI4 Alarm Set Courier Number (Decimal) 4x02957 4x02958 G35 2 50 Setting CLI4 Minimum to CLI4 Maximum step 0.1 CLI4 Minimum CLI4 Maximum0.1 2 * * * * * * *
4D 72 CLI4 Alarm Delay Courier Number (Time) 4x02959 G2 1 1s Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 74 CLI4 Trip Indexed String 4x02960 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 76 CLI4 Trip Fn Indexed String 4x02961 G154 G154 1 Over Setting 0 = Under, 1 = Over 0 1 1 2 * * * * * * *
4D 78 CLI4 Trip Set Courier Number (Decimal) 4x02962 4x02963 G35 2 60 Setting CLI4 Minimum to CLI4 Maximum step 0.1 CLI4 Minimum CLI4 Maximum0.1 2 * * * * * * *
4D 7A CLI4 Trip Delay Courier Number (Time) 4x02964 G2 1 0s Setting 0s to 100s step 0.1s 0 100 0.1 2 * * * * * * *
4D 7C CLI4 I< Alarm Indexed String 4x02965 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D 7E CLI4 I< Alm Set Courier Number (Current) 4x02966 G2 1 0.0035 Setting 0mA to 4mA step 0.4mA 0 0.004 0.0004 2 * * * * * * *
4D A0 CLIO Output 1 Indexed String 4x02967 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D A2 CLO1 Output Type Indexed String 4x02968 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 2 1 2 * * * * * * *
4D A4 CLO1 Set Values Indexed String 4x02969 G54 G54 1 Primary Setting Primary, Secondary 0 1 1 2 * * * * * * *
4D A6 CLO1 Parameter Indexed String 4x02970 G155 G155 1 IA Magnitude Setting See CLIO measurement table 0 See G155 1 2 * * * * * * *
4D A8 CLO1 Minimum Courier Number 4x02971 4x02972 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D AA CLO1 Maximum Courier Number 4x02973 4x02974 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D B0 CLIO Output 2 Indexed String 4x02975 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D B2 CLO2 Output Type Indexed String 4x02976 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 2 1 2 * * * * * * *
4D B4 CLO2 Set Values Indexed String 4x02977 G54 G54 1 Primary Setting Primary, Secondary 0 1 1 2 * * * * * * *
4D B6 CLO2 Parameter Indexed String 4x02978 G155 G155 1 IB Magnitude Setting See CLIO measurement table 0 See G155 1 2 * * * * * * *
4D B8 CLO2 Minimum Courier Number 4x02979 4x02980 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D BA CLO2 Maximum Courier Number 4x02981 4x02982 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D C0 CLIO Output 3 Indexed String 4x02983 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D C2 CLO3 Output Type Indexed String 4x02984 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 2 1 2 * * * * * * *
4D C4 CLO3 Set Values Indexed String 4x02985 G54 G54 1 Primary Setting Primary, Secondary 0 1 1 2 * * * * * * *
4D C6 CLO3 Parameter Indexed String 4x02986 G155 G155 1 IC Magnitude Setting See CLIO measurement table 0 See G155 1 2 * * * * * * *
4D C8 CLO3 Minimum Courier Number 4x02987 4x02988 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D CA CLO3 Maximum Courier Number 4x02989 4x02990 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D D0 CLIO Output 4 Indexed String 4x02991 G37 G37 1 Disabled Setting Disabled, Enabled 0 1 1 2 * * * * * * *
4D D2 CLO4 Output Type Indexed String 4x02992 G153 G153 1 4-20mA Setting 0 = 0-1mA, 1 = 0-10mA, 2 = 0-20mA, 3 = 4-20mA 0 2 1 2 * * * * * * *
4D D4 CLO4 Set Values Indexed String 4x02993 G54 G54 1 Primary Setting Primary, Secondary 0 1 1 2 * * * * * * *
4D D6 CLO4 Parameter Indexed String 4x02994 G155 G155 1 IN Measured Setting See CLIO measurement table 0 See G155 1 2 * * * * * *
Mag *
IN Derived Mag
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 19 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
4D D8 CLO4 Minimum Courier Number 4x02995 4x02996 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4D DA CLO4 Maximum Courier Number 4x02997 4x02998 G35 2 See G155 table Setting See CLIO measurement table See G155 Meas. Range Table 2 * * * * * * *
4E 00 GROUP 1 SYSTEM CHECKS * *
4E 01 VOLTAGE MONITORS (Sub Heading) * * * * * * *
4E 02 Live Voltage Courier Number (Voltage) 4x11200 G2 G2 32 Setting 1*V1 to 132*V1 step = 0.5 1*V1 132*V1 0.5*V1 2 * * * * * * *
4E 03 Dead Voltage Courier Number (Voltage) 4x11201 G2 G2 13 Setting 1*V1 to 132*V1 step = 0.5 1*V1 132*V1 0.5*V1 2 * * * * * * *
4E 04 Gen UnderVoltage Courier Number (Voltage) 4x11202 G2 G2 54 Setting 1*V1 to 132*V1 step = 0.5 1*V1 132*V1 0.5*V1 2 * * * * * * *
4E 05 Gen Over Voltage Courier Number (Voltage) 4x11203 G2 G2 130 Setting 1*V1 to 185*V1 step = 0.5 1*V1 185*V1 0.5*V1 2 * * * * * * *
4E 06 Bus UnderVoltage Courier Number (Voltage) 4x11204 G2 G2 54 Setting 10*V1 to 132*V1 step = 0.5 10*V1 132*V1 0.5*V1 2 * * * * * * *
4E 07 Bus Over Voltage Courier Number (Voltage) 4x11205 G2 G2 130 Setting 60*V1 to 185*V1 step = 0.5 60*V1 185*V1 0.5*V1 2 * * * * * * *
4E 08 CS Diff Voltage Courier Number (Number) 4x11206 G2 G2 6.5 Setting 1*V1 to 132*V1 step = 0.5 1.0*V1 132.0*V1 0.5*V1 2 * * * * * * *
4E 09 CS Voltage Block Indexed String 4x11207 G41 G41 V< Setting 0 7 1 2 * * * * * * *
4E 0A Gen Under Freq Courier Number (Frequency) 4x11208 G2 G2 49.5 Setting 45HZ 65HZ 0.01HZ 2 * * * * * * *
4E 0B Gen Over Freq Courier Number (Frequency) 4x11209 G2 G2 50.5 Setting 45HZ 65HZ 0.01HZ 2 * * * * * * *
4E 10 CHECK SYNC (Sub Heading) * * * * * * *
4E 11 CS1 Status Indexed String 4x11210 G37 G37 Enabled Setting 0 1 1 2 * * * * * * *
4E 12 CS1 Phase Angle Courier Number (Angle) 4x11211 G2 G2 20 Setting 5 90 1 2 * * * * * * *
4E 13 CS1 Slip Control Indexed String 4x11212 G42 G42 Frequency only Setting 0 3 1 2 * * * * * * *
4E 14 CS1 Slip Freq Courier Number (Frequency) 4x11213 G2 G2 0.05 Setting 0.01 1 0.01 2 * * * * * * *
4E 15 CS1 Slip Timer Courier Number (Time) 4x11214 G2 G2 1 Setting 0 99 0.01 2 * * * * * * *
4E 16 CS2 Status Indexed String 4x11215 G37 G37 Disabled Setting 0 1 1 2 * * * * * * *
4E 17 CS2 Phase Angle Courier Number (Angle) 4x11216 G2 G2 20 Setting 5 90 1 2 * * * * * * *
4E 18 CS2 Slip Control Indexed String 4x11217 G156 G156 Frequency only Setting 0 4 1 2 * * * * * * *
4E 19 CS2 Slip Freq Courier Number (Frequency) 4x11218 G2 G2 0.05 Setting 0.01 1 0.01 2 * * * * * * *
4E 1A CS2 Slip Timer Courier Number (Time) 4x11219 G2 G2 1 Setting 0 99 0.01 2 * * * * * * *
4E 20 SYSTEM SPLIT (Sub Heading) * * *
4E 21 SS Status Indexed String 4x11220 G37 G37 Enabled Setting 0 1 1 2 * * * * * * *
4E 22 SS Phase Angle Courier Number (Angle) 4x11221 G2 G2 120 Setting 90 175 1 2 * * * * * * *
4E 23 SS Under V Block Indexed String 4x11222 G37 G37 Enabled Setting 0 1 1 2 * * * * * * *
4E 24 SS UnderVoltage Courier Number (Number) 4x11223 G2 G2 54 Setting 10.0*V1 132.0*V1 0.5*V1 2 * * * * * * *
4E 25 SS Timer Courier Number (time) 4x11224 G2 G2 1 Setting 0 99 0.01 2 * * * * * * *
4E 30 CB Close Time Courier Number (time) 4x11225 G2 1 0.05 Setting 0 0.5 0.001 2 * * *
50 00 GROUP 2 PROTECTION SETTINGS * * * * * * *
Repeat of Group 1 columns/rows 4x03000 4x04999 * * * * * * *
4x13000 4x14999
70 00 GROUP 3 PROTECTION SETTINGS * * * * * * *
Repeat of Group 1 columns/rows 4x05000 4x06999 * * * * * * *
4x15000 4x16999
90 00 GROUP 4 PROTECTION SETTINGS * * * * * * *
Repeat of Group 1 columns/rows 4x07000 4x08999 * * * * * * *
4x17000 4x18999
B0 00 (No Header) Auto extraction Event Record Column N/A * * * * * * *
B0 01 Select Record Unsigned Integer(2) Setting 0 to 65535 step 1 0 65535 1 * * * * * * *
B0 40 Faulted Phase Binary Flag (8 Bits) G16 Data * * * * * * *
B0 42 Start Elements1 Binary Flag (32 Bits) Indexed String G84 Data * * * * * * *
B0 43 Start Elements2 Binary Flag (32 Bits) Indexed String G107 Data * * * * * * *
B0 44 Start Elements3 Binary Flag (32 Bits) Indexed String G129 Data * * * * * * *
B0 45 Start Elements4 Binary Flag (32 Bits) G131 Data * * * * * * * For fault record use only.
B0 49 Trip Elements1 Binary Flag (32 Bits) Indexed String G85 Data * * * * * * *
B0 4A Trip Elements2 Binary Flag (32 Bits) Indexed String G86 Data * * * * * * *
B0 4B Trip Elements3 Binary Flag (32 Bits) Indexed String G130 Data * * * * * * *
B0 4C Trip Elements4 Binary Flag (32 Bits) N/A G132 Data * * * * * * *
B0 50 Fault Alarms Binary Flag (32 Bits) Indexed String G87 Data * * * * * * *
B0 51 Fault Alarms 2 Binary Flag (32 Bits) N/A G89 Data * * * * * * *
B0 55 Fault Time IEC870 Time & Date Data * * * * * * *
B0 57 Active Group Unsigned Integer Data * * * * * * *
B0 59 System Frequency Courier Number (frequency) Data * * * * * * *
B0 5B Fault Duration Courier Number (time) Data * * * * * * *
B0 5E CB Operate Time Courier Number (time) Data * * * * * * *
B0 60 Relay Trip Time Courier Number (time) Data * * * * * * *
B0 62 IA Courier Number (current) Data * * *
B0 62 IA-1 Courier Number (current) Data * * * *
B0 63 IB Courier Number (current) Data * * *
B0 63 IB-1 Courier Number (current) Data * * * *
B0 64 IC Courier Number (current) Data * * *
B0 64 IC-1 Courier Number (current) Data * * * *
B0 65 VAB Courier Number (voltage) Data * * * * * * *
B0 66 VBC Courier Number (voltage) Data * * * * * * *
B0 67 VCA Courier Number (voltage) Data * * * * * * *
B0 68 VAN Courier Number (voltage) Data * * * * * * *
B0 69 VBN Courier Number (voltage) Data * * * * * * *
B0 6A VCN Courier Number (voltage) Data * * * * * * *
B0 70 IA-2 Courier Number (current) Data * * * *
B0 71 IB-2 Courier Number (current) Data * * * *
B0 72 IC-2 Courier Number (current) Data * * * *
B0 80 IA Differential Courier Number (current) Data * * * *
B0 81 IB Differential Courier Number (current) Data * * * *
B0 82 IC Differential Courier Number (current) Data * * * *
B0 83 IA Diff PU Courier Number (current) Data * * * *
B0 84 IB Diff PU Courier Number (current) Data * * * *
B0 85 IC Diff PU Courier Number (current) Data * * * *
B0 86 IA Diff 2H Courier Number (current) Data * * * *
B0 87 IB Diff 2H Courier Number (current) Data * * * *
B0 88 IC Diff 2H Courier Number (current) Data * * * *
B0 89 IA Diff 5H Courier Number (current) Data * * * *
B0 8A IB Diff 5H Courier Number (current) Data * * * *
B0 8B IC Diff 5H Courier Number (current) Data * * * *
B0 90 VN Measured Courier Number (voltage) Data * * * * *
B0 90 VN1 Measured Courier Number (voltage) Data * *
B0 92 VN2 Measured Courier Number (voltage) Data * *
B0 94 VN Derived Courier Number (voltage) Data * * * * * * *
B0 96 IN Measured Courier Number (current) Data * * * * *
B0 96 IN Derived Courier Number (current) Data * *
B0 99 I Sensitive Courier Number (current) Data * * * * * * *
B0 9A I Sensitive2 Courier Number (current) *
B0 9C IREF Diff Courier Number (current) Data * * * * *
B0 9D IREF Bias Courier Number (current) Data * * * * *
B0 A0 I2 Courier Number (current) Data * * * * * * *
B0 A2 V2 Courier Number (voltage) Data * * * * * * *
B0 A6 3 Phase Watts Courier Number (Power) Data * * * * * * *
B0 A8 3 Phase VArs Courier Number (VAr) Data * * * * * * *
B0 AA 3Ph Power Factor Courier Number (Decimal) Data * * * * * * *
B0 B0 RTD 1 Courier Number (Temperature) Data * * * * *
B0 B1 RTD 2 Courier Number (Temperature) Data * * * * *
B0 B2 RTD 3 Courier Number (Temperature) Data * * * * *
B0 B3 RTD 4 Courier Number (Temperature) Data * * * * *
B0 B4 RTD 5 Courier Number (Temperature) Data * * * * *
B0 B5 RTD 6 Courier Number (Temperature) Data * * * * *
B0 B6 RTD 7 Courier Number (Temperature) Data * * * * *
B0 B7 RTD 8 Courier Number (Temperature) Data * * * * *
B0 B8 RTD 9 Courier Number (Temperature) Data * * * * *
B0 B9 RTD 10 Courier Number (Temperature) Data * * * * *
B0 C2 df/dt Courier Number (Hz/s) Data * *
B0 C4 V Vector Shift Courier Number (Angle) Data * *
B0 C6 CLIO Input 1 Courier Number (Decimal) Data * * * * * * *
B0 C7 CLIO Input 2 Courier Number (Decimal) Data * * * * * * *
B0 C8 CLIO Input 3 Courier Number (Decimal) Data * * * * * * *
B0 C9 CLIO Input 4 Courier Number (Decimal) Data * * * * * * *
B0 CA 64S V Magnitude Courier Number (voltage) Data *
B0 CB 64S I Magnitude Courier Number (current) Data *
B0 CC 64S R primary Courier Number (resistance) Data *
B0 CD 64R CL Input Courier Number (current) Data * * * * *
B0 CE 64R R Fault Courier Number (resistance) Data * * * * *
B0 D0 DLR Ambient Temp Courier Number (Temperature) Data *
B0 D1 Wind Velocity Courier Number (Velocity) Data *
B0 D2 Wind Direction Courier Number (Decimal) Data *
B0 D3 Solar Radiation Courier Number (Power) Data *
B0 D4 DLR Ampacity Courier Number (Current) Data *
B0 D5 DLR CurrentRatio Courier Number (Percentage) Data *
B0 D6 Dyn Conduct Temp Courier Number (Temperature) Data *
B0 E4 IA Peak Mag Courier Number (Current) G24 2 Data Not settable * * * * * IA(CT1) Peak Magnitude
B0 E5 IB Peak Mag Courier Number (Current) G24 2 Data Not settable * * * * * IB(CT1) Peak Magnitude
B0 E6 IC Peak Mag Courier Number (Current) G24 2 Data Not settable * * * * * IC(CT1) Peak Magnitude
B0 E7 I2t Phase A Courier Number (I2t) G24 2 Data Not settable * * * * * I2t(CT1) Phase A
B0 E8 I2t Phase B Courier Number (I2t) G24 2 Data Not settable * * * * * I2t(CT1) Phase B
B0 E9 I2t Phase C Courier Number (I2t) G24 2 Data Not settable * * * * * I2t(CT1) Phase C
B0 EA IA-2 Peak Mag Courier Number (Current) G24 2 Data Not settable * * * * IA(CT2) Peak Magnitude
B0 EB IB-2 Peak Mag Courier Number (Current) G24 2 Data Not settable * * * * IB(CT2) Peak Magnitude
B0 EC IC-2 Peak Mag Courier Number (Current) G24 2 Data Not settable * * * * IC(CT2) Peak Magnitude
B0 ED I2t Phase A-2 Courier Number (I2t) G24 2 Data Not settable * * * * I2t(CT2) Phase A
B0 EE I2t Phase B-2 Courier Number (I2t) G24 2 Data Not settable * * * * I2t(CT2) Phase B
B0 EF I2t Phase C-2 Courier Number (I2t) G24 2 Data Not settable * * * * I2t(CT2) Phase C
B1 00 No Header N/A * * * * * * *
B1 01 Select Record UINT16 Setting 0 to 65535 step 1 0 65535 1 * * * * * * *
470234511.xls
Relay Menu Database Courier & Modbus Database
Page 20 of 163

CourierRef
Col Row Courier Text Courier Data Type LCD ref Modbus Register Data Group Data Group Max Modbus Modbus Default Setting Cell Type Available Setting Min Max Step Password Model Description
Start End Courier Modbus numeric setting Registers Level P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36) P345 (V.36) P346 (V.36) P341 (V.70)
B1 02 Time and Date IEC Date and Time Data * * * * * * *
B1 03 Maint Text ASCII Text Data * * * * * * *
B1 04 Maint Type UINT32 Data * * * * * * *
B1 05 Maint Data UINT32 Data * * * * * * *
B2 00 DATA TRANSFER (No Header) N/A
B2 04 Domain Indexed String G57 PSL Settings Setting 0 to 1 step 1 0 1 1 2 * * * * * * *
B2 08 Sub-Domain Indexed String G90 Group 1 Setting 0 to 3 step 1 0 3 1 2 * * * * * * *
B2 0C Version Unsigned Integer (2 Bytes) 256 Setting 0 to 65535 step 1 0 65535 1 2 * * * * * * *
B2 10 Start Not Used * * * * * * *
B2 14 Length Not Used * * * * * * *
B2 18 Data Transfer Reference * * * * * * *
B2 1C Transfer Mode Unsigned Integer Indexed Strings G76 6 Setting 0 to 7 step 1 0 7 1 2 * * * * * * *
B2 20 Data Transfer Repeated groups of Unsigned Integers Setting * * * * * * *
B3 00 RECORDER CONTROL (No Header) N/A * * * * * * *
B3 01 UNUSED * * * * * * *
B3 02 Recorder Source Indexed String Samples Data * * * * * * *
B3 03-1F Reserved for future use * * * * * * *
B4 00 RECORDER EXTRACTION COLUMN (No Header) N/A * * * * * * *
B4 01 Select Record Unsigned Integer 0 Setting -199 to 199 step 1 -199 199 1 0 * * * * * * *
B4 02 Trigger Time IEC870 Time & Date Data * * * * * * *
B4 03 Active Channels Binary Flag Data * * * * * * *
B4 04 Channel Types Binary Flag Data * * * * * * *
B4 05 Channel Offsets Courier Number (decimal) Data * * * * * * *
B4 06 Channel Scaling Courier Number (decimal) Data * * * * * * *
B4 07 Channel SkewVal Integer Data * * * * * * *
B4 08 Channel MinVal Integer Data * * * * * * *
B4 09 Channel MaxVal Integer Data * * * * * * *
B4 0A Format Unsigned Integer Data * * * * * * * Record format: 0 = uncompressed, 1 = compressed
B4 0B Upload Unsigned Integer Data * * * * * * *
B4 0C-0F UNUSED
B4 10 No. Of Samples Unsigned Integer Data * * * * * * *
B4 11 Trig Position Unsigned Integer Data * * * * * * *
B4 12 Time Base Courier Number (time) Data * * * * * * *
B4 13 UNUSED
B4 14 Sample Timer Unsigned Integer Data * * * * * * *
B4 15-1F UNUSED
B4 20 Dist. Channel 1 Integer Data * * * * * * *
B4 21 Dist. Channel 2 Integer Data * * * * * * *
B4 22 Dist. Channel 3 Integer Data * * * * * * *
B4 23 Dist. Channel 4 Integer Data * * * * * * *
B4 24 Dist. Channel 5 Integer Data * * * * * * *
B4 25 Dist. Channel 6 Integer Data * * * * * * *
B4 26 Dist. Channel 7 Integer Data * * * * * * *
B4 27 Dist. Channel 8 Integer Data * * * * * * *
B4 28 Dist. Channel 9 Integer Data * * * * * * *
B4 29 Dist. Channel 10 Integer Data * * * * * * *
B4 2A Dist. Channel 11 Integer Data * * * * * * *
B4 2B Dist. Channel 12 Integer Data * * * * * * *
B4 2C Dist. Channel 13 Integer Data * * * * * * *
B4 2D-3D UNUSED
B4 3E Dist. Channel 31 Binary Flag Data * * * * * * *
B4 3F Dist. Channel 32 Binary Flag Data * * * * * * *
B5 Calibration Coefficients (Hidden) (Note No Text) N/A * * * * * * *
B5 01 Cal Soft Version ASCII text 16 chars * * * * * * *
B5 02 Cal Date and Time IEC Date and time * * * * * * *
B5 03 Channel Types Repeated Group 16 * Binary Flag 8 bits * * * * * * *
B5 04 Cal Coeffs Block transfer Repeated Group of UINT32 (4 coeffs voltage channel, 8 coeffs current channel) * * * * * * *
B6 00 Comms Diagnostics (Hidden) Note: No text in column text N/A * * * * * * *
B6 01 Bus Comms Err Count Front UINT32 * * * * * * *
B6 02 Bus Message Count Front UINT32 * * * * * * *
B6 03 Protocol Err Count Front UINT32 * * * * * * *
B6 04 Slave Message Count Front UNIT32
B6 05 Reset front count (Reset Menu Cell cmd only) * * * * * * *
B6 06 Bus Comms Err Count Rear UINT32 * * * * * * *
B6 07 Protocol Err Count Rear UINT32 * * * * * * *
B6 08 Slave Message Count Rear UINT32
B6 09 Busy Count Rear UINT32 * * * * * * *
B6 0A Reset Rear Count (Reset Menu Cell cmd only) * * * * * * *
B7 00 PSL DATA
B7 01 Grp 1 PSL Ref ASCII Text (32 Chars) 3x01000 3x01015 G3 16 Data * * * * * * *
B7 02 Date/Time IEC 870 Date & Time 3x01016 3x01019 G12 4 Data * * * * * * *
B7 03 Grp 1 PSL ID Unsigned Integer (32 bits) 3x01020 3x01021 G27 2 Data * * * * * * *
B7 11 Grp 2 PSL Ref ASCII Text (32 Chars) 3x01022 3x01037 G3 16 Data * * * * * * *
B7 12 Date/Time IEC 870 Date & Time 3x01038 3x01041 G12 4 Data * * * * * * *
B7 13 Grp 2 PSL ID Unsigned Integer (32 bits) 3x01042 3x01043 G27 2 Data * * * * * * *
B7 21 Grp 3 PSL Ref ASCII Text (32 Chars) 3x01044 3x01059 G3 16 Data * * * * * * *
B7 22 Date/Time IEC 870 Date & Time 3x01060 3x01063 G12 4 Data * * * * * * *
B7 23 Grp 3 PSL ID Unsigned Integer (32 bits) 3x01064 3x01065 G27 2 Data * * * * * * *
B7 31 Grp 4 PSL Ref ASCII Text (32 Chars) 3x01066 3x01079 G3 16 Data * * * * * * *
B7 32 Date/Time IEC 870 Date & Time 3x01082 3x01085 G12 4 Data * * * * * * *
B7 33 Grp 4 PSL ID Unsigned Integer (32 bits) 3x01086 3x01087 G27 2 Data * * * * * * *
B8 00 USER CURVES DATA N/A
B8 01 Curve 1 Name ASCII Text (32 Chars) 3x31088 3x31103 G3 16 Data * * * * * * *
B8 02 Date & Time IEC 870 Date & Time 3x31104 3x31107 G12 4 Data * * * * * * *
B8 03 Curve 1 ID Unsigned Integer (16 bits) 3x31108 G1 1 Data * * * * * * *
B8 04 Curve 1 Version Indexed String 3x31172 G300 1 Operate 1.0 Setting 0 1 1 * * * * * * *
B8 11 Curve 2 Name ASCII Text (32 Chars) 3x31109 3x31124 G3 16 Data * * * * * * *
B8 12 Date & Time IEC 870 Date & Time 3x31125 3x31128 G12 4 Data * * * * * * *
B8 13 Curve 2 ID Unsigned Integer (16 bits) 3x31129 G1 1 Data * * * * * * *
B8 14 Curve 2 Version Indexed String 3x31173 G300 1 Operate 1.0 Setting 0 1 1 * * * * * * *
B8 21 Curve 3 Name ASCII Text (32 Chars) 3x31130 3x31145 G3 16 Data * * * * * * *
B8 22 Date & Time IEC 870 Date & Time 3x31146 3x31149 G12 4 Data * * * * * * *
B8 23 Curve 3 ID Unsigned Integer (16 bits) 3x31150 G1 1 Data * * * * * * *
B8 24 Curve 3 Version Indexed String 3x31174 G300 1 Reset 1.1 Setting 0 1 1 * * * * * * *
B8 31 Curve 4 Name ASCII Text (32 Chars) 3x31151 3x31166 G3 16 Data * * * * * * *
B8 32 Date & Time IEC 870 Date & Time 3x31167 3x31170 G12 4 Data * * * * * * *
B8 33 Curve 4 ID Unsigned Integer (16 bits) 3x31171 G1 1 Data * * * * * *
B8 34 Curve 4 Version Indexed String 3x31175 G300 1 Reset 1.1 Setting 0 1 1 * * * * * * *
B8 F0 Restore Def Crv Indexed String Cmd * * * * * * *
BF 00 COMMS SYS DATA N/A * * * * * * *
BF 01 Dist Record Cntrl Ref Menu Cell(2) B300 Data * * * * * * *
BF 02 Dist Record Extract Ref Menu Cell(2) B400 Data * * * * * * *
BF 03 Setting Transfer Unsigned Integer Setting * * * * * * *
BF 04 Reset Demand None (Reset Menu Cell) Data(but supports Reset Menu cell) * * * * * * *
BF 05 UNUSED * * * * * * *
BF 06 Block Xfer Ref Menu Cell(2) B200 Data * * * * * * *
E0 00 DIAGNOSTICS (hidden) * * * * * * *
E0 01 Enable Column Indexed String G11 0 (No) Setting 0 1 1 2 * * * * * * *
E0 11 CPU Load-Instant Unsigned Integer (32 bits) Data * * * * * * *
E0 12 CPU Load-Average Unsigned Integer (32 bits) Data * * * * * * *
E0 13 CPU Load-Min Unsigned Integer (32 bits) Data * * * * * * *
E0 14 CPU Load-Max Unsigned Integer (32 bits) Data * * * * * * *
E0 1F CPU Load Reset Indexed String G11 0 (No) Setting 0 1 1 2 * * * * * * *
E0 21 DDB to set: Unsigned Integer (32 bits) Setting 0 1022 1 2 * * * * * * *
E0 22 DDB to reset: Unsigned Integer (32 bits) Setting 0 1022 1 2 * * * * * * *
E0 23 DDB to pulse: Unsigned Integer (32 bits) Setting 0 1022 1 2 * * * * * * *
E0 26 Name Unfitted IO Indexed String G11 0 (No) Setting 0 1 1 2 * * * * * * *
E0 31 UINT32 - 1 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * * * *
E0 32 UINT32 - 2 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * * * *
E0 33 UINT32 - 3 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * * * *
E0 34 UINT32 - 4 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * * * *
E0 35 UINT32 - 5 Unsigned Integer (32 bits) Setting 0 2^32-1 1 2 * * * * * * *
E0 41 INT32 - 1 Signed Integer (32 bits) Data * * * * * * *
E0 42 INT32 - 2 Signed Integer (32 bits) Data * * * * * * *
E0 43 INT32 - 3 Signed Integer (32 bits) Data * * * * * * *
E0 44 INT32 - 4 Signed Integer (32 bits) Data * * * * * * *
E0 45 INT32 - 5 Signed Integer (32 bits) Data * * * * * * *
E0 51 BIN32 - 1 Binary Flag (32 bits) Data * * * * * * *
E0 52 BIN32 - 2 Binary Flag (32 bits) Data * * * * * * *
E0 53 BIN32 - 3 Binary Flag (32 bits) Data * * * * * * *
E0 54 BIN32 - 4 Binary Flag (32 bits) Data * * * * * * *
E0 55 BIN32 - 5 Binary Flag (32 bits) Data * * * * * * *
E0 61 FLT32 - 1 Courier Number (meters) Data * * * * * * *
E0 62 FLT32 - 2 Courier Number (meters) Data * * * * * * *
E0 63 FLT32 - 3 Courier Number (meters) Data * * * * * * *
E0 64 FLT32 - 4 Courier Number (meters) Data * * * * * * *
E0 65 FLT32 - 5 Courier Number (meters) Data * * * * * * *
F0 00 ETHERNET STATUS Heading N/A * * * * * * *
F0 01 Ethernet Status Selector Unsigned Integer Setting 0 239 1 1 * * * * * * *
F0 02
F0 03 Ethernet Status Number Unsigned Integer Data * * * * * * *
F0 04 Ethernet Fatal Error Unsigned Integer Data * * * * * * *
470234511.xls
Relay Menu Database DataTypes
Page 21 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x

G1 1 Register UNSIGNED INTEGER (16 bits) * * * * * *

G2 1 Register NUMERIC SETTING (Unsigned 16 bit) * * * * * *


Used for floating point settings. The setting value is represented as the number of step increments from the
minimum value (see also G35).
Data formatted as per data type G1.
I.e. Setting value = (setting minimum) + ((register value) x (setting step size))

G3 1 Register ASCII TEXT CHARACTERS (2 characters per register) * * * * * *


Bit Mask (hex)
0xFF00 First character in high order 8 bits
0x00FF Second character in low order 8 bits

G4 2 Registers PLANT STATUS (32 bits)


Bit Mask (hex) Data formatted as per data type G27.
0x00000001 CB1 Open (0 = Off, 1 = On) * * * * * *
0x00000002 CB1 Closed (0 = Off, 1 = On) * * * * * *
0x00000004 Not Used (0 = Off, 1 = On)
0x00000008 Not Used (0 = Off, 1 = On)
0x00000010 Not Used (0 = Off, 1 = On)
0x00000020 Not Used (0 = Off, 1 = On)
0x00000040 Not Used (0 = Off, 1 = On)
0x00000080 Not Used (0 = Off, 1 = On)
0x00000100 Not Used (0 = Off, 1 = On)
0x00000200 Not Used (0 = Off, 1 = On)
0x00000400 Not Used (0 = Off, 1 = On)
0x00000800 Not Used (0 = Off, 1 = On)
0x00001000 Not Used (0 = Off, 1 = On)
0x00002000 Not Used (0 = Off, 1 = On)
0x00004000 Not Used (0 = Off, 1 = On)
0x00008000 Not Used (0 = Off, 1 = On)
0x00010000 Not Used (0 = Off, 1 = On)
0x00020000 Not Used (0 = Off, 1 = On)
0x00040000 Not Used (0 = Off, 1 = On)
0x00080000 Not Used (0 = Off, 1 = On)
0x00100000 Not Used (0 = Off, 1 = On)
0x00200000 Not Used (0 = Off, 1 = On)
0x00400000 Not Used (0 = Off, 1 = On)
0x00800000 Not Used (0 = Off, 1 = On)
0x01000000 Not Used (0 = Off, 1 = On)
0x02000000 Not Used (0 = Off, 1 = On)
0x04000000 Not Used (0 = Off, 1 = On)
0x08000000 Not Used (0 = Off, 1 = On)
0x10000000 Not Used (0 = Off, 1 = On)
0x20000000 Not Used (0 = Off, 1 = On)
0x40000000 Not Used (0 = Off, 1 = On)
0x80000000 Not Used (0 = Off, 1 = On)

G5 2 Registers CONTROL STATUS (32 Bits)


Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Not Used (0 = Off, 1 = On)
0x00000002 Not Used (0 = Off, 1 = On)
0x00000004 Not Used (0 = Off, 1 = On)
0x00000008 Not Used (0 = Off, 1 = On)
0x00000010 Not Used (0 = Off, 1 = On)
0x00000020 Not Used (0 = Off, 1 = On)
0x00000040 Not Used (0 = Off, 1 = On)
0x00000080 Not Used (0 = Off, 1 = On)
0x00000100 Not Used (0 = Off, 1 = On)
0x00000200 Not Used (0 = Off, 1 = On)
0x00000400 Not Used (0 = Off, 1 = On)
0x00000800 Not Used (0 = Off, 1 = On)
0x00001000 Not Used (0 = Off, 1 = On)
0x00002000 Not Used (0 = Off, 1 = On)
0x00004000 Not Used (0 = Off, 1 = On)
0x00008000 Not Used (0 = Off, 1 = On)
0x00010000 Not Used (0 = Off, 1 = On)
0x00020000 Not Used (0 = Off, 1 = On)
0x00040000 Not Used (0 = Off, 1 = On)
0x00080000 Not Used (0 = Off, 1 = On)
0x00100000 Not Used (0 = Off, 1 = On)
0x00200000 Not Used (0 = Off, 1 = On)
0x00400000 Not Used (0 = Off, 1 = On)
0x00800000 Not Used (0 = Off, 1 = On)
0x01000000 Not Used (0 = Off, 1 = On)
0x02000000 Not Used (0 = Off, 1 = On)
0x04000000 Not Used (0 = Off, 1 = On)
0x08000000 Not Used (0 = Off, 1 = On)
0x10000000 Not Used (0 = Off, 1 = On)
0x20000000 Not Used (0 = Off, 1 = On)
0x40000000 Not Used (0 = Off, 1 = On)
0x80000000 Not Used (0 = Off, 1 = On)

G6 1 Register Record Control Command Register * * * * * *


Value
0 No operation
1 Clear Event records
2 Clear Fault Record
3 Clear Maintenance Records
4 Reset Indications
5 Clear Disturbance Records

G7 1 Register VTS Indicate/Block * * * * * *


Value
0 Blocking
470234511.xls
Relay Menu Database DataTypes
Page 22 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
1 Indication

G8 2 Registers LOGIC INPUT STATUS (32 Bits)


Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Opto 1 Input State (0=Off, 1=Energised) * * * * * *
0x00000002 Opto 2 Input State (0=Off, 1=Energised) * * * * * *
0x00000004 Opto 3 Input State (0=Off, 1=Energised) * * * * * *
0x00000008 Opto 4 Input State (0=Off, 1=Energised) * * * * * *
0x00000010 Opto 5 Input State (0=Off, 1=Energised) * * * * * *
0x00000020 Opto 6 Input State (0=Off, 1=Energised) * * * * * *
0x00000040 Opto 7 Input State (0=Off, 1=Energised) * * * * * *
0x00000080 Opto 8 Input State (0=Off, 1=Energised) * * * * * *
0x00000100 Opto 9 Input State (0=Off, 1=Energised) * * * * * *
0x00000200 Opto 10 Input State (0=Off, 1=Energised) * * * * * *
0x00000400 Opto 11 Input State (0=Off, 1=Energised) * * * * * *
0x00000800 Opto 12 Input State (0=Off, 1=Energised) * * * * * *
0x00001000 Opto 13 Input State (0=Off, 1=Energised) * * * * * *
0x00002000 Opto 14 Input State (0=Off, 1=Energised) * * * * * *
0x00004000 Opto 15 Input State (0=Off, 1=Energised) * * * * * *
0x00008000 Opto 16 Input State (0=Off, 1=Energised) * * * * * *
0x00010000 Opto 17 Input State (0=Off, 1=Energised) * * * * * *
0x00020000 Opto 18 Input State (0=Off, 1=Energised) * * * * * *
0x00040000 Opto 19 Input State (0=Off, 1=Energised) * * * * * *
0x00080000 Opto 20 Input State (0=Off, 1=Energised) * * * * * *
0x00100000 Opto 21 Input State (0=Off, 1=Energised) * * * * * *
0x00200000 Opto 22 Input State (0=Off, 1=Energised) * * * * * *
0x00400000 Opto 23 Input State (0=Off, 1=Energised) * * * * * *
0x00800000 Opto 24 Input State (0=Off, 1=Energised) * * * * * *
0x01000000 Opto 25 Input State (0=Off, 1=Energised) * * *
0x02000000 Opto 26 Input State (0=Off, 1=Energised) * * *
0x04000000 Opto 27 Input State (0=Off, 1=Energised) * * *
0x08000000 Opto 28 Input State (0=Off, 1=Energised) * * *
0x10000000 Opto 29 Input State (0=Off, 1=Energised) * * *
0x20000000 Opto 30 Input State (0=Off, 1=Energised) * * *
0x40000000 Opto 31 Input State (0=Off, 1=Energised) * * *
0x80000000 Opto 32 Input State (0=Off, 1=Energised) * * *

G9 2 Registers RELAY OUTPUT STATUS (32 Bits)


Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Relay 1 (0=Not Operated, 1=Operated) * * * * * *
0x00000002 Relay 2 (0=Not Operated, 1=Operated) * * * * * *
0x00000004 Relay 3 (0=Not Operated, 1=Operated) * * * * * *
0x00000008 Relay 4 (0=Not Operated, 1=Operated) * * * * * *
0x00000010 Relay 5 (0=Not Operated, 1=Operated) * * * * * *
0x00000020 Relay 6 (0=Not Operated, 1=Operated) * * * * * *
0x00000040 Relay 7 (0=Not Operated, 1=Operated) * * * * * *
0x00000080 Relay 8 (0=Not Operated, 1=Operated) * * * * * *
0x00000100 Relay 9 (0=Not Operated, 1=Operated) * * * * * *
0x00000200 Relay 10 (0=Not Operated, 1=Operated) * * * * * *
0x00000400 Relay 11 (0=Not Operated, 1=Operated) * * * * * *
0x00000800 Relay 12 (0=Not Operated, 1=Operated) * * * * * *
0x00001000 Relay 13 (0=Not Operated, 1=Operated) * * * * * *
0x00002000 Relay 14 (0=Not Operated, 1=Operated) * * * * * *
0x00004000 Relay 15 (0=Not Operated, 1=Operated) * * * * * *
0x00008000 Relay 16 (0=Not Operated, 1=Operated) * * * * * *
0x00010000 Relay 17 (0=Not Operated, 1=Operated) * * * * * *
0x00020000 Relay 18 (0=Not Operated, 1=Operated) * * * * * *
0x00040000 Relay 19 (0=Not Operated, 1=Operated) * * * * * *
0x00080000 Relay 20 (0=Not Operated, 1=Operated) * * * * * *
0x00100000 Relay 21 (0=Not Operated, 1=Operated) * * * * * *
0x00200000 Relay 22 (0=Not Operated, 1=Operated) * * * * * *
0x00400000 Relay 23 (0=Not Operated, 1=Operated) * * * * * *
0x00800000 Relay 24 (0=Not Operated, 1=Operated) * * * * * *
0x01000000 Relay 25 (0=Not Operated, 1=Operated) * * *
0x02000000 Relay 26 (0=Not Operated, 1=Operated) * * *
0x04000000 Relay 27 (0=Not Operated, 1=Operated) * * *
0x08000000 Relay 28 (0=Not Operated, 1=Operated) * * *
0x10000000 Relay 29 (0=Not Operated, 1=Operated) * * *
0x20000000 Relay 30 (0=Not Operated, 1=Operated) * * *
0x40000000 Relay 31 (0=Not Operated, 1=Operated) * * *
0x80000000 Relay 32 (0=Not Operated, 1=Operated) * * *

G10 1 Register Signed fixed point number with 1 decimal place (16 bits) * * * * * *
I.e. divide register value by 10 to obtain actual value.

G11 1 Register YES/NO * * * * * *


Value
0 No
1 Yes

G12 4 Registers TIME AND DATE (Modbus only) * * * * * *


Bit Mask (hex) IEC60870-5-4 "Binary Time 2a" format
"Standard" presentation form - see G238
0xFFFF First Register: (format bytes 1 + 2)
-- High Byte: Milli-seconds low byte
-- Low Byte: Milli-seconds high byte
0xBF9F Second Register: (format bytes 3 + 4)
-- High Byte: Validity (mask 0x80) and minutes (mask 0x3F)
-- Low byte: Summertime (mask 0x80) and hours (mask 0x1F)
0xFF0F Third register: (format bytes 5 + 6)
-- High Byte: Day of week (mask 0xE0) and day of month (mask 0x1F)
-- Low Byte: Month of year (mask 0x0F)
0x7F00 Fourth register: (format bytes 7 + "dummy")
-- High Byte: Years of century (mask 0x7F)
-- Low Byte: "dummy" byte (always zero in value)
470234511.xls
Relay Menu Database DataTypes
Page 23 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
"Reverse" presentation format - see G238
0x007F First register: (format bytes "dummy" + 7)
-- High Byte: "dummy" byte (always zero in value)
-- Low Byte: Years of century (mask 0x7F)
0x0FFF Second register: (format bytes 6 + 5)
-- High Byte: Month of year (mask 0x0F)
-- Low Byte: Day of week (mask 0xE0) and day of month (mask 0x1F)
0x9FBF Third Register: (format bytes 4 + 3)
-- High byte: Summertime (mask 0x80) and hours (mask 0x1F)
-- Low Byte: Validity (mask 0x80) and minutes (mask 0x3F)
0xFFFF Forth Register: (format bytes 2 + 1)
-- High Byte: Milli-seconds High byte
-- Low Byte: Milli-seconds Low byte
NB High byte transmitted first, followed by low byte, for each register.

G13 1 Register EVENT RECORD TYPE * * * * * *


Value
0 Latched alarm active
1 Latched alarm inactive
2 Self reset alarm active
3 Self reset alarm inactive
4 Relay contact event
5 Opto-isolated input event
6 Protection event
7 General event
8 Fault record event
9 Maintenance record event

G14 1 Register I> Function Link * * * * * *


Bit Mask (hex)
0x0001 I>1 VTS Block
0x0002 I>2 VTS Block
0x0004 I>3 VTS Block
0x0008 I>4 VTS Block
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used

G15 1 Register DISTURBANCE RECORD INDEX STATUS * * * * * *


Value
0 No Record
1 Unextracted
2 Extracted

G16 1 Register FAULTED PHASE * * * * * *


Bit Mask (hex)
0x0001 Start A
0x0002 Start B
0x0004 Start C
0x0008 Start N
0x0010 Trip A
0x0020 Trip B
0x0040 Trip C
0x0080 Trip N

G17 1 Register IRIG-B STATUS * * * * * *


Value
0 Card not fitted
1 Card failed
2 Signal healthy
3 No signal

G18 1 Register Record Selection Command Register (MODBUS) * * * * * *


Bit Mask (hex)
0x0000 No Operation
0x0001 Select next event
0x0002 Accept Event
0x0004 Select next Disturbance Record
0x0008 Accept disturbance record
0x0010 Select Next Disturbance record page

G19 1 Register LANGUAGE (for P34xxxxxxx0xxx - EN/FR/DE/ES) * * * * * *


Value
0 English
1 Francais
2 Deutsch
3 Espanol

G19 1 Register LANGUAGE (for P34xxxxxxx5xxx - EN/FR/DE/RU) * * * * * *


Value
0 English
1 Francais
2 Deutsch
3 Russian

G19 1 Register LANGUAGE (for P34xxxxxxxCxxx - EN/FR/CN) * * * * * *


Value
0 English
1 Francais
2 中文(Chinese)

G20 2 Registers PASSWORD (4 Characters packed into 32 bits) * * * * * *


Bit Mask (hex) Data formatted as per data type G3.
0xFF00 First register, first password character
0x00FF First register, second password character
470234511.xls
Relay Menu Database DataTypes
Page 24 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0xFF00 Second register, third password character
0x00FF Second register, fourth password character
NOTE THAT WHEN REGISTERS OF THIS TYPE ARE READ THE SLAVE WILL
ALWAYS INDICATE AN "*" IN EACH CHARACTER POSITION TO PRESERVE
THE PASSWORD SECURITY.

G21 1 Register Rear Port 1 Interface Selection * * * * * *


Value
0 Copper
1 Fibre Optic

G22 1 Register PASSWORD CONTROL ACCESS LEVEL * * * * * *


Value
0 Level 0 - Passwords required for levels 1 & 2.
1 Level 1 - Password required for level 2.
2 Level 2 - No passwords required.

G23 1 Register Voltage Curve selection * * * * * *


Value
0 Disabled
1 DT
2 IDMT
3 User Curve 1
4 User Curve 2
5 User Curve 3
6 User Curve 4

G24 2 REGISTERS Unsigned fixed point number with 3 decimal places (32 bits) * * * * * *
Data formatted as per data type G27.
I.e. divide 'G27' value by 1000 to obtain actual value.
Current 0 - 4,000,000A Resolution 1mA
Voltage 0 - 4MV Resolution 1mV

G25 1 REGISTER Unsigned fixed point number with 3 decimal places (16 bits) * * * * * *
I.e. divide register value by 1000 to obtain actual value.
Time Interval 0.000 - 655.000s Resolution 1ms
Frequency 0.000 - 655.000Hz Resolution 0.001Hz

G26 1 Register MODBUS RELAY STATUS REGISTER * * * * * *


Bit Mask (hex)
0x0001 In Service Status (1= In service, 0= Out of service)
0x0002 Minor self test failure (=1, 0 otherwise)
0x0004 New auto-extraction event available (=1, 0 otherwise)
Time Synchronised (=1 after Modbus time synch. Resets to 0 after 5 minutes unless re-time synch'd. Other
0x0008
time synch sources do not affect this bit.)
0x0010 New auto-extraction disturbance record available (=1, 0 otherwise)
0x0020 Fault (not used, always zero)
0x0040 Trip LED status (1=LED On, 0 = LED Off)
0x0080 Alarm status summary (logical OR of all alarm status bits)
0x0100 Unused
0x0200 Unused
0x0400 Unused
0x0800 Unused
0x1000 Unused
0x2000 Unused
0x4000 Unused
0x8000 Unused

G27 2 REGISTERS UNSIGNED LONG (32 bit) VALUE * * * * * *


High order word stored in 1st register
Low order word stored in 2nd register

G28 1 REGISTER SIGNED INTEGER (16 bit) * * * * * *

G29 3 REGISTER INTEGER POWER/ENERGY WITH MULTIPLIER * * * * * *


First Register Per unit value formatted as a G28.
Second & third Scalar, formatted as a G27.
registers
Overall value = 'G28'x'G27' see Section 3.9 of Chapter 5 of Technical Guide for details

G30 1 REGISTER SIGNED VALUE, 2 DECIMAL PLACES * * * * * *


I.e. divide register value by 100 to obtain actual value.

G31 1 Register ANALOGUE CHANNEL ASSIGNMENT SELECTOR (Generator specific)


Value Value Value Value Value Value
Unused 0 0 0 0 0 0
VAN 1 1 1 1 1 1
VBN 2 2 2 2 2 2
VCN 3 3 3 3 3 3
VN1 4 4 4 4 4 4
IA 5 5 5
IA-1 5 5 5
IB 6 6 6
IB-1 6 6 6
IC 7 7 7
IC-1 7 7 7
IN 8 8 8 8
I Sensitive 8 9 9 9 9 8
IA-2 10 10 10
IB-2 11 11 11
IC-2 12 12 12
VN2 13 13
V64S 14
470234511.xls
Relay Menu Database DataTypes
Page 25 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
I64S 15
Frequency 9 10 13 14 16 9
64R CL Input Raw 10 11 14 15 17 10
64R R Fault Raw 11 12 15 16 18 11
64R R Fault 12 13 16 17 19 12
C/S Voltage 13 14 17 18 20 13

G32 1 Register DISTURBANCE RECORD DIGITAL CHANNEL ASSIGNMENT SELECTOR * * * * * *


Value
0 Not used (i.e. nothing recorded for the channel)
1 onwards See separate G32 DDB Table

G34 1 Register TRIGGER MODE * * * * * *


Value
0 Single
1 Extended

G35 2 Registers Numeric Setting (Unsigned 32 bit) * * * * * *


Used for floating point settings. The setting value is represented as the number of step increments from the
minimum value (see also G2).
Data formatted as per data type G27.
I.e. Setting value = (setting minimum) + (('G27' value) x (setting step size))

G36 1 Register REAL NUMBERS * * * * * *


Value
0 Polar
1 Rectangular

G37 1 Register ENABLED / DISABLED * * * * * *


Value
0 Disabled
1 Enabled

G38c COMMUNICATION BAUD RATE (COURIER) * * * * * *


Value
0 9600 bits/s
1 19200 bits/s
2 38400 bits/s

G38m COMMUNICATION BAUD RATE (MODBUS) * * * * * *


Value
0 9600 bits/s
1 19200 bits/s
2 38400 bits/s

G38v COMMUNICATION BAUD RATE (IEC60870-5-103) * * * * * *


Value
0 9600 bits/s
1 19200 bits/s

G38d COMMUNICATION BAUD RATE (DNP 3.0) * * * * * *


Value
0 1200 bits/s
1 2400 bits/s
2 4800 bits/s
3 9600 bits/s
4 19200 bits/s
5 38400 bits/s

G39 1 Register COMMUNICATIONS PARITY * * * * * *


Value
0 Odd
1 Even
2 None

G40 1 register C/S Location * * * * * *


value
0 A-N
1 B-N
2 C-N
3 A-B
4 B-C
5 C-A

G41 1 register C/S Voltage Blocking * * * * * *


value
0 None
1 V<
2 V>
3 Vdiff>
4 V< and V>
5 V< and V diff>
6 V> and V diff>
7 V< V> V diff>

G42 1 register C/S Slip Control 1 * * * * * *


value
0 none
1 Timer only
2 Frequency only
3 Frequency+Timer

G43 1 Register IDMT CURVE TYPE (Obsolete - See G150-G152) * * * * * *


Value
0 Disabled
1 DT
470234511.xls
Relay Menu Database DataTypes
Page 26 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
2 IEC S Inverse
3 IEC V Inverse
4 IEC E Inverse
5 UK LT Inverse
6 IEEE M Inverse
7 IEEE V Inverse
8 IEEE E Inverse
9 US Inverse
10 US ST Inverse

G44 1 Register DIRECTION * * * * * *


Value
0 Non-Directional
1 Directional Fwd
2 Directional Rev

G45 1 Register VTS BLOCK * * * * * *


Value
0 Block
1 Non-Directional

G46 1 Register POLARISATION * *


Value
0 Zero Sequence
1 Neg Sequence

G47 1 Register MEASURING MODE * * * * * *


Value
0 Phase-Phase
1 Phase-Neutral

G48 1 Register OPERATION MODE * * * * * *


Value
0 Any Phase
1 Three Phase

G49 1 Register VN OR IN INPUT * * * * * *


Value
0 Measured
1 Derived

G50 1 Register RTD SELECT * * * *


Bit Mask (hex)
0x0001 RTD Input #1
0x0002 RTD Input #2
0x0004 RTD Input #3
0x0008 RTD Input #4
0x0010 RTD Input #5
0x0020 RTD Input #6
0x0040 RTD Input #7
0x0080 RTD Input #8
0x0100 RTD Input #9
0x0200 RTD Input #10

G52 1 Register DEFAULT DISPLAY * * * * * *


Value
0 3Ph + N Current
1 3 Ph-neutral Voltage
2 Power
3 Date and Time
4 Description
5 Plant Reference
6 Frequency
7 Access Level

G53 1 Register SELECT FACTORY DEFAULTS * * * * * *


Value
0 No Operation
1 All Settings
2 Setting Group 1
3 Setting Group 2
4 Setting Group 3
5 Setting Group 4

G54 1 Register SELECT PRIMARY SECONDARY MEASUREMENTS * * * * * *


Value
0 Primary
1 Secondary

G55 1 Register CIRCUIT BREAKER CONTROL * *


Value
0 No Operation
1 Trip
2 Close

G56 1 Register PHASE MEASUREMENT REFERENCE * * * * * *


Value
0 VA
1 VB
2 VC
3 IA
4 IB
5 IC

G57 1 Register Data Transfer Domain * * * * * *


Value
470234511.xls
Relay Menu Database DataTypes
Page 27 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0 PSL Settings
1 PSL Configuration

G58 1 Register SEF/REF SELECTION


Value
0 SEF * * * * * *
1 SEF cos(PHI) * * * * * *
2 SEF sin(PHI) * * * * * *
3 Wattmetric * * * * * *
4 Hi Z REF * * * * * *
5 Lo Z REF * * * *
6 Lo Z REF+SEF * * * *
7 Lo Z REF+Wattmet * * * *

G59 1 Register BATTERY STATUS * * * * * *


Value
0 Dead
1 Healthy

G60 1 Register Time Delay Selection * * * * * *


Value
0 DT
1 Inverse

G61 1 Register ACTIVE GROUP CONTROL * * * * * *


Value
0 Select via Menu
1 Select via PSL

G62 1 Register SAVE AS * * * * * *


Value
0 No Operation
1 Save
2 Abort

G63 1 Register IN> Function Link


Bit Mask (hex)
0x0001 IN>1 VTS Block * *
0x0002 IN>2 VTS Block * *
0x0004 IN>3 VTS Block * *
0x0008 IN>4 VTS Block * *
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used

G64 1 Register ISEF> Func Link


Bit Mask (hex)
0x0001 ISEF>1 VTS Block * * * * * *
0x0002 ISEF>2 VTS Block * *
0x0004 ISEF>3 VTS Block * *
0x0008 ISEF>4 VTS Block * *
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used

G65 1 Register F< Function Link * * * * * *


Bit Mask (hex)
0x0001 F<1 Poledead Blk
0x0002 F<2 Poledead Blk
0x0004 F<3 Poledead Blk
0x0008 F<4 Poledead Blk
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used

G66 1 Register DISTURBANCE RECORDER DIGITAL CHANNEL TRIGGER * * * * * *


Value
0 No Trigger
1 Trigger L/H
2 Trigger H/L

G67 1 Register THERMAL OVERLOAD * * * * * *


Value
0 Single
1 Dual

G68 1 Register CB Fail Reset Options * * * * * *


Value
0 I< Only
1 CB Open & I<
2 Prot Reset & I<

G69 1 Register VTS RESET MODE * * * * * *


Value
0 Manual
1 Auto

G71 1 Register PROTOCOL * * * * * *


Value
0 Courier
1 IEC870-5-103
2 Modbus
3 DNP 3.0
470234511.xls
Relay Menu Database DataTypes
Page 28 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x

G76 1 Register TRANSFER MODE * * * * * *


Value
0 Prepare Rx
1 Complete Rx
2 Prepare Tx
3 Complete Tx
4 Rx Prepared
5 Tx Prepared
6 OK
7 Error

G79 1 Register Custom Settings * * * * * *


Value
0 Disabled
1 Basic
2 Complete

G80 1 Register Visible/Invisible * * * * * *


Value
0 Invisible
1 Visible

G81 1 Register Reset Lockout by * * * * * *


Value
0 User Interface
1 CB Close

G84 2 Registers Started Elements - 1 (32 bits)


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 General Start * * * * * *
0x00000002 Start Power1 * * * * * *
0x00000004 Start Power2 * * * * * *
0x00000008 Start FFail1 * * * *
0x00000010 Start FFail2 * * * *
0x00000020 Start V Dep O/C * * * *
0x00000040 Start I>1 * * * * * *
0x00000080 Start I>2 * * * * * *
0x00000100 Start I>3 * * * * * *
0x00000200 Start I>4 * * * * * *
0x00000400 Start IN>1 * * * * * *
0x00000800 Start IN>2 * * * * * *
0x00001000 Start IN>3 * *
0x00002000 Start IN>4 * *
0x00004000 Start ISEF>1 * * * * * *
0x00008000 Start ISEF>2 * *
0x00010000 Start ISEF>3 * *
0x00020000 Start ISEF>4 * *
0x00040000 Start NVD VN>1 * * * * * *
0x00080000 Start NVD VN>2 * * * * * *
0x00100000 Start 100%StEF3H * * *
0x00200000 Start Sen Power1 * * * * * *
0x00400000 Start Sen Power2 * * * * * *
0x00800000 Start z PSlip Z1 * * *
0x01000000 Start z PSlip Z2 * * *
0x02000000 Start Z<1 * * * *
0x04000000 Start Z<2 * * * *
0x08000000 Strt Xformer Dif * * *
0x10000000 Start TF I> * * * *
0x20000000 Not Used
0x40000000 Not Used
0x80000000 Not Used

G85 2 Registers Tripped Elements - 1 (32 Bits)


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Any Trip * * * * * *
0x00000002 Trip Gen Diff * * *
0x00000004 Trip Power1 * * * * * *
0x00000008 Trip Power2 * * * * * *
0x00000010 Trip FFail1 * * * *
0x00000020 Trip FFail2 * * * *
0x00000040 Trip NPS Thermal * * * *
0x00000080 Trip V Dep O/C * * * *
0x00000100 Trip I>1 * * * * * *
0x00000200 Trip I>2 * * * * * *
0x00000400 Trip I>3 * * * * * *
0x00000800 Trip I>4 * * * * * *
0x00001000 Trip IN>1 * * * * * *
0x00002000 Trip IN>2 * * * * * *
0x00004000 Trip IN>3 * *
0x00008000 Trip IN>4 * *
0x00010000 Trip ISEF>1 * * * * * *
0x00020000 Trip ISEF>2 * *
0x00040000 Trip ISEF>3 * *
0x00080000 Trip ISEF>4 * *
0x00100000 Trip IREF> * * * * * *
0x00200000 Trip NVD VN>1 * * * * * *
0x00400000 Trip NVD VN>2 * * * * * *
0x00800000 Trip 100%StEF3H * * *
0x01000000 Trip Dead Mach * * *
0x02000000 Trip Sen Power1 * * * * * *
0x04000000 Trip Sen Power2 * * * * * *
470234511.xls
Relay Menu Database DataTypes
Page 29 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0x08000000 Trip z PSlip Z1 * * *
0x10000000 Trip z PSlip Z2 * * *
0x20000000 Trip Thermal O/L * * * * * *
0x40000000 Trip Z<1 * * * *
0x80000000 Trip Z<2 * * * *

G86 2 Registers Tripped Elements - 2 (32 Bits)


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Trip V<1 * * * * * *
0x00000002 Trip V<2 * * * * * *
0x00000004 Trip V< A/AB * * * * * *
0x00000008 Trip V< B/BC * * * * * *
0x00000010 Trip V< C/CA * * * * * *
0x00000020 Trip V>1 * * * * * *
0x00000040 Trip V>2 * * * * * *
0x00000080 Trip V> A/AB * * * * * *
0x00000100 Trip V> B/BC * * * * * *
0x00000200 Trip V> C/CA * * * * * *
0x00000400 Trip F<1 * * * * * *
0x00000800 Trip F<2 * * * * * *
0x00001000 Trip F<3 * * * * * *
0x00002000 Trip F<4 * * * * * *
0x00004000 Trip F>1 * * * * * *
0x00008000 Trip F>2 * * * * * *
0x00010000 Trip V/Hz * * * *
0x00010000 Trip V Shift * *
0x00020000 Trp Xformer Dif * * *
0x00040000 Trip RTD 1 * * * *
0x00080000 Trip RTD 2 * * * *
0x00100000 Trip RTD 3 * * * *
0x00200000 Trip RTD 4 * * * *
0x00400000 Trip RTD 5 * * * *
0x00800000 Trip RTD 6 * * * *
0x01000000 Trip RTD 7 * * * *
0x02000000 Trip RTD 8 * * * *
0x04000000 Trip RTD 9 * * * *
0x08000000 Trip RTD 10 * * * *
0x10000000 Trip CL Input 1 * * * * * *
0x20000000 Trip CL Input 2 * * * * * *
0x40000000 Trip CL Input 3 * * * * * *
0x80000000 Trip CL Input 4 * * * * * *

G87 2 Registers Fault Alarms (32 Bit)


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 CB Fail 1 * * * * * *
0x00000002 CB Fail 2 * * * * * *
0x00000004 VTS * * * * * *
0x00000008 CTS-1 * * * * * *
0x00000010 Alarm FFail * * * *
0x00000020 Alm NPS Thermal * * * *
0x00000040 Alarm V/Hz * * * *
0x00000080 Alarm RTD 1 * * * *
0x00000100 Alarm RTD 2 * * * *
0x00000200 Alarm RTD 3 * * * *
0x00000400 Alarm RTD 4 * * * *
0x00000800 Alarm RTD 5 * * * *
0x00001000 Alarm RTD 6 * * * *
0x00002000 Alarm RTD 7 * * * *
0x00004000 Alarm RTD 8 * * * *
0x00008000 Alarm RTD 9 * * * *
0x00010000 Alarm RTD 10 * * * *
0x00020000 Alarm Thermal * * * * * *
0x00040000 Alarm CL Input 1 * * * * * *
0x00080000 Alarm CL Input 2 * * * * * *
0x00100000 Alarm CL Input 3 * * * * * *
0x00200000 Alarm CL Input 4 * * * * * *
0x00400000 CTS-2 * * *
0x00800000 64S R<1 Alarm *
0x01000000 64S Fail Alarm *
0x02000000 64R R<1 Alarm * * * *
0x04000000 64R CL I/P Fail * * * *
0x08000000 Amb T Fail Alm *
0x10000000 Wind V Fail Alm *
0x20000000 Wind D Fail Alm *
0x40000000 Solar R Fail Alm *
0x80000000 Not Used

G88 1 Register Alarms * * * * * *


Value
0 Alarm Disabled
1 Alarm Enabled

G89 2 Registers Fault Alarms 2 (32 Bit)


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 CT Mismatch Alm * * *
0x00000002 Loss of Life Alm * * * *
0x00000004 FAA Alarm * * * *
0x00000008 Thru Fault Alm * * * *
0x00000010 Circuit Flt Alm * * *
0x00000020 Therm Pretrip Alm * * * *
470234511.xls
Relay Menu Database DataTypes
Page 30 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0x00000040 Diff CTS Alarm * * *
0x00000080 System Split Alm * * * * * *
0x00000100 Not Used
0x00000200 Not Used
0x00000400 Not Used
0x00000800 Not Used
0x00001000 Not Used
0x00002000 Not Used
0x00004000 Not Used
0x00008000 Not Used
0x00010000 Not Used
0x00020000 Not Used
0x00040000 Not Used
0x00080000 Not Used
0x00100000 Not Used
0x00200000 Not Used
0x00400000 Not Used
0x00800000 Not Used
0x01000000 Not Used
0x02000000 Not Used
0x04000000 Not Used
0x08000000 Not Used
0x10000000 Not Used
0x20000000 Not Used
0x40000000 Not Used
0x80000000 Not Used

G90 1 Register Group Selection * * * * * *


Value
0 Group 1
1 Group 2
2 Group 3
3 Group 4

G93 1 Register Output Contact Commission Test * * * * * *


Value
0 No Operation
1 Apply Test
2 Remove Test

G94 1 Register Commission Test * * * * * *


Value
0 No Operation
1 Apply Test

G95 1 Register System Fn Links * * * * * *


Bit Mask (hex)
0x0001 Trip led self reset (1 = enable self reset)
0x0002 Not Used
0x0004 Not Used
0x0008 Not used
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used

G96 2 Registers Alarm Status 1 (alarms 1 - 32) (32 Bits)


Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Not Used * * * * * *
0x00000002 Freq out of range * * * * * *
0x00000004 SG-opto Invalid * * * * * *
0x00000008 Prot'n Disabled * * * * * *
0x00000010 VT Fail Alarm * * * * * *
0x00000020 CTS Fail Alarm * * *
0x00000020 CTS-1 Fail Alarm * * *
0x00000040 CB Fail * * * * * *
0x00000080 I^ Maint Alarm * * * * * *
0x00000100 I^ Maint Lockout * * * * * *
0x00000200 CB OPs Maint * * * * * *
0x00000400 CB OPs Lock * * * * * *
0x00000800 CB Time Maint * * * * * *
0x00001000 CB Time Lockout * * * * * *
0x00002000 Fault Freq Lock * * * * * *
0x00004000 CB Status Alarm * * * * * *
0x00008000 CB Trip Fail * * * * * *
0x00010000 CB Close Fail * * * * * *
0x00020000 Man CB Unhealthy * * * * * *
0x00040000 NPS Alarm * * * *
0x00080000 Thermal Alarm * * * * * *
0x00100000 V/Hz Alarm * * * *
0x00200000 Field Fail Alarm * * * *
0x00400000 RTD Thermal Alm * * * *
0x00800000 RTD Open Cct * * * *
0x01000000 RTD short Cct * * * *
0x02000000 RTD Data Error * * * *
0x04000000 RTD Board Fail * * * *
0x08000000 Freq Prot Alm * * * * * *
0x10000000 Voltage Prot Alm * * * * * *
0x20000000 CTS-2 Fail Alarm * * *
0x40000000 64S R<1 Alarm *
0x80000000 64S Fail Alarm *

G98 1 Register Copy to * * * * * *


Value
0 No Operation
1 Group 1
470234511.xls
Relay Menu Database DataTypes
Page 31 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
2 Group 2
3 Group 3
4 Group 4

G99 1 Register CB Control * *


Value
0 Disabled
1 Local
2 Remote
3 Local+Remote
4 Opto
5 Opto+local
6 Opto+Remote
7 Opto+Rem+local

G100 Not used

G101 1 Register Gen Diff Function Select * * *


Value
0 Disabled
1 Percentage Bias
2 High Impedance
3 Interturn

G102 1 Register Power Function Select * * * * * *


Value
0 Disabled
1 Reverse
2 Low Forward
3 Over

G103 1 Register System Backup Function Select * * * *


Value
0 Disabled
1 Volt controlled
2 Volt restrained

G104 1 Register System Backup Vector Rotation * * * *


Value
0 None
1 Delta-Star

G105 1 Register DEFINITE TIME OVERCURRENT SELECTION * * * * * *


Value
0 Disabled
1 DT

G107 2 Registers Started Elements - 2 (32 Bits)


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Start V<1 * * * * * *
0x00000002 Start V<2 * * * * * *
0x00000004 Start V< A/AB * * * * * *
0x00000008 Start V< B/BC * * * * * *
0x00000010 Start V< C/CA * * * * * *
0x00000020 Start V>1 * * * * * *
0x00000040 Start V>2 * * * * * *
0x00000080 Start V> A/AB * * * * * *
0x00000100 Start V> B/BC * * * * * *
0x00000200 Start V> C/CA * * * * * *
0x00000400 Start F<1 * * * * * *
0x00000800 Start F<2 * * * * * *
0x00001000 Start F<3 * * * * * *
0x00002000 Start F<4 * * * * * *
0x00004000 Start F>1 * * * * * *
0x00008000 Start F>2 * * * * * *
0x00010000 Start V/Hz>1 * * * *
0x00020000 Unused
0x00040000 Start CLI1 Alarm * * * * * *
0x00080000 Start CLI2 Alarm * * * * * *
0x00100000 Start CLI3 Alarm * * * * * *
0x00200000 Start CLI4 Alarm * * * * * *
0x00400000 Start CLI1 Trip * * * * * *
0x00800000 Start CLI2 Trip * * * * * *
0x01000000 Start CLI3 Trip * * * * * *
0x02000000 Start CLI4 Trip * * * * * *
0x04000000 Start df/dt >1 * * * * * *
0x08000000 Start df/dt >2 * * * * * *
0x10000000 Start df/dt >3 * * * * * *
0x20000000 Start df/dt >4 * * * * * *
0x40000000
0x80000000

G108 1 Register RTD Open Circuit Flags * * * *


Bit Mask (hex)
0x0001 RTD 1 label
0x0002 RTD 2 label
0x0004 RTD 3 label
0x0008 RTD 4 label
0x0010 RTD 5 label
0x0020 RTD 6 label
0x0040 RTD 7 label
0x0080 RTD 8 label
0x0100 RTD 9 label
470234511.xls
Relay Menu Database DataTypes
Page 32 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0x0200 RTD 10 label

G109 1 Register RTD Short Circuit Flags * * * *


Bit Mask (hex)
0x0001 RTD 1 label
0x0002 RTD 2 label
0x0004 RTD 3 label
0x0008 RTD 4 label
0x0010 RTD 5 label
0x0020 RTD 6 label
0x0040 RTD 7 label
0x0080 RTD 8 label
0x0100 RTD 9 label
0x0200 RTD 10 label

G110 1 Register RTD Data Error * * * *


Bit Mask (hex)
0x0001 RTD 1 label
0x0002 RTD 2 label
0x0004 RTD 3 label
0x0008 RTD 4 label
0x0010 RTD 5 label
0x0020 RTD 6 label
0x0040 RTD 7 label
0x0080 RTD 8 label
0x0100 RTD 9 label
0x0200 RTD 10 label

G111 1 Register System Backup V Dep OC IDMT Curve Type * * * *


Value
0 DT (DT)
1 IEC S Inverse (TMS)
2 IEC V Inverse (TMS)
3 IEC E Inverse (TMS)
4 UK LT Inverse (TMS)
5 Rectifier (TMS)
6 RI (K)
7 IEEE M Inverse (TD)
8 IEEE V Inverse (TD)
9 IEEE E Inverse (TD)
10 US Inverse (TD)
11 US ST Inverse (TD)
12 User Curve 1
13 User Curve 2
14 User Curve 3
15 User Curve 4

G112 1 Register 100% stator Earth Fault Status * * *


Value
0 Disabled
1 VN3H< Enabled
2 VN3H> Enabled

G113 1 Register Pole Slipping Operating Mode * * *


Value
0 Generating
1 Motoring
2 Both

G114 1 Register SEF/REF/SPower Selection * * * * * *


Value
0 Disabled
1 SEF/REF
2 Sensitive Power

G115 1 Register Power protection Operating Mode * * * * * *


Value
0 Generating
1 Motoring

G116 1 Register CT Source * * *


Value
0 IA-1 IB-1 IC-1
1 IA-2 IB-2 IC-2

G118 1 Register CB Control Logic Input Assignments * * * * * *


Value
0 None
1 52A
2 52B
3 Both 52A and 52B

G119 1 Register TEST MODE * * * * * *


Value
0 Disabled
1 Test Mode
2 Blocked

G125 2 REGISTERS IEEE FLOATING POINT FORMAT (Short float; 32 bits) * * * * * *


Bit 31 = sign
Bits 30-23 = e7 - e0
Implicit 1.
Bits 22-0 = f22 - f0
(32 bit value formatted as per data type G27)

G128 2 Registers Alarm Status 2 (alarms 33 - 64) (32 Bits) * * * * * *


470234511.xls
Relay Menu Database DataTypes
Page 33 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
Bit Mask (hex) Data formatted as per data type G27
0x00000001 CL Card I/P Fail * * * * * *
0x00000002 CL Card O/P Fail * * * * * *
0x00000004 CL Input 1 Alarm * * * * * *
0x00000008 CL Input 2 Alarm * * * * * *
0x00000010 CL Input 3 Alarm * * * * * *
0x00000020 CL Input 4 Alarm * * * * * *
0x00000040 CLI1 I< Fail Alm * * * * * *
0x00000080 CLI2 I< Fail Alm * * * * * *
0x00000100 CLI3 I< Fail Alm * * * * * *
0x00000200 CLI4 I< Fail Alm * * * * * *
0x00000400 64R R<1 Alarm * * * *
0x00000800 64R CL I/P Fail * * * *
* * *
0x00001000 CT Mismatch Alm *
0x00001000 Amb T Fail Alm *
* * *
0x00002000 Thru Fault Alm *
0x00002000 Wind V Fail Alm *
* * * *
0x00004000 Loss of Life Alm *
0x00004000 Wind D Fail Alm *
* * * *
0x00008000 FAA Alarm *
0x00008000 Solar R Fail Alm *
0x00010000 Circuit Flt Alm * * *
0x00020000 Therm Pretrip Alm * * *
0x00040000 Diff CTS Alarm * * * *
0x00080000 Man No Checksync * * * * * *
0x00100000 System Split Alm * * * * * *
0x00200000 MR User Alarm 11 * * * * * *
0x00400000 MR User Alarm 10 * * * * * *
0x00800000 MR User Alarm 9 * * * * * *
0x01000000 MR User Alarm 8 * * * * * *
0x02000000 MR User Alarm 7 * * * * * *
0x04000000 MR User Alarm 6 * * * * * *
0x08000000 MR User Alarm 5 * * * * * *
0x10000000 MR User Alarm 4 * * * * * *
0x20000000 SR User Alarm 3 * * * * * *
0x40000000 SR User Alarm 2 * * * * * *
0x80000000 SR User Alarm 1 * * * * * *

G129 2 Registers Started Elements - 3 (32 bits) * * * * * *


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data Format as per data type G27.
0x00000001 Start NVD VN>3 * * * * * *
0x00000002 Start NVD VN>4 * * * * * *
0x00000004 Start NVD VN>5 * *
0x00000008 Start NVD VN>6 * *
0x00000010 Start S2>1 * * * *
0x00000020 Start Freq Band1 * * * *
0x00000040 Start Freq Band2 * * * *
0x00000080 Start Freq Band3 * * * *
0x00000100 Start Freq Band4 * * * *
0x00000200 Start Freq Band5 * * * *
0x00000400 Start Freq Band6 * * * *
0x00000800 Start I2>1 * * * * * *
0x00001000 Start I2>2 * * * * * *
0x00002000 Start I2>3 * * * * * *
0x00004000 Start I2>4 * * * * * *
0x00008000 Start V2>1 * * * * * *
0x00010000 Start V/Hz>2 * * * *
0x00020000 Start V/Hz>3 * * * *
0x00040000 Start V/Hz>4 * * * *
0x00080000 Start 64S I>1 *
0x00100000 Start64S R<1 Alm *
0x00200000 Start 64S R<2 *
0x00400000 Start64R R<1 Alm * * * *
0x00800000 Start 64R R<2 * * * *
0x01000000 Start DLR I>1 *
0x02000000 Start DLR I>2 *
0x04000000 Start DLR I>3 *
0x08000000 Start DLR I>4 *
0x10000000 Start DLR I>5 *
0x20000000 Start DLR I>6 *
0x40000000 Not Used
0x80000000 Not Used

G130 2 Registers Tripped Elements - 3 (32 bits) * * * * * *


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data Format as per data type G27.
0x00000001 Trip NVD VN>3
0x00000002 Trip NVD VN>4 * * * * * *
0x00000004 Trip NVD VN>5 * * * * * *
0x00000008 Trip NVD VN>6 * *
0x00000010 Trip S2>1 * *
0x00000020 Trip Freq Band1 * * * *
0x00000040 Trip Freq Band2 * * * *
0x00000080 Trip Freq Band3 * * * *
0x00000100 Trip Freq Band4 * * * *
0x00000200 Trip Freq Band5 * * * *
0x00000400 Trip Freq Band6 * * * *
0x00000800 Trip I2>1 * * * * * *
470234511.xls
Relay Menu Database DataTypes
Page 34 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0x00001000 Trip I2>2 * * * * * *
0x00002000 Trip I2>3 * * * * * *
0x00004000 Trip I2>4 * * * * * *
0x00008000 Trip V2>1 * * * * * *
0x00010000 Trip V/Hz>2 * * * *
0x00020000 Trip V/Hz>3 * * * *
0x00040000 Trip V/Hz>4 * * * *
0x00080000 Trip 64S I>1 *
0x00100000 Trip 64S R<2 *
0x00200000 Trip 64R R<2 * * * *
0x00400000 Trip DLR I>1 *
0x00800000 Trip DLR I>2 *
0x01000000 Trip DLR I>3 *
0x02000000 Trip DLR I>4 *
0x04000000 Trip DLR I>5 *
0x08000000 Trip DLR I>6 *
0x10000000
0x20000000
0x40000000
0x80000000

G131 2 Registers Started Elements - 4 (32 bits) * * * *


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data Format as per data type G27.
0x00000001 Start HoTSpot >1 * * * *
0x00000002 Start HoTSpot >2 * * * *
0x00000004 Start HoTSpot >3 * * * *
0x00000008 Start Top Oil >1 * * * *
0x00000010 Start Top Oil >2 * * * *
0x00000020 Start Top Oil >3 * * * *
0x00000040 Not Used
0x00000080 Not Used
0x00000100 Not Used
0x00000200 Not Used
0x00000400 Not Used
0x00000800 Not Used
0x00001000 Not Used
0x00002000 Not Used
0x00004000 Not Used
0x00008000 Not Used
0x00010000 Not Used
0x00020000 Not Used
0x00040000 Not Used
0x00080000 Not Used
0x00100000 Not Used
0x00200000 Not Used
0x00400000 Not Used
0x00800000 Not Used
0x01000000 Not Used
0x02000000 Not Used
0x04000000 Not Used
0x08000000 Not Used
0x10000000 Not Used
0x20000000 Not Used
0x40000000 Not Used
0x80000000 Not Used

G132 2 Registers Tripped Elements - 4 (32 bits) * * * * * *


(For fault record use only. The associated Modbus registers cannot be accessed unless a fault
record is selected.)
Bit Mask (hex) Data Format as per data type G27.
0x00000001 Trip Hot Spot >1 * * * *
0x00000002 Trip Hot Spot >2 * * * *
0x00000004 Trip Hot Spot >3 * * * *
0x00000008 Trip Top Oil >1 * * * *
0x00000010 Trip Top Oil >2 * * * *
0x00000020 Trip Top Oil >3 * * * *
0x00000040 Trip df/dt >1 * * * * * *
0x00000080 Trip df/dt >2 * * * * * *
0x00000100 Trip df/dt >3 * * * * * *
0x00000200 Trip df/dt >4 * * * * * *
0x00000400 Not Used
0x00000800 Not Used
0x00001000 Not Used
0x00002000 Not Used
0x00004000 Not Used
0x00008000 Not Used
0x00010000 Not Used
0x00020000 Not Used
0x00040000 Not Used
0x00080000 Not Used
0x00100000 Not Used
0x00200000 Not Used
0x00400000 Not Used
0x00800000 Not Used
0x01000000 Not Used
0x02000000 Not Used
0x04000000 Not Used
0x08000000 Not Used
0x10000000 Not Used
0x20000000 Not Used
0x40000000 Not Used
0x80000000 Not Used
470234511.xls
Relay Menu Database DataTypes
Page 35 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
G140 1 Regsiter User Curve Reset Timer Delay Selection * * * * * *
Value
0 DT
1 User Curve 1
2 User Curve 2
3 User Curve 3
4 User Curve 4

G150 1 Register POC IDMT CURVE TYPE * * * * * *


Value
0 Disabled
1 DT (DT)
2 IEC S Inverse (TMS)
3 IEC V Inverse (TMS)
4 IEC E Inverse (TMS)
5 UK LT Inverse (TMS)
6 Rectifier (TMS)
7 RI (K)
8 IEEE M Inverse (TD)
9 IEEE V Inverse (TD)
10 IEEE E Inverse (TD)
11 US Inverse (TD)
12 US ST Inverse (TD)
13 User Curve 1
14 User Curve 2
15 User Curve 3
16 User Curve 4

G151 1 Register EF IDMT CURVE TYPE * * * * * *


Value
0 Disabled
1 DT (DT)
2 IEC S Inverse (TMS)
3 IEC V Inverse (TMS)
4 IEC E Inverse (TMS)
5 UK LT Inverse (TMS)
6 RI (K)
7 IEEE M Inverse (TD)
8 IEEE V Inverse (TD)
9 IEEE E Inverse (TD)
10 US Inverse (TD)
11 US ST Inverse (TD)
12 IDG
13 User Curve 1
14 User Curve 2
15 User Curve 3
16 User Curve 4

G152 1 Register SEF IDMT CURVE TYPE * * * * * *


Value
0 Disabled
1 DT (DT)
2 IEC S Inverse (TMS)
3 IEC V Inverse (TMS)
4 IEC E Inverse (TMS)
5 UK LT Inverse (TMS)
6 IEEE M Inverse (TD)
7 IEEE V Inverse (TD)
8 IEEE E Inverse (TD)
9 US Inverse (TD)
10 US ST Inverse (TD)
11 IDG
12 User Curve 1
13 User Curve 2
14 User Curve 3
15 User Curve 4

G153 1 Register CLIO Input Range * * * * * *


Value
0 0-1mA
1 0-10mA
2 0-20mA
3 4-20mA

G154 1 Register CLIO Trip / Alarm operating mode * * * * * *


Value
0 Under
1 Over

G155 2 Register CLIO Output Measurement


Value Value Value Value Value Value
IA Magnitude 0 0 0 0 0 0
IB Magnitude 1 1 1 1 1 1
IC Magnitude 2 2 2 2 2 2
IN Measured Mag 3 3 3 3
IN Derived Mag 3 3
I Sen Magnitude 4 4 4 4 4 4
I1 Magnitude 5 5 5 5 5 5
I2 Magnitude 6 6 6 6 6 6
I0 Magnitude 7 7 7 7 7 7
IA RMS 8 8 8 8 8 8
470234511.xls
Relay Menu Database DataTypes
Page 36 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
IB RMS 9 9 9 9 9 9
IC RMS 10 10 10 10 10 10
VAB Magnitude 11 11 11 11 11 11
VBC Magnitude 12 12 12 12 12 12
VCA Magnitude 13 13 13 13 13 13
VAN Magnitude 14 14 14 14 14 14
VBN Magnitude 15 15 15 15 15 15
VCN Magnitude 16 16 16 16 16 16
VN1 Magnitude 17 17 17 17 17 17
VN Derived Mag 18 18 18 18 18 18
V1 Magnitude 19 19 19 19 19 19
V2 Magnitude 20 20 20 20 20 20
V0 Magnitude 21 21 21 21 21 21
VAN RMS 22 22 22 22 22 22
VBN RMS 23 23 23 23 23 23
VCN RMS 24 24 24 24 24 24
Frequency 25 25 25 25 25 25
3 Phase Watts 26 26 26 26 26 26
A Phase Watts 27 27 27 27 27 27
B Phase Watts 28 28 28 28 28 28
C Phase Watts 29 29 29 29 29 29
3 Phase Vars 30 30 30 30 30 30
A Phase Vars 31 31 31 31 31 31
B Phase Vars 32 32 32 32 32 32
C Phase Vars 33 33 33 33 33 33
3 Phase VA 34 34 34 34 34 34
A Phase VA 35 35 35 35 35 35
B Phase VA 36 36 36 36 36 36
C Phase VA 37 37 37 37 37 37
3Ph Power Factor 38 38 38 38 38 38
APh Power Factor 39 39 39 39 39 39
BPh Power Factor 40 40 40 40 40 40
CPh Power Factor 41 41 41 41 41 41
3Ph W Fix Demand 42 42 42 42 42 42
3Ph Vars Fix Dem 43 43 43 43 43 43
IA Fixed Demand 44 44 44 44 44 44
IB Fixed Demand 45 45 45 45 45 45
IC Fixed Demand 46 46 46 46 46 46
3 Ph W Roll Dem 47 47 47 47 47 47
3Ph Vars RollDem 48 48 48 48 48 48
IA Roll Demand 49 49 49 49 49 49
IB Roll Demand 50 50 50 50 50 50
IC Roll Demand 51 51 51 51 51 51
3Ph W Peak Dem 52 52 52 52 52 52
3Ph Var Peak Dem 53 53 53 53 53 53
IA Peak Demand 54 54 54 54 54 54
IB Peak Demand 55 55 55 55 55 55
IC Peak Demand 56 56 56 56 56 56
VN 3rd Harmonic 57 57 57
NPS Thermal 57 58 58 58
Thermal Overload 57 58 59 59 59 57
RTD 1 59 60 60 60
RTD 2 60 61 61 61
RTD 3 61 62 62 62
RTD 4 62 63 63 63
RTD 5 63 64 64 64
RTD 6 64 65 65 65
RTD 7 65 66 66 66
RTD 8 66 67 67 67
RTD 9 67 68 68 68
RTD 10 68 69 69 69
CL Input 1 58 69 70 70 70 58
CL Input 2 59 70 71 71 71 59
CL Input 3 60 71 72 72 72 60
CL Input 4 61 72 73 73 73 61
IN Derived Mag 73
IN-1 Derived Mag 74 74 74
IN-2 Derived Mag 75 75 75
VN2 Magnitude 76 76
Volts/Hz 74 76 77 77
DLR Ampacity 62
Max Iac 63
Df/dt 62 75 77 78 78 64
C/S Voltage Mag 63 76 78 79 79 65
C/S Gen-Bus Mag 64 77 79 80 80 66
Slip Frequency 65 78 80 81 81 67

G156 C/S Slip Control 2 * * * * * *


0 None
1 Timer only
2 Frequency only
3 Frequency+Timer
4 Frequency+CB

G158 1 Register I2> Function Link * * * * * *


Bit Mask (hex)
0x0001 I2>1 VTS Block
0x0002 I2>2 VTS Block
0x0004 I2>3 VTS Block
0x0008 I2>4 VTS Block
0x0010 Not Used
0x0020 Not Used
0x0040 Not Used
0x0080 Not Used

G159 1 Register VN Input Selection * * * * * *


470234511.xls
Relay Menu Database DataTypes
Page 37 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
Value
0 Derived * * * * * *
1 VN1 * * * * * *
2 VN2 * *

G160 1 Register V/Hz Curve Selection * * * *


Value
0 DT
1 IDMT
2 User Curve 1
3 User Curve 2
4 User Curve 3
5 User Curve 4

G161 1 Register NVD (Residual OV) Curve Selection * * * * * *


Value
0 DT
1 IDMT
2 User Curve 1
3 User Curve 2
4 User Curve 3
5 User Curve 4

G162 1 Register VT Nominal Rating *


Value
0 100/120V
1 380/480V

G163 1 Register Phase Sequence * * * * * *


Value
0 Standard ABC
1 Reverse ACB

G164 1 Register CT/VT 3-Phase Phase-Reversal Swap * * * * * *


Value
0 No Swap
1 A-B Swapped
2 B-C Swapped
3 C-A Swapped

G165 1 Register CT/VT Polarity * * * * * *


value
0 Standard
1 Inverted

G166 1 Register Current Loop Selection * * * *


Value
0 Current Loop CL1
1 Current Loop CL2
2 Current Loop CL3
3 Current Loop CL4

G168 1 Register Injection Frequency * * * *


Value
0 0.25 Hz
1 0.5 Hz
2 1.0 Hz

G169 BRITISH CONDUCTOR TYPE (CAN BE EXTENDED TO GLOBAL CONDUCTORS) *


Value
0 Gopher
1 Weasel
2 Ferret
3 Rabbit
4 Horse
5 Dog
6 Wolf
7 Dingo
8 Lynx
9 Caracal
10 Panther
11 Jaguar
12 Zebra
13 Fox
14 Mink
15 Skunk
16 Beaver
17 Raccoon
18 Otter
19 Cat
20 Hare
21 Hyena
22 Leopard
23 Tiger
24 Coyote
25 Lion
26 Bear
27 Batang
28 Goat
29 Antelope
30 Sheep
31 Bison
32 Deer
33 Camel
34 Elk
470234511.xls
Relay Menu Database DataTypes
Page 38 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
35 Moose
36 Custom

G170 Dynamic Line Rating (DLR) Channels Selection *


Value
0 Disabled
1 CLI1
2 CLI2
3 CLI3
4 CLI4

G171 Dynamic Line Rating (DLR) Protection Algorithm Selection *


Value
0 Disabled
1 CIGRE Std 207
2 IEEE Std 738

G172 Power Transformer (PTR) Cooling Method * *


Value
0 Natural (ON..)
1 Forced (OF..)
2 Direct (OD..)

G174 1 register Winding Type * * *


value
0 Generator
1 Xformer

G175 1 register HV Connection * * *


value
0 Y-Wye
1 D-Delta
2 Z-Zigzag

G176 1 register Grounding * * *


value
0 Grounded
1 Ungrounded

G177 1 register Main VT Location * * * * * *


value
0 Gen
1 Bus

G180 1 register C/S Slip Mode * * * * * *


value
0 Positive
1 Negative

G182 1 register DF/DT Dir'n * * * * * *


value
0 Negative
1 Positive
2 Both

G185 1 Register Set Mode * * *


Value
0 Simple
1 Advanced

G186 1 Register Winding * * *


Value
0 HV
1 LV

G187 1 Register Diff CTS Status * * *


Value
0 Indication
1 Restrain

G189 1 Register Ambient T * * * *


Value
0 RTD1
1 RTD2
2 RTD3
3 RTD4
4 RTD5
5 RTD6
6 RTD7
7 RTD8
8 RTD9
9 RTD10
10 AVERAGE
11 CLIO1
12 CLIO2
13 CLIO3
14 CLIO4

G190 1 Register Top Oil T * * * *


Value
0 RTD1
1 RTD2
2 RTD3
470234511.xls
Relay Menu Database DataTypes
Page 39 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
3 RTD4
4 RTD5
5 RTD6
6 RTD7
7 RTD8
8 RTD9
9 RTD10
10 CALCULATED
11 CLIO1
12 CLIO2
13 CLIO3
14 CLIO4

G191 1 Register Cooling Mode * * * *


Value
0 Natural
1 Forced Air
2 Forced Oil
3 Forced Air & Oil
4 Select via PSL

G192 1 Register Mn't Winding * * * *


Value
0 HV Current
1 LV Current
2 Biased Current

G193 1 Register Dfdt Algorithm * * * * *


Value
0 Fixed Window
1 Rolling Window

G200 1 Register Global Opto Nominal Voltage Selection * * * * * *


Value
0 24-27V
1 30-34V
2 48-54V
3 110-125V
4 220-250V
5 Custom

G201 1 Register Single Opto Nominal Voltage Selection * * * * * *


Value
0 24-27V
1 30-34V
2 48-54V
3 110-125V
4 220-250V

G202 2 Registers Control Input Status (32 Bits) * * * * * *


Bit Mask (hex) Data formatted as per data type G27.
0x00000001 Control Input 1 (0 = Reset, 1 = Set)
0x00000002 Control Input 2 (0 = Reset, 1 = Set)
0x00000004 Control Input 3 (0 = Reset, 1 = Set)
0x00000008 Control Input 4 (0 = Reset, 1 = Set)
0x00000010 Control Input 5 (0 = Reset, 1 = Set)
0x00000020 Control Input 6 (0 = Reset, 1 = Set)
0x00000040 Control Input 7 (0 = Reset, 1 = Set)
0x00000080 Control Input 8 (0 = Reset, 1 = Set)
0x00000100 Control Input 9 (0 = Reset, 1 = Set)
0x00000200 Control Input 10 (0 = Reset, 1 = Set)
0x00000400 Control Input 11 (0 = Reset, 1 = Set)
0x00000800 Control Input 12 (0 = Reset, 1 = Set)
0x00001000 Control Input 13 (0 = Reset, 1 = Set)
0x00002000 Control Input 14 (0 = Reset, 1 = Set)
0x00004000 Control Input 15 (0 = Reset, 1 = Set)
0x00008000 Control Input 16 (0 = Reset, 1 = Set)
0x00010000 Control Input 17 (0 = Reset, 1 = Set)
0x00020000 Control Input 18 (0 = Reset, 1 = Set)
0x00040000 Control Input 19 (0 = Reset, 1 = Set)
0x00080000 Control Input 20 (0 = Reset, 1 = Set)
0x00100000 Control Input 21 (0 = Reset, 1 = Set)
0x00200000 Control Input 22 (0 = Reset, 1 = Set)
0x00400000 Control Input 23 (0 = Reset, 1 = Set)
0x00800000 Control Input 24 (0 = Reset, 1 = Set)
0x01000000 Control Input 25 (0 = Reset, 1 = Set)
0x02000000 Control Input 26 (0 = Reset, 1 = Set)
0x04000000 Control Input 27 (0 = Reset, 1 = Set)
0x08000000 Control Input 28 (0 = Reset, 1 = Set)
0x10000000 Control Input 29 (0 = Reset, 1 = Set)
0x20000000 Control Input 30 (0 = Reset, 1 = Set)
0x40000000 Control Input 31 (0 = Reset, 1 = Set)
0x80000000 Control Input 32 (0 = Reset, 1 = Set)

G203 1 Register Virtual Input * * * * * *


Value
0 No Operation
1 Set
2 Reset

G204 1 Register REAR COMMS CARD STATUS * * * * * *


Value
0 Unsupported
1 Card Not Fitted
2 EIA232 OK
3 EIA485 OK
470234511.xls
Relay Menu Database DataTypes
Page 40 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
4 K-Bus OK

G205 1 Register Second rear communications port configuration (model option) * * * * * *


Value
0 EIA232 (RS232)
1 EIA485 (RS485)
2 K-Bus

G206 1 Register COMMS MODE (IEC60870-5-2) * * * * * *


Value
0 IEC60870 FT1.2
1 10-bit no parity

G207 Port Config (First Rear Port) * * * * * *


Value
0 K-Bus
1 EIA485 (RS485)

G208 First Rear Port (RP1) Status * * * * * *


Value
0 K-Bus OK
1 EIA485 OK
2 Fibre Optic OK

G210 1 Register CS103 Blocking * * * * * *


Value
0 Disabled
1 Monitor Blocking
2 Command Blocking

G221 GOOSE STARTUP MODE * * * * * *


0 Promiscuous
1 Broadcast

G222 AE QUALIFIER SELECTOR (Reserved) * * * * * *


0 Not Used
1 Used

G223 IED STATISTICS RESET * * * * * *


0 None
1 Local IED
2 Viewed IED
2 All Enrolled
3 All Enrolled + Local

G224 ETHERNET LOOPBACK MODE (Reserved) * * * * * *


0 Loopback Off
1 Internal Loop
2 External Loop

G225 SOFTWARE RELOAD MODE * * * * * *


0 No Action
1 Reload Software

G226 LINK STATUS REPORT MODE * * * * * *


0 Alarm
1 Event
2 None

G227 GOOSE VIP STATUS * * * * * *


0 GOOSE VIP 1
1 GOOSE VIP 2
2 GOOSE VIP 3
3 GOOSE VIP 4
4 GOOSE VIP 5
5 GOOSE VIP 6
6 GOOSE VIP 7
7 GOOSE VIP 8
8 GOOSE VIP 9
9 GOOSE VIP 10
10 GOOSE VIP 11
11 GOOSE VIP 12
12 GOOSE VIP 13
13 GOOSE VIP 14
14 GOOSE VIP 15
15 GOOSE VIP 16
16 GOOSE VIP 17
17 GOOSE VIP 18
18 GOOSE VIP 19
19 GOOSE VIP 20
20 GOOSE VIP 21
21 GOOSE VIP 22
22 GOOSE VIP 23
23 GOOSE VIP 24
24 GOOSE VIP 25
25 GOOSE VIP 26
26 GOOSE VIP 27
27 GOOSE VIP 28
28 GOOSE VIP 29
29 GOOSE VIP 30
30 GOOSE VIP 31
31 GOOSE VIP 32
32 GOOSE VIP 33
33 GOOSE VIP 34
34 GOOSE VIP 35
35 GOOSE VIP 36
470234511.xls
Relay Menu Database DataTypes
Page 41 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
36 GOOSE VIP 37
37 GOOSE VIP 38
38 GOOSE VIP 39
39 GOOSE VIP 40
40 GOOSE VIP 41
41 GOOSE VIP 42
42 GOOSE VIP 43
43 GOOSE VIP 44
44 GOOSE VIP 45
45 GOOSE VIP 46
46 GOOSE VIP 47
47 GOOSE VIP 48
48 GOOSE VIP 49
49 GOOSE VIP 50
50 GOOSE VIP 51
51 GOOSE VIP 52
52 GOOSE VIP 53
53 GOOSE VIP 54
54 GOOSE VIP 55
55 GOOSE VIP 56
56 GOOSE VIP 57
57 GOOSE VIP 58
58 GOOSE VIP 59
59 GOOSE VIP 60
60 GOOSE VIP 61
61 GOOSE VIP 62
62 GOOSE VIP 63
63 GOOSE VIP 64

G228 2 Registers Alarm Status 3 (alarms 65 - 96) (32 Bits) * * * * * *


Bit Mask (hex) Data formatted as per data type G27
0x00000001 Battery Fail
0x00000002 Field Volt Fail
0x00000004 Rear Comm 2 Fail
0x00000008 GOOSE IED Absent
0x00000010 NIC Not Fitted
0x00000020 NIC No Response
0x00000040 NIC Fatal Error
0x00000080 NIC Soft. Reload
0x00000100 Bad TCP/IP Cfg.
0x00000200 Bad OSI Config.
0x00000400 NIC Link Fail
0x00000800 NIC SW Mis-Match
0x00001000 IP Addr Conflict
0x00002000 Unused
0x00004000 Unused
0x00008000 Unused
0x00010000 Unused
0x00020000 Unused
0x00040000 Unused
0x00080000 Unused
0x00100000 Unused
0x00200000 Bad Opto Charact
0x00400000 Unused
0x00800000 Unused
0x01000000 Unused
0x02000000 Unused
0x04000000 Unused
0x08000000 Unused
0x10000000 Unused
0x20000000 Unused
0x40000000 Unused
0x80000000 Unused

G229 Enrolled Flags * * * * * *


0 IED Status 1
1 IED Status 2
2 IED Status 3
3 IED Status 4
4 IED Status 5
5 IED Status 6
6 IED Status 7
7 IED Status 8
8 IED Status 9
9 IED Status 10
10 IED Status 11
11 IED Status 12
12 IED Status 13
13 IED Status 14
14 IED Status 15
15 IED Status 16
16 IED Status 17
17 IED Status 18
18 IED Status 19
19 IED Status 20
20 IED Status 21
21 IED Status 22
22 IED Status 23
23 IED Status 24
24 IED Status 25
25 IED Status 26
26 IED Status 27
27 IED Status 28
28 IED Status 29
29 IED Status 30
30 IED Status 31
470234511.xls
Relay Menu Database DataTypes
Page 42 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
31 IED Status 32
32 IED Status 33
33 IED Status 34
34 IED Status 35
35 IED Status 36
36 IED Status 37
37 IED Status 38
38 IED Status 39
39 IED Status 40
40 IED Status 41
41 IED Status 42
42 IED Status 43
43 IED Status 44
44 IED Status 45
45 IED Status 46
46 IED Status 47
47 IED Status 48
48 IED Status 49
49 IED Status 50
50 IED Status 51
51 IED Status 52
52 IED Status 53
53 IED Status 54
54 IED Status 55
55 IED Status 56
56 IED Status 57
57 IED Status 58
58 IED Status 59
59 IED Status 60
60 IED Status 61
61 IED Status 62
62 IED Status 63
63 IED Status 64

G231 DIRECT ACCESS KEYS * * * * * *


Value
0 Disabled
1 Enabled
2 Hotkey Only
3 CB Ctrl Only

G232 CONTROL INPUT COMMAND TEXT * * * * * *


Value
0 ON/OFF
1 SET/RESET
2 IN/OUT
3 ENABLED/DISABLED

G233 HOTKEY ENABLED CONTROL INPUTS * * * * * *


0x00000001 Control Input 01
0x00000002 Control Input 02
0x00000004 Control Input 03
0x00000008 Control Input 04
0x00000010 Control Input 05
0x00000020 Control Input 06
0x00000040 Control Input 07
0x00000080 Control Input 08
0x00000100 Control Input 09
0x00000200 Control Input 10
0x00000400 Control Input 11
0x00000800 Control Input 12
0x00001000 Control Input 13
0x00002000 Control Input 14
0x00004000 Control Input 15
0x00008000 Control Input 16
0x00010000 Control Input 17
0x00020000 Control Input 18
0x00040000 Control Input 19
0x00080000 Control Input 20
0x00100000 Control Input 21
0x00200000 Control Input 22
0x00400000 Control Input 23
0x00800000 Control Input 24
0x01000000 Control Input 25
0x02000000 Control Input 26
0x04000000 Control Input 27
0x08000000 Control Input 28
0x10000000 Control Input 29
0x20000000 Control Input 30
0x40000000 Control Input 31
0x80000000 Control Input 32

G234 CONTROL INPUT SIGNAL TYPE * * * * * *


Value
0 Latched
1 Pulsed

G235 Ethernet Protocol * * * * * *


Value
0 UCA2.0
1 UCA2.0 GOOSE
2 IEC61850
3 DNP3.0

G237 Opto Isolated Status Input Characteristic * * * * * *


Value
470234511.xls
Relay Menu Database DataTypes
Page 43 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
0 Standard 60%-80%
1 50% - 70%

G238 Time & date (type G12) format selector * * * * * *


Value (Modbus only)
0 Standard
1 Reverse

G242 Value FUNCTION KEY STATUS (Extended CPU2 only) *


0 Disabled
1 Unlocked (Enabled)
2 Locked

G243 Value FUNCTION KEY MODE (Extended CPU2 only) *


0 Normal
1 Toggled

G244 NOT USED * * * * * *

G245 IEC61850 DATA TYPES * * * * * *


0 NONE
1 BSTR2
2 BOOL
3 INT8
4 INT16
5 INT32
6 UINT8
7 UINT16
8 UINT32
9 SPS
10 DPS
11 INS

G246 IEC61850 TEST MODE * * * * * *


0 Disabled
1 Pass Through
2 Forced

G247 SNTP Status * * * * * *


0 Disabled
1 Trying Server 1
2 Trying Server 2
3 Server 1 OK
4 Server 2 OK
5 No response
6 No valid clock

G248 IEC61850 Setting Banks * * * * * *


0 No Action
2 Switch Banks

G249 DNP3 Measurment Scaling * * * * * *


0 Normalised
1 Primary
2 Secondary

G250 Days of the week * * * * * *


0 Sunday
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday

G251 Months Of The Year * * * * * *


0 January
1 February
2 March
3 April
4 May
5 June
6 July
7 August
8 September
9 October
10 November
11 December

G252 Week Number * * * * * *


0 First
1 Second
2 Third
3 Fourth
4 Last

G253 0 UTC * * * * * *
1 Local

G254 Local Time * * * * * *


0 Disabled
1 Fixed
2 Flexible

G256 Restore MCL * * * * * *


0 No Action
470234511.xls
Relay Menu Database DataTypes
Page 44 of 163

Data Types
TYPE DESCRIPTION Model
P341 P342 P343 P344 P345 P341
3x 3x 3x 3x 3x 7x
1 Restore MCL

G300 User Curve Type * * * * * *


0 Operate 1.0
1 Reset 1.1
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 45 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
0
1 see 4B01 see 4B01 see 4B01 see 4B01
2 see 4B02 see 4B02 see 4B02 see 4B02
3 see 4B03 see 4B03 see 4B03 see 4B03
4 see 4B04 see 4B04 see 4B04 see 4B04
5 see 4B05 see 4B05 see 4B05 see 4B05
6 see 4B06 see 4B06 see 4B06 see 4B06
7 see 4B07 see 4B07 see 4B07 see 4B07
8 see 4B08 see 4B08 see 4B08 see 4B08
9 see 4B09 see 4B09 see 4B09 see 4B09
10 see 4B0A see 4B0A see 4B0A see 4B0A
11 see 4B0B see 4B0B see 4B0B see 4B0B
12 see 4B0C see 4B0C see 4B0C see 4B0C
13 see 4B0D see 4B0D see 4B0D see 4B0D
14 see 4B0E see 4B0E see 4B0E see 4B0E
15 see 4B0F see 4B0F see 4B0F see 4B0F
16 see 4B10 see 4B10 see 4B10 see 4B10
17 see 4B11 see 4B11 see 4B11 see 4B11
18 see 4B12 see 4B12 see 4B12 see 4B12
19 see 4B13 see 4B13 see 4B13 see 4B13
20 see 4B14 see 4B14 see 4B14 see 4B14
21 see 4B15 see 4B15 see 4B15 see 4B15
22 see 4B16 see 4B16 see 4B16 see 4B16
23 see 4B17 see 4B17 see 4B17 see 4B17
24 see 4B18 see 4B18 see 4B18 see 4B18
25 see 4A01 see 4A01 see 4B19 see 4B19
26 see 4A02 see 4A02 see 4B1A see 4B1A
27 see 4A03 see 4A03 see 4B1B see 4B1B
28 see 4A04 see 4A04 see 4B1C see 4B1C
29 see 4A05 see 4A05 see 4B1D see 4B1D
30 see 4A06 see 4A06 see 4B1E see 4B1E
31 see 4A07 see 4A07 see 4B1F see 4B1F
32 see 4A08 see 4A08 see 4B20 see 4B20
33 see 4A09 see 4A09 see 4A01 see 4A01
34 see 4A0A see 4A0A see 4A02 see 4A02
35 see 4A0B see 4A0B see 4A03 see 4A03
36 see 4A0C see 4A0C see 4A04 see 4A04
37 see 4A0D see 4A0D see 4A05 see 4A05
38 see 4A0E see 4A0E see 4A06 see 4A06
39 see 4A0F see 4A0F see 4A07 see 4A07
40 see 4A10 see 4A10 see 4A08 see 4A08
41 see 4A11 see 4A11 see 4A09 see 4A09
42 see 4A12 see 4A12 see 4A0A see 4A0A
43 see 4A13 see 4A13 see 4A0B see 4A0B
44 see 4A14 see 4A14 see 4A0C see 4A0C
45 see 4A15 see 4A15 see 4A0D see 4A0D
46 see 4A16 see 4A16 see 4A0E see 4A0E
47 see 4A17 see 4A17 see 4A0F see 4A0F
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 46 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
48 see 4A18 see 4A18 see 4A10 see 4A10
49 LED 1 LED 1 see 4A11 see 4A11
50 LED 2 LED 2 see 4A12 see 4A12
51 LED 3 LED 3 see 4A13 see 4A13
52 LED 4 LED 4 see 4A14 see 4A14
53 LED 5 LED 5 see 4A15 see 4A15
54 LED 6 LED 6 see 4A16 see 4A16
55 LED 7 LED 7 see 4A17 see 4A17
56 LED 8 LED 8 see 4A18 see 4A18
57 F out of Range F out of Range see 4A19 see 4A19
58 SG-DDB Invalid SG-DDB Invalid see 4A1A see 4A1A
59 Prot'n Disabled Prot'n Disabled see 4A1B see 4A1B
60 VT Fail Alarm VT Fail Alarm see 4A1C see 4A1C
61 CT-1 Fail Alarm CT-1 Fail Alarm see 4A1D see 4A1D
62 CB Fail Alarm CB Fail Alarm see 4A1E see 4A1E
63 I^ Maint Alarm I^ Maint Alarm see 4A1F see 4A1F
64 I^ Lockout Alarm I^ Lockout Alarm see 4A20 see 4A20
65 CB Ops Maint CB Ops Maint LED1 Red LED1 Red
66 CB Ops Lockout CB Ops Lockout LED1 Grn LED1 Grn
67 CB Op Time Maint CB Op Time Maint LED2 Red LED2 Red
68 CB Op Time Lock CB Op Time Lock LED2 Grn LED2 Grn
69 Fault Freq Lock Fault Freq Lock LED3 Red LED3 Red
70 CB Status Alarm CB Status Alarm LED3 Grn LED3 Grn
71 Man CB Trip Fail Man CB Trip Fail LED4 Red LED4 Red
72 Man CB Cls Fail Man CB Cls Fail LED4 Grn LED4 Grn
73 Man CB Unhealthy Man CB Unhealthy LED5 Red LED5 Red
74 Thermal Alarm NPS Thermal Alm LED5 Grn LED5 Grn
75 Freq Prot Alm Thermal Alarm LED6 Red LED6 Red
76 Voltage Prot Alm V/Hz Alarm LED6 Grn LED6 Grn
77 CL Card I/P Fail Field Fail Alarm LED7 Red LED7 Red
78 CL Card O/P Fail RTD Thermal Alm LED7 Grn LED7 Grn
79 CL Input 1 Alarm RTD Open Cct LED8 Red LED8 Red
80 CL Input 2 Alarm RTD short Cct LED8 Grn LED8 Grn
81 CL Input 3 Alarm RTD Data Error FnKey LED1 Red FnKey LED1 Red
82 CL Input 4 Alarm RTD Board Fail FnKey LED1 Grn FnKey LED1 Grn
83 CLI1 I< Fail Alm Freq Prot Alm FnKey LED2 Red FnKey LED2 Red
84 CLI2 I< Fail Alm Voltage Prot Alm FnKey LED2 Grn FnKey LED2 Grn
85 CLI3 I< Fail Alm CL Card I/P Fail FnKey LED3 Red FnKey LED3 Red
86 CLI4 I< Fail Alm CL Card O/P Fail FnKey LED3 Grn FnKey LED3 Grn
87 Man No Checksync CL Input 1 Alarm FnKey LED4 Red FnKey LED4 Red
88 System Split CL Input 2 Alarm FnKey LED4 Grn FnKey LED4 Grn
89 MR User Alarm 11 CL Input 3 Alarm FnKey LED5 Red FnKey LED5 Red
90 MR User Alarm 10 CL Input 4 Alarm FnKey LED5 Grn FnKey LED5 Grn
91 MR User Alarm 9 CLI1 I< Fail Alm FnKey LED6 Red FnKey LED6 Red
92 MR User Alarm 8 CLI2 I< Fail Alm FnKey LED6 Grn FnKey LED6 Grn
93 MR User Alarm 7 CLI3 I< Fail Alm FnKey LED7 Red FnKey LED7 Red
94 MR User Alarm 6 CLI4 I< Fail Alm FnKey LED7 Grn FnKey LED7 Grn
95 MR User Alarm 5 64R R<1 Alarm FnKey LED8 Red FnKey LED8 Red
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 47 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
96 SR User Alarm 4 64R CL I/P Fail FnKey LED8 Grn FnKey LED8 Grn
97 SR User Alarm 3 LOL Alarm FnKey LED9 Red FnKey LED9 Red
98 SR User Alarm 2 FAA Alarm FnKey LED9 Grn FnKey LED9 Grn
99 SR User Alarm 1 Thru fault Alm FnKey LED10 Red FnKey LED10 Red
100 Battery Fail Tol Pretrip Alm FnKey LED10 Grn FnKey LED10 Grn
101 Field Volts Fail Man No Checksync Function Key 1 Function Key 1
102 Rear Comm 2 Fail System Split Function Key 2 Function Key 2
103 GOOSE IED Absent MR User Alarm 11 Function Key 3 Function Key 3
104 NIC Not Fitted MR User Alarm 10 Function Key 4 Function Key 4
105 NIC No Response MR User Alarm 9 Function Key 5 Function Key 5
106 NIC Fatal Error MR User Alarm 8 Function Key 6 Function Key 6
107 NIC Soft. Reload MR User Alarm 7 Function Key 7 Function Key 7
108 Bad TCP/IP Cfg. MR User Alarm 6 Function Key 8 Function Key 8
109 Bad OSI Config. MR User Alarm 5 Function Key 9 Function Key 9
110 NIC Link Fail SR User Alarm 4 Function Key 10 Function Key 10
111 NIC SW Mis-Match SR User Alarm 3 F out of Range F out of Range
112 IP Addr Conflict SR User Alarm 2 SG-DDB Invalid SG-DDB Invalid
113 IM Loopback SR User Alarm 1 Prot'n Disabled Prot'n Disabled
114 IM Message Fail Battery Fail VT Fail Alarm VT Fail Alarm
115 IM Data CD Fail Field Volts Fail CT-1 Fail Alarm CT-1 Fail Alarm
116 IM Channel Fail Rear Comm 2 Fail CB Fail Alarm CB Fail Alarm
117 Any Trip GOOSE IED Absent I^ Maint Alarm I^ Maint Alarm
118 IN>1 Trip NIC Not Fitted I^ Lockout Alarm I^ Lockout Alarm
119 IN>2 Trip NIC No Response CB Ops Maint CB Ops Maint
120 IN>3 Trip NIC Fatal Error CB Ops Lockout CB Ops Lockout
121 IN>4 Trip NIC Soft. Reload CB Op Time Maint CB Op Time Maint
122 IREF> Trip Bad TCP/IP Cfg. CB Op Time Lock CB Op Time Lock
123 ISEF>1 Trip Bad OSI Config. Fault Freq Lock Fault Freq Lock
124 ISEF>2 Trip NIC Link Fail CB Status Alarm CB Status Alarm
125 ISEF>3 Trip NIC SW Mis-Match Man CB Trip Fail Man CB Trip Fail
126 ISEF>4 Trip IP Addr Conflict Man CB Cls Fail Man CB Cls Fail
127 I>1 Trip IM Loopback Man CB Unhealthy Man CB Unhealthy
128 I>1 Trip A IM Message Fail NPS Thermal Alm NPS Thermal Alm
129 I>1 Trip B IM Data CD Fail Thermal Alarm Thermal Alarm
130 I>1 Trip C IM Channel Fail V/Hz Alarm V/Hz Alarm
131 I>2 Trip Any Trip Field Fail Alarm Field Fail Alarm
132 I>2 Trip A IN>1 Trip RTD Thermal Alm RTD Thermal Alm
133 I>2 Trip B IN>2 Trip RTD Open Cct RTD Open Cct
134 I>2 Trip C IREF> Trip RTD short Cct RTD short Cct
135 I>3 Trip ISEF>1 Trip RTD Data Error RTD Data Error
136 I>3 Trip A 64R R<2 Trip RTD Board Fail RTD Board Fail
137 I>3 Trip B I>1 Trip Freq Prot Alm Freq Prot Alm
138 I>3 Trip C I>1 Trip A Voltage Prot Alm Voltage Prot Alm
139 I>4 Trip I>1 Trip B CT-2 Fail Alarm CT-2 Fail Alarm
140 I>4 Trip A I>1 Trip C CL Card I/P Fail CL Card I/P Fail
141 I>4 Trip B I>2 Trip CL Card O/P Fail CL Card O/P Fail
142 I>4 Trip C I>2 Trip A CL Input 1 Alarm CL Input 1 Alarm
143 I2>1 Trip I>2 Trip B CL Input 2 Alarm CL Input 2 Alarm
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 48 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
144 I2>2 Trip I>2 Trip C CL Input 3 Alarm CL Input 3 Alarm
145 I2>3 Trip I>3 Trip CL Input 4 Alarm CL Input 4 Alarm
146 I2>4 Trip I>3 Trip A CLI1 I< Fail Alm CLI1 I< Fail Alm
147 Bfail1 Trip 3ph I>3 Trip B CLI2 I< Fail Alm CLI2 I< Fail Alm
148 Bfail2 Trip 3ph I>3 Trip C CLI3 I< Fail Alm CLI3 I< Fail Alm
149 VN>1 Trip I>4 Trip CLI4 I< Fail Alm CLI4 I< Fail Alm
150 VN>2 Trip I>4 Trip A 64R R<1 Alarm 64R R<1 Alarm
151 VN>3 Trip I>4 Trip B 64R CL I/P Fail 64R CL I/P Fail
152 VN>4 Trip I>4 Trip C CT Para Mismatch CT Para Mismatch
153 V>1 Trip I2>1 Trip LOL Alarm LOL Alarm
154 V>1 Trip A/AB I2>2 Trip FAA Alarm FAA Alarm
155 V>1 Trip B/BC I2>3 Trip Thru fault Alm Thru fault Alm
156 V>1 Trip C/CA I2>4 Trip Cct Fail Alarm Cct Fail Alarm
157 V>2 Trip Bfail1 Trip 3ph Tol Pretrip Alm Tol Pretrip Alm
158 V>2 Trip A/AB Bfail2 Trip 3ph CT Fail Alarm CT Fail Alarm
159 V>2 Trip B/BC VN>1 Trip Man No Checksync Man No Checksync
160 V>2 Trip C/CA VN>2 Trip System Split System Split
161 V2>1 Trip VN>3 Trip MR User Alarm 11 MR User Alarm 11
162 V<1 Trip VN>4 Trip MR User Alarm 10 MR User Alarm 10
163 V<1 Trip A/AB V>1 Trip MR User Alarm 9 MR User Alarm 9
164 V<1 Trip B/BC V>1 Trip A/AB MR User Alarm 8 MR User Alarm 8
165 V<1 Trip C/CA V>1 Trip B/BC MR User Alarm 7 MR User Alarm 7
166 V<2 Trip V>1 Trip C/CA MR User Alarm 6 MR User Alarm 6
167 V<2 Trip A/AB V>2 Trip MR User Alarm 5 MR User Alarm 5
168 V<2 Trip B/BC V>2 Trip A/AB SR User Alarm 4 SR User Alarm 4
169 V<2 Trip C/CA V>2 Trip B/BC SR User Alarm 3 SR User Alarm 3
170 Power1 Trip V>2 Trip C/CA SR User Alarm 2 SR User Alarm 2
171 Power2 Trip V2>1 Trip SR User Alarm 1 SR User Alarm 1
172 SPower1 Trip V<1 Trip Battery Fail Battery Fail
173 SPower2 Trip V<1 Trip A/AB Field Volts Fail Field Volts Fail
174 F<1 Trip V<1 Trip B/BC Rear Comm 2 Fail Rear Comm 2 Fail
175 F<2 Trip V<1 Trip C/CA GOOSE IED Absent GOOSE IED Absent
176 F<3 Trip V<2 Trip NIC Not Fitted NIC Not Fitted
177 F<4 Trip V<2 Trip A/AB NIC No Response NIC No Response
178 F>1 Trip V<2 Trip B/BC NIC Fatal Error NIC Fatal Error
179 F>2 Trip V<2 Trip C/CA NIC Soft. Reload NIC Soft. Reload
180 Trip df/dt>1 Field Fail1 Trip Bad TCP/IP Cfg. Bad TCP/IP Cfg.
181 Trip df/dt>2 Field Fail2 Trip Bad OSI Config. Bad OSI Config.
182 Trip df/dt>3 V Dep OC Trip NIC Link Fail NIC Link Fail
183 Trip df/dt>4 V Dep OC Trip A NIC SW Mis-Match NIC SW Mis-Match
184 V Shift Trip V Dep OC Trip B IP Addr Conflict IP Addr Conflict
185 df/dt>1 Under F V Dep OC Trip C IM Loopback IM Loopback
186 df/dt>1 Over F Z<1 Trip IM Message Fail IM Message Fail
187 Thermal O/L Trip Z<1 Trip A IM Data CD Fail IM Data CD Fail
188 CL Input 1 Trip Z<1 Trip B IM Channel Fail IM Channel Fail
189 CL Input 2 Trip Z<1 Trip C Any Trip Any Trip
190 CL Input 3 Trip Z<2 Trip Gen Diff Trip Gen Diff Trip
191 CL Input 4 Trip Z<2 Trip A Gen Diff Trip A Gen Diff Trip A
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 49 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
192 Any Start Z<2 Trip B Gen Diff Trip B Gen Diff Trip B
193 IN>1 Start Z<2 Trip C Gen Diff Trip C Gen Diff Trip C
194 IN>2 Start S2>1 Trip Xform Dif Trp Xform Dif Trp
195 IN>3 Start Power1 Trip Xform Dif Trp A Xform Dif Trp A
196 IN>4 Start Power2 Trip Xform Dif Trp B Xform Dif Trp B
197 ISEF>1 Start SPower1 Trip Xform Dif Trp C Xform Dif Trp C
198 ISEF>2 Start SPower2 Trip Xform Bias Trp A Xform Bias Trp A
199 ISEF>3 Start V/Hz>1 Trip Xform Bias Trp B Xform Bias Trp B
200 ISEF>4 Start V/Hz>2 Trip Xform Bias Trp C Xform Bias Trp C
201 I>1 Start V/Hz>3 Trip Xform HS1 Trp A Xform HS1 Trp A
202 I>1 Start A V/Hz>4 Trip Xform HS1 Trp B Xform HS1 Trp B
203 I>1 Start B F<1 Trip Xform HS1 Trp C Xform HS1 Trp C
204 I>1 Start C F<2 Trip Xform HS2 Trp A Xform HS2 Trp A
205 I>2 Start F<3 Trip Xform HS2 Trp B Xform HS2 Trp B
206 I>2 Start A F<4 Trip Xform HS2 Trp C Xform HS2 Trp C
207 I>2 Start B F>1 Trip IN>1 Trip IN>1 Trip
208 I>2 Start C F>2 Trip IN>2 Trip IN>2 Trip
209 I>3 Start Freq Band1 Trip IREF> Trip IREF> Trip
210 I>3 Start A Freq Band2 Trip ISEF>1 Trip ISEF>1 Trip
211 I>3 Start B Freq Band3 Trip 100%StEF3H Trip 100%StEF3H Trip
212 I>3 Start C Freq Band4 Trip 64R R<2 Trip 64R R<2 Trip
213 I>4 Start Freq Band5 Trip I>1 Trip I>1 Trip
214 I>4 Start A Freq Band6 Trip I>1 Trip A I>1 Trip A
215 I>4 Start B Trip df/dt>1 I>1 Trip B I>1 Trip B
216 I>4 Start C Trip df/dt>2 I>1 Trip C I>1 Trip C
217 I2>1 Start Trip df/dt>3 I>2 Trip I>2 Trip
218 I2>2 Start Trip df/dt>4 I>2 Trip A I>2 Trip A
219 I2>3 Start V Shift Trip I>2 Trip B I>2 Trip B
220 I2>4 Start df/dt>1 Under F I>2 Trip C I>2 Trip C
221 IA< Start df/dt>1 Over F I>3 Trip I>3 Trip
222 IB< Start NPS Thermal Trip I>3 Trip A I>3 Trip A
223 IC< Start Thermal O/L Trip I>3 Trip B I>3 Trip B
224 ISEF< Start Hot Spot>1 Trip I>3 Trip C I>3 Trip C
225 I> BlockStart Hot Spot>2 Trip I>4 Trip I>4 Trip
226 IN/SEF>Blk Start Hot Spot>3 Trip I>4 Trip A I>4 Trip A
227 VN>1 Start Top Oil>1 Trip I>4 Trip B I>4 Trip B
228 VN>2 Start Top Oil>2 Trip I>4 Trip C I>4 Trip C
229 VN>3 Start Top Oil>3 Trip I2>1 Trip I2>1 Trip
230 VN>4 Start RTD 1 Trip I2>2 Trip I2>2 Trip
231 V>1 Start RTD 2 Trip I2>3 Trip I2>3 Trip
232 V>1 Start A/AB RTD 3 Trip I2>4 Trip I2>4 Trip
233 V>1 Start B/BC RTD 4 Trip Bfail1 Trip 3ph Bfail1 Trip 3ph
234 V>1 Start C/CA RTD 5 Trip Bfail2 Trip 3ph Bfail2 Trip 3ph
235 V>2 Start RTD 6 Trip VN>1 Trip VN>1 Trip
236 V>2 Start A/AB RTD 7 Trip VN>2 Trip VN>2 Trip
237 V>2 Start B/BC RTD 8 Trip VN>3 Trip VN>3 Trip
238 V>2 Start C/CA RTD 9 Trip VN>4 Trip VN>4 Trip
239 V2>1 Start RTD 10 Trip V>1 Trip VN>5 Trip
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 50 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
240 V<1 Start Any RTD Trip V>1 Trip A/AB VN>6 Trip
241 V<1 Start A/AB CL Input 1 Trip V>1 Trip B/BC V>1 Trip
242 V<1 Start B/BC CL Input 2 Trip V>1 Trip C/CA V>1 Trip A/AB
243 V<1 Start C/CA CL Input 3 Trip V>2 Trip V>1 Trip B/BC
244 V<2 Start CL Input 4 Trip V>2 Trip A/AB V>1 Trip C/CA
245 V<2 Start A/AB Any Start V>2 Trip B/BC V>2 Trip
246 V<2 Start B/BC IN>1 Start V>2 Trip C/CA V>2 Trip A/AB
247 V<2 Start C/CA IN>2 Start V2>1 Trip V>2 Trip B/BC
248 Power1 Start ISEF>1 Start V<1 Trip V>2 Trip C/CA
249 Power2 Start 64R Start R<1Alm V<1 Trip A/AB V2>1 Trip
250 SPower1 Start 64R R<2 Start V<1 Trip B/BC V<1 Trip
251 SPower2 Start I>1 Start V<1 Trip C/CA V<1 Trip A/AB
252 F<1 Start I>1 Start A V<2 Trip V<1 Trip B/BC
253 F<2 Start I>1 Start B V<2 Trip A/AB V<1 Trip C/CA
254 F<3 Start I>1 Start C V<2 Trip B/BC V<2 Trip
255 F<4 Start I>2 Start V<2 Trip C/CA V<2 Trip A/AB
256 F>1 Start I>2 Start A Field Fail1 Trip V<2 Trip B/BC
257 F>2 Start I>2 Start B Field Fail2 Trip V<2 Trip C/CA
258 Start df/dt>1 I>2 Start C PSlipz Z1 Trip Field Fail1 Trip
259 Start df/dt>2 I>3 Start PSlipz Z2 Trip Field Fail2 Trip
260 Start df/dt>3 I>3 Start A V Dep OC Trip PSlipz Z1 Trip
261 Start df/dt>4 I>3 Start B V Dep OC Trip A PSlipz Z2 Trip
262 CLI1 Alarm Start I>3 Start C V Dep OC Trip B V Dep OC Trip
263 CLI2 Alarm Start I>4 Start V Dep OC Trip C V Dep OC Trip A
264 CLI3 Alarm Start I>4 Start A Z<1 Trip V Dep OC Trip B
265 CLI4 Alarm Start I>4 Start B Z<1 Trip A V Dep OC Trip C
266 CLI1 Trip Start I>4 Start C Z<1 Trip B Z<1 Trip
267 CLI2 Trip Start I2>1 Start Z<1 Trip C Z<1 Trip A
268 CLI3 Trip Start I2>2 Start Z<2 Trip Z<1 Trip B
269 CLI4 Trip Start I2>3 Start Z<2 Trip A Z<1 Trip C
270 VTS Fast Block I2>4 Start Z<2 Trip B Z<2 Trip
271 VTS Slow Block IA< Start Z<2 Trip C Z<2 Trip A
272 CTS-1 Block IB< Start DeadMachine Trip Z<2 Trip B
273 Control Trip IC< Start S2>1 Trip Z<2 Trip C
274 Control Close ISEF< Start Power1 Trip DeadMachine Trip
275 Close in Prog IN< Start Power2 Trip S2>1 Trip
276 Lockout Alarm VN>1 Start SPower1 Trip Power1 Trip
277 CB Open 3 ph VN>2 Start SPower2 Trip Power2 Trip
278 CB Closed 3 ph VN>3 Start V/Hz>1 Trip SPower1 Trip
279 All Poles Dead VN>4 Start V/Hz>2 Trip SPower2 Trip
280 Any Pole Dead V>1 Start V/Hz>3 Trip V/Hz>1 Trip
281 Pole Dead A V>1 Start A/AB V/Hz>4 Trip V/Hz>2 Trip
282 Pole Dead B V>1 Start B/BC F<1 Trip V/Hz>3 Trip
283 Pole Dead C V>1 Start C/CA F<2 Trip V/Hz>4 Trip
284 Freq High V>2 Start F<3 Trip F<1 Trip
285 Freq Low V>2 Start A/AB F<4 Trip F<2 Trip
286 Freq Not found V>2 Start B/BC F>1 Trip F<3 Trip
287 Reconnection V>2 Start C/CA F>2 Trip F<4 Trip
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 51 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
288 Check Sync 1 OK V2>1 Start Freq Band1 Trip F>1 Trip
289 Check Sync 2 OK V<1 Start Freq Band2 Trip F>2 Trip
290 Control Input 1 V<1 Start A/AB Freq Band3 Trip Freq Band1 Trip
291 Control Input 2 V<1 Start B/BC Freq Band4 Trip Freq Band2 Trip
292 Control Input 3 V<1 Start C/CA Freq Band5 Trip Freq Band3 Trip
293 Control Input 4 V<2 Start Freq Band6 Trip Freq Band4 Trip
294 Control Input 5 V<2 Start A/AB Trip df/dt>1 Freq Band5 Trip
295 Control Input 6 V<2 Start B/BC Trip df/dt>2 Freq Band6 Trip
296 Control Input 7 V<2 Start C/CA Trip df/dt>3 Trip df/dt>1
297 Control Input 8 FFail1 Start Trip df/dt>4 Trip df/dt>2
298 Control Input 9 FFail2 Start V Shift Trip Trip df/dt>3
299 Control Input 10 V Dep OC Start df/dt>1 Under F Trip df/dt>4
300 Control Input 11 V Dep OC Start A df/dt>1 Over F V Shift Trip
301 Control Input 12 V Dep OC Start B NPS Thermal Trip df/dt>1 Under F
302 Control Input 13 V Dep OC Start C Thermal O/L Trip df/dt>1 Over F
303 Control Input 14 Z<1 Start Hot Spot>1 Trip NPS Thermal Trip
304 Control Input 15 Z<1 Start A Hot Spot>2 Trip Thermal O/L Trip
305 Control Input 16 Z<1 Start B Hot Spot>3 Trip Hot Spot>1 Trip
306 Control Input 17 Z<1 Start C Top Oil>1 Trip Hot Spot>2 Trip
307 Control Input 18 Z<2 Start Top Oil>2 Trip Hot Spot>3 Trip
308 Control Input 19 Z<2 Start A Top Oil>3 Trip Top Oil>1 Trip
309 Control Input 20 Z<2 Start B RTD 1 Trip Top Oil>2 Trip
310 Control Input 21 Z<2 Start C RTD 2 Trip Top Oil>3 Trip
311 Control Input 22 S2>1 Start RTD 3 Trip RTD 1 Trip
312 Control Input 23 Power1 Start RTD 4 Trip RTD 2 Trip
313 Control Input 24 Power2 Start RTD 5 Trip RTD 3 Trip
314 Control Input 25 SPower1 Start RTD 6 Trip RTD 4 Trip
315 Control Input 26 SPower2 Start RTD 7 Trip RTD 5 Trip
316 Control Input 27 V/Hz>1 Start RTD 8 Trip RTD 6 Trip
317 Control Input 28 V/Hz>2 Start RTD 9 Trip RTD 7 Trip
318 Control Input 29 V/Hz>3 Start RTD 10 Trip RTD 8 Trip
319 Control Input 30 V/Hz>4 Start Any RTD Trip RTD 9 Trip
320 Control Input 31 F<1 Start CL Input 1 Trip RTD 10 Trip
321 Control Input 32 F<2 Start CL Input 2 Trip Any RTD Trip
322 Virtual Input 01 F<3 Start CL Input 3 Trip CL Input 1 Trip
323 Virtual Input 02 F<4 Start CL Input 4 Trip CL Input 2 Trip
324 Virtual Input 03 F>1 Start Any Start CL Input 3 Trip
325 Virtual Input 04 F>2 Start Xform Bias StrtA CL Input 4 Trip
326 Virtual Input 05 Freq Band1 Start Xform Bias StrtB Any Start
327 Virtual Input 06 Freq Band2 Start Xform Bias StrtC Xform Bias StrtA
328 Virtual Input 07 Freq Band3 Start IN>1 Start Xform Bias StrtB
329 Virtual Input 08 Freq Band4 Start IN>2 Start Xform Bias StrtC
330 Virtual Input 09 Freq Band5 Start ISEF>1 Start IN>1 Start
331 Virtual Input 10 Freq Band6 Start 100%StEF3H Start IN>2 Start
332 Virtual Input 11 Start df/dt>1 64R Start R<1Alm ISEF>1 Start
333 Virtual Input 12 Start df/dt>2 64R R<2 Start 100%StEF3H Start
334 Virtual Input 13 Start df/dt>3 I>1 Start 64R Start R<1Alm
335 Virtual Input 14 Start df/dt>4 I>1 Start A 64R R<2 Start
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 52 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
336 Virtual Input 15 Hot Spot>1 Start I>1 Start B I>1 Start
337 Virtual Input 16 Hot Spot>2 Start I>1 Start C I>1 Start A
338 Virtual Input 17 Hot Spot>3 Start I>2 Start I>1 Start B
339 Virtual Input 18 Top Oil>1 start I>2 Start A I>1 Start C
340 Virtual Input 19 Top Oil>2 start I>2 Start B I>2 Start
341 Virtual Input 20 Top Oil>3 start I>2 Start C I>2 Start A
342 Virtual Input 21 CLI1 Alarm Start I>3 Start I>2 Start B
343 Virtual Input 22 CLI2 Alarm Start I>3 Start A I>2 Start C
344 Virtual Input 23 CLI3 Alarm Start I>3 Start B I>3 Start
345 Virtual Input 24 CLI4 Alarm Start I>3 Start C I>3 Start A
346 Virtual Input 25 CLI1 Trip Start I>4 Start I>3 Start B
347 Virtual Input 26 CLI2 Trip Start I>4 Start A I>3 Start C
348 Virtual Input 27 CLI3 Trip Start I>4 Start B I>4 Start
349 Virtual Input 28 CLI4 Trip Start I>4 Start C I>4 Start A
350 Virtual Input 29 VTS Fast Block I2>1 Start I>4 Start B
351 Virtual Input 30 VTS Slow Block I2>2 Start I>4 Start C
352 Virtual Input 31 CTS-1 Block I2>3 Start I2>1 Start
353 Virtual Input 32 Control Trip I2>4 Start I2>2 Start
354 Virtual Input 33 Control Close IA< Start I2>3 Start
355 Virtual Input 34 Close in Prog IB< Start I2>4 Start
356 Virtual Input 35 Lockout Alarm IC< Start IA< Start
357 Virtual Input 36 CB Open 3 ph ISEF< Start IB< Start
358 Virtual Input 37 CB Closed 3 ph IN< Start IC< Start
359 Virtual Input 38 All Poles Dead VN>1 Start ISEF< Start
360 Virtual Input 39 Any Pole Dead VN>2 Start IN< Start
361 Virtual Input 40 Pole Dead A VN>3 Start VN>1 Start
362 Virtual Input 41 Pole Dead B VN>4 Start VN>2 Start
363 Virtual Input 42 Pole Dead C V>1 Start VN>3 Start
364 Virtual Input 43 Freq High V>1 Start A/AB VN>4 Start
365 Virtual Input 44 Freq Low V>1 Start B/BC VN>5 Start
366 Virtual Input 45 Freq Not found V>1 Start C/CA VN>6 Start
367 Virtual Input 46 RTD 1 Alarm V>2 Start V>1 Start
368 Virtual Input 47 RTD 2 Alarm V>2 Start A/AB V>1 Start A/AB
369 Virtual Input 48 RTD 3 Alarm V>2 Start B/BC V>1 Start B/BC
370 Virtual Input 49 RTD 4 Alarm V>2 Start C/CA V>1 Start C/CA
371 Virtual Input 50 RTD 5 Alarm V2>1 Start V>2 Start
372 Virtual Input 51 RTD 6 Alarm V<1 Start V>2 Start A/AB
373 Virtual Input 52 RTD 7 Alarm V<1 Start A/AB V>2 Start B/BC
374 Virtual Input 53 RTD 8 Alarm V<1 Start B/BC V>2 Start C/CA
375 Virtual Input 54 RTD 9 Alarm V<1 Start C/CA V2>1 Start
376 Virtual Input 55 RTD 10 Alarm V<2 Start V<1 Start
377 Virtual Input 56 Check Sync 1 OK V<2 Start A/AB V<1 Start A/AB
378 Virtual Input 57 Check Sync 2 OK V<2 Start B/BC V<1 Start B/BC
379 Virtual Input 58 Control Input 1 V<2 Start C/CA V<1 Start C/CA
380 Virtual Input 59 Control Input 2 FFail1 Start V<2 Start
381 Virtual Input 60 Control Input 3 FFail2 Start V<2 Start A/AB
382 Virtual Input 61 Control Input 4 PSlipz Z1 Start V<2 Start B/BC
383 Virtual Input 62 Control Input 5 PSlipz Z2 Start V<2 Start C/CA
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 53 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
384 Virtual Input 63 Control Input 6 PSlipz LensStart FFail1 Start
385 Virtual Input 64 Control Input 7 PSlipz BlindStrt FFail2 Start
386 Virtual Output01 Control Input 8 PSlipz ReactStrt PSlipz Z1 Start
387 Virtual Output02 Control Input 9 V Dep OC Start PSlipz Z2 Start
388 Virtual Output03 Control Input 10 V Dep OC Start A PSlipz LensStart
389 Virtual Output04 Control Input 11 V Dep OC Start B PSlipz BlindStrt
390 Virtual Output05 Control Input 12 V Dep OC Start C PSlipz ReactStrt
391 Virtual Output06 Control Input 13 Z<1 Start V Dep OC Start
392 Virtual Output07 Control Input 14 Z<1 Start A V Dep OC Start A
393 Virtual Output08 Control Input 15 Z<1 Start B V Dep OC Start B
394 Virtual Output09 Control Input 16 Z<1 Start C V Dep OC Start C
395 Virtual Output10 Control Input 17 Z<2 Start Z<1 Start
396 Virtual Output11 Control Input 18 Z<2 Start A Z<1 Start A
397 Virtual Output12 Control Input 19 Z<2 Start B Z<1 Start B
398 Virtual Output13 Control Input 20 Z<2 Start C Z<1 Start C
399 Virtual Output14 Control Input 21 S2>1 Start Z<2 Start
400 Virtual Output15 Control Input 22 Power1 Start Z<2 Start A
401 Virtual Output16 Control Input 23 Power2 Start Z<2 Start B
402 Virtual Output17 Control Input 24 SPower1 Start Z<2 Start C
403 Virtual Output18 Control Input 25 SPower2 Start S2>1 Start
404 Virtual Output19 Control Input 26 V/Hz>1 Start Power1 Start
405 Virtual Output20 Control Input 27 V/Hz>2 Start Power2 Start
406 Virtual Output21 Control Input 28 V/Hz>3 Start SPower1 Start
407 Virtual Output22 Control Input 29 V/Hz>4 Start SPower2 Start
408 Virtual Output23 Control Input 30 F<1 Start V/Hz>1 Start
409 Virtual Output24 Control Input 31 F<2 Start V/Hz>2 Start
410 Virtual Output25 Control Input 32 F<3 Start V/Hz>3 Start
411 Virtual Output26 Virtual Input 01 F<4 Start V/Hz>4 Start
412 Virtual Output27 Virtual Input 02 F>1 Start F<1 Start
413 Virtual Output28 Virtual Input 03 F>2 Start F<2 Start
414 Virtual Output29 Virtual Input 04 Freq Band1 Start F<3 Start
415 Virtual Output30 Virtual Input 05 Freq Band2 Start F<4 Start
416 Virtual Output31 Virtual Input 06 Freq Band3 Start F>1 Start
417 Virtual Output32 Virtual Input 07 Freq Band4 Start F>2 Start
418 Virtual Output33 Virtual Input 08 Freq Band5 Start Freq Band1 Start
419 Virtual Output34 Virtual Input 09 Freq Band6 Start Freq Band2 Start
420 Virtual Output35 Virtual Input 10 Start df/dt>1 Freq Band3 Start
421 Virtual Output36 Virtual Input 11 Start df/dt>2 Freq Band4 Start
422 Virtual Output37 Virtual Input 12 Start df/dt>3 Freq Band5 Start
423 Virtual Output38 Virtual Input 13 Start df/dt>4 Freq Band6 Start
424 Virtual Output39 Virtual Input 14 Hot Spot>1 Start Start df/dt>1
425 Virtual Output40 Virtual Input 15 Hot Spot>2 Start Start df/dt>2
426 Virtual Output41 Virtual Input 16 Hot Spot>3 Start Start df/dt>3
427 Virtual Output42 Virtual Input 17 Top Oil>1 start Start df/dt>4
428 Virtual Output43 Virtual Input 18 Top Oil>2 start Hot Spot>1 Start
429 Virtual Output44 Virtual Input 19 Top Oil>3 start Hot Spot>2 Start
430 Virtual Output45 Virtual Input 20 CLI1 Alarm Start Hot Spot>3 Start
431 Virtual Output46 Virtual Input 21 CLI2 Alarm Start Top Oil>1 start
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 54 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
432 Virtual Output47 Virtual Input 22 CLI3 Alarm Start Top Oil>2 start
433 Virtual Output48 Virtual Input 23 CLI4 Alarm Start Top Oil>3 start
434 Virtual Output49 Virtual Input 24 CLI1 Trip Start CLI1 Alarm Start
435 Virtual Output50 Virtual Input 25 CLI2 Trip Start CLI2 Alarm Start
436 Virtual Output51 Virtual Input 26 CLI3 Trip Start CLI3 Alarm Start
437 Virtual Output52 Virtual Input 27 CLI4 Trip Start CLI4 Alarm Start
438 Virtual Output53 Virtual Input 28 VTS Fast Block CLI1 Trip Start
439 Virtual Output54 Virtual Input 29 VTS Slow Block CLI2 Trip Start
440 Virtual Output55 Virtual Input 30 CTS-1 Block CLI3 Trip Start
441 Virtual Output56 Virtual Input 31 CTS-2 Block CLI4 Trip Start
442 Virtual Output57 Virtual Input 32 CTS BLK VTS Fast Block
443 Virtual Output58 Virtual Input 33 CTS CT1 VTS Slow Block
444 Virtual Output59 Virtual Input 34 CTS CT2 CTS-1 Block
445 Virtual Output60 Virtual Input 35 CctFail Blk A CTS-2 Block
446 Virtual Output61 Virtual Input 36 CctFail Blk B CTS BLK
447 Virtual Output62 Virtual Input 37 CctFail Blk C CTS CT1
448 Virtual Output63 Virtual Input 38 2nd Har Blk A CTS CT2
449 Virtual Output64 Virtual Input 39 2nd Har Blk B CctFail Blk A
450 Virtual Input 40 2nd Har Blk C CctFail Blk B
451 Virtual Input 41 5nd Har Blk A CctFail Blk C
452 Virtual Input 42 5nd Har Blk B 2nd Har Blk A
453 Virtual Input 43 5nd Har Blk C 2nd Har Blk B
454 Virtual Input 44 Control Trip 2nd Har Blk C
455 Virtual Input 45 Control Close 5nd Har Blk A
456 Virtual Input 46 Close in Prog 5nd Har Blk B
457 Virtual Input 47 Lockout Alarm 5nd Har Blk C
458 Virtual Input 48 CB Open 3 ph Control Trip
459 Virtual Input 49 CB Closed 3 ph Control Close
460 Virtual Input 50 All Poles Dead Close in Prog
461 Virtual Input 51 Any Pole Dead Lockout Alarm
462 Virtual Input 52 Pole Dead A CB Open 3 ph
463 Virtual Input 53 Pole Dead B CB Closed 3 ph
464 Virtual Input 54 Pole Dead C All Poles Dead
465 Virtual Input 55 Freq High Any Pole Dead
466 Virtual Input 56 Freq Low Pole Dead A
467 Virtual Input 57 Freq Not found Pole Dead B
468 Virtual Input 58 RTD 1 Alarm Pole Dead C
469 Virtual Input 59 RTD 2 Alarm Freq High
470 Virtual Input 60 RTD 3 Alarm Freq Low
471 Virtual Input 61 RTD 4 Alarm Freq Not found
472 Virtual Input 62 RTD 5 Alarm RTD 1 Alarm
473 Virtual Input 63 RTD 6 Alarm RTD 2 Alarm
474 Virtual Input 64 RTD 7 Alarm RTD 3 Alarm
475 Virtual Output01 RTD 8 Alarm RTD 4 Alarm
476 Virtual Output02 RTD 9 Alarm RTD 5 Alarm
477 Virtual Output03 RTD 10 Alarm RTD 6 Alarm
478 Virtual Output04 Check Sync 1 OK RTD 7 Alarm
479 Virtual Output05 Check Sync 2 OK RTD 8 Alarm
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 55 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
480 Virtual Output06 Control Input 1 RTD 9 Alarm
481 Virtual Output07 Control Input 2 RTD 10 Alarm
482 Virtual Output08 Control Input 3 Check Sync 1 OK
483 Virtual Output09 Control Input 4 Check Sync 2 OK
484 Virtual Output10 Control Input 5 Control Input 1
485 Virtual Output11 Control Input 6 Control Input 2
486 Virtual Output12 Control Input 7 Control Input 3
487 Virtual Output13 Control Input 8 Control Input 4
488 Virtual Output14 Control Input 9 Control Input 5
489 Virtual Output15 Control Input 10 Control Input 6
490 Virtual Output16 Control Input 11 Control Input 7
491 Virtual Output17 Control Input 12 Control Input 8
492 Virtual Output18 Control Input 13 Control Input 9
493 Virtual Output19 Control Input 14 Control Input 10
494 Virtual Output20 Control Input 15 Control Input 11
495 Virtual Output21 Control Input 16 Control Input 12
496 Virtual Output22 Control Input 17 Control Input 13
497 Virtual Output23 Control Input 18 Control Input 14
498 Virtual Output24 Control Input 19 Control Input 15
499 Virtual Output25 Control Input 20 Control Input 16
500 Virtual Output26 Control Input 21 Control Input 17
501 Virtual Output27 Control Input 22 Control Input 18
502 Virtual Output28 Control Input 23 Control Input 19
503 Virtual Output29 Control Input 24 Control Input 20
504 Virtual Output30 Control Input 25 Control Input 21
505 Virtual Output31 Control Input 26 Control Input 22
506 Virtual Output32 Control Input 27 Control Input 23
507 Virtual Output33 Control Input 28 Control Input 24
508 Virtual Output34 Control Input 29 Control Input 25
509 Virtual Output35 Control Input 30 Control Input 26
510 Virtual Output36 Control Input 31 Control Input 27
511 Virtual Output37 Control Input 32 Control Input 28
512 Virtual Output38 Virtual Input 01 Control Input 29
513 Virtual Output39 Virtual Input 02 Control Input 30
514 Virtual Output40 Virtual Input 03 Control Input 31
515 Virtual Output41 Virtual Input 04 Control Input 32
516 Virtual Output42 Virtual Input 05 Virtual Input 01
517 Virtual Output43 Virtual Input 06 Virtual Input 02
518 Virtual Output44 Virtual Input 07 Virtual Input 03
519 Virtual Output45 Virtual Input 08 Virtual Input 04
520 Virtual Output46 Virtual Input 09 Virtual Input 05
521 Virtual Output47 Virtual Input 10 Virtual Input 06
522 Virtual Output48 Virtual Input 11 Virtual Input 07
523 Virtual Output49 Virtual Input 12 Virtual Input 08
524 Virtual Output50 Virtual Input 13 Virtual Input 09
525 Virtual Output51 Virtual Input 14 Virtual Input 10
526 Virtual Output52 Virtual Input 15 Virtual Input 11
527 Virtual Output53 Virtual Input 16 Virtual Input 12
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 56 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
528 Virtual Output54 Virtual Input 17 Virtual Input 13
529 Virtual Output55 Virtual Input 18 Virtual Input 14
530 Virtual Output56 Virtual Input 19 Virtual Input 15
531 Virtual Output57 Virtual Input 20 Virtual Input 16
532 Virtual Output58 Virtual Input 21 Virtual Input 17
533 Virtual Output59 Virtual Input 22 Virtual Input 18
534 Virtual Output60 Virtual Input 23 Virtual Input 19
535 Virtual Output61 Virtual Input 24 Virtual Input 20
536 Virtual Output62 Virtual Input 25 Virtual Input 21
537 Virtual Output63 Virtual Input 26 Virtual Input 22
538 Virtual Output64 Virtual Input 27 Virtual Input 23
539 Virtual Input 28 Virtual Input 24
540 Virtual Input 29 Virtual Input 25
541 Virtual Input 30 Virtual Input 26
542 Virtual Input 31 Virtual Input 27
543 Virtual Input 32 Virtual Input 28
544 Virtual Input 33 Virtual Input 29
545 Virtual Input 34 Virtual Input 30
546 Virtual Input 35 Virtual Input 31
547 Virtual Input 36 Virtual Input 32
548 Virtual Input 37 Virtual Input 33
549 Virtual Input 38 Virtual Input 34
550 Virtual Input 39 Virtual Input 35
551 Virtual Input 40 Virtual Input 36
552 Virtual Input 41 Virtual Input 37
553 Virtual Input 42 Virtual Input 38
554 Virtual Input 43 Virtual Input 39
555 Virtual Input 44 Virtual Input 40
556 Virtual Input 45 Virtual Input 41
557 Virtual Input 46 Virtual Input 42
558 Virtual Input 47 Virtual Input 43
559 Virtual Input 48 Virtual Input 44
560 Virtual Input 49 Virtual Input 45
561 Virtual Input 50 Virtual Input 46
562 Virtual Input 51 Virtual Input 47
563 Virtual Input 52 Virtual Input 48
564 Virtual Input 53 Virtual Input 49
565 Virtual Input 54 Virtual Input 50
566 Virtual Input 55 Virtual Input 51
567 Virtual Input 56 Virtual Input 52
568 Virtual Input 57 Virtual Input 53
569 Virtual Input 58 Virtual Input 54
570 Virtual Input 59 Virtual Input 55
571 Virtual Input 60 Virtual Input 56
572 Virtual Input 61 Virtual Input 57
573 Virtual Input 62 Virtual Input 58
574 Virtual Input 63 Virtual Input 59
575 Virtual Input 64 Virtual Input 60
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 57 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
576 Virtual Output01 Virtual Input 61
577 Virtual Output02 Virtual Input 62
578 Virtual Output03 Virtual Input 63
579 Virtual Output04 Virtual Input 64
580 Virtual Output05 Virtual Output01
581 Virtual Output06 Virtual Output02
582 Virtual Output07 Virtual Output03
583 Virtual Output08 Virtual Output04
584 Virtual Output09 Virtual Output05
585 Virtual Output10 Virtual Output06
586 Virtual Output11 Virtual Output07
587 Virtual Output12 Virtual Output08
588 Virtual Output13 Virtual Output09
589 Virtual Output14 Virtual Output10
590 Virtual Output15 Virtual Output11
591 Virtual Output16 Virtual Output12
592 Virtual Output17 Virtual Output13
593 Virtual Output18 Virtual Output14
594 Virtual Output19 Virtual Output15
595 Virtual Output20 Virtual Output16
596 Virtual Output21 Virtual Output17
597 Virtual Output22 Virtual Output18
598 Virtual Output23 Virtual Output19
599 Virtual Output24 Virtual Output20
600 Virtual Output25 Virtual Output21
601 Virtual Output26 Virtual Output22
602 Virtual Output27 Virtual Output23
603 Virtual Output28 Virtual Output24
604 Virtual Output29 Virtual Output25
605 Virtual Output30 Virtual Output26
606 Virtual Output31 Virtual Output27
607 Virtual Output32 Virtual Output28
608 Virtual Output33 Virtual Output29
609 Virtual Output34 Virtual Output30
610 Virtual Output35 Virtual Output31
611 Virtual Output36 Virtual Output32
612 Virtual Output37 Virtual Output33
613 Virtual Output38 Virtual Output34
614 Virtual Output39 Virtual Output35
615 Virtual Output40 Virtual Output36
616 Virtual Output41 Virtual Output37
617 Virtual Output42 Virtual Output38
618 Virtual Output43 Virtual Output39
619 Virtual Output44 Virtual Output40
620 Virtual Output45 Virtual Output41
621 Virtual Output46 Virtual Output42
622 Virtual Output47 Virtual Output43
623 Virtual Output48 Virtual Output44
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 58 of 163

G32 DIGITAL CHANNEL ASSIGNMENT SELECTOR


P341 (V.36) P342 (V.36) P343 (V.36) P344 (V.36)
624 Virtual Output49 Virtual Output45
625 Virtual Output50 Virtual Output46
626 Virtual Output51 Virtual Output47
627 Virtual Output52 Virtual Output48
628 Virtual Output53 Virtual Output49
629 Virtual Output54 Virtual Output50
630 Virtual Output55 Virtual Output51
631 Virtual Output56 Virtual Output52
632 Virtual Output57 Virtual Output53
633 Virtual Output58 Virtual Output54
634 Virtual Output59 Virtual Output55
635 Virtual Output60 Virtual Output56
636 Virtual Output61 Virtual Output57
637 Virtual Output62 Virtual Output58
638 Virtual Output63 Virtual Output59
639 Virtual Output64 Virtual Output60
640 Virtual Output61
641 Virtual Output62
642 Virtual Output63
643 Virtual Output64
644
645
646
647
648
649
650
651
652
653
654
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 59 of 163

P345 (V.36) P341 (V.70)

see 4B01 see 4B01


see 4B02 see 4B02
see 4B03 see 4B03
see 4B04 see 4B04
see 4B05 see 4B05
see 4B06 see 4B06
see 4B07 see 4B07
see 4B08 see 4B08
see 4B09 see 4B09
see 4B0A see 4B0A
see 4B0B see 4B0B
see 4B0C see 4B0C
see 4B0D see 4B0D
see 4B0E see 4B0E
see 4B0F see 4B0F
see 4B10 see 4B10
see 4B11 see 4B11
see 4B12 see 4B12
see 4B13 see 4B13
see 4B14 see 4B14
see 4B15 see 4B15
see 4B16 see 4B16
see 4B17 see 4B17
see 4B18 see 4B18
see 4B19 see 4A01
see 4B1A see 4A02
see 4B1B see 4A03
see 4B1C see 4A04
see 4B1D see 4A05
see 4B1E see 4A06
see 4B1F see 4A07
see 4B20 see 4A08
see 4A01 see 4A09
see 4A02 see 4A0A
see 4A03 see 4A0B
see 4A04 see 4A0C
see 4A05 see 4A0D
see 4A06 see 4A0E
see 4A07 see 4A0F
see 4A08 see 4A10
see 4A09 see 4A11
see 4A0A see 4A12
see 4A0B see 4A13
see 4A0C see 4A14
see 4A0D see 4A15
see 4A0E see 4A16
see 4A0F see 4A17
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 60 of 163

P345 (V.36) P341 (V.70)


see 4A10 see 4A18
see 4A11 LED 1
see 4A12 LED 2
see 4A13 LED 3
see 4A14 LED 4
see 4A15 LED 5
see 4A16 LED 6
see 4A17 LED 7
see 4A18 LED 8
see 4A19 F out of Range
see 4A1A SG-DDB Invalid
see 4A1B Prot'n Disabled
see 4A1C VT Fail Alarm
see 4A1D CT-1 Fail Alarm
see 4A1E CB Fail Alarm
see 4A1F I^ Maint Alarm
see 4A20 I^ Lockout Alarm
LED1 Red CB Ops Maint
LED1 Grn CB Ops Lockout
LED2 Red CB Op Time Maint
LED2 Grn CB Op Time Lock
LED3 Red Fault Freq Lock
LED3 Grn CB Status Alarm
LED4 Red Man CB Trip Fail
LED4 Grn Man CB Cls Fail
LED5 Red Man CB Unhealthy
LED5 Grn Thermal Alarm
LED6 Red Freq Prot Alm
LED6 Grn Voltage Prot Alm
LED7 Red CL Card I/P Fail
LED7 Grn CL Card O/P Fail
LED8 Red CL Input 1 Alarm
LED8 Grn CL Input 2 Alarm
FnKey LED1 Red CL Input 3 Alarm
FnKey LED1 Grn CL Input 4 Alarm
FnKey LED2 Red CLI1 I< Fail Alm
FnKey LED2 Grn CLI2 I< Fail Alm
FnKey LED3 Red CLI3 I< Fail Alm
FnKey LED3 Grn CLI4 I< Fail Alm
FnKey LED4 Red Amb T Fail Alm
FnKey LED4 Grn Wind V Fail Alm
FnKey LED5 Red Wind D Fail Alm
FnKey LED5 Grn Solar R Fail Alm
FnKey LED6 Red Man No Checksync
FnKey LED6 Grn System Split
FnKey LED7 Red MR User Alarm 11
FnKey LED7 Grn MR User Alarm 10
FnKey LED8 Red MR User Alarm 9
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 61 of 163

P345 (V.36) P341 (V.70)


FnKey LED8 Grn MR User Alarm 8
FnKey LED9 Red MR User Alarm 7
FnKey LED9 Grn MR User Alarm 6
FnKey LED10 Red MR User Alarm 5
FnKey LED10 Grn SR User Alarm 4
Function Key 1 SR User Alarm 3
Function Key 2 SR User Alarm 2
Function Key 3 SR User Alarm 1
Function Key 4 Battery Fail
Function Key 5 Field Volts Fail
Function Key 6 Rear Comm 2 Fail
Function Key 7 GOOSE IED Absent
Function Key 8 NIC Not Fitted
Function Key 9 NIC No Response
Function Key 10 NIC Fatal Error
F out of Range NIC Soft. Reload
SG-DDB Invalid Bad TCP/IP Cfg.
Prot'n Disabled Bad OSI Config.
VT Fail Alarm NIC Link Fail
CT-1 Fail Alarm NIC SW Mis-Match
CB Fail Alarm IP Addr Conflict
I^ Maint Alarm IM Loopback
I^ Lockout Alarm IM Message Fail
CB Ops Maint IM Data CD Fail
CB Ops Lockout IM Channel Fail
CB Op Time Maint Any Trip
CB Op Time Lock IN>1 Trip
Fault Freq Lock IN>2 Trip
CB Status Alarm IN>3 Trip
Man CB Trip Fail IN>4 Trip
Man CB Cls Fail IREF> Trip
Man CB Unhealthy ISEF>1 Trip
NPS Thermal Alm ISEF>2 Trip
Thermal Alarm ISEF>3 Trip
V/Hz Alarm ISEF>4 Trip
Field Fail Alarm I>1 Trip
RTD Thermal Alm I>1 Trip A
RTD Open Cct I>1 Trip B
RTD short Cct I>1 Trip C
RTD Data Error I>2 Trip
RTD Board Fail I>2 Trip A
Freq Prot Alm I>2 Trip B
Voltage Prot Alm I>2 Trip C
CT-2 Fail Alarm I>3 Trip
64S R<1 Alarm I>3 Trip A
64S Fail Alarm I>3 Trip B
CL Card I/P Fail I>3 Trip C
CL Card O/P Fail I>4 Trip
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 62 of 163

P345 (V.36) P341 (V.70)


CL Input 1 Alarm I>4 Trip A
CL Input 2 Alarm I>4 Trip B
CL Input 3 Alarm I>4 Trip C
CL Input 4 Alarm I2>1 Trip
CLI1 I< Fail Alm I2>2 Trip
CLI2 I< Fail Alm I2>3 Trip
CLI3 I< Fail Alm I2>4 Trip
CLI4 I< Fail Alm Bfail1 Trip 3ph
64R R<1 Alarm Bfail2 Trip 3ph
64R CL I/P Fail VN>1 Trip
CT Para Mismatch VN>2 Trip
LOL Alarm VN>3 Trip
FAA Alarm VN>4 Trip
Thru fault Alm V>1 Trip
Cct Fail Alarm V>1 Trip A/AB
Tol Pretrip Alm V>1 Trip B/BC
CT Fail Alarm V>1 Trip C/CA
Man No Checksync V>2 Trip
System Split V>2 Trip A/AB
MR User Alarm 11 V>2 Trip B/BC
MR User Alarm 10 V>2 Trip C/CA
MR User Alarm 9 V2>1 Trip
MR User Alarm 8 V<1 Trip
MR User Alarm 7 V<1 Trip A/AB
MR User Alarm 6 V<1 Trip B/BC
MR User Alarm 5 V<1 Trip C/CA
SR User Alarm 4 V<2 Trip
SR User Alarm 3 V<2 Trip A/AB
SR User Alarm 2 V<2 Trip B/BC
SR User Alarm 1 V<2 Trip C/CA
Battery Fail Power1 Trip
Field Volts Fail Power2 Trip
Rear Comm 2 Fail SPower1 Trip
GOOSE IED Absent SPower2 Trip
NIC Not Fitted F<1 Trip
NIC No Response F<2 Trip
NIC Fatal Error F<3 Trip
NIC Soft. Reload F<4 Trip
Bad TCP/IP Cfg. F>1 Trip
Bad OSI Config. F>2 Trip
NIC Link Fail Trip df/dt>1
NIC SW Mis-Match Trip df/dt>2
IP Addr Conflict Trip df/dt>3
IM Loopback Trip df/dt>4
IM Message Fail V Shift Trip
IM Data CD Fail df/dt>1 Under F
IM Channel Fail df/dt>1 Over F
Any Trip Thermal O/L Trip
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 63 of 163

P345 (V.36) P341 (V.70)


Gen Diff Trip DLR I>1 Trip
Gen Diff Trip A DLR I>2 Trip
Gen Diff Trip B DLR I>3 Trip
Gen Diff Trip C DLR I>4 Trip
Xform Dif Trp DLR I>5 Trip
Xform Dif Trp A DLR I>6 Trip
Xform Dif Trp B CL Input 1 Trip
Xform Dif Trp C CL Input 2 Trip
Xform Bias Trp A CL Input 3 Trip
Xform Bias Trp B CL Input 4 Trip
Xform Bias Trp C Any Start
Xform HS1 Trp A IN>1 Start
Xform HS1 Trp B IN>2 Start
Xform HS1 Trp C IN>3 Start
Xform HS2 Trp A IN>4 Start
Xform HS2 Trp B ISEF>1 Start
Xform HS2 Trp C ISEF>2 Start
IN>1 Trip ISEF>3 Start
IN>2 Trip ISEF>4 Start
IREF> Trip I>1 Start
ISEF>1 Trip I>1 Start A
100%StEF3H Trip I>1 Start B
64S I>1 Trip I>1 Start C
64S R<2 Trip I>2 Start
64R R<2 Trip I>2 Start A
I>1 Trip I>2 Start B
I>1 Trip A I>2 Start C
I>1 Trip B I>3 Start
I>1 Trip C I>3 Start A
I>2 Trip I>3 Start B
I>2 Trip A I>3 Start C
I>2 Trip B I>4 Start
I>2 Trip C I>4 Start A
I>3 Trip I>4 Start B
I>3 Trip A I>4 Start C
I>3 Trip B I2>1 Start
I>3 Trip C I2>2 Start
I>4 Trip I2>3 Start
I>4 Trip A I2>4 Start
I>4 Trip B IA< Start
I>4 Trip C IB< Start
I2>1 Trip IC< Start
I2>2 Trip ISEF< Start
I2>3 Trip I> BlockStart
I2>4 Trip IN/SEF>Blk Start
Bfail1 Trip 3ph VN>1 Start
Bfail2 Trip 3ph VN>2 Start
VN>1 Trip VN>3 Start
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 64 of 163

P345 (V.36) P341 (V.70)


VN>2 Trip VN>4 Start
VN>3 Trip V>1 Start
VN>4 Trip V>1 Start A/AB
VN>5 Trip V>1 Start B/BC
VN>6 Trip V>1 Start C/CA
V>1 Trip V>2 Start
V>1 Trip A/AB V>2 Start A/AB
V>1 Trip B/BC V>2 Start B/BC
V>1 Trip C/CA V>2 Start C/CA
V>2 Trip V2>1 Start
V>2 Trip A/AB V<1 Start
V>2 Trip B/BC V<1 Start A/AB
V>2 Trip C/CA V<1 Start B/BC
V2>1 Trip V<1 Start C/CA
V<1 Trip V<2 Start
V<1 Trip A/AB V<2 Start A/AB
V<1 Trip B/BC V<2 Start B/BC
V<1 Trip C/CA V<2 Start C/CA
V<2 Trip Power1 Start
V<2 Trip A/AB Power2 Start
V<2 Trip B/BC SPower1 Start
V<2 Trip C/CA SPower2 Start
Field Fail1 Trip F<1 Start
Field Fail2 Trip F<2 Start
PSlipz Z1 Trip F<3 Start
PSlipz Z2 Trip F<4 Start
V Dep OC Trip F>1 Start
V Dep OC Trip A F>2 Start
V Dep OC Trip B Start df/dt>1
V Dep OC Trip C Start df/dt>2
Z<1 Trip Start df/dt>3
Z<1 Trip A Start df/dt>4
Z<1 Trip B DLR I>1 Start
Z<1 Trip C DLR I>2 Start
Z<2 Trip DLR I>3 Start
Z<2 Trip A DLR I>4 Start
Z<2 Trip B DLR I>5 Start
Z<2 Trip C DLR I>6 Start
DeadMachine Trip CLI1 Alarm Start
S2>1 Trip CLI2 Alarm Start
Power1 Trip CLI3 Alarm Start
Power2 Trip CLI4 Alarm Start
SPower1 Trip CLI1 Trip Start
SPower2 Trip CLI2 Trip Start
V/Hz>1 Trip CLI3 Trip Start
V/Hz>2 Trip CLI4 Trip Start
V/Hz>3 Trip VTS Fast Block
V/Hz>4 Trip VTS Slow Block
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 65 of 163

P345 (V.36) P341 (V.70)


F<1 Trip CTS-1 Block
F<2 Trip Control Trip
F<3 Trip Control Close
F<4 Trip Close in Prog
F>1 Trip Lockout Alarm
F>2 Trip CB Open 3 ph
Freq Band1 Trip CB Closed 3 ph
Freq Band2 Trip All Poles Dead
Freq Band3 Trip Any Pole Dead
Freq Band4 Trip Pole Dead A
Freq Band5 Trip Pole Dead B
Freq Band6 Trip Pole Dead C
Trip df/dt>1 Freq High
Trip df/dt>2 Freq Low
Trip df/dt>3 Freq Not found
Trip df/dt>4 Reconnection
V Shift Trip Check Sync 1 OK
df/dt>1 Under F Check Sync 2 OK
df/dt>1 Over F Control Input 1
NPS Thermal Trip Control Input 2
Thermal O/L Trip Control Input 3
Hot Spot>1 Trip Control Input 4
Hot Spot>2 Trip Control Input 5
Hot Spot>3 Trip Control Input 6
Top Oil>1 Trip Control Input 7
Top Oil>2 Trip Control Input 8
Top Oil>3 Trip Control Input 9
RTD 1 Trip Control Input 10
RTD 2 Trip Control Input 11
RTD 3 Trip Control Input 12
RTD 4 Trip Control Input 13
RTD 5 Trip Control Input 14
RTD 6 Trip Control Input 15
RTD 7 Trip Control Input 16
RTD 8 Trip Control Input 17
RTD 9 Trip Control Input 18
RTD 10 Trip Control Input 19
Any RTD Trip Control Input 20
CL Input 1 Trip Control Input 21
CL Input 2 Trip Control Input 22
CL Input 3 Trip Control Input 23
CL Input 4 Trip Control Input 24
Any Start Control Input 25
Xform Bias StrtA Control Input 26
Xform Bias StrtB Control Input 27
Xform Bias StrtC Control Input 28
IN>1 Start Control Input 29
IN>2 Start Control Input 30
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 66 of 163

P345 (V.36) P341 (V.70)


ISEF>1 Start Control Input 31
100%StEF3H Start Control Input 32
64S I< Start Virtual Input 01
64S V< Start Virtual Input 02
64S I>1 Start Virtual Input 03
64S Start R<1Alm Virtual Input 04
64S R<2 Start Virtual Input 05
64R Start R<1Alm Virtual Input 06
64R R<2 Start Virtual Input 07
I>1 Start Virtual Input 08
I>1 Start A Virtual Input 09
I>1 Start B Virtual Input 10
I>1 Start C Virtual Input 11
I>2 Start Virtual Input 12
I>2 Start A Virtual Input 13
I>2 Start B Virtual Input 14
I>2 Start C Virtual Input 15
I>3 Start Virtual Input 16
I>3 Start A Virtual Input 17
I>3 Start B Virtual Input 18
I>3 Start C Virtual Input 19
I>4 Start Virtual Input 20
I>4 Start A Virtual Input 21
I>4 Start B Virtual Input 22
I>4 Start C Virtual Input 23
I2>1 Start Virtual Input 24
I2>2 Start Virtual Input 25
I2>3 Start Virtual Input 26
I2>4 Start Virtual Input 27
IA< Start Virtual Input 28
IB< Start Virtual Input 29
IC< Start Virtual Input 30
ISEF< Start Virtual Input 31
IN< Start Virtual Input 32
VN>1 Start Virtual Input 33
VN>2 Start Virtual Input 34
VN>3 Start Virtual Input 35
VN>4 Start Virtual Input 36
VN>5 Start Virtual Input 37
VN>6 Start Virtual Input 38
V>1 Start Virtual Input 39
V>1 Start A/AB Virtual Input 40
V>1 Start B/BC Virtual Input 41
V>1 Start C/CA Virtual Input 42
V>2 Start Virtual Input 43
V>2 Start A/AB Virtual Input 44
V>2 Start B/BC Virtual Input 45
V>2 Start C/CA Virtual Input 46
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 67 of 163

P345 (V.36) P341 (V.70)


V2>1 Start Virtual Input 47
V<1 Start Virtual Input 48
V<1 Start A/AB Virtual Input 49
V<1 Start B/BC Virtual Input 50
V<1 Start C/CA Virtual Input 51
V<2 Start Virtual Input 52
V<2 Start A/AB Virtual Input 53
V<2 Start B/BC Virtual Input 54
V<2 Start C/CA Virtual Input 55
FFail1 Start Virtual Input 56
FFail2 Start Virtual Input 57
PSlipz Z1 Start Virtual Input 58
PSlipz Z2 Start Virtual Input 59
PSlipz LensStart Virtual Input 60
PSlipz BlindStrt Virtual Input 61
PSlipz ReactStrt Virtual Input 62
V Dep OC Start Virtual Input 63
V Dep OC Start A Virtual Input 64
V Dep OC Start B Virtual Output01
V Dep OC Start C Virtual Output02
Z<1 Start Virtual Output03
Z<1 Start A Virtual Output04
Z<1 Start B Virtual Output05
Z<1 Start C Virtual Output06
Z<2 Start Virtual Output07
Z<2 Start A Virtual Output08
Z<2 Start B Virtual Output09
Z<2 Start C Virtual Output10
S2>1 Start Virtual Output11
Power1 Start Virtual Output12
Power2 Start Virtual Output13
SPower1 Start Virtual Output14
SPower2 Start Virtual Output15
V/Hz>1 Start Virtual Output16
V/Hz>2 Start Virtual Output17
V/Hz>3 Start Virtual Output18
V/Hz>4 Start Virtual Output19
F<1 Start Virtual Output20
F<2 Start Virtual Output21
F<3 Start Virtual Output22
F<4 Start Virtual Output23
F>1 Start Virtual Output24
F>2 Start Virtual Output25
Freq Band1 Start Virtual Output26
Freq Band2 Start Virtual Output27
Freq Band3 Start Virtual Output28
Freq Band4 Start Virtual Output29
Freq Band5 Start Virtual Output30
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 68 of 163

P345 (V.36) P341 (V.70)


Freq Band6 Start Virtual Output31
Start df/dt>1 Virtual Output32
Start df/dt>2 Virtual Output33
Start df/dt>3 Virtual Output34
Start df/dt>4 Virtual Output35
Hot Spot>1 Start Virtual Output36
Hot Spot>2 Start Virtual Output37
Hot Spot>3 Start Virtual Output38
Top Oil>1 start Virtual Output39
Top Oil>2 start Virtual Output40
Top Oil>3 start Virtual Output41
CLI1 Alarm Start Virtual Output42
CLI2 Alarm Start Virtual Output43
CLI3 Alarm Start Virtual Output44
CLI4 Alarm Start Virtual Output45
CLI1 Trip Start Virtual Output46
CLI2 Trip Start Virtual Output47
CLI3 Trip Start Virtual Output48
CLI4 Trip Start Virtual Output49
VTS Fast Block Virtual Output50
VTS Slow Block Virtual Output51
CTS-1 Block Virtual Output52
CTS-2 Block Virtual Output53
CTS BLK Virtual Output54
CTS CT1 Virtual Output55
CTS CT2 Virtual Output56
CctFail Blk A Virtual Output57
CctFail Blk B Virtual Output58
CctFail Blk C Virtual Output59
2nd Har Blk A Virtual Output60
2nd Har Blk B Virtual Output61
2nd Har Blk C Virtual Output62
5nd Har Blk A Virtual Output63
5nd Har Blk B Virtual Output64
5nd Har Blk C
Control Trip
Control Close
Close in Prog
Lockout Alarm
CB Open 3 ph
CB Closed 3 ph
All Poles Dead
Any Pole Dead
Pole Dead A
Pole Dead B
Pole Dead C
Freq High
Freq Low
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 69 of 163

P345 (V.36) P341 (V.70)


Freq Not found
64S F Band Block
64S Fail
RTD 1 Alarm
RTD 2 Alarm
RTD 3 Alarm
RTD 4 Alarm
RTD 5 Alarm
RTD 6 Alarm
RTD 7 Alarm
RTD 8 Alarm
RTD 9 Alarm
RTD 10 Alarm
Check Sync 1 OK
Check Sync 2 OK
Control Input 1
Control Input 2
Control Input 3
Control Input 4
Control Input 5
Control Input 6
Control Input 7
Control Input 8
Control Input 9
Control Input 10
Control Input 11
Control Input 12
Control Input 13
Control Input 14
Control Input 15
Control Input 16
Control Input 17
Control Input 18
Control Input 19
Control Input 20
Control Input 21
Control Input 22
Control Input 23
Control Input 24
Control Input 25
Control Input 26
Control Input 27
Control Input 28
Control Input 29
Control Input 30
Control Input 31
Control Input 32
Virtual Input 01
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 70 of 163

P345 (V.36) P341 (V.70)


Virtual Input 02
Virtual Input 03
Virtual Input 04
Virtual Input 05
Virtual Input 06
Virtual Input 07
Virtual Input 08
Virtual Input 09
Virtual Input 10
Virtual Input 11
Virtual Input 12
Virtual Input 13
Virtual Input 14
Virtual Input 15
Virtual Input 16
Virtual Input 17
Virtual Input 18
Virtual Input 19
Virtual Input 20
Virtual Input 21
Virtual Input 22
Virtual Input 23
Virtual Input 24
Virtual Input 25
Virtual Input 26
Virtual Input 27
Virtual Input 28
Virtual Input 29
Virtual Input 30
Virtual Input 31
Virtual Input 32
Virtual Input 33
Virtual Input 34
Virtual Input 35
Virtual Input 36
Virtual Input 37
Virtual Input 38
Virtual Input 39
Virtual Input 40
Virtual Input 41
Virtual Input 42
Virtual Input 43
Virtual Input 44
Virtual Input 45
Virtual Input 46
Virtual Input 47
Virtual Input 48
Virtual Input 49
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 71 of 163

P345 (V.36) P341 (V.70)


Virtual Input 50
Virtual Input 51
Virtual Input 52
Virtual Input 53
Virtual Input 54
Virtual Input 55
Virtual Input 56
Virtual Input 57
Virtual Input 58
Virtual Input 59
Virtual Input 60
Virtual Input 61
Virtual Input 62
Virtual Input 63
Virtual Input 64
Virtual Output01
Virtual Output02
Virtual Output03
Virtual Output04
Virtual Output05
Virtual Output06
Virtual Output07
Virtual Output08
Virtual Output09
Virtual Output10
Virtual Output11
Virtual Output12
Virtual Output13
Virtual Output14
Virtual Output15
Virtual Output16
Virtual Output17
Virtual Output18
Virtual Output19
Virtual Output20
Virtual Output21
Virtual Output22
Virtual Output23
Virtual Output24
Virtual Output25
Virtual Output26
Virtual Output27
Virtual Output28
Virtual Output29
Virtual Output30
Virtual Output31
Virtual Output32
Virtual Output33
470234511.xls
Relay Menu Database G32_DDB_Lists
Page 72 of 163

P345 (V.36) P341 (V.70)


Virtual Output34
Virtual Output35
Virtual Output36
Virtual Output37
Virtual Output38
Virtual Output39
Virtual Output40
Virtual Output41
Virtual Output42
Virtual Output43
Virtual Output44
Virtual Output45
Virtual Output46
Virtual Output47
Virtual Output48
Virtual Output49
Virtual Output50
Virtual Output51
Virtual Output52
Virtual Output53
Virtual Output54
Virtual Output55
Virtual Output56
Virtual Output57
Virtual Output58
Virtual Output59
Virtual Output60
Virtual Output61
Virtual Output62
Virtual Output63
Virtual Output64
470234511.xls
Relay Menu Database G155 Meas. Range
Page 73 of 163

Measurements Range For Each G155 Selection


CLIO Output Measurement Unit Minimum Maximum Step Size Default Minimum Default Maximum Pri/Sec Mulitplier
IA Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IB Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IC Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IN Measured Mag A 0*I2 16*I2 0.01*I2 0*I2 1.2*I2 M5
IN Derived Mag A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IN-1 Derived Mag A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IN-2 Derived Mag A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
I Sen Magnitude A 0*I3 16*I3 0.01*I3 0*I3 1.2*I3 M6
I1 Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
I2 Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
I0 Magnitude A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IA RMS A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IB RMS A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IC RMS A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
VAB Magnitude V 0*V1 200*V1 0.1*V1 0*V1 140*V1 M1
VBC Magnitude V 0*V1 200*V1 0.1*V1 0*V1 140*V1 M1
VCA Magnitude V 0*V1 200*V1 0.1*V1 0*V1 140*V1 M1
VAN Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VBN Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VCN Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VN1 Magnitude V 0*V3 200*V3 0.1*V3 0*V3 80*V3 M3
VN Derived Mag V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VN2 Magnitude V 0*V2 200*V2 0.1*V2 0*V2 80*V2 M2
V1 Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
V2 Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
V0 Magnitude V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VAN RMS V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VBN RMS V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
VCN RMS V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
Frequency Hz 0 70 0.01 45 65
Volts/Hz V/Hz 0*V1 20*V1 0.01*V1 0*V1 4*V1 M1
3 Phase Watts W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
A Phase Watts W -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
B Phase Watts W -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
C Phase Watts W -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
3 Phase Vars Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
A Phase Vars Var -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
B Phase Vars Var -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
C Phase Vars Var -2000*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
3 Phase VA VA 0*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
A Phase VA VA 0*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
B Phase VA VA 0*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
C Phase VA VA 0*V1*I1 2000*V1*I1 1*V1*I1 0*V1*I1 100*V1*I1 M1*M4
3Ph Power Factor -1 1 0.01 0 1
APh Power Factor -1 1 0.01 0 1
BPh Power Factor -1 1 0.01 0 1
CPh Power Factor -1 1 0.01 0 1
3Ph W Fix Demand W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
3Ph Vars Fix Dem Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
IA Fixed Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IB Fixed Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IC Fixed Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
3 Ph W Roll Dem W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
3Ph Vars RollDem Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
IA Roll Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IB Roll Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IC Roll Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
3Ph W Peak Dem W -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
3Ph Var Peak Dem Var -6000*V1*I1 6000*V1*I1 1*V1*I1 0*V1*I1 300*V1*I1 M1*M4
IA Peak Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IB Peak Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
IC Peak Demand A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
VN 3rd Harmonic V 0*V3 200*V3 0.1*V3 0*V3 80*V3 M3
NPS Thermal % 0 200 0.01 0 120
Thermal Overload % 0 200 0.01 0 120
RTD 1 °C -40 300 0.1 0 200
RTD 2 °C -40 300 0.1 0 200
RTD 3 °C -40 300 0.1 0 200
RTD 4 °C -40 300 0.1 0 200
RTD 5 °C -40 300 0.1 0 200
RTD 6 °C -40 300 0.1 0 200
RTD 7 °C -40 300 0.1 0 200
RTD 8 °C -40 300 0.1 0 200
RTD 9 °C -40 300 0.1 0 200
RTD 10 °C -40 300 0.1 0 200
CL Input 1 -9999 9999 0.1 0 9999
CL Input 2 -9999 9999 0.1 0 9999
CL Input 3 -9999 9999 0.1 0 9999
CL Input 4 -9999 9999 0.1 0 9999
DLR Ampacity A 0*I1 4*I1 0.001*I1 0*I1 4*I1 M4
Max Iac A 0*I1 16*I1 0.01*I1 0*I1 1.2*I1 M4
Df/dt Hz/s -10 10 0.01 -1 1
C/S Voltage Mag V 0*VCS 200*VCS 0.1*VCS 0*VCS 80*V1 MCS/M2/M3
CS Gen-Bus Mag V 0*V1 200*V1 0.1*V1 0*V1 80*V1 M1
Slip Frequency Hz 0 70 0.01 -0.5 0.5
470234511.xls
Relay Menu Database DDBSignals
Page 74 of 163

DDB Signals
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_OUTPUT_RELAY_1 0 SW RELAY event_RelayChange Output Relay 1 see 4B01 * * * * * * *
DDB_OUTPUT_RELAY_2 1 SW RELAY event_RelayChange Output Relay 2 see 4B02 * * * * * * *
DDB_OUTPUT_RELAY_3 2 SW RELAY event_RelayChange Output Relay 3 see 4B03 * * * * * * *
DDB_OUTPUT_RELAY_4 3 SW RELAY event_RelayChange Output Relay 4 see 4B04 * * * * * * *
DDB_OUTPUT_RELAY_5 4 SW RELAY event_RelayChange Output Relay 5 see 4B05 * * * * * * *
DDB_OUTPUT_RELAY_6 5 SW RELAY event_RelayChange Output Relay 6 see 4B06 * * * * * * *
DDB_OUTPUT_RELAY_7 6 SW RELAY event_RelayChange Output Relay 7 see 4B07 * * * * * * *
DDB_OUTPUT_RELAY_8 7 SW RELAY event_RelayChange Output Relay 8 see 4B08 * * * * * * *
DDB_OUTPUT_RELAY_9 8 SW RELAY event_RelayChange Output Relay 9 see 4B09 * * * * * * *
DDB_OUTPUT_RELAY_10 9 SW RELAY event_RelayChange Output Relay 10 see 4B0A * * * * * * *
DDB_OUTPUT_RELAY_11 10 SW RELAY event_RelayChange Output Relay 11 see 4B0B * * * * * * *
DDB_OUTPUT_RELAY_12 11 SW RELAY event_RelayChange Output Relay 12 see 4B0C * * * * * * *
DDB_OUTPUT_RELAY_13 12 SW RELAY event_RelayChange Output Relay 13 see 4B0D * * * * * * *
DDB_OUTPUT_RELAY_14 13 SW RELAY event_RelayChange Output Relay 14 see 4B0E * * * * * * *
DDB_OUTPUT_RELAY_15 14 SW RELAY event_RelayChange Output Relay 15 see 4B0F * * * * * * *
DDB_OUTPUT_RELAY_16 15 SW RELAY event_RelayChange Output Relay 16 see 4B10 * * * * * * *
DDB_OUTPUT_RELAY_17 16 SW RELAY event_RelayChange Output Relay 17 see 4B11 * * * * * * *
DDB_OUTPUT_RELAY_18 17 SW RELAY event_RelayChange Output Relay 18 see 4B12 * * * * * * *
DDB_OUTPUT_RELAY_19 18 SW RELAY event_RelayChange Output Relay 19 see 4B13 * * * * * * *
DDB_OUTPUT_RELAY_20 19 SW RELAY event_RelayChange Output Relay 20 see 4B14 * * * * * * *
DDB_OUTPUT_RELAY_21 20 SW RELAY event_RelayChange Output Relay 21 see 4B15 * * * * * * *
DDB_OUTPUT_RELAY_22 21 SW RELAY event_RelayChange Output Relay 22 see 4B16 * * * * * * *
DDB_OUTPUT_RELAY_23 22 SW RELAY event_RelayChange Output Relay 23 see 4B17 * * * * * * *
DDB_OUTPUT_RELAY_24 23 SW RELAY event_RelayChange Output Relay 24 see 4B18 * * * * * * *
DDB_OUTPUT_RELAY_25 24 SW RELAY event_RelayChange Output Relay 25 see 4B19 * * * *
DDB_OUTPUT_RELAY_26 25 SW RELAY event_RelayChange Output Relay 26 see 4B1A * * * *
DDB_OUTPUT_RELAY_27 26 SW RELAY event_RelayChange Output Relay 27 see 4B1B * * * *
DDB_OUTPUT_RELAY_28 27 SW RELAY event_RelayChange Output Relay 28 see 4B1C * * * *
DDB_OUTPUT_RELAY_29 28 SW RELAY event_RelayChange Output Relay 29 see 4B1D * * * *
DDB_OUTPUT_RELAY_30 29 SW RELAY event_RelayChange Output Relay 30 see 4B1E * * * *
DDB_OUTPUT_RELAY_31 30 SW RELAY event_RelayChange Output Relay 31 see 4B1F * * * *
DDB_OUTPUT_RELAY_32 31 SW RELAY event_RelayChange Output Relay 32 see 4B20 * * * *
DDB_OPTO_ISOLATOR_1 32 SW OPTO event_OptoChange Opto Isolator Input 1 see 4A01 * * * * * * *
DDB_OPTO_ISOLATOR_2 33 SW OPTO event_OptoChange Opto Isolator Input 2 see 4A02 * * * * * * *
DDB_OPTO_ISOLATOR_3 34 SW OPTO event_OptoChange Opto Isolator Input 3 see 4A03 * * * * * * *
DDB_OPTO_ISOLATOR_4 35 SW OPTO event_OptoChange Opto Isolator Input 4 see 4A04 * * * * * * *
DDB_OPTO_ISOLATOR_5 36 SW OPTO event_OptoChange Opto Isolator Input 5 see 4A05 * * * * * * *
DDB_OPTO_ISOLATOR_6 37 SW OPTO event_OptoChange Opto Isolator Input 6 see 4A06 * * * * * * *
DDB_OPTO_ISOLATOR_7 38 SW OPTO event_OptoChange Opto Isolator Input 7 see 4A07 * * * * * * *
DDB_OPTO_ISOLATOR_8 39 SW OPTO event_OptoChange Opto Isolator Input 8 see 4A08 * * * * * * *
DDB_OPTO_ISOLATOR_9 40 SW OPTO event_OptoChange Opto Isolator Input 9 see 4A09 * * * * * * *
DDB_OPTO_ISOLATOR_10 41 SW OPTO event_OptoChange Opto Isolator Input 10 see 4A0A * * * * * * *
DDB_OPTO_ISOLATOR_11 42 SW OPTO event_OptoChange Opto Isolator Input 11 see 4A0B * * * * * * *
DDB_OPTO_ISOLATOR_12 43 SW OPTO event_OptoChange Opto Isolator Input 12 see 4A0C * * * * * * *
DDB_OPTO_ISOLATOR_13 44 SW OPTO event_OptoChange Opto Isolator Input 13 see 4A0D * * * * * * *
DDB_OPTO_ISOLATOR_14 45 SW OPTO event_OptoChange Opto Isolator Input 14 see 4A0E * * * * * * *
DDB_OPTO_ISOLATOR_15 46 SW OPTO event_OptoChange Opto Isolator Input 15 see 4A0F * * * * * * *
DDB_OPTO_ISOLATOR_16 47 SW OPTO event_OptoChange Opto Isolator Input 16 see 4A10 * * * * * * *
DDB_OPTO_ISOLATOR_17 48 SW OPTO event_OptoChange Opto Isolator Input 17 see 4A11 * * * * * * *
DDB_OPTO_ISOLATOR_18 49 SW OPTO event_OptoChange Opto Isolator Input 18 see 4A12 * * * * * * *
DDB_OPTO_ISOLATOR_19 50 SW OPTO event_OptoChange Opto Isolator Input 19 see 4A13 * * * * * * *
DDB_OPTO_ISOLATOR_20 51 SW OPTO event_OptoChange Opto Isolator Input 20 see 4A14 * * * * * * *
DDB_OPTO_ISOLATOR_21 52 SW OPTO event_OptoChange Opto Isolator Input 21 see 4A15 * * * * * * *
DDB_OPTO_ISOLATOR_22 53 SW OPTO event_OptoChange Opto Isolator Input 22 see 4A16 * * * * * * *
DDB_OPTO_ISOLATOR_23 54 SW OPTO event_OptoChange Opto Isolator Input 23 see 4A17 * * * * * * *
DDB_OPTO_ISOLATOR_24 55 SW OPTO event_OptoChange Opto Isolator Input 24 see 4A18 * * * * * * *
DDB_OPTO_ISOLATOR_25 56 SW OPTO event_OptoChange Opto Isolator Input 25 see 4A19 * * * *
DDB_OPTO_ISOLATOR_26 57 SW OPTO event_OptoChange Opto Isolator Input 26 see 4A1A * * * *
DDB_OPTO_ISOLATOR_27 58 SW OPTO event_OptoChange Opto Isolator Input 27 see 4A1B * * * *
DDB_OPTO_ISOLATOR_28 59 SW OPTO event_OptoChange Opto Isolator Input 28 see 4A1C * * * *
DDB_OPTO_ISOLATOR_29 60 SW OPTO event_OptoChange Opto Isolator Input 29 see 4A1D * * * *
DDB_OPTO_ISOLATOR_30 61 SW OPTO event_OptoChange Opto Isolator Input 30 see 4A1E * * * *
DDB_OPTO_ISOLATOR_31 62 SW OPTO event_OptoChange Opto Isolator Input 31 see 4A1F * * * *
DDB_OPTO_ISOLATOR_32 63 SW OPTO event_OptoChange Opto Isolator Input 32 see 4A20 * * * *
DDB_OUTPUT_CON_1 64 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 1 Relay Cond 1 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 75 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_OUTPUT_CON_2 65 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 2 Relay Cond 2 * * * * * * *
DDB_OUTPUT_CON_3 66 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 3 Relay Cond 3 * * * * * * *
DDB_OUTPUT_CON_4 67 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 4 Relay Cond 4 * * * * * * *
DDB_OUTPUT_CON_5 68 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 5 Relay Cond 5 * * * * * * *
DDB_OUTPUT_CON_6 69 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 6 Relay Cond 6 * * * * * * *
DDB_OUTPUT_CON_7 70 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 7 Relay Cond 7 * * * * * * *
DDB_OUTPUT_CON_8 71 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 8 Relay Cond 8 * * * * * * *
DDB_OUTPUT_CON_9 72 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 9 Relay Cond 9 * * * * * * *
DDB_OUTPUT_CON_10 73 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 10 Relay Cond 10 * * * * * * *
DDB_OUTPUT_CON_11 74 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 11 Relay Cond 11 * * * * * * *
DDB_OUTPUT_CON_12 75 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 12 Relay Cond 12 * * * * * * *
DDB_OUTPUT_CON_13 76 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 13 Relay Cond 13 * * * * * * *
DDB_OUTPUT_CON_14 77 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 14 Relay Cond 14 * * * * * * *
DDB_OUTPUT_CON_15 78 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 15 Relay Cond 15 * * * * * * *
DDB_OUTPUT_CON_16 79 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 16 Relay Cond 16 * * * * * * *
DDB_OUTPUT_CON_17 80 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 17 Relay Cond 17 * * * * * * *
DDB_OUTPUT_CON_18 81 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 18 Relay Cond 18 * * * * * * *
DDB_OUTPUT_CON_19 82 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 19 Relay Cond 19 * * * * * * *
DDB_OUTPUT_CON_20 83 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 20 Relay Cond 20 * * * * * * *
DDB_OUTPUT_CON_21 84 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 21 Relay Cond 21 * * * * * * *
DDB_OUTPUT_CON_22 85 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 22 Relay Cond 22 * * * * * * *
DDB_OUTPUT_CON_23 86 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 23 Relay Cond 23 * * * * * * *
DDB_OUTPUT_CON_24 87 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 24 Relay Cond 24 * * * * * * *
DDB_OUTPUT_CON_25 88 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 25 Relay Cond 25 * * * *
DDB_OUTPUT_CON_26 89 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 26 Relay Cond 26 * * * *
DDB_OUTPUT_CON_27 90 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 27 Relay Cond 27 * * * *
DDB_OUTPUT_CON_28 91 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 28 Relay Cond 28 * * * *
DDB_OUTPUT_CON_29 92 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 29 Relay Cond 29 * * * *
DDB_OUTPUT_CON_30 93 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 30 Relay Cond 30 * * * *
DDB_OUTPUT_CON_31 94 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 31 Relay Cond 31 * * * *
DDB_OUTPUT_CON_32 95 PSL OUTPUT_CON NO_RESPONSE Relay Conditioner 32 Relay Cond 32 * * * *
DDB_OUTPUT_TRI_LED_1_RED 96 SW TRI_LED NO_RESPONSE Tri-LED - 1 - Red LED1 Red * * * *
DDB_OUTPUT_TRI_LED_1_GRN 97 SW TRI_LED NO_RESPONSE Tri-LED - 1 - Green LED1 Grn * * * *
DDB_OUTPUT_TRI_LED_2_RED 98 SW TRI_LED NO_RESPONSE Tri-LED - 2 - Red LED2 Red * * * *
DDB_OUTPUT_TRI_LED_2_GRN 99 SW TRI_LED NO_RESPONSE Tri-LED - 2 - Green LED2 Grn * * * *
DDB_OUTPUT_TRI_LED_3_RED 100 SW TRI_LED NO_RESPONSE Tri-LED - 3 - Red LED3 Red * * * *
DDB_OUTPUT_TRI_LED_3_GRN 101 SW TRI_LED NO_RESPONSE Tri-LED - 3 - Green LED3 Grn * * * *
DDB_OUTPUT_TRI_LED_4_RED 102 SW TRI_LED NO_RESPONSE Tri-LED - 4 - Red LED4 Red * * * *
DDB_OUTPUT_TRI_LED_4_GRN 103 SW TRI_LED NO_RESPONSE Tri-LED - 4 - Green LED4 Grn * * * *
DDB_OUTPUT_TRI_LED_5_RED 104 SW TRI_LED NO_RESPONSE Tri-LED - 5 - Red LED5 Red * * * *
DDB_OUTPUT_TRI_LED_5_GRN 105 SW TRI_LED NO_RESPONSE Tri-LED - 5 - Green LED5 Grn * * * *
DDB_OUTPUT_TRI_LED_6_RED 106 SW TRI_LED NO_RESPONSE Tri-LED - 6 - Red LED6 Red * * * *
DDB_OUTPUT_TRI_LED_6_GRN 107 SW TRI_LED NO_RESPONSE Tri-LED - 6 - Green LED6 Grn * * * *
DDB_OUTPUT_TRI_LED_7_RED 108 SW TRI_LED NO_RESPONSE Tri-LED - 7 - Red LED7 Red * * * *
DDB_OUTPUT_TRI_LED_7_GRN 109 SW TRI_LED NO_RESPONSE Tri-LED - 7 - Green LED7 Grn * * * *
DDB_OUTPUT_TRI_LED_8_RED 110 SW TRI_LED NO_RESPONSE Tri-LED - 8 - Red LED8 Red * * * *
DDB_OUTPUT_TRI_LED_8_GRN 111 SW TRI_LED NO_RESPONSE Tri-LED - 8 - Green LED8 Grn * * * *
DDB_OUTPUT_TRI_LED_9_RED 112 SW TRI_LED NO_RESPONSE Tri-LED - 9 - Red FnKey LED1 Red * * * *
DDB_OUTPUT_TRI_LED_9_GRN 113 SW TRI_LED NO_RESPONSE Tri-LED - 9 - Green FnKey LED1 Grn * * * *
DDB_OUTPUT_TRI_LED_10_RED 114 SW TRI_LED NO_RESPONSE Tri-LED - 10 - Red FnKey LED2 Red * * * *
DDB_OUTPUT_TRI_LED_10_GRN 115 SW TRI_LED NO_RESPONSE Tri-LED - 10 - Green FnKey LED2 Grn * * * *
DDB_OUTPUT_TRI_LED_11_RED 116 SW TRI_LED NO_RESPONSE Tri-LED - 11 - Red FnKey LED3 Red * * * *
DDB_OUTPUT_TRI_LED_11_GRN 117 SW TRI_LED NO_RESPONSE Tri-LED - 11 - Green FnKey LED3 Grn * * * *
DDB_OUTPUT_TRI_LED_12_RED 118 SW TRI_LED NO_RESPONSE Tri-LED - 12 - Red FnKey LED4 Red * * * *
DDB_OUTPUT_TRI_LED_12_GRN 119 SW TRI_LED NO_RESPONSE Tri-LED - 12 - Green FnKey LED4 Grn * * * *
DDB_OUTPUT_TRI_LED_13_RED 120 SW TRI_LED NO_RESPONSE Tri-LED - 13 - Red FnKey LED5 Red * * * *
DDB_OUTPUT_TRI_LED_13_GRN 121 SW TRI_LED NO_RESPONSE Tri-LED - 13 - Green FnKey LED5 Grn * * * *
DDB_OUTPUT_TRI_LED_14_RED 122 SW TRI_LED NO_RESPONSE Tri-LED - 14 - Red FnKey LED6 Red * * * *
DDB_OUTPUT_TRI_LED_14_GRN 123 SW TRI_LED NO_RESPONSE Tri-LED - 14 - Green FnKey LED6 Grn * * * *
DDB_OUTPUT_TRI_LED_15_RED 124 SW TRI_LED NO_RESPONSE Tri-LED - 15 - Red FnKey LED7 Red * * * *
DDB_OUTPUT_TRI_LED_15_GRN 125 SW TRI_LED NO_RESPONSE Tri-LED - 15 - Green FnKey LED7 Grn * * * *
DDB_OUTPUT_TRI_LED_16_RED 126 SW TRI_LED NO_RESPONSE Tri-LED - 16 - Red FnKey LED8 Red * * * *
DDB_OUTPUT_TRI_LED_16_GRN 127 SW TRI_LED NO_RESPONSE Tri-LED - 16 - Green FnKey LED8 Grn * * * *
DDB_OUTPUT_TRI_LED_17_RED 128 SW TRI_LED NO_RESPONSE Tri-LED - 17 - Red FnKey LED9 Red * * * *
DDB_OUTPUT_TRI_LED_17_GRN 129 SW TRI_LED NO_RESPONSE Tri-LED - 17 - Green FnKey LED9 Grn * * * *
DDB_OUTPUT_TRI_LED_18_RED 130 SW TRI_LED NO_RESPONSE Tri-LED - 18 - Red FnKey LED10 Red * * * *
DDB_OUTPUT_TRI_LED_18_GRN 131 SW TRI_LED NO_RESPONSE Tri-LED - 18 - Green FnKey LED10 Grn * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 76 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 132 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 133 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 134 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 135 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 136 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 137 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 138 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 139 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 140 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 141 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 142 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 143 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 144 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 145 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 146 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 147 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 148 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 149 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 150 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 151 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 152 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 153 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 154 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 155 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 156 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 157 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 158 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 159 SW UNUSED NO_RESPONSE Unused
DDB_TRI_LED_RED_CON_1 160 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 1 - Red LED1 Con R * * * *
DDB_TRI_LED_GRN_CON_1 161 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner- 1 - Green LED1 Con G * * * *
DDB_TRI_LED_RED_CON_2 162 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 2 - Red LED2 Con R * * * *
DDB_TRI_LED_GRN_CON_2 163 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 2 - Green LED2 Con G * * * *
DDB_TRI_LED_RED_CON_3 164 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 3 - Red LED3 Con R * * * *
DDB_TRI_LED_GRN_CON_3 165 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 3 - Green LED3 Con G * * * *
DDB_TRI_LED_RED_CON_4 166 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 4 - Red LED4 Con R * * * *
DDB_TRI_LED_GRN_CON_4 167 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 4 - Green LED4 Con G * * * *
DDB_TRI_LED_RED_CON_5 168 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 5 - Red LED5 Con R * * * *
DDB_TRI_LED_GRN_CON_5 169 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 5 - Green LED5 Con G * * * *
DDB_TRI_LED_RED_CON_6 170 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 6 - Red LED6 Con R * * * *
DDB_TRI_LED_GRN_CON_6 171 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 6 - Green LED6 Con G * * * *
DDB_TRI_LED_RED_CON_7 172 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 7 - Red LED7 Con R * * * *
DDB_TRI_LED_GRN_CON_7 173 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 7 - Green LED7 Con G * * * *
DDB_TRI_LED_RED_CON_8 174 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 8 - Red LED8 Con R * * * *
DDB_TRI_LED_GRN_CON_8 175 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 8 - Green LED8 Con G * * * *
DDB_TRI_LED_RED_CON_9 176 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 9 - Red FnKey LED1 ConR * * * *
DDB_TRI_LED_GRN_CON_9 177 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 9 - Green FnKey LED1 ConG * * * *
DDB_TRI_LED_RED_CON_10 178 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 10 - Red FnKey LED2 ConR * * * *
DDB_TRI_LED_GRN_CON_10 179 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 10 - Green FnKey LED2 ConG * * * *
DDB_TRI_LED_RED_CON_11 180 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 11 - Red FnKey LED3 ConR * * * *
DDB_TRI_LED_GRN_CON_11 181 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 11 - Green FnKey LED3 ConG * * * *
DDB_TRI_LED_RED_CON_12 182 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 12 - Red FnKey LED4 ConR * * * *
DDB_TRI_LED_GRN_CON_12 183 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 12 - Green FnKey LED4 ConG * * * *
DDB_TRI_LED_RED_CON_13 184 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 13 - Red FnKey LED5 ConR * * * *
DDB_TRI_LED_GRN_CON_13 185 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 13 - Green FnKey LED5 ConG * * * *
DDB_TRI_LED_RED_CON_14 186 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 14 - Red FnKey LED6 ConR * * * *
DDB_TRI_LED_GRN_CON_14 187 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 14 - Green FnKey LED6 ConG * * * *
DDB_TRI_LED_RED_CON_15 188 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 15 - Red FnKey LED7 ConR * * * *
DDB_TRI_LED_GRN_CON_15 189 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 15 - Green FnKey LED7 ConG * * * *
DDB_TRI_LED_RED_CON_16 190 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 16 - Red FnKey LED8 ConR * * * *
DDB_TRI_LED_GRN_CON_16 191 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 16 - Green FnKey LED8 ConG * * * *
DDB_TRI_LED_RED_CON_17 192 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 17 - Red FnKey LED9 ConR * * * *
DDB_TRI_LED_GRN_CON_17 193 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 17 - Green FnKey LED9 ConG * * * *
DDB_TRI_LED_RED_CON_18 194 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 18 - Red FnKey LED10 ConR * * * *
DDB_TRI_LED_GRN_CON_18 195 PSL TRI_LED_CON NO_RESPONSE Tri-LED Conditioner - 18 - Green FnKey LED10 ConG * * * *
DDB_UNUSED 196 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 197 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 198 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 77 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 199 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 200 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 201 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 202 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 203 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 204 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 205 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 206 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 207 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 208 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 209 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 210 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 211 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 212 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 213 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 214 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 215 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 216 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 217 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 218 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 219 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 220 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 221 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 222 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 223 SW UNUSED NO_RESPONSE Unused
DDB_OUTPUT_LED_1 224 SW LED NO_RESPONSE LED 1 LED 1 * * *
DDB_OUTPUT_LED_2 225 SW LED NO_RESPONSE LED 2 LED 2 * * *
DDB_OUTPUT_LED_3 226 SW LED NO_RESPONSE LED 3 LED 3 * * *
DDB_OUTPUT_LED_4 227 SW LED NO_RESPONSE LED 4 LED 4 * * *
DDB_OUTPUT_LED_5 228 SW LED NO_RESPONSE LED 5 LED 5 * * *
DDB_OUTPUT_LED_6 229 SW LED NO_RESPONSE LED 6 LED 6 * * *
DDB_OUTPUT_LED_7 230 SW LED NO_RESPONSE LED 7 LED 7 * * *
DDB_OUTPUT_LED_8 231 SW LED NO_RESPONSE LED 8 LED 8 * * *
DDB_LED_CON_1 232 PSL LED_CON NO_RESPONSE LED Conditioner IN 1 LED Cond IN 1 * * *
DDB_LED_CON_2 233 PSL LED_CON NO_RESPONSE LED Conditioner IN 2 LED Cond IN 2 * * *
DDB_LED_CON_3 234 PSL LED_CON NO_RESPONSE LED Conditioner IN 3 LED Cond IN 3 * * *
DDB_LED_CON_4 235 PSL LED_CON NO_RESPONSE LED Conditioner IN 4 LED Cond IN 4 * * *
DDB_LED_CON_5 236 PSL LED_CON NO_RESPONSE LED Conditioner IN 5 LED Cond IN 5 * * *
DDB_LED_CON_6 237 PSL LED_CON NO_RESPONSE LED Conditioner IN 6 LED Cond IN 6 * * *
DDB_LED_CON_7 238 PSL LED_CON NO_RESPONSE LED Conditioner IN 7 LED Cond IN 7 * * *
DDB_LED_CON_8 239 PSL LED_CON NO_RESPONSE LED Conditioner IN 8 LED Cond IN 8 * * *
DDB_UNUSED 240 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 241 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 242 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 243 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 244 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 245 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 246 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 247 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 248 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 249 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 250 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 251 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 252 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 253 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 254 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 255 SW UNUSED NO_RESPONSE Unused
DDB_FN_KEY_1 256 SW FUNCTION_KEY event_Protection Function Key 1 Function Key 1 * * * *
DDB_FN_KEY_2 257 SW FUNCTION_KEY event_Protection Function Key 2 Function Key 2 * * * *
DDB_FN_KEY_3 258 SW FUNCTION_KEY event_Protection Function Key 3 Function Key 3 * * * *
DDB_FN_KEY_4 259 SW FUNCTION_KEY event_Protection Function Key 4 Function Key 4 * * * *
DDB_FN_KEY_5 260 SW FUNCTION_KEY event_Protection Function Key 5 Function Key 5 * * * *
DDB_FN_KEY_6 261 SW FUNCTION_KEY event_Protection Function Key 6 Function Key 6 * * * *
DDB_FN_KEY_7 262 SW FUNCTION_KEY event_Protection Function Key 7 Function Key 7 * * * *
DDB_FN_KEY_8 263 SW FUNCTION_KEY event_Protection Function Key 8 Function Key 8 * * * *
DDB_FN_KEY_9 264 SW FUNCTION_KEY event_Protection Function Key 9 Function Key 9 * * * *
DDB_FN_KEY_10 265 SW FUNCTION_KEY event_Protection Function Key 10 Function Key 10 * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 78 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 266 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 267 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 268 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 269 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 270 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 271 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 272 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 273 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 274 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 275 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 276 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 277 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 278 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 279 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 280 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 281 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 282 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 283 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 284 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 285 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 286 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 287 SW UNUSED NO_RESPONSE Unused
DDB_TIMEROUT_1 288 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 1 Timer out 1 * * * * * * *
DDB_TIMEROUT_2 289 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 2 Timer out 2 * * * * * * *
DDB_TIMEROUT_3 290 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 3 Timer out 3 * * * * * * *
DDB_TIMEROUT_4 291 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 4 Timer out 4 * * * * * * *
DDB_TIMEROUT_5 292 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 5 Timer out 5 * * * * * * *
DDB_TIMEROUT_6 293 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 6 Timer out 6 * * * * * * *
DDB_TIMEROUT_7 294 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 7 Timer out 7 * * * * * * *
DDB_TIMEROUT_8 295 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 8 Timer out 8 * * * * * * *
DDB_TIMEROUT_9 296 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 9 Timer out 9 * * * * * * *
DDB_TIMEROUT_10 297 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 10 Timer out 10 * * * * * * *
DDB_TIMEROUT_11 298 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 11 Timer out 11 * * * * * * *
DDB_TIMEROUT_12 299 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 12 Timer out 12 * * * * * * *
DDB_TIMEROUT_13 300 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 13 Timer out 13 * * * * * * *
DDB_TIMEROUT_14 301 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 14 Timer out 14 * * * * * * *
DDB_TIMEROUT_15 302 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 15 Timer out 15 * * * * * * *
DDB_TIMEROUT_16 303 SW TIMEROUT NO_RESPONSE Auxiliary Timer out 16 Timer out 16 * * * * * * *
DDB_UNUSED 304 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 305 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 306 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 307 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 308 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 309 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 310 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 311 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 312 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 313 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 314 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 315 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 316 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 317 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 318 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 319 SW UNUSED NO_RESPONSE Unused
DDB_TIMERIN_1 320 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 1 Timer in 1 * * * * * * *
DDB_TIMERIN_2 321 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 2 Timer in 2 * * * * * * *
DDB_TIMERIN_3 322 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 3 Timer in 3 * * * * * * *
DDB_TIMERIN_4 323 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 4 Timer in 4 * * * * * * *
DDB_TIMERIN_5 324 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 5 Timer in 5 * * * * * * *
DDB_TIMERIN_6 325 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 6 Timer in 6 * * * * * * *
DDB_TIMERIN_7 326 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 7 Timer in 7 * * * * * * *
DDB_TIMERIN_8 327 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 8 Timer in 8 * * * * * * *
DDB_TIMERIN_9 328 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 9 Timer in 9 * * * * * * *
DDB_TIMERIN_10 329 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 10 Timer in 10 * * * * * * *
DDB_TIMERIN_11 330 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 11 Timer in 11 * * * * * * *
DDB_TIMERIN_12 331 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 12 Timer in 12 * * * * * * *
DDB_TIMERIN_13 332 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 13 Timer in 13 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 79 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_TIMERIN_14 333 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 14 Timer in 14 * * * * * * *
DDB_TIMERIN_15 334 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 15 Timer in 15 * * * * * * *
DDB_TIMERIN_16 335 PSL TIMERIN NO_RESPONSE Auxiliary Timer in 16 Timer in 16 * * * * * * *
DDB_UNUSED 336 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 337 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 338 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 339 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 340 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 341 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 342 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 343 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 344 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 345 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 346 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 347 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 348 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 349 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 350 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 351 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 352 SW UNUSED NO_RESPONSE Unused
DDB_FREQ_ALARM 353 FL PFSO event_AlarmSelfReset Frequency Out of Range F out of Range * * * * * * *
DDB_ILLEGAL_OPTO_SETTINGS_GROUP 354 SW PFSO event_AlarmSelfReset Setting Group selection by DDB inputs invalid SG-DDB Invalid * * * * * * *
DDB_OOS_ALARM 355 SW PFSO event_AlarmSelfReset Test Mode Enabled Prot'n Disabled * * * * * * *
DDB_VTS_INDICATION 356 SW PFSO event_AlarmSelfReset VTS VT Fail Alarm VT Fail Alarm * * * * * * *
DDB_CTS_INDICATION 357 SW PFSO event_AlarmSelfReset CTS-1 CT-1 Fail Alarm CT-1 Fail Alarm * * * * * * *
DDB_BREAKER_FAIL_ALARM 358 SW PFSO event_AlarmLatched Breaker Fail Any Trip CB Fail Alarm * * * * * * *
DDB_BROKEN_CURRENT_ALARM 359 SW PFSO event_AlarmSelfReset Broken Current Maintenance Alarm I^ Maint Alarm * * * * * * *
DDB_BROKEN_CURRENT_LOCKOUT 360 SW PFSO event_AlarmSelfReset Broken Current Lockout Alarm I^ Lockout Alarm * * * * * * *
DDB_MAINTENANCE_ALARM 361 SW PFSO event_AlarmSelfReset Number of CB Operations Maintenance Alarm CB Ops Maint * * * * * * *
DDB_MAINTENANCE_LOCKOUT 362 SW PFSO event_AlarmSelfReset Number of CB Operations Maintenance Lockout CB Ops Lockout * * * * * * *
DDB_EXCESSIVE_OP_TIME_ALARM 363 SW PFSO event_AlarmSelfReset Excessive CB Operation Time Maintenance Alarm CB Op Time Maint * * * * * * *
DDB_EXCESSIVE_OP_TIME_LOCKOUT 364 SW PFSO event_AlarmSelfReset Excessive CB Operation Time Lockout Alarm CB Op Time Lock * * * * * * *
DDB_EFF_LOCKOUT 365 SW PFSO event_AlarmSelfReset Excessive Fault Frequency Lockout Alarm Fault Freq Lock * * * * * * *
DDB_CB_STATUS_ALARM 366 SW PFSO event_AlarmLatched CB Status Alarm CB Status Alarm * * * * * * *
DDB_CB_FAILED_TO_TRIP 367 SW PFSO event_AlarmLatched CB Failed to Trip Man CB Trip Fail * * * * * * *
DDB_CB_FAILED_TO_CLOSE 368 SW PFSO event_AlarmLatched CB Failed to Close Man CB Cls Fail * * * * * * *
DDB_CONTROL_CB_UNHEALTHY 369 SW PFSO event_AlarmLatched Control CB Unhealthy Man CB Unhealthy * * * * * * *
DDB_NPS_ALARM 370 SW PFSO event_AlarmLatched Negative Phase Sequence thermal Alarm NPS Thermal Alm * * * * *
DDB_GEN_THERMAL_ALARM 371 SW PFSO event_AlarmLatched Thermal Overload Alarm Gen Thermal Alm * * * * * * *
DDB_VPERHZ_ALARM 372 SW PFSO event_AlarmLatched Volts Per Hz Alarm V/Hz Alarm * * * * *
DDB_FIELDF_ALARM 373 SW PFSO event_AlarmLatched Field Failure Alarm Field Fail Alarm * * * * *
DDB_RTD_ALARM 374 FL PFSO event_AlarmLatched RTD Thermal Alarm RTD Thermal Alm * * * * *
DDB_RTD_OPEN_CCT 375 SW PFSO event_AlarmLatched RTD Open Circuit Failure RTD Open Cct * * * * *
DDB_RTD_SHORT_CCT 376 SW PFSO event_AlarmLatched RTD Short Circuit Failure RTD short Cct * * * * *
DDB_RTD_DATA_ERROR 377 SW PFSO event_AlarmLatched RTD Data Inconsistency Error RTD Data Error * * * * *
DDB_RTD_BOARD_FAILURE 378 SW PFSO event_AlarmLatched RTD Board Failure RTD Board Fail * * * * *
DDB_FREQ_PROT_ALM 379 PSL PFSI event_AlarmLatched Frequency Protection Alarm Freq Prot Alm * * * * * * *
DDB_VOLTAGE_PROT_ALM 380 PSL PFSI event_AlarmLatched Voltage Protection Alarm Voltage Prot Alm * * * * * * *
DDB_CTS_2_INDICATION 381 SW PFSO event_AlarmSelfReset CTS-2 CT-2 Fail Alarm CT-2 Fail Alarm * * * *
DDB_STEFI_UR_1_TRIP 382 SW PFSO event_AlarmLatched 64S 100% St EF Under Resistance Stage 1 Alarm 64S R<1 Alarm *
DDB_STEFI_FAIL_ALARM 383 PSL PFSI event_AlarmSelfReset 64S Injection Fail Alarm 64S Fail Alarm *
DDB_CLIO_CARD_INPUT_FAIL 384 SW PFSO event_AlarmLatched CLIO Input Board Failure CL Card I/P Fail * * * * * * *
DDB_CLIO_CARD_OUTPUT_FAIL 385 SW PFSO event_AlarmLatched CLIO Output Board Failure CL Card O/P Fail * * * * * * *
DDB_CL_INPUT_1_ALARM 386 SW PFSO event_AlarmLatched Current Loop Input 1 Alarm CL Input 1 Alarm * * * * * * *
DDB_CL_INPUT_2_ALARM 387 SW PFSO event_AlarmLatched Current Loop Input 2 Alarm CL Input 2 Alarm * * * * * * *
DDB_CL_INPUT_3_ALARM 388 SW PFSO event_AlarmLatched Current Loop Input 3 Alarm CL Input 3 Alarm * * * * * * *
DDB_CL_INPUT_4_ALARM 389 SW PFSO event_AlarmLatched Current Loop Input 4 Alarm CL Input 4 Alarm * * * * * * *
DDB_CLI_1_UNDERCURRENT_ALARM 390 SW PFSO event_AlarmLatched Current Loop Input 1 Undercurrent Fail Alarm CLI1 I< Fail Alm * * * * * * *
DDB_CLI_2_UNDERCURRENT_ALARM 391 SW PFSO event_AlarmLatched Current Loop Input 2 Undercurrent Fail Alarm CLI2 I< Fail Alm * * * * * * *
DDB_CLI_3_UNDERCURRENT_ALARM 392 SW PFSO event_AlarmLatched Current Loop Input 3 Undercurrent Fail Alarm CLI3 I< Fail Alm * * * * * * *
DDB_CLI_4_UNDERCURRENT_ALARM 393 SW PFSO event_AlarmLatched Current Loop Input 4 Undercurrent Fail Alarm CLI4 I< Fail Alm * * * * * * *
DDB_64R_UR_1_TRIP 394 SW PFSO event_AlarmLatched 64R Rotor EF Under Resistance Stage 1 Alarm 64R R<1 Alarm * * * * *
DDB_64R_CLIO_INPUT_FAIL 395 SW PFSO event_AlarmLatched 64R Rotor EF Current Loop Input Fail 64R CL I/P Fail * * * * *
DDB_CT_PARA_MISMATCH_ALARM 396 SW PFSO event_AlarmSelfReset CT parameter mismatch alarm CT Mismatch Alm * * * *
DDB_DLR_UC_AMBT_TEMP_ALARM 396 SW PFSO event_AlarmLatched DLR Input Ambient Temperature Fail alarm Amb T Fail Alm *
DDB_LOL_ALARM 397 SW PFSO event_AlarmLatched Loss of Life Alarm Loss of Life Alm * * * * *
DDB_DLR_UC_WIND_V_ALARM 397 SW PFSO event_AlarmLatched DLR Input Wind Velocity Fail alarm Wind V Fail Alm *
470234511.xls
Relay Menu Database DDBSignals
Page 80 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_FAA_ALARM 398 SW PFSO event_AlarmLatched Aging Acceleration Factor Alarm FAA Alarm * * * * *
DDB_DLR_UC_WIND_DIRECT_ALARM 398 SW PFSO event_AlarmLatched DLR Input Wind Direction Fail alarm Wind D Fail Alm *
DDB_THROUGH_FAULT_ALARM 399 SW PFSO event_AlarmLatched Through Fault Alarm Thru Fault Alm * * * * *
DDB_DLR_UC_SOLAR_RAD_ALARM 399 SW PFSO event_AlarmLatched DLR Input Solar Radiation Fail alarm Solar R Fail Alm *
DDB_CIRCUITRY_FLT_ALM 400 SW PFSO event_AlarmSelfReset Circuitry Fault Alarm Circuit Flt Alm * * * *
DDB_TOL_PRETRIP_ALARM 401 SW PFSO event_AlarmLatched Tol Pretrip Alm XThermPretrp Alm * * * * *
DDB_DIFF_CTS_INDICATION 402 SW PFSO event_AlarmSelfReset differential CTS Diff CTS Alarm * * * *
DDB_CONTROL_NO_CHECK_SYNC 403 SW PFSO event_AlarmLatched Manual close CB but do not satisfy CS condition Man No Checksync * * * * * * *
DDB_SYSTEM_SPLIT_ALARM 404 SW PFSO event_AlarmSelfReset System Split Alarm System Split Alm * * * * * * *
DDB_USER_ALARM_11 405 PSL PFSI event_AlarmLatched User Definable Alarm 11 (Manual Reset) MR User Alarm 11 * * * * * * *
DDB_USER_ALARM_10 406 PSL PFSI event_AlarmLatched User Definable Alarm 10 (Manual Reset) MR User Alarm 10 * * * * * * *
DDB_USER_ALARM_9 407 PSL PFSI event_AlarmLatched User Definable Alarm 9 (Manual Reset) MR User Alarm 9 * * * * * * *
DDB_USER_ALARM_8 408 PSL PFSI event_AlarmLatched User Definable Alarm 8 (Manual Reset) MR User Alarm 8 * * * * * * *
DDB_USER_ALARM_7 409 PSL PFSI event_AlarmLatched User Definable Alarm 7 (Manual Reset) MR User Alarm 7 * * * * * * *
DDB_USER_ALARM_6 410 PSL PFSI event_AlarmLatched User Definable Alarm 6 (Manual Reset) MR User Alarm 6 * * * * * * *
DDB_USER_ALARM_5 411 PSL PFSI event_AlarmLatched User Definable Alarm 5 (Manual Reset) MR User Alarm 5 * * * * * * *
DDB_USER_ALARM_4 412 PSL PFSI event_AlarmSelfReset User Definable Alarm 4 (Self Reset) SR User Alarm 4 * * * * * * *
DDB_USER_ALARM_3 413 PSL PFSI event_AlarmSelfReset User Definable Alarm 3 (Self Reset) SR User Alarm 3 * * * * * * *
DDB_USER_ALARM_2 414 PSL PFSI event_AlarmSelfReset User Definable Alarm 2 (Self Reset) SR User Alarm 2 * * * * * * *
DDB_USER_ALARM_1 415 PSL PFSI event_AlarmSelfReset User Definable Alarm 1 (Self Reset) SR User Alarm 1 * * * * * * *
DDB_BATTERY_FAIL_ALARM 416 SW PFSO NO_RESPONSE Battery Fail alarm indication Battery Fail * * * * * * *
DDB_FIELD_VOLTS_FAIL 417 SW PFSO NO_RESPONSE Field Voltage Failure Field Volts Fail * * * * * * *
DDB_INTERMICOM_FAIL_ALARM 418 SW PFSO NO_RESPONSE InterMiCOM Second rear comm card failure indication Rear Comm 2 Fail * * * * * * *
DDB_GOOSE_MISSING_IED_ALARM 419 SW PFSO NO_RESPONSE Enrolled GOOSE IED absent alarm indication GOOSE IED Absent * * * * * * *
DDB_ECARD_NOT_FITTED_ALARM 420 SW PFSO NO_RESPONSE Network Interface Card not fitted/failed alarm NIC Not Fitted * * * * * * *
DDB_NIC_NOT_RESPONDING_ALARM 421 SW PFSO NO_RESPONSE Network Interface Card not responding alarm NIC No Response * * * * * * *
DDB_NIC_FATAL_ERROR_ALARM 422 SW PFSO NO_RESPONSE Network Interface Card fatal error alarm indication NIC Fatal Error * * * * * * *
DDB_NIC_SOFTWARE_RELOAD_ALARM 423 SW PFSO NO_RESPONSE Network Interface Card software reload alarm NIC Soft. Reload * * * * * * *
DDB_INVALID_TCP_IP_CONFIG_ALARM 424 SW PFSO NO_RESPONSE Bad TCP/IP Configuration Alarm Bad TCP/IP Cfg. * * * * * * *
DDB_INVALID_OSI_CONFIG_ALARM 425 SW PFSO NO_RESPONSE Bad OSI Configuration Alarm Bad OSI Config. * * * * * * *
DDB_NIC_LINK_FAIL_ALARM 426 SW PFSO NO_RESPONSE Network Interface Card link fail alarm indication NIC Link Fail * * * * * * *
DDB_SW_MISMATCH_ALARM 427 SW PFSO NO_RESPONSE Main card/NIC software mismatch alarm indication NIC SW Mis-Match * * * * * * *
DDB_IP_ADDRESS_CONFLICT_ALARM 428 SW PFSO NO_RESPONSE IP address conflict alarm indication IP Addr Conflict * * * * * * *
DDB_INTERIN_LOOPBACK_ALARM 429 SW PFSO NO_RESPONSE InterMiCOM Loop-back alarm indication IM Loopback * * * * * * *
DDB_INTERIN_MSG_FAIL_ALARM 430 SW PFSO NO_RESPONSE InterMiCOM Message Fail alarm indication IM Message Fail * * * * * * *
DDB_INTERIN_DCD_FAIL_ALARM 431 SW PFSO NO_RESPONSE InterMiCOM DCD Fail alarm indication IM Data CD Fail * * * * * * *
DDB_INTERIN_CHAN_FAIL_ALARM 432 SW PFSO NO_RESPONSE InterMiCOM Channel Fail alarm indication IM Channel Fail * * * * * * *
DDB_UNUSED 433 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 434 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 435 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 436 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 437 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 438 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 439 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 440 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 441 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 442 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 443 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 444 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 445 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 446 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 447 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 448 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 449 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 450 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 451 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 452 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 453 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 454 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 455 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 456 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 457 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 458 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 459 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 460 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 461 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 462 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 81 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 463 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 464 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 465 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 466 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 467 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 468 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 469 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 470 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 471 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 472 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 473 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 474 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 475 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 476 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 477 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 478 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 479 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 480 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 481 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 482 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 483 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 484 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 485 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 486 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 487 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 488 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 489 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 490 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 491 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 492 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 493 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 494 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 495 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 496 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 497 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 498 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 499 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 500 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 501 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 502 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 503 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 504 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 505 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 506 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 507 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 508 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 509 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 510 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 511 SW UNUSED NO_RESPONSE Unused
DDB_GENDIFF_BLOCK 512 PSL PFSI NO_RESPONSE Block Generator Differential protection Gen Diff Block * * * *
DDB_BLK_XFORMER_DIFF 513 PSL PFSI NO_RESPONSE Block Xformer Differential protection Xform Diff Block * * * *
DDB_DIFF_INHIBIT_CTS 514 PSL PFSI event_Protection differential CTS Inhibit Diff CTS * * * *
DDB_UNUSED 515 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 516 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 517 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 518 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 519 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 520 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 521 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 522 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 523 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 524 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 525 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 526 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 527 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 528 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 529 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 82 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 530 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 531 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 532 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 533 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 534 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 535 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 536 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 537 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 538 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 539 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 540 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 541 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 542 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 543 SW UNUSED NO_RESPONSE Unused
DDB_EF1_1_TIMER_BLOCK 544 PSL PFSI NO_RESPONSE Block Earth Fault Stage 1 time delay IN>1 Timer Blk * * * * * * *
DDB_EF1_2_TIMER_BLOCK 545 PSL PFSI NO_RESPONSE Block Earth Fault Stage 2 time delay IN>2 Timer Blk * * * * * * *
DDB_EF1_3_TIMER_BLOCK 546 PSL PFSI NO_RESPONSE Block Earth Fault Stage 3 time delay IN>3 Timer Blk * *
DDB_EF1_4_TIMER_BLOCK 547 PSL PFSI NO_RESPONSE Block Earth Fault Stage 4 time delay IN>4 Timer Blk * *
DDB_SEF_1_TIMER_BLOCK 548 PSL PFSI NO_RESPONSE Block SEF Stage 1 time delay ISEF>1 Timer Blk * * * * * * *
DDB_SEF_2_TIMER_BLOCK 549 PSL PFSI NO_RESPONSE Block SEF Stage 2 time delay ISEF>2 Timer Blk * *
DDB_SEF_3_TIMER_BLOCK 550 PSL PFSI NO_RESPONSE Block SEF Stage 3 time delay ISEF>3 Timer Blk * *
DDB_SEF_4_TIMER_BLOCK 551 PSL PFSI NO_RESPONSE Block SEF Stage 4 time delay ISEF>4 Timer Blk * *
DDB_STEFI_OC_1_INHIBIT 552 PSL PFSI NO_RESPONSE Inhibit 64S Overcurrent Protection 64S I>1 Inhibit *
DDB_STEFI_UR_1_INHIBIT 553 PSL PFSI NO_RESPONSE Inhibit 64S Under Impedance Stage 1 64S R<1 Inhibit *
DDB_STEFI_UR_2_INHIBIT 554 PSL PFSI NO_RESPONSE Inhibit 64S Under Impedance Stage 2 64S R<2 Inhibit *
DDB_STEFI_FILTER_ON 555 PSL PFSI NO_RESPONSE Enable the 64S band pass filter permanently 64S Filter On *
DDB_64R_UR_1_INHIBIT 556 PSL PFSI NO_RESPONSE Inhibit 64R Under Impedance Stage 1 64R R<1 Inhibit * * * * *
DDB_64R_UR_2_INHIBIT 557 PSL PFSI NO_RESPONSE Inhibit 64R Under Impedance Stage 2 64R R<2 Inhibit * * * * *
DDB_UNUSED 558 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 559 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 560 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 561 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 562 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 563 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 564 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 565 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 566 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 567 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 568 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 569 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 570 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 571 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 572 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 573 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 574 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 575 SW UNUSED NO_RESPONSE Unused
DDB_POC_1_TIMER_BLOCK 576 PSL PFSI NO_RESPONSE Block Phase Overcurrent Stage 1 time delay I>1 Timer Block * * * * * * *
DDB_POC_2_TIMER_BLOCK 577 PSL PFSI NO_RESPONSE Block Phase Overcurrent Stage 2 time delay I>2 Timer Block * * * * * * *
DDB_POC_3_TIMER_BLOCK 578 PSL PFSI NO_RESPONSE Block Phase Overcurrent Stage 3 time delay I>3 Timer Block * * * * * * *
DDB_POC_4_TIMER_BLOCK 579 PSL PFSI NO_RESPONSE Block Phase Overcurrent Stage 4 time delay I>4 Timer Block * * * * * * *
DDB_UNUSED 580 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 581 SW UNUSED NO_RESPONSE Unused
DDB_NPSOC_INHIBIT 582 PSL PFSI NO_RESPONSE Inhibit NPS Overcurrent protection I2> Inhibit * * * * * * *
DDB_NPSOC_1_TIMER_BLOCK 583 PSL PFSI NO_RESPONSE Block NPS Overcurrent Stage 1 Timer I2>1 Timer Block * * * * * * *
DDB_NPSOC_2_TIMER_BLOCK 584 PSL PFSI NO_RESPONSE Block NPS Overcurrent Stage 2 Timer I2>2 Timer Block * * * * * * *
DDB_NPSOC_3_TIMER_BLOCK 585 PSL PFSI NO_RESPONSE Block NPS Overcurrent Stage 3 Timer I2>3 Timer Block * * * * * * *
DDB_NPSOC_4_TIMER_BLOCK 586 PSL PFSI NO_RESPONSE Block NPS Overcurrent Stage 4 Timer I2>4 Timer Block * * * * * * *
DDB_UNUSED 587 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 588 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 589 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 590 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 591 SW UNUSED NO_RESPONSE Unused
DDB_RESOV_1_TIMER_BLOCK 592 PSL PFSI NO_RESPONSE Block Residual Over Voltage Stage 1 time delay VN>1 Timer Blk * * * * * * *
DDB_RESOV_2_TIMER_BLOCK 593 PSL PFSI NO_RESPONSE Block Residual Over Voltage Stage 2 time delay VN>2 Timer Blk * * * * * * *
DDB_RESOV_3_TIMER_BLOCK 594 PSL PFSI NO_RESPONSE Block Residual Over Voltage Stage 3 Timer VN>3 Timer Block * * * * * * *
DDB_RESOV_4_TIMER_BLOCK 595 PSL PFSI NO_RESPONSE Block Residual Over Voltage Stage 4 Timer VN>4 Timer Block * * * * * * *
DDB_RESOV_5_TIMER_BLOCK 596 PSL PFSI NO_RESPONSE Block Residual Over Voltage Stage 5 Timer VN>5 Timer Block * *
470234511.xls
Relay Menu Database DDBSignals
Page 83 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_RESOV_6_TIMER_BLOCK 597 PSL PFSI NO_RESPONSE Block Residual Over Voltage Stage 6 Timer VN>6 Timer Block * *
DDB_POV_1_TIMER_BLOCK 598 PSL PFSI NO_RESPONSE Block Phase Over Voltage Stage 1 time delay V>1 Timer Block * * * * * * *
DDB_POV_2_TIMER_BLOCK 599 PSL PFSI NO_RESPONSE Block Phase Over Voltage Stage 2 time delay V>2 Timer Block * * * * * * *
DDB_NPSOV_1_ACCELERATE 600 PSL PFSI NO_RESPONSE Accelerate NPS Over Voltage Stage 1 Start V2>1 Accelerate * * * * * * *
DDB_PUV_1_TIMER_BLOCK 601 PSL PFSI NO_RESPONSE Block Phase Under Voltage Stage 1 time delay V<1 Timer Block * * * * * * *
DDB_PUV_2_TIMER_BLOCK 602 PSL PFSI NO_RESPONSE Block Phase Under Voltage Stage 2 time delay V<2 Timer Block * * * * * * *
DDB_UNUSED 603 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 604 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 605 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 606 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 607 SW UNUSED NO_RESPONSE Unused
DDB_VOLT_DEP_OC_TIMER_BLOCK 608 PSL PFSI NO_RESPONSE Voltage Dependant Overcurrent time delay VDepOC Timer Blk * * * * *
DDB_UNDERZ_TIMER_BLOCK 609 PSL PFSI NO_RESPONSE Under Impedance time delay UnderZ Timer Blk * * * * *
DDB_UNUSED 610 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 611 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 612 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 613 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 614 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 615 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 616 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 617 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 618 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 619 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 620 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 621 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 622 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 623 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 624 SW UNUSED NO_RESPONSE Unused
DDB_VPERHZ_TRIP1_INH 625 PSL PFSI NO_RESPONSE Inhibit Volts per Hz Stage 1 V/Hz>1 Inhibit * * * * *
DDB_UFREQ_1_TIMER_BLOCK 626 PSL PFSI NO_RESPONSE Block Under Frequency Stage 1 Timer F<1 Timer Block * * * * * * *
DDB_UFREQ_2_TIMER_BLOCK 627 PSL PFSI NO_RESPONSE Block Under Frequency Stage 2 Timer F<2 Timer Block * * * * * * *
DDB_UFREQ_3_TIMER_BLOCK 628 PSL PFSI NO_RESPONSE Block Under Frequency Stage 3 Timer F<3 Timer Block * * * * * * *
DDB_UFREQ_4_TIMER_BLOCK 629 PSL PFSI NO_RESPONSE Block Under Frequency Stage 4 Timer F<4 Timer Block * * * * * * *
DDB_OFREQ_1_TIMER_BLOCK 630 PSL PFSI NO_RESPONSE Block Over Frequency Stage 1 Timer F>1 Timer Block * * * * * * *
DDB_OFREQ_2_TIMER_BLOCK 631 PSL PFSI NO_RESPONSE Block Over Frequency Stage 2 Timer F>2 Timer Block * * * * * * *
DDB_TAF1_INHIBIT 632 PSL PFSI NO_RESPONSE Inhibit Turbine Abnormal Frequency Protection Turbine F Inh * * * * *
DDB_DFDT_INHIBIT 633 PSL PFSI NO_RESPONSE df/dt> Inhibit df/dt> Inhibit * * * * * * *
DDB_DFDT_1_TIMER_BLOCK 634 PSL PFSI NO_RESPONSE df/dt>1 Tmr Blk df/dt>1 Tmr Blk * * * * * * *
DDB_DFDT_2_TIMER_BLOCK 635 PSL PFSI NO_RESPONSE df/dt>2 Tmr Blk df/dt>2 Tmr Blk * * * * * * *
DDB_DFDT_3_TIMER_BLOCK 636 PSL PFSI NO_RESPONSE df/dt>3 Tmr Blk df/dt>3 Tmr Blk * * * * * * *
DDB_DFDT_4_TIMER_BLOCK 637 PSL PFSI NO_RESPONSE df/dt>4 Tmr Blk df/dt>4 Tmr Blk * * * * * * *
DDB_UNUSED 638 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 639 SW UNUSED NO_RESPONSE Unused
DDB_RESET_NPS_THERMAL 640 PSL PFSI NO_RESPONSE Reset NPS Thermal State Reset I2 Thermal * * * * *
DDB_RESET_GEN_THERMAL 641 PSL PFSI NO_RESPONSE Reset Thermal Overload State Reset GenThermal * * * * * * *
DDB_DLR_AMP_TRIP_1_INHIBIT 642 PSL PFSI NO_RESPONSE Inhibit DLR Stage 1 DLR I>1 Inhibit *
DDB_DLR_AMP_TRIP_2_INHIBIT 643 PSL PFSI NO_RESPONSE Inhibit DLR Stage 2 DLR I>2 Inhibit *
DDB_DLR_AMP_TRIP_3_INHIBIT 644 PSL PFSI NO_RESPONSE Inhibit DLR Stage 3 DLR I>3 Inhibit *
DDB_DLR_AMP_TRIP_4_INHIBIT 645 PSL PFSI NO_RESPONSE Inhibit DLR Stage 4 DLR I>4 Inhibit *
DDB_DLR_AMP_TRIP_5_INHIBIT 646 PSL PFSI NO_RESPONSE Inhibit DLR Stage 5 DLR I>5 Inhibit *
DDB_DLR_AMP_TRIP_6_INHIBIT 647 PSL PFSI NO_RESPONSE Inhibit DLR Stage 6 DLR I>6 Inhibit *
DDB_DLR_SCHEME_INHIBIT 648 PSL PFSI NO_RESPONSE Scheme Logic Inhibit DLR Scheme Inh *
DDB_RESET_XTHERMAL 649 PSL PFSI NO_RESPONSE Reset Xformer Thermal Overload State Reset XThermal * * * * *
DDB_XTHERMAL_AIRCOOL 650 PSL PFSI event_Protection Select forced air cooling Forced Air Cool * * * * *
DDB_XTHERMAL_OILCOOL 651 PSL PFSI event_Protection Select forced oil cooling Forced Oil Cool * * * * *
DDB_TFR_DE_ENERGISED 652 PSL PFSI NO_RESPONSE Xformer De-energised Status TFR De-energised * * * * *
DDB_UNUSED 653 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 654 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 655 SW UNUSED NO_RESPONSE Unused
DDB_CL_INPUT_1_BLOCK 656 PSL PFSI NO_RESPONSE Block Current Loop Input 1 protection CL Input 1 Blk * * * * * * *
DDB_CL_INPUT_2_BLOCK 657 PSL PFSI NO_RESPONSE Block Current Loop Input 2 protection CL Input 2 Blk * * * * * * *
DDB_CL_INPUT_3_BLOCK 658 PSL PFSI NO_RESPONSE Block Current Loop Input 3 protection CL Input 3 Blk * * * * * * *
DDB_CL_INPUT_4_BLOCK 659 PSL PFSI NO_RESPONSE Block Current Loop Input 4 protection CL Input 4 Blk * * * * * * *
DDB_UNUSED 660 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 661 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 662 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 663 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 84 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 664 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 665 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 666 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 667 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 668 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 669 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 670 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 671 SW UNUSED NO_RESPONSE Unused
DDB_FAULT_RECORDER_START 672 PSL FRT NO_RESPONSE Fault Record Trigger Input Fault REC TRIG * * * * * * *
DDB_UNUSED 673 SW UNUSED NO_RESPONSE Unused
DDB_ANY_TRIP 674 PSL PFSI event_Protection Any Trip Any Trip * * * * * * *
DDB_SG_SELECTOR_X1 675 PSL PFSI event_Protection Setting Group Selector x1 (bit 0) SG Select x1 * * * * * * *
DDB_SG_SELECTOR_1X 676 PSL PFSI event_Protection Setting Group Selector 1x (bit 1) SG Select 1x * * * * * * *
DDB_TEST_MODE 677 PSL PFSI NO_RESPONSE Initiate Test Mode Test Mode * * * * * * *
DDB_LOGIC_INPUT_TRIP 678 PSL PFSI NO_RESPONSE Logic Input Trip CB Init Trip CB * * * * * * *
DDB_LOGIC_INPUT_CLOSE 679 PSL PFSI NO_RESPONSE Logic Input Close CB Init Close CB * * * * * * *
DDB_EXTERNAL_TRIP_3PH 680 PSL PFSI NO_RESPONSE External Trip 3ph Ext. Trip 3ph * * * * * * *
DDB_CB_THREE_PHASE_52A 681 PSL PFSI NO_RESPONSE 52-A (3 phase) CB Aux 3ph(52-A) * * * * * * *
DDB_CB_THREE_PHASE_52B 682 PSL PFSI NO_RESPONSE 52-B (3 phase) CB Aux 3ph(52-B) * * * * * * *
DDB_CB_HEALTHY 683 PSL PFSI NO_RESPONSE CB Healthy CB Healthy * * * * * * *
DDB_VTS_MCB_OPTO 684 PSL PFSI NO_RESPONSE MCB/VTS opto MCB/VTS * * * * * * *
DDB_CS103_BLOCK 685 PSL PFSI event_Protection IEC60870-5-103 Monitor Blocking Monitor Blocked * * * * * * *
DDB_CS103_CMD_BLOCK 686 PSL PFSI event_Protection IEC60870-5-103 Command Blocking Command Blocked * * * * * * *
DDB_TIME_SYNCH 687 PSL PFSI event_TimeSync Time synchronise to nearest minute on 0-1 change Time Synch * * * * * * *
DDB_RESET_CB_CLOSE_DELAY 688 PSL PFSI NO_RESPONSE Reset Manual CB Close Time Delay Reset Close Dly * * * * * * *
DDB_RESET_RELAYS_LEDS 689 PSL PFSI event_OptoResetInd Reset Latched Relays & LED’s Reset Relays/LED * * * * * * *
DDB_RESET_LOCKOUT 690 PSL PFSI NO_RESPONSE Reset Lockout Opto Input Reset Lockout * * * * * * *
DDB_RESET_ALL_VALUES 691 PSL PFSI NO_RESPONSE Reset CB Maintenance Values Reset All Values * * * * * * *
DDB_RP1_READ_ONLY 692 PSL PFSI ddbRF_ReadOnly_RP1 Remote Read Only 1 DDB RP1 Read Only * * * * * * *
DDB_RP2_READ_ONLY 693 PSL PFSI ddbRF_ReadOnly_RP2 Remote Read Only 2 DDB RP2 Read Only * * * * * * *
DDB_NIC_READ_ONLY 694 PSL PFSI ddbRF_ReadOnly_NIC Remote Read Only NIC DDB NIC Read Only * * * * * * *
DDB_MONITOR_BLOCKING 695 PSL PFSI ddbRF_103MonitorBlck Monitor Block 103 MonitorBlock * * * * * * *
DDB_COMMAND_BLOCKING 696 PSL PFSI ddbRF_103CommandBlck Command Block 103 CommandBlock * * * * * * *
In the previous version, these DDBs are exist and have related DNP3 address number.
However in 36 version these DDBs are not used.
DDB_USER_ALARM_16 697 PSL PFSI NO_RESPONSE If these DDBs are removed in 36 version, then most of the address numbers in 'DNP3 Object01' will be changed. Not Used 1 * * * * * * *
DDB_USER_ALARM_15 698 PSL PFSI NO_RESPONSE Not Used 2 * * * * * * *
DDB_USER_ALARM_14 699 PSL PFSI NO_RESPONSE Not Used 3 * * * * * * *
DDB_USER_ALARM_13 700 PSL PFSI NO_RESPONSE Not Used 4 * * * * * * *
DDB_USER_ALARM_12 701 PSL PFSI NO_RESPONSE So in order to keep the communication application of version 36 compatible with the previous version, Not Used 5 * * * * * * *
DDB_DFDT_TRIP 702 SW PFSO NO_RESPONSE Not Used 6 * * * * * * *
DDB_DFDT_START 703 SW PFSO NO_RESPONSE Not Used 7 * * * * * * *
DDB_UNUSED 704 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 705 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 706 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 707 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 708 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 709 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 710 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 711 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 712 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 713 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 714 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 715 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 716 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 717 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 718 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 719 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 720 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 721 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 722 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 723 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 724 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 725 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 726 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 727 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 728 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 85 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 729 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 730 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 731 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 732 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 733 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 734 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 735 SW UNUSED NO_RESPONSE Unused
DDB_GENDIFF_3PH_TRIP 736 SW PFSO event_Protection Generator Differential Trip 3ph Gen Diff Trip * * * *
DDB_GENDIFF_PH_A_TRIP 737 SW PFSO event_Protection Generator Differential Trip A Gen Diff Trip A * * * *
DDB_GENDIFF_PH_B_TRIP 738 SW PFSO event_Protection Generator Differential Trip B Gen Diff Trip B * * * *
DDB_GENDIFF_PH_C_TRIP 739 SW PFSO event_Protection Generator Differential Trip C Gen Diff Trip C * * * *
DDB_XFORMER_DIFF_3PH_TRIP 740 SW PFSO event_Protection Xformer Differential Trip 3ph Xform Dif Trp * * * *
DDB_XFORMER_DIFF_PH_A_TRIP 741 SW PFSO event_Protection Xformer Differential Trip A Xform Dif Trip A * * * *
DDB_XFORMER_DIFF_PH_B_TRIP 742 SW PFSO event_Protection Xformer Differential Trip B Xform Dif Trip B * * * *
DDB_XFORMER_DIFF_PH_C_TRIP 743 SW PFSO event_Protection Xformer Differential Trip C Xform Dif Trip C * * * *
DDB_XFORMER_DIFF_BIAS_TRIP_A 744 SW PFSO event_Protection Xformer Differential Low Set Trip A Xform Bias Trp A * * * *
DDB_XFORMER_DIFF_BIAS_TRIP_B 745 SW PFSO event_Protection Xformer Differential Low Set Trip B Xform Bias Trp B * * * *
DDB_XFORMER_DIFF_BIAS_TRIP_C 746 SW PFSO event_Protection Xformer Differential Low Set Trip C Xform Bias Trp C * * * *
DDB_XFORMER_DIFF_HS1_TRIP_A 747 SW PFSO event_Protection Xformer Differential HS1 Trip A Xform HS1 Trip A * * * *
DDB_XFORMER_DIFF_HS1_TRIP_B 748 SW PFSO event_Protection Xformer Differential HS1Trip B Xform HS1 Trip B * * * *
DDB_XFORMER_DIFF_HS1_TRIP_C 749 SW PFSO event_Protection Xformer Differential HS1Trip C Xform HS1 Trip C * * * *
DDB_XFORMER_DIFF_HS2_TRIP_A 750 SW PFSO event_Protection Xformer Differential HS2 Trip A Xform HS2 Trip A * * * *
DDB_XFORMER_DIFF_HS2_TRIP_B 751 SW PFSO event_Protection Xformer Differential HS2Trip B Xform HS2 Trip B * * * *
DDB_XFORMER_DIFF_HS2_TRIP_C 752 SW PFSO event_Protection Xformer Differential HS2Trip C Xform HS2 Trip C * * * *
DDB_UNUSED 753 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 754 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 755 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 756 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 757 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 758 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 759 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 760 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 761 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 762 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 763 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 764 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 765 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 766 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 767 SW UNUSED NO_RESPONSE Unused
DDB_EF1_1_TRIP 768 SW PFSO event_Protection 1st Stage EF Trip IN>1 Trip * * * * * * *
DDB_EF1_2_TRIP 769 SW PFSO event_Protection 2nd Stage EF Trip IN>2 Trip * * * * * * *
DDB_EF1_3_TRIP 770 SW PFSO event_Protection 3rd Stage EF Trip IN>3 Trip * *
DDB_EF1_4_TRIP 771 SW PFSO event_Protection 4th Stage EF Trip IN>4 Trip * *
DDB_REF_TRIP 772 SW PFSO event_Protection REF Trip IREF> Trip * * * * * * *
DDB_SEF_1_TRIP 773 SW PFSO event_Protection 1st Stage SEF Trip ISEF>1 Trip * * * * * * *
DDB_SEF_2_TRIP 774 SW PFSO event_Protection 2nd Stage SEF Trip ISEF>2 Trip * *
DDB_SEF_3_TRIP 775 SW PFSO event_Protection 3rd Stage SEF Trip ISEF>3 Trip * *
DDB_SEF_4_TRIP 776 SW PFSO event_Protection 4th Stage SEF Trip ISEF>4 Trip * *
DDB_V3H_TRIP 777 SW PFSO event_Protection 100% Stator Earth Fault (3rd harmonic) Trip 100%StEF3H Trip * * *
DDB_STEFI_OC_1_TRIP 778 SW PFSO event_Protection 64S 100% Stator Earth Fault Overcurrent Trip 64S I>1 Trip *
DDB_STEFI_UR_2_TRIP 779 SW PFSO event_Protection 64S 100% St EF Under Resistance Stage 2 Trip 64S R<2 Trip *
DDB_64R_UR_2_TRIP 780 SW PFSO event_Protection 64R Rotor Earth Fault Under Resistance Stage 2 Trip 64R R<2 Trip * * * * *
DDB_UNUSED 781 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 782 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 783 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 784 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 785 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 786 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 787 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 788 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 789 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 790 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 791 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 792 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 793 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 794 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 795 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 86 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 796 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 797 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 798 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 799 SW UNUSED NO_RESPONSE Unused
DDB_POC_1_3PH_TRIP 800 SW PFSO event_Protection 1st Stage O/C Trip 3ph I>1 Trip * * * * * * *
DDB_POC_1_PH_A_TRIP 801 SW PFSO event_Protection 1st Stage O/C Trip A I>1 Trip A * * * * * * *
DDB_POC_1_PH_B_TRIP 802 SW PFSO event_Protection 1st Stage O/C Trip B I>1 Trip B * * * * * * *
DDB_POC_1_PH_C_TRIP 803 SW PFSO event_Protection 1st Stage O/C Trip C I>1 Trip C * * * * * * *
DDB_POC_2_3PH_TRIP 804 SW PFSO event_Protection 2nd Stage O/C Trip 3ph I>2 Trip * * * * * * *
DDB_POC_2_PH_A_TRIP 805 SW PFSO event_Protection 2nd Stage O/C Trip A I>2 Trip A * * * * * * *
DDB_POC_2_PH_B_TRIP 806 SW PFSO event_Protection 2nd Stage O/C Trip B I>2 Trip B * * * * * * *
DDB_POC_2_PH_C_TRIP 807 SW PFSO event_Protection 2nd Stage O/C Trip C I>2 Trip C * * * * * * *
DDB_POC_3_3PH_TRIP 808 SW PFSO event_Protection 3rd Stage O/C Trip 3ph I>3 Trip * * * * * * *
DDB_POC_3_PH_A_TRIP 809 SW PFSO event_Protection 3rd Stage O/C Trip A I>3 Trip A * * * * * * *
DDB_POC_3_PH_B_TRIP 810 SW PFSO event_Protection 3rd Stage O/C Trip B I>3 Trip B * * * * * * *
DDB_POC_3_PH_C_TRIP 811 SW PFSO event_Protection 3rd Stage O/C Trip C I>3 Trip C * * * * * * *
DDB_POC_4_3PH_TRIP 812 SW PFSO event_Protection 4th Stage O/C Trip 3ph I>4 Trip * * * * * * *
DDB_POC_4_PH_A_TRIP 813 SW PFSO event_Protection 4th Stage O/C Trip A I>4 Trip A * * * * * * *
DDB_POC_4_PH_B_TRIP 814 SW PFSO event_Protection 4th Stage O/C Trip B I>4 Trip B * * * * * * *
DDB_POC_4_PH_C_TRIP 815 SW PFSO event_Protection 4th Stage O/C Trip C I>4 Trip C * * * * * * *
DDB_UNUSED 816 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 817 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 818 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 819 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 820 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 821 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 822 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 823 SW UNUSED NO_RESPONSE Unused
DDB_NPSOC_1_TRIP 824 SW PFSO event_Protection NPS Overcurrent Stage 1 Trip I2>1 Trip * * * * * * *
DDB_NPSOC_2_TRIP 825 SW PFSO event_Protection NPS Overcurrent Stage 2 Trip I2>2 Trip * * * * * * *
DDB_NPSOC_3_TRIP 826 SW PFSO event_Protection NPS Overcurrent Stage 3 Trip I2>3 Trip * * * * * * *
DDB_NPSOC_4_TRIP 827 SW PFSO event_Protection NPS Overcurrent Stage 4 Trip I2>4 Trip * * * * * * *
DDB_CBF1_TRIP_3PH 828 SW PFSO event_Protection tBF1 Trip 3ph Bfail1 Trip 3ph * * * * * * *
DDB_CBF2_TRIP_3PH 829 SW PFSO event_Protection tBF2 Trip 3ph Bfail2 Trip 3ph * * * * * * *
DDB_UNUSED 830 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 831 SW UNUSED NO_RESPONSE Unused
DDB_RESOV_1_TRIP 832 SW PFSO event_Protection 1st Stage Residual O/V Trip VN>1 Trip * * * * * * *
DDB_RESOV_2_TRIP 833 SW PFSO event_Protection 2nd Stage Residual O/V Trip VN>2 Trip * * * * * * *
DDB_RESOV_3_TRIP 834 SW PFSO event_Protection Residual O/V Stage 3 Trip VN>3 Trip * * * * * * *
DDB_RESOV_4_TRIP 835 SW PFSO event_Protection Residual O/V Stage 4 Trip VN>4 Trip * * * * * * *
DDB_RESOV_5_TRIP 836 SW PFSO event_Protection Residual O/V Stage 5 Trip VN>5 Trip * *
DDB_RESOV_6_TRIP 837 SW PFSO event_Protection Residual O/V Stage 6 Trip VN>6 Trip * *
DDB_POV_1_3PH_TRIP 838 SW PFSO event_Protection 1st Stage Phase O/V Trip 3ph V>1 Trip * * * * * * *
DDB_POV_1_PH_A_TRIP 839 SW PFSO event_Protection 1st Stage Phase O/V Trip A/AB V>1 Trip A/AB * * * * * * *
DDB_POV_1_PH_B_TRIP 840 SW PFSO event_Protection 1st Stage Phase O/V Trip B/BC V>1 Trip B/BC * * * * * * *
DDB_POV_1_PH_C_TRIP 841 SW PFSO event_Protection 1st Stage Phase O/V Trip C/CA V>1 Trip C/CA * * * * * * *
DDB_POV_2_3PH_TRIP 842 SW PFSO event_Protection 2nd Stage Phase O/V Trip 3ph V>2 Trip * * * * * * *
DDB_POV_2_PH_A_TRIP 843 SW PFSO event_Protection 2nd Stage Phase O/V Trip A/AB V>2 Trip A/AB * * * * * * *
DDB_POV_2_PH_B_TRIP 844 SW PFSO event_Protection 2nd Stage Phase O/V Trip B/BC V>2 Trip B/BC * * * * * * *
DDB_POV_2_PH_C_TRIP 845 SW PFSO event_Protection 2nd Stage Phase O/V Trip C/CA V>2 Trip C/CA * * * * * * *
DDB_NPSOV_1_TRIP 846 SW PFSO event_Protection NPS Over Voltage Stage 1 Trip V2>1 Trip * * * * * * *
DDB_PUV_1_3PH_TRIP 847 SW PFSO event_Protection 1st Stage Phase U/V Trip 3ph V<1 Trip * * * * * * *
DDB_PUV_1_PH_A_TRIP 848 SW PFSO event_Protection 1st Stage Phase U/V Trip A/AB V<1 Trip A/AB * * * * * * *
DDB_PUV_1_PH_B_TRIP 849 SW PFSO event_Protection 1st Stage Phase U/V Trip B/BC V<1 Trip B/BC * * * * * * *
DDB_PUV_1_PH_C_TRIP 850 SW PFSO event_Protection 1st Stage Phase U/V Trip C/CA V<1 Trip C/CA * * * * * * *
DDB_PUV_2_3PH_TRIP 851 SW PFSO event_Protection 2nd Stage Phase U/V Trip 3ph V<2 Trip * * * * * * *
DDB_PUV_2_PH_A_TRIP 852 SW PFSO event_Protection 2nd Stage Phase U/V Trip A/AB V<2 Trip A/AB * * * * * * *
DDB_PUV_2_PH_B_TRIP 853 SW PFSO event_Protection 2nd Stage Phase U/V Trip B/BC V<2 Trip B/BC * * * * * * *
DDB_PUV_2_PH_C_TRIP 854 SW PFSO event_Protection 2nd Stage Phase U/V Trip C/CA V<2 Trip C/CA * * * * * * *
DDB_UNUSED 855 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 856 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 857 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 858 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 859 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 860 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 861 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 862 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 87 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 863 SW UNUSED NO_RESPONSE Unused
DDB_FIELDF_1_TRIP 864 SW PFSO event_Protection Field Failure Stage 1 Trip Field Fail1 Trip * * * * *
DDB_FIELDF_2_TRIP 865 SW PFSO event_Protection Field Failure Stage 2 Trip Field Fail2 Trip * * * * *
DDB_POLESLZ_ZONE1_TRIP 866 SW PFSO event_Protection Pole Slip (Impedance) Zone1 Trip PSlipz Z1 Trip * * *
DDB_POLESLZ_ZONE2_TRIP 867 SW PFSO event_Protection Pole Slip (Impedance) Zone2 Trip PSlipz Z2 Trip * * *
DDB_VOLT_DEP_OC_3PH_TRIP 868 SW PFSO event_Protection Voltage Dependant Overcurrent Trip 3ph V Dep OC Trip * * * * *
DDB_VOLT_DEP_OC_PH_A_TRIP 869 SW PFSO event_Protection Voltage Dependant Overcurrent Trip A V Dep OC Trip A * * * * *
DDB_VOLT_DEP_OC_PH_B_TRIP 870 SW PFSO event_Protection Voltage Dependant Overcurrent Trip B V Dep OC Trip B * * * * *
DDB_VOLT_DEP_OC_PH_C_TRIP 871 SW PFSO event_Protection Voltage Dependant Overcurrent Trip C V Dep OC Trip C * * * * *
DDB_UNDERZ_1_3PH_TRIP 872 SW PFSO event_Protection Under Impedance 3Phase Stage 1 Trip Z<1 Trip * * * * *
DDB_UNDERZ_1_PH_A_TRIP 873 SW PFSO event_Protection Under Impedance Phase A Stage 1 Trip Z<1 Trip A * * * * *
DDB_UNDERZ_1_PH_B_TRIP 874 SW PFSO event_Protection Under Impedance Phase B Stage 1 Trip Z<1 Trip B * * * * *
DDB_UNDERZ_1_PH_C_TRIP 875 SW PFSO event_Protection Under Impedance Phase C Stage 1 Trip Z<1 Trip C * * * * *
DDB_UNDERZ_2_3PH_TRIP 876 SW PFSO event_Protection Under Impedance 3Phase Stage 2 Trip Z<2 Trip * * * * *
DDB_UNDERZ_2_PH_A_TRIP 877 SW PFSO event_Protection Under Impedance Phase A Stage 2 Trip Z<2 Trip A * * * * *
DDB_UNDERZ_2_PH_B_TRIP 878 SW PFSO event_Protection Under Impedance Phase B Stage 2 Trip Z<2 Trip B * * * * *
DDB_UNDERZ_2_PH_C_TRIP 879 SW PFSO event_Protection Under Impedance Phase C Stage 2 Trip Z<2 Trip C * * * * *
DDB_DEADMACH_TRIP 880 SW PFSO event_Protection Dead Machine Protection Trip DeadMachine Trip * * *
DDB_PWRNPS_1_TRIP 881 SW PFSO event_Protection NPS Overpower Stage 1 trip S2>1 Trip * * * * *
DDB_POWER_1_TRIP 882 SW PFSO event_Protection Power Stage 1 Trip Power1 Trip * * * * * * *
DDB_POWER_2_TRIP 883 SW PFSO event_Protection Power Stage 2 Trip Power2 Trip * * * * * * *
DDB_SPOWER_1_TRIP 884 SW PFSO event_Protection Sensitive A Phase Power Stage 1 Trip SPower1 Trip * * * * * * *
DDB_SPOWER_2_TRIP 885 SW PFSO event_Protection Sensitive A Phase Power Stage 2 Trip SPower2 Trip * * * * * * *
DDB_UNUSED 886 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 887 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 888 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 889 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 890 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 891 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 892 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 893 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 894 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 895 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 896 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 897 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 898 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 899 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 900 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 901 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 902 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 903 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 904 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 905 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 906 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 907 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 908 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 909 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 910 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 911 SW UNUSED NO_RESPONSE Unused
DDB_VPERHZ_TRIP 912 SW PFSO event_Protection 1st Stage Volts per Hz Trip V/Hz>1 Trip * * * * *
DDB_VPERHZ_TRIP2 913 SW PFSO event_Protection Volts per Hz Stage 2 Trip V/Hz>2 Trip * * * * *
DDB_VPERHZ_TRIP3 914 SW PFSO event_Protection Volts per Hz Stage 3 Trip V/Hz>3 Trip * * * * *
DDB_VPERHZ_TRIP4 915 SW PFSO event_Protection Volts per Hz Stage 4 Trip V/Hz>4 Trip * * * * *
DDB_UFREQ_1_TRIP 916 SW PFSO event_Protection Under Frequency Stage 1 Trip F<1 Trip * * * * * * *
DDB_UFREQ_2_TRIP 917 SW PFSO event_Protection Under Frequency Stage 2 Trip F<2 Trip * * * * * * *
DDB_UFREQ_3_TRIP 918 SW PFSO event_Protection Under Frequency Stage 3 Trip F<3 Trip * * * * * * *
DDB_UFREQ_4_TRIP 919 SW PFSO event_Protection Under Frequency Stage 4 Trip F<4 Trip * * * * * * *
DDB_OFREQ_1_TRIP 920 SW PFSO event_Protection Over Frequency Stage 1 Trip F>1 Trip * * * * * * *
DDB_OFREQ_2_TRIP 921 SW PFSO event_Protection Over Frequency Stage 2 Trip F>2 Trip * * * * * * *
DDB_TAF1_TRIP1 922 SW PFSO event_Protection Turbine Abnormal Frequency Band 1 Trip Freq Band1 Trip * * * * *
DDB_TAF1_TRIP2 923 SW PFSO event_Protection Turbine Abnormal Frequency Band 2 Trip Freq Band2 Trip * * * * *
DDB_TAF1_TRIP3 924 SW PFSO event_Protection Turbine Abnormal Frequency Band 3 Trip Freq Band3 Trip * * * * *
DDB_TAF1_TRIP4 925 SW PFSO event_Protection Turbine Abnormal Frequency Band 4 Trip Freq Band4 Trip * * * * *
DDB_TAF1_TRIP5 926 SW PFSO event_Protection Turbine Abnormal Frequency Band 5 Trip Freq Band5 Trip * * * * *
DDB_TAF1_TRIP6 927 SW PFSO event_Protection Turbine Abnormal Frequency Band 6 Trip Freq Band6 Trip * * * * *
DDB_DFDT_1_TRIP 928 SW PFSO event_Protection df/dt>1 Trip df/dt>1 Trip * * * * * * *
DDB_DFDT_2_TRIP 929 SW PFSO event_Protection df/dt>2 Trip df/dt>2 Trip * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 88 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_DFDT_3_TRIP 930 SW PFSO event_Protection df/dt>3 Trip df/dt>3 Trip * * * * * * *
DDB_DFDT_4_TRIP 931 SW PFSO event_Protection df/dt>4 Trip df/dt>4 Trip * * * * * * *
DDB_UNUSED 932 SW UNUSED NO_RESPONSE Unused
DDB_VSHIFT_TRIP 933 SW PFSO event_Protection Voltage Vector Shift Trip V Shift Trip * *
DDB_UNUSED 934 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 935 SW UNUSED NO_RESPONSE Unused
DDB_DFDT_1_UF 936 SW PFSO event_Protection Rate Of Change Of Frequency Stage 1 Under Frequency df/dt>1 Under F * * * * * * *
DDB_DFDT_1_OF 937 SW PFSO event_Protection Rate Of Change Of Frequency Stage 1 Over Frequency df/dt>1 Over F * * * * * * *
DDB_UNUSED 938 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 939 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 940 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 941 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 942 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 943 SW UNUSED NO_RESPONSE Unused
DDB_NPS_TRIP 944 SW PFSO event_Protection Negative Phase Sequence Thermal Trip NPS Thermal Trip * * * * *
DDB_GEN_THERMAL_TRIP 945 SW PFSO event_Protection Thermal Overload Trip Gen Thermal Trip * * * * * * *
DDB_XFORMER_HOT_SPOT_1_TRIP 946 SW PFSO event_Protection Hot Spot>1 Trip Hot Spot>1 Trip * * * * *
DDB_XFORMER_HOT_SPOT_2_TRIP 947 SW PFSO event_Protection Hot Spot>2 Trip Hot Spot>2 Trip * * * * *
DDB_XFORMER_HOT_SPOT_3_TRIP 948 SW PFSO event_Protection Hot Spot>3 Trip Hot Spot>3 Trip * * * * *
DDB_XFORMER_TOP_OIL_1_TRIP 949 SW PFSO event_Protection Top Oil>1 Trip Top Oil>1 Trip * * * * *
DDB_XFORMER_TOP_OIL_2_TRIP 950 SW PFSO event_Protection Top Oil>2 Trip Top Oil>2 Trip * * * * *
DDB_XFORMER_TOP_OIL_3_TRIP 951 SW PFSO event_Protection Top Oil>3 Trip Top Oil>3 Trip * * * * *
DDB_DLR_AMP_1_TRIP 952 SW PFSO event_Protection DLR Ampacity prot. stage 1 trip DLR I>1 Trip *
DDB_DLR_AMP_2_TRIP 953 SW PFSO event_Protection DLR Ampacity prot. stage 2 trip DLR I>2 Trip *
DDB_DLR_AMP_3_TRIP 954 SW PFSO event_Protection DLR Ampacity prot. stage 3 trip DLR I>3 Trip *
DDB_DLR_AMP_4_TRIP 955 SW PFSO event_Protection DLR Ampacity prot. stage 4 trip DLR I>4 Trip *
DDB_DLR_AMP_5_TRIP 956 SW PFSO event_Protection DLR Ampacity prot. stage 5 trip DLR I>5 Trip *
DDB_DLR_AMP_6_TRIP 957 SW PFSO event_Protection DLR Ampacity prot. stage 6 trip DLR I>6 Trip *
DDB_UNUSED 958 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 959 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 960 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 961 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 962 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 963 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 964 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 965 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 966 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 967 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 968 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 969 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 970 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 971 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 972 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 973 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 974 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 975 SW UNUSED NO_RESPONSE Unused
DDB_RTD_1_TRIP 976 SW PFSO event_Protection RTD 1 Trip RTD 1 Trip * * * * *
DDB_RTD_2_TRIP 977 SW PFSO event_Protection RTD 2 Trip RTD 2 Trip * * * * *
DDB_RTD_3_TRIP 978 SW PFSO event_Protection RTD 3 Trip RTD 3 Trip * * * * *
DDB_RTD_4_TRIP 979 SW PFSO event_Protection RTD 4 Trip RTD 4 Trip * * * * *
DDB_RTD_5_TRIP 980 SW PFSO event_Protection RTD 5 Trip RTD 5 Trip * * * * *
DDB_RTD_6_TRIP 981 SW PFSO event_Protection RTD 6 Trip RTD 6 Trip * * * * *
DDB_RTD_7_TRIP 982 SW PFSO event_Protection RTD 7 Trip RTD 7 Trip * * * * *
DDB_RTD_8_TRIP 983 SW PFSO event_Protection RTD 8 Trip RTD 8 Trip * * * * *
DDB_RTD_9_TRIP 984 SW PFSO event_Protection RTD 9 Trip RTD 9 Trip * * * * *
DDB_RTD_10_TRIP 985 SW PFSO event_Protection RTD 10 Trip RTD 10 Trip * * * * *
DDB_ANY_RTD_TRIP 986 FL PFSO event_Protection Any RTD Trip Any RTD Trip * * * * *
DDB_CL_INPUT_1_TRIP 987 SW PFSO event_Protection Current Loop Input 1 Trip CL Input 1 Trip * * * * * * *
DDB_CL_INPUT_2_TRIP 988 SW PFSO event_Protection Current Loop Input 2 Trip CL Input 2 Trip * * * * * * *
DDB_CL_INPUT_3_TRIP 989 SW PFSO event_Protection Current Loop Input 3 Trip CL Input 3 Trip * * * * * * *
DDB_CL_INPUT_4_TRIP 990 SW PFSO event_Protection Current Loop Input 4 Trip CL Input 4 Trip * * * * * * *
DDB_UNUSED 991 SW UNUSED NO_RESPONSE Unused
DDB_ANY_START 992 FL PFSO event_FAN_Protection Any Start Any Start * * * * * * *
DDB_XFORMER_DIFF_BIAS_STARTA 993 SW PFSO event_Protection Xformer Differential Start A Xform Bias StrtA * * * *
DDB_XFORMER_DIFF_BIAS_STARTB 994 SW PFSO event_Protection Xformer Differential Start B Xform Bias StrtB * * * *
DDB_XFORMER_DIFF_BIAS_STARTC 995 SW PFSO event_Protection Xformer Differential Start C Xform Bias StrtC * * * *
DDB_UNUSED 996 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 89 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 997 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 998 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 999 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1000 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1001 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1002 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1003 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1004 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1005 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1006 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1007 SW UNUSED NO_RESPONSE Unused
DDB_EF1_1_START 1008 SW PFSO event_Protection 1st Stage EF Start IN>1 Start * * * * * * *
DDB_EF1_2_START 1009 SW PFSO event_Protection 2nd Stage EF Start IN>2 Start * * * * * * *
DDB_EF1_3_START 1010 SW PFSO event_Protection 3rd Stage EF Start IN>3 Start * *
DDB_EF1_4_START 1011 SW PFSO event_Protection 4th Stage EF Start IN>4 Start * *
DDB_SEF_1_START 1012 SW PFSO event_Protection 1st Stage SEF Start ISEF>1 Start * * * * * * *
DDB_SEF_2_START 1013 SW PFSO event_Protection 2nd Stage SEF Start ISEF>2 Start * *
DDB_SEF_3_START 1014 SW PFSO event_Protection 3rd Stage SEF Start ISEF>3 Start * *
DDB_SEF_4_START 1015 SW PFSO event_Protection 4th Stage SEF Start ISEF>4 Start * *
DDB_V3H_START 1016 SW PFSO event_Protection 100% Stator Earth Fault (3rd harmonic) Start 100%StEF3H Start * * *
DDB_STEFI_FAIL_I_START 1017 SW PFSO event_Protection 64S 100% Stator Earth Fault Undercurrent Start 64S I< Start *
DDB_STEFI_FAIL_V_START 1018 SW PFSO event_Protection 64S 100% Stator Earth Fault Undervoltage Start 64S V< Start *
DDB_STEFI_OC_1_START 1019 SW PFSO event_Protection 64S 100% Stator Earth Fault Overcurrent Start 64S I>1 Start *
DDB_STEFI_UR_1_START 1020 SW PFSO event_Protection 64S 100% St EF Under Resistance Stg 1 Alm Start 64S Start R<1Alm *
DDB_STEFI_UR_2_START 1021 SW PFSO event_Protection 64S 100% St EF Under Resistance Stg 2 Trip Start 64S R<2 Start *
DDB_64R_UR_1_START 1022 SW PFSO event_Protection 64R Rotor EF Under Resistance Stg 1 Alm Start 64R Start R<1Alm * * * * *
DDB_64R_UR_2_START 1023 SW PFSO event_Protection 64R Rotor EF Under Resistance Stg 2 Trip Start 64R R<2 Start * * * * *
DDB_UNUSED 1024 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1025 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1026 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1027 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1028 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1029 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1030 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1031 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1032 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1033 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1034 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1035 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1036 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1037 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1038 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1039 SW UNUSED NO_RESPONSE Unused
DDB_POC_1_3PH_START 1040 SW PFSO event_Protection 1st Stage O/C Start 3ph I>1 Start * * * * * * *
DDB_POC_1_PH_A_START 1041 SW PFSO event_Protection 1st Stage O/C Start A I>1 Start A * * * * * * *
DDB_POC_1_PH_B_START 1042 SW PFSO event_Protection 1st Stage O/C Start B I>1 Start B * * * * * * *
DDB_POC_1_PH_C_START 1043 SW PFSO event_Protection 1st Stage O/C Start C I>1 Start C * * * * * * *
DDB_POC_2_3PH_START 1044 SW PFSO event_Protection 2nd Stage O/C Start 3ph I>2 Start * * * * * * *
DDB_POC_2_PH_A_START 1045 SW PFSO event_Protection 2nd Stage O/C Start A I>2 Start A * * * * * * *
DDB_POC_2_PH_B_START 1046 SW PFSO event_Protection 2nd Stage O/C Start B I>2 Start B * * * * * * *
DDB_POC_2_PH_C_START 1047 SW PFSO event_Protection 2nd Stage O/C Start C I>2 Start C * * * * * * *
DDB_POC_3_3PH_START 1048 SW PFSO event_Protection 3rd Stage O/C Start 3ph I>3 Start * * * * * * *
DDB_POC_3_PH_A_START 1049 SW PFSO event_Protection 3rd Stage O/C Start A I>3 Start A * * * * * * *
DDB_POC_3_PH_B_START 1050 SW PFSO event_Protection 3rd Stage O/C Start B I>3 Start B * * * * * * *
DDB_POC_3_PH_C_START 1051 SW PFSO event_Protection 3rd Stage O/C Start C I>3 Start C * * * * * * *
DDB_POC_4_3PH_START 1052 SW PFSO event_Protection 4th Stage O/C Start 3ph I>4 Start * * * * * * *
DDB_POC_4_PH_A_START 1053 SW PFSO event_Protection 4th Stage O/C Start A I>4 Start A * * * * * * *
DDB_POC_4_PH_B_START 1054 SW PFSO event_Protection 4th Stage O/C Start B I>4 Start B * * * * * * *
DDB_POC_4_PH_C_START 1055 SW PFSO event_Protection 4th Stage O/C Start C I>4 Start C * * * * * * *
DDB_UNUSED 1056 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1057 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1058 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1059 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1060 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1061 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1062 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1063 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 90 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_NPSOC_1_START 1064 SW PFSO event_Protection NPS Overcurrent Stage 1 Start I2>1 Start * * * * * * *
DDB_NPSOC_2_START 1065 SW PFSO event_Protection NPS Overcurrent Stage 2 Start I2>2 Start * * * * * * *
DDB_NPSOC_3_START 1066 SW PFSO event_Protection NPS Overcurrent Stage 3 Start I2>3 Start * * * * * * *
DDB_NPSOC_4_START 1067 SW PFSO event_Protection NPS Overcurrent Stage 4 Start I2>4 Start * * * * * * *
DDB_PHASE_A_UNDERCURRENT 1068 SW PFSO NO_RESPONSE Fast under current: Phase A IA< Start * * * * * * *
DDB_PHASE_B_UNDERCURRENT 1069 SW PFSO NO_RESPONSE Fast under current: Phase B IB< Start * * * * * * *
DDB_PHASE_C_UNDERCURRENT 1070 SW PFSO NO_RESPONSE Fast under current: Phase C IC< Start * * * * * * *
DDB_SEF_UNDERCURRENT 1071 SW PFSO NO_RESPONSE ISEF< Operate ISEF< Start * * * * * * *
DDB_EF_UNDERCURRENT 1072 SW PFSO NO_RESPONSE IN< Operate IN< Start * * * * *
DDB_PH_BLOCKED_OC_START 1073 SW PFSO event_Protection I> Blocked O/C Start I> BlockStart * *
DDB_N_BLOCKED_OC_START 1074 SW PFSO event_Protection IN/ISEF> Blocked O/C Start IN/SEF>Blk Start * *
DDB_THROUGH_FAULT_OC_START 1075 SW PFSO event_Protection Through fault START TF OC Start * * * * *
DDB_UNUSED 1076 SW UNUSED NO_RESPONSE Unused
DDB_THROUGH_FAULT_RECORDER 1077 SW PFSO NO_RESPONSE Through fault TRIGGER TF Recorder trig * * * * *
DDB_UNUSED 1078 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1079 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1080 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1081 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1082 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1083 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1084 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1085 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1086 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1087 SW UNUSED NO_RESPONSE Unused
DDB_RESOV_1_START 1088 SW PFSO event_Protection 1st Stage Residual O/V Start VN>1 Start * * * * * * *
DDB_RESOV_2_START 1089 SW PFSO event_Protection 2nd Stage Residual O/V Start VN>2 Start * * * * * * *
DDB_RESOV_3_START 1090 SW PFSO event_Protection Residual O/V Stage 3 Start VN>3 Start * * * * * * *
DDB_RESOV_4_START 1091 SW PFSO event_Protection Residual O/V Stage 4 Start VN>4 Start * * * * * * *
DDB_RESOV_5_START 1092 SW PFSO event_Protection Residual O/V Stage 5 Start VN>5 Start * *
DDB_RESOV_6_START 1093 SW PFSO event_Protection Residual O/V Stage 6 Start VN>6 Start * *
DDB_POV_1_3PH_START 1094 SW PFSO event_Protection 1st Stage Phase O/V Start 3ph V>1 Start * * * * * * *
DDB_POV_1_PH_A_START 1095 SW PFSO event_Protection 1st Stage Phase O/V Start A/AB V>1 Start A/AB * * * * * * *
DDB_POV_1_PH_B_START 1096 SW PFSO event_Protection 1st Stage Phase O/V Start B/BC V>1 Start B/BC * * * * * * *
DDB_POV_1_PH_C_START 1097 SW PFSO event_Protection 1st Stage Phase O/V Start C/CA V>1 Start C/CA * * * * * * *
DDB_POV_2_3PH_START 1098 SW PFSO event_Protection 2nd Stage Phase O/V Start 3ph V>2 Start * * * * * * *
DDB_POV_2_PH_A_START 1099 SW PFSO event_Protection 2nd Stage Phase O/V Start A/AB V>2 Start A/AB * * * * * * *
DDB_POV_2_PH_B_START 1100 SW PFSO event_Protection 2nd Stage Phase O/V Start B/BC V>2 Start B/BC * * * * * * *
DDB_POV_2_PH_C_START 1101 SW PFSO event_Protection 2nd Stage Phase O/V Start C/CA V>2 Start C/CA * * * * * * *
DDB_NPSOV_1_START 1102 SW PFSO event_Protection NPS Over Voltage Stage 1 Start V2>1 Start * * * * * * *
DDB_PUV_1_3PH_START 1103 SW PFSO event_Protection 1st Stage Phase U/V Start 3ph V<1 Start * * * * * * *
DDB_PUV_1_PH_A_START 1104 SW PFSO event_Protection 1st Stage Phase U/V Start A/AB V<1 Start A/AB * * * * * * *
DDB_PUV_1_PH_B_START 1105 SW PFSO event_Protection 1st Stage Phase U/V Start B/BC V<1 Start B/BC * * * * * * *
DDB_PUV_1_PH_C_START 1106 SW PFSO event_Protection 1st Stage Phase U/V Start C/CA V<1 Start C/CA * * * * * * *
DDB_PUV_2_3PH_START 1107 SW PFSO event_Protection 2nd Stage Phase U/V Start 3ph V<2 Start * * * * * * *
DDB_PUV_2_PH_A_START 1108 SW PFSO event_Protection 2nd Stage Phase U/V Start A/AB V<2 Start A/AB * * * * * * *
DDB_PUV_2_PH_B_START 1109 SW PFSO event_Protection 2nd Stage Phase U/V Start B/BC V<2 Start B/BC * * * * * * *
DDB_PUV_2_PH_C_START 1110 SW PFSO event_Protection 2nd Stage Phase U/V Start C/CA V<2 Start C/CA * * * * * * *
DDB_UNUSED 1111 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1112 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1113 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1114 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1115 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1116 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1117 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1118 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1119 SW UNUSED NO_RESPONSE Unused
DDB_FIELDF_1_START 1120 SW PFSO event_Protection Field Failure Stage 1 Start FFail1 Start * * * * *
DDB_FIELDF_2_START 1121 SW PFSO event_Protection Field Failure Stage 2 Start FFail2 Start * * * * *
DDB_POLESLZ_ZONE1_START 1122 SW PFSO event_Protection Pole Slip (Impedance) Zone1 Start PSlipz Z1 Start * * *
DDB_POLESLZ_ZONE2_START 1123 SW PFSO event_Protection Pole Slip (Impedance) Zone2 Start PSlipz Z2 Start * * *
DDB_POLESLZ_LENS_START 1124 SW PFSO event_Protection Pole Slip (impedance) Lens Start PSlipz LensStart * * *
DDB_POLESLZ_BLINDER_START 1125 SW PFSO event_Protection Pole Slip (impedance) Blinder Start PSlipz BlindStrt * * *
DDB_POLESLZ_REACT_START 1126 SW PFSO NO_RESPONSE Pole Slip (impedance) Reactance Line Start PSlipz ReactStrt * * *
DDB_VOLT_DEP_OC_3PH_START 1127 SW PFSO event_Protection Voltage Dependant Overcurrent Start 3Ph V Dep OC Start * * * * *
DDB_VOLT_DEP_OC_PH_A_START 1128 SW PFSO event_Protection Voltage Dependant Overcurrent Start A V Dep OC Start A * * * * *
DDB_VOLT_DEP_OC_PH_B_START 1129 SW PFSO event_Protection Voltage Dependant Overcurrent Start B V Dep OC Start B * * * * *
DDB_VOLT_DEP_OC_PH_C_START 1130 SW PFSO event_Protection Voltage Dependant Overcurrent Start C V Dep OC Start C * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 91 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNDERZ_1_3PH_START 1131 SW PFSO event_Protection Under Impedance 3Phase Stage 1 Start Z<1 Start * * * * *
DDB_UNDERZ_1_PH_A_START 1132 SW PFSO event_Protection Under Impedance Phase A Stage 1 Start Z<1 Start A * * * * *
DDB_UNDERZ_1_PH_B_START 1133 SW PFSO event_Protection Under Impedance Phase B Stage 1 Start Z<1 Start B * * * * *
DDB_UNDERZ_1_PH_C_START 1134 SW PFSO event_Protection Under Impedance Phase C Stage 1 Start Z<1 Start C * * * * *
DDB_UNDERZ_2_3PH_START 1135 SW PFSO event_Protection Under Impedance 3Phase Stage 2 Start Z<2 Start * * * * *
DDB_UNDERZ_2_PH_A_START 1136 SW PFSO event_Protection Under Impedance Phase A Stage 2 Start Z<2 Start A * * * * *
DDB_UNDERZ_2_PH_B_START 1137 SW PFSO event_Protection Under Impedance Phase B Stage 2 Start Z<2 Start B * * * * *
DDB_UNDERZ_2_PH_C_START 1138 SW PFSO event_Protection Under Impedance Phase C Stage 2 Start Z<2 Start C * * * * *
DDB_PWRNPS_1_START 1139 SW PFSO event_Protection NPS Overpower Stage 1 Start S2>1 Start * * * * *
DDB_POWER_1_START 1140 SW PFSO event_Protection Power Stage 1 Start Power1 Start * * * * * * *
DDB_POWER_2_START 1141 SW PFSO event_Protection Power Stage 2 Start Power2 Start * * * * * * *
DDB_SPOWER_1_START 1142 SW PFSO event_Protection Sensitive A Phase Power Stage 1 Start SPower1 Start * * * * * * *
DDB_SPOWER_2_START 1143 SW PFSO event_Protection Sensitive A Phase Power Stage 2 Start SPower2 Start * * * * * * *
DDB_UNUSED 1144 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1145 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1146 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1147 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1148 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1149 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1150 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1151 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1152 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1153 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1154 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1155 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1156 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1157 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1158 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1159 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1160 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1161 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1162 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1163 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1164 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1165 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1166 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1167 SW UNUSED NO_RESPONSE Unused
DDB_VPERHZ_START 1168 SW PFSO event_Protection 1st Stage Volts per Hz Start V/Hz>1 Start * * * * *
DDB_VPERHZ_START2 1169 SW PFSO event_Protection Volts per Hz Stage 2 Start V/Hz>2 Start * * * * *
DDB_VPERHZ_START3 1170 SW PFSO event_Protection Volts per Hz Stage 3 Start V/Hz>3 Start * * * * *
DDB_VPERHZ_START4 1171 SW PFSO event_Protection Volts per Hz Stage 4 Start V/Hz>4 Start * * * * *
DDB_UFREQ_1_START 1172 SW PFSO event_Protection Under Frequency Stage 1 Start F<1 Start * * * * * * *
DDB_UFREQ_2_START 1173 SW PFSO event_Protection Under Frequency Stage 2 Start F<2 Start * * * * * * *
DDB_UFREQ_3_START 1174 SW PFSO event_Protection Under Frequency Stage 3 Start F<3 Start * * * * * * *
DDB_UFREQ_4_START 1175 SW PFSO event_Protection Under Frequency Stage 4 Start F<4 Start * * * * * * *
DDB_OFREQ_1_START 1176 SW PFSO event_Protection Over Frequency Stage 1 Start F>1 Start * * * * * * *
DDB_OFREQ_2_START 1177 SW PFSO event_Protection Over Frequency Stage 2 Start F>2 Start * * * * * * *
DDB_TAF1_START1 1178 SW PFSO event_Protection Turbine Abnormal Frequency Band 1 Start Freq Band1 Start * * * * *
DDB_TAF1_START2 1179 SW PFSO event_Protection Turbine Abnormal Frequency Band 2 Start Freq Band2 Start * * * * *
DDB_TAF1_START3 1180 SW PFSO event_Protection Turbine Abnormal Frequency Band 3 Start Freq Band3 Start * * * * *
DDB_TAF1_START4 1181 SW PFSO event_Protection Turbine Abnormal Frequency Band 4 Start Freq Band4 Start * * * * *
DDB_TAF1_START5 1182 SW PFSO event_Protection Turbine Abnormal Frequency Band 5 Start Freq Band5 Start * * * * *
DDB_TAF1_START6 1183 SW PFSO event_Protection Turbine Abnormal Frequency Band 6 Start Freq Band6 Start * * * * *
DDB_DFDT_1_START 1184 SW PFSO event_Protection df/dt>1 Start df/dt>1 Start * * * * * * *
DDB_DFDT_2_START 1185 SW PFSO event_Protection df/dt>2 Start df/dt>2 Start * * * * * * *
DDB_DFDT_3_START 1186 SW PFSO event_Protection df/dt>3 Start df/dt>3 Start * * * * * * *
DDB_DFDT_4_START 1187 SW PFSO event_Protection df/dt>4 Start df/dt>4 Start * * * * * * *
DDB_UNUSED 1188 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1189 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1190 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1191 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1192 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1193 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1194 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1195 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1196 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1197 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 92 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 1198 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1199 SW UNUSED NO_RESPONSE Unused
DDB_XFORMER_HOT_SPOT_1_START 1200 SW PFSO event_Protection HotSpot>1 Start Hot Spot>1 Start * * * * *
DDB_XFORMER_HOT_SPOT_2_START 1201 SW PFSO event_Protection HotSpot>2 Start Hot Spot>2 Start * * * * *
DDB_XFORMER_HOT_SPOT_3_START 1202 SW PFSO event_Protection HotSpot>3 Start Hot Spot>3 Start * * * * *
DDB_XFORMER_TOP_OIL_1_START 1203 SW PFSO event_Protection Top Oil>1 Start Top Oil>1 start * * * * *
DDB_XFORMER_TOP_OIL_2_START 1204 SW PFSO event_Protection Top Oil>2 Start Top Oil>2 start * * * * *
DDB_XFORMER_TOP_OIL_3_START 1205 SW PFSO event_Protection Top Oil>3 Start Top Oil>3 start * * * * *
DDB_DLR_AMP_1_START 1206 SW PFSO event_Protection DLR Trip 1 Start DLR I>1 Start *
DDB_DLR_AMP_2_START 1207 SW PFSO event_Protection DLR Trip 2 Start DLR I>2 Start *
DDB_DLR_AMP_3_START 1208 SW PFSO event_Protection DLR Trip 3 Start DLR I>3 Start *
DDB_DLR_AMP_4_START 1209 SW PFSO event_Protection DLR Trip 4 Start DLR I>4 Start *
DDB_DLR_AMP_5_START 1210 SW PFSO event_Protection DLR Trip 5 Start DLR I>5 Start *
DDB_DLR_AMP_6_START 1211 SW PFSO event_Protection DLR Trip 6 Start DLR I>6 Start *
DDB_UNUSED 1212 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1213 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1214 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1215 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1216 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1217 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1218 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1219 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1220 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1221 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1222 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1223 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1224 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1225 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1226 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1227 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1228 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1229 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1230 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1231 SW UNUSED NO_RESPONSE Unused
DDB_CL_INPUT_1_ALARM_START 1232 SW PFSO event_Protection Current Loop Input 1 Alarm Start CLI1 Alarm Start * * * * * * *
DDB_CL_INPUT_2_ALARM_START 1233 SW PFSO event_Protection Current Loop Input 2 Alarm Start CLI2 Alarm Start * * * * * * *
DDB_CL_INPUT_3_ALARM_START 1234 SW PFSO event_Protection Current Loop Input 3 Alarm Start CLI3 Alarm Start * * * * * * *
DDB_CL_INPUT_4_ALARM_START 1235 SW PFSO event_Protection Current Loop Input 4 Alarm Start CLI4 Alarm Start * * * * * * *
DDB_CL_INPUT_1_TRIP_START 1236 SW PFSO event_Protection Current Loop Input 1 Trip Start CLI1 Trip Start * * * * * * *
DDB_CL_INPUT_2_TRIP_START 1237 SW PFSO event_Protection Current Loop Input 2 Trip Start CLI2 Trip Start * * * * * * *
DDB_CL_INPUT_3_TRIP_START 1238 SW PFSO event_Protection Current Loop Input 3 Trip Start CLI3 Trip Start * * * * * * *
DDB_CL_INPUT_4_TRIP_START 1239 SW PFSO event_Protection Current Loop Input 4 Trip Start CLI4 Trip Start * * * * * * *
DDB_UNUSED 1240 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1241 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1242 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1243 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1244 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1245 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1246 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1247 SW UNUSED NO_RESPONSE Unused
DDB_VTS_FAST_BLOCK 1248 SW PFSO event_Protection VTS Fast Block VTS Fast Block * * * * * * *
DDB_VTS_SLOW_BLOCK 1249 SW PFSO event_Protection VTS Slow Block VTS Slow Block * * * * * * *
DDB_UNUSED 1250 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1251 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1252 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1253 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1254 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1255 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1256 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1257 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1258 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1259 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1260 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1261 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1262 SW UNUSED NO_RESPONSE Unused
DDB_CTS_BLOCK 1263 SW PFSO event_Protection CTS-1 Block CTS-1 Block * * * * * * *
DDB_CTS_2_BLOCK 1264 SW PFSO event_Protection CTS-2 Block CTS-2 Block * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 93 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_DIFF_CTS_BLK 1265 SW PFSO event_Protection differential CTS Diff CTS BLK * * * *
DDB_DIFF_CTS_CT1 1266 SW PFSO event_Protection differential CTS Diff CTS CT1 * * * *
DDB_DIFF_CTS_CT2 1267 SW PFSO event_Protection differential CTS Diff CTS CT2 * * * *
DDB_UNUSED 1268 SW UNUSED NO_RESPONSE Unused
DDB_CIR_FLT_A 1269 SW PFSO event_Protection Circuitry Fault Alarm A CctFail Blk A * * * *
DDB_CIR_FLT_B 1270 SW PFSO event_Protection Circuitry Fault Alarm B CctFail Blk B * * * *
DDB_CIR_FLT_C 1271 SW PFSO event_Protection Circuitry Fault Alarm C CctFail Blk C * * * *
DDB_2ND_HAR_BLKA 1272 SW PFSO event_Protection 2nd Harmonic A 2nd Har Blk A * * * *
DDB_2ND_HAR_BLKB 1273 SW PFSO event_Protection 2nd Harmonic B 2nd Har Blk B * * * *
DDB_2ND_HAR_BLKC 1274 SW PFSO event_Protection 2nd Harmonic C 2nd Har Blk C * * * *
DDB_5TH_HAR_BLKA 1275 SW PFSO event_Protection 5th Har Blk A 5nd Har Blk A * * * *
DDB_5TH_HAR_BLKB 1276 SW PFSO event_Protection 5th Har Blk B 5nd Har Blk B * * * *
DDB_5TH_HAR_BLKC 1277 SW PFSO event_Protection 5th Har Blk C 5nd Har Blk C * * * *
DDB_CONTROL_TRIP 1278 SW PFSO event_Protection Control Trip Control Trip * * * * * * *
DDB_CONTROL_CLOSE 1279 SW PFSO event_Protection Control Close Control Close * * * * * * *
DDB_CONTROL_CLOSE_IN_PROGRESS 1280 SW PFSO event_Protection Control Close in Progress Close in Prog * * * * * * *
DDB_CB_LOCKOUT_ALARM 1281 SW PFSO event_Protection Composite Lockout Alarm Lockout Alarm * * * * * * *
DDB_CB_OPEN 1282 SW PFSO event_Protection 3 ph CB Open CB Open 3 ph * * * * * * *
DDB_CB_CLOSED 1283 SW PFSO event_Protection 3 ph CB Closed CB Closed 3 ph * * * * * * *
DDB_ALL_POLEDEAD 1284 SW PFSO event_Protection All Poles Dead All Poles Dead * * * * * * *
DDB_ANY_POLEDEAD 1285 SW PFSO event_Protection Any Pole Dead Any Pole Dead * * * * * * *
DDB_PHASE_A_POLEDEAD 1286 SW PFSO event_Protection Phase A Pole Dead Pole Dead A * * * * * * *
DDB_PHASE_B_POLEDEAD 1287 SW PFSO event_Protection Phase B Pole Dead Pole Dead B * * * * * * *
DDB_PHASE_C_POLEDEAD 1288 SW PFSO event_Protection Phase C Pole Dead Pole Dead C * * * * * * *
DDB_UNUSED 1289 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1290 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1291 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1292 SW UNUSED NO_RESPONSE Unused
DDB_FREQ_ABOVE_RANGE_LIMIT 1293 SW PFSO NO_RESPONSE Freq High Freq High * * * * * * *
DDB_FREQ_BELOW_RANGE_LIMIT 1294 SW PFSO NO_RESPONSE Freq Low Freq Low * * * * * * *
DDB_FREQ_NOT_FOUND 1295 SW PFSO NO_RESPONSE Freq Not Found Freq Not found * * * * * * *
DDB_UNUSED 1296 SW UNUSED NO_RESPONSE Unused
DDB_STEFI_LOW_F_BLOCK 1297 SW PFSO event_Protection 64S 100% Stator Earth Fault - System frequency in blocking band 64S F Band Block *
DDB_STEFI_FAIL 1298 SW PFSO event_Protection 64S 100% Stator Earth Fault - Injection failure 64S Fail *
DDB_RECONNECTION_OUTPUT 1299 SW PFSO event_Protection Reconnection Time Delay Output Reconnection * *
DDB_UNUSED 1300 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1301 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1302 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1303 SW UNUSED NO_RESPONSE Unused
DDB_RTD_1_ALARM 1304 SW PFSO event_Protection RTD 1 Alarm RTD 1 Alarm * * * * *
DDB_RTD_2_ALARM 1305 SW PFSO event_Protection RTD 2 Alarm RTD 2 Alarm * * * * *
DDB_RTD_3_ALARM 1306 SW PFSO event_Protection RTD 3 Alarm RTD 3 Alarm * * * * *
DDB_RTD_4_ALARM 1307 SW PFSO event_Protection RTD 4 Alarm RTD 4 Alarm * * * * *
DDB_RTD_5_ALARM 1308 SW PFSO event_Protection RTD 5 Alarm RTD 5 Alarm * * * * *
DDB_RTD_6_ALARM 1309 SW PFSO event_Protection RTD 6 Alarm RTD 6 Alarm * * * * *
DDB_RTD_7_ALARM 1310 SW PFSO event_Protection RTD 7 Alarm RTD 7 Alarm * * * * *
DDB_RTD_8_ALARM 1311 SW PFSO event_Protection RTD 8 Alarm RTD 8 Alarm * * * * *
DDB_RTD_9_ALARM 1312 SW PFSO event_Protection RTD 9 Alarm RTD 9 Alarm * * * * *
DDB_RTD_10_ALARM 1313 SW PFSO event_Protection RTD 10 Alarm RTD 10 Alarm * * * * *
DDB_BLOCK_REMOTE_CB_OPS 1314 PSL PFSI NO_RESPONSE Blocks remote CB Trip/Close commands when asserted Blk Rmt. CB Ops * * * * * * *
DDB_UNUSED 1315 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1316 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1317 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1318 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1319 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1320 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1321 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1322 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1323 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1324 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1325 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1326 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1327 SW UNUSED NO_RESPONSE Unused
DDB_SYSCHECKS_GEN_LIVE 1328 SW PFSO NO_RESPONSE Live Gen Live Gen * * * * * * *
DDB_SYSCHECKS_GEN_DEAD 1329 SW PFSO NO_RESPONSE Dead Gen Dead Gen * * * * * * *
DDB_SYSCHECKS_BUS_LIVE 1330 SW PFSO NO_RESPONSE Live Bus Live Bus * * * * * * *
DDB_SYSCHECKS_BUS_DEAD 1331 SW PFSO NO_RESPONSE Dead Bus Dead Bus * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 94 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_CHECKSYNC_1_OK 1332 SW PFSO NO_RESPONSE Check Sync 1 OK Check Sync 1 OK * * * * * * *
DDB_CHECKSYNC_2_OK 1333 SW PFSO NO_RESPONSE Check Sync 2 OK Check Sync 2 OK * * * * * * *
DDB_UNUSED 1334 SW UNUSED NO_RESPONSE Unused
DDB_SYSCHECKS_INACTIVE 1335 SW PFSO NO_RESPONSE SysChks Inactive SysChks Inactive * * * * * * *
DDB_CHECKSYNC_1_ENABLED 1336 PSL PFSI NO_RESPONSE CS1 Enabled CS1 Enabled * * * * * * *
DDB_CHECKSYNC_2_ENABLED 1337 PSL PFSI NO_RESPONSE CS2 Enabled CS2 Enabled * * * * * * *
DDB_SYSTEM_SPLIT_ENABLED 1338 PSL PFSI NO_RESPONSE SysSplit Enabled SysSplit Enabled * * * * * * *
DDB_CS1_SLIP_ABOVE_SETTING 1339 SW PFSO event_Protection Check Synch 1 Slip > Setting CS1 Slipfreq> * * * * * * *
DDB_CS1_SLIP_BELOW_SETTING 1340 SW PFSO NO_RESPONSE Check Synch 1 Slip < Setting CS1 Slipfreq< * * * * * * *
DDB_CS2_SLIP_ABOVE_SETTING 1341 SW PFSO event_Protection Check Synch 2 Slip > Setting CS2 Slipfreq> * * * * * * *
DDB_CS2_SLIP_BELOW_SETTING 1342 SW PFSO NO_RESPONSE Check Synch 2 Slip < Setting CS2 Slipfreq< * * * * * * *
DDB_SYSCHECKS_VGEN_UV 1343 SW PFSO NO_RESPONSE Gen volts less than CS undervoltage setting CS Vgen< * * * * * * *
DDB_SYSCHECKS_VBUS_UV 1344 SW PFSO NO_RESPONSE Bus volts less than CS undervoltage setting CS Vbus< * * * * * * *
DDB_SYSCHECKS_VGEN_OV 1345 SW PFSO NO_RESPONSE Gen volts greater than CS overvoltage setting CS Vgen> * * * * * * *
DDB_SYSCHECKS_VBUS_OV 1346 SW PFSO NO_RESPONSE Bus volts greater than CS overvoltage setting CS Vbus> * * * * * * *
DDB_SYSCHECKS_FGEN_UF 1347 SW PFSO NO_RESPONSE Gen freq less than CS underfreq setting CS Freq Low * * * * * * *
DDB_SYSCHECKS_FGEN_OF 1348 SW PFSO NO_RESPONSE Gen freq greater than CS overfreq setting CS Freq High * * * * * * *
DDB_SYSCHECKS_VGEN_DIFF_HIGH 1349 SW PFSO NO_RESPONSE Gen volts greater than (bus volts + CS diff voltage setting) CS Vgen>Vbus * * * * * * *
DDB_SYSCHECKS_VBUS_DIFF_HIGH 1350 SW PFSO NO_RESPONSE Bus volts greater than (line volts + CS diff voltage setting) CS Vgen<Vbus * * * * * * *
DDB_CS1_GEN_FREQ_GT_BUS_FREQ 1351 SW PFSO NO_RESPONSE Gen freq greater than (bus freq + CS1 slip freq setting) CS1 Fgen>Fbus * * * * * * *
DDB_CS1_GEN_FREQ_LT_BUS_FREQ 1352 SW PFSO NO_RESPONSE Bus freq greater than (line freq + CS1 slip freq setting) CS1 Fgen<Fbus * * * * * * *
DDB_CS1_ANG_NOT_OK_POS 1353 SW PFSO NO_RESPONSE Gen angle in range (CS1 ang setting to +180 deg) CS1 Ang Not OK + * * * * * * *
DDB_CS1_ANG_NOT_OK_NEG 1354 SW PFSO NO_RESPONSE Gen angle in range (-CS1 ang setting to -180 deg) CS1 Ang Not OK - * * * * * * *
DDB_CS2_GEN_FREQ_GT_BUS_FREQ 1355 SW PFSO NO_RESPONSE Gen freq greater than (bus freq + CS2 slip freq setting) CS2 Fgen>Fbus * * * * * * *
DDB_CS2_GEN_FREQ_LT_BUS_FREQ 1356 SW PFSO NO_RESPONSE Bus freq greater than (gen freq + CS2 slip freq setting) CS2 Fgen<Fbus * * * * * * *
DDB_CS2_ANG_NOT_OK_POS 1357 SW PFSO NO_RESPONSE Gen angle in range (CS2 angle setting to +180 deg) CS2 Ang Not OK + * * * * * * *
DDB_CS2_ANG_NOT_OK_NEG 1358 SW PFSO NO_RESPONSE Gen angle in range (-CS2 angle setting to -180 deg) CS2 Ang Not OK - * * * * * * *
DDB_SYSCHECKS_ANG_ACW 1359 SW PFSO NO_RESPONSE Gen/Bus phase angle is rotating anti-clockwise CS Ang Rot ACW * * * * * * *
DDB_SYSCHECKS_ANG_CW 1360 SW PFSO NO_RESPONSE Gen/Bus phase angle is rotating clockwise CS Ang Rot CW * * * * * * *
DDB_CHECKSYNC_GUARD_ON 1361 SW PFSO NO_RESPONSE Check Synch Guard on CS Guard Enabled * * * * * * *
DDB_MAN_SYSCHECKS 1362 PSL PFSI NO_RESPONSE Manual check synchronization conditions are satisfied Man Check Synch * * * * * * *
DDB_CHECKSYNC_GUARD_IN 1363 PSL PFSI NO_RESPONSE Check Synch Guard input CS Guard Enable * * * * * * *
DDB_UNUSED 1364 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1365 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1366 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1367 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1368 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1369 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1370 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1371 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1372 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1373 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1374 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1375 SW UNUSED NO_RESPONSE Unused
DDB_CONTROL_1 1376 SW CONTROL event_Protection Control Input 1 Control Input 1 * * * * * * *
DDB_CONTROL_2 1377 SW CONTROL event_Protection Control Input 2 Control Input 2 * * * * * * *
DDB_CONTROL_3 1378 SW CONTROL event_Protection Control Input 3 Control Input 3 * * * * * * *
DDB_CONTROL_4 1379 SW CONTROL event_Protection Control Input 4 Control Input 4 * * * * * * *
DDB_CONTROL_5 1380 SW CONTROL event_Protection Control Input 5 Control Input 5 * * * * * * *
DDB_CONTROL_6 1381 SW CONTROL event_Protection Control Input 6 Control Input 6 * * * * * * *
DDB_CONTROL_7 1382 SW CONTROL event_Protection Control Input 7 Control Input 7 * * * * * * *
DDB_CONTROL_8 1383 SW CONTROL event_Protection Control Input 8 Control Input 8 * * * * * * *
DDB_CONTROL_9 1384 SW CONTROL event_Protection Control Input 9 Control Input 9 * * * * * * *
DDB_CONTROL_10 1385 SW CONTROL event_Protection Control Input 10 Control Input 10 * * * * * * *
DDB_CONTROL_11 1386 SW CONTROL event_Protection Control Input 11 Control Input 11 * * * * * * *
DDB_CONTROL_12 1387 SW CONTROL event_Protection Control Input 12 Control Input 12 * * * * * * *
DDB_CONTROL_13 1388 SW CONTROL event_Protection Control Input 13 Control Input 13 * * * * * * *
DDB_CONTROL_14 1389 SW CONTROL event_Protection Control Input 14 Control Input 14 * * * * * * *
DDB_CONTROL_15 1390 SW CONTROL event_Protection Control Input 15 Control Input 15 * * * * * * *
DDB_CONTROL_16 1391 SW CONTROL event_Protection Control Input 16 Control Input 16 * * * * * * *
DDB_CONTROL_17 1392 SW CONTROL event_Protection Control Input 17 Control Input 17 * * * * * * *
DDB_CONTROL_18 1393 SW CONTROL event_Protection Control Input 18 Control Input 18 * * * * * * *
DDB_CONTROL_19 1394 SW CONTROL event_Protection Control Input 19 Control Input 19 * * * * * * *
DDB_CONTROL_20 1395 SW CONTROL event_Protection Control Input 20 Control Input 20 * * * * * * *
DDB_CONTROL_21 1396 SW CONTROL event_Protection Control Input 21 Control Input 21 * * * * * * *
DDB_CONTROL_22 1397 SW CONTROL event_Protection Control Input 22 Control Input 22 * * * * * * *
DDB_CONTROL_23 1398 SW CONTROL event_Protection Control Input 23 Control Input 23 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 95 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_CONTROL_24 1399 SW CONTROL event_Protection Control Input 24 Control Input 24 * * * * * * *
DDB_CONTROL_25 1400 SW CONTROL event_Protection Control Input 25 Control Input 25 * * * * * * *
DDB_CONTROL_26 1401 SW CONTROL event_Protection Control Input 26 Control Input 26 * * * * * * *
DDB_CONTROL_27 1402 SW CONTROL event_Protection Control Input 27 Control Input 27 * * * * * * *
DDB_CONTROL_28 1403 SW CONTROL event_Protection Control Input 28 Control Input 28 * * * * * * *
DDB_CONTROL_29 1404 SW CONTROL event_Protection Control Input 29 Control Input 29 * * * * * * *
DDB_CONTROL_30 1405 SW CONTROL event_Protection Control Input 30 Control Input 30 * * * * * * *
DDB_CONTROL_31 1406 SW CONTROL event_Protection Control Input 31 Control Input 31 * * * * * * *
DDB_CONTROL_32 1407 SW CONTROL event_Protection Control Input 32 Control Input 32 * * * * * * *
DDB_GOOSEIN_1 1408 SW GOOSEIN event_Protection Virtual Input 01 Virtual Input 01 * * * * * * *
DDB_GOOSEIN_2 1409 SW GOOSEIN event_Protection Virtual Input 02 Virtual Input 02 * * * * * * *
DDB_GOOSEIN_3 1410 SW GOOSEIN event_Protection Virtual Input 03 Virtual Input 03 * * * * * * *
DDB_GOOSEIN_4 1411 SW GOOSEIN event_Protection Virtual Input 04 Virtual Input 04 * * * * * * *
DDB_GOOSEIN_5 1412 SW GOOSEIN event_Protection Virtual Input 05 Virtual Input 05 * * * * * * *
DDB_GOOSEIN_6 1413 SW GOOSEIN event_Protection Virtual Input 06 Virtual Input 06 * * * * * * *
DDB_GOOSEIN_7 1414 SW GOOSEIN event_Protection Virtual Input 07 Virtual Input 07 * * * * * * *
DDB_GOOSEIN_8 1415 SW GOOSEIN event_Protection Virtual Input 08 Virtual Input 08 * * * * * * *
DDB_GOOSEIN_9 1416 SW GOOSEIN event_Protection Virtual Input 09 Virtual Input 09 * * * * * * *
DDB_GOOSEIN_10 1417 SW GOOSEIN event_Protection Virtual Input 10 Virtual Input 10 * * * * * * *
DDB_GOOSEIN_11 1418 SW GOOSEIN event_Protection Virtual Input 11 Virtual Input 11 * * * * * * *
DDB_GOOSEIN_12 1419 SW GOOSEIN event_Protection Virtual Input 12 Virtual Input 12 * * * * * * *
DDB_GOOSEIN_13 1420 SW GOOSEIN event_Protection Virtual Input 13 Virtual Input 13 * * * * * * *
DDB_GOOSEIN_14 1421 SW GOOSEIN event_Protection Virtual Input 14 Virtual Input 14 * * * * * * *
DDB_GOOSEIN_15 1422 SW GOOSEIN event_Protection Virtual Input 15 Virtual Input 15 * * * * * * *
DDB_GOOSEIN_16 1423 SW GOOSEIN event_Protection Virtual Input 16 Virtual Input 16 * * * * * * *
DDB_GOOSEIN_17 1424 SW GOOSEIN event_Protection Virtual Input 17 Virtual Input 17 * * * * * * *
DDB_GOOSEIN_18 1425 SW GOOSEIN event_Protection Virtual Input 18 Virtual Input 18 * * * * * * *
DDB_GOOSEIN_19 1426 SW GOOSEIN event_Protection Virtual Input 19 Virtual Input 19 * * * * * * *
DDB_GOOSEIN_20 1427 SW GOOSEIN event_Protection Virtual Input 20 Virtual Input 20 * * * * * * *
DDB_GOOSEIN_21 1428 SW GOOSEIN event_Protection Virtual Input 21 Virtual Input 21 * * * * * * *
DDB_GOOSEIN_22 1429 SW GOOSEIN event_Protection Virtual Input 22 Virtual Input 22 * * * * * * *
DDB_GOOSEIN_23 1430 SW GOOSEIN event_Protection Virtual Input 23 Virtual Input 23 * * * * * * *
DDB_GOOSEIN_24 1431 SW GOOSEIN event_Protection Virtual Input 24 Virtual Input 24 * * * * * * *
DDB_GOOSEIN_25 1432 SW GOOSEIN event_Protection Virtual Input 25 Virtual Input 25 * * * * * * *
DDB_GOOSEIN_26 1433 SW GOOSEIN event_Protection Virtual Input 26 Virtual Input 26 * * * * * * *
DDB_GOOSEIN_27 1434 SW GOOSEIN event_Protection Virtual Input 27 Virtual Input 27 * * * * * * *
DDB_GOOSEIN_28 1435 SW GOOSEIN event_Protection Virtual Input 28 Virtual Input 28 * * * * * * *
DDB_GOOSEIN_29 1436 SW GOOSEIN event_Protection Virtual Input 29 Virtual Input 29 * * * * * * *
DDB_GOOSEIN_30 1437 SW GOOSEIN event_Protection Virtual Input 30 Virtual Input 30 * * * * * * *
DDB_GOOSEIN_31 1438 SW GOOSEIN event_Protection Virtual Input 31 Virtual Input 31 * * * * * * *
DDB_GOOSEIN_32 1439 SW GOOSEIN event_Protection Virtual Input 32 Virtual Input 32 * * * * * * *
DDB_GOOSEIN_33 1440 SW GOOSEIN event_Protection Virtual Input 33 Virtual Input 33 * * * * * * *
DDB_GOOSEIN_34 1441 SW GOOSEIN event_Protection Virtual Input 34 Virtual Input 34 * * * * * * *
DDB_GOOSEIN_35 1442 SW GOOSEIN event_Protection Virtual Input 35 Virtual Input 35 * * * * * * *
DDB_GOOSEIN_36 1443 SW GOOSEIN event_Protection Virtual Input 36 Virtual Input 36 * * * * * * *
DDB_GOOSEIN_37 1444 SW GOOSEIN event_Protection Virtual Input 37 Virtual Input 37 * * * * * * *
DDB_GOOSEIN_38 1445 SW GOOSEIN event_Protection Virtual Input 38 Virtual Input 38 * * * * * * *
DDB_GOOSEIN_39 1446 SW GOOSEIN event_Protection Virtual Input 39 Virtual Input 39 * * * * * * *
DDB_GOOSEIN_40 1447 SW GOOSEIN event_Protection Virtual Input 40 Virtual Input 40 * * * * * * *
DDB_GOOSEIN_41 1448 SW GOOSEIN event_Protection Virtual Input 41 Virtual Input 41 * * * * * * *
DDB_GOOSEIN_42 1449 SW GOOSEIN event_Protection Virtual Input 42 Virtual Input 42 * * * * * * *
DDB_GOOSEIN_43 1450 SW GOOSEIN event_Protection Virtual Input 43 Virtual Input 43 * * * * * * *
DDB_GOOSEIN_44 1451 SW GOOSEIN event_Protection Virtual Input 44 Virtual Input 44 * * * * * * *
DDB_GOOSEIN_45 1452 SW GOOSEIN event_Protection Virtual Input 45 Virtual Input 45 * * * * * * *
DDB_GOOSEIN_46 1453 SW GOOSEIN event_Protection Virtual Input 46 Virtual Input 46 * * * * * * *
DDB_GOOSEIN_47 1454 SW GOOSEIN event_Protection Virtual Input 47 Virtual Input 47 * * * * * * *
DDB_GOOSEIN_48 1455 SW GOOSEIN event_Protection Virtual Input 48 Virtual Input 48 * * * * * * *
DDB_GOOSEIN_49 1456 SW GOOSEIN event_Protection Virtual Input 49 Virtual Input 49 * * * * * * *
DDB_GOOSEIN_50 1457 SW GOOSEIN event_Protection Virtual Input 50 Virtual Input 50 * * * * * * *
DDB_GOOSEIN_51 1458 SW GOOSEIN event_Protection Virtual Input 51 Virtual Input 51 * * * * * * *
DDB_GOOSEIN_52 1459 SW GOOSEIN event_Protection Virtual Input 52 Virtual Input 52 * * * * * * *
DDB_GOOSEIN_53 1460 SW GOOSEIN event_Protection Virtual Input 53 Virtual Input 53 * * * * * * *
DDB_GOOSEIN_54 1461 SW GOOSEIN event_Protection Virtual Input 54 Virtual Input 54 * * * * * * *
DDB_GOOSEIN_55 1462 SW GOOSEIN event_Protection Virtual Input 55 Virtual Input 55 * * * * * * *
DDB_GOOSEIN_56 1463 SW GOOSEIN event_Protection Virtual Input 56 Virtual Input 56 * * * * * * *
DDB_GOOSEIN_57 1464 SW GOOSEIN event_Protection Virtual Input 57 Virtual Input 57 * * * * * * *
DDB_GOOSEIN_58 1465 SW GOOSEIN event_Protection Virtual Input 58 Virtual Input 58 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 96 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_GOOSEIN_59 1466 SW GOOSEIN event_Protection Virtual Input 59 Virtual Input 59 * * * * * * *
DDB_GOOSEIN_60 1467 SW GOOSEIN event_Protection Virtual Input 60 Virtual Input 60 * * * * * * *
DDB_GOOSEIN_61 1468 SW GOOSEIN event_Protection Virtual Input 61 Virtual Input 61 * * * * * * *
DDB_GOOSEIN_62 1469 SW GOOSEIN event_Protection Virtual Input 62 Virtual Input 62 * * * * * * *
DDB_GOOSEIN_63 1470 SW GOOSEIN event_Protection Virtual Input 63 Virtual Input 63 * * * * * * *
DDB_GOOSEIN_64 1471 SW GOOSEIN event_Protection Virtual Input 64 Virtual Input 64 * * * * * * *
DDB_UNUSED 1472 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1473 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1474 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1475 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1476 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1477 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1478 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1479 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1480 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1481 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1482 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1483 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1484 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1485 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1486 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1487 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1488 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1489 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1490 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1491 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1492 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1493 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1494 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1495 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1496 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1497 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1498 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1499 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1500 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1501 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1502 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1503 SW UNUSED NO_RESPONSE Unused
DDB_VIP_QUALITY_1 1504 SW PFSO event_Protection GOOSE Virtual input 1 Quality bit Quality VIP 1 * * * * * * *
DDB_VIP_QUALITY_2 1505 SW PFSO event_Protection GOOSE Virtual input 2 Quality bit Quality VIP 2 * * * * * * *
DDB_VIP_QUALITY_3 1506 SW PFSO event_Protection GOOSE Virtual input 3 Quality bit Quality VIP 3 * * * * * * *
DDB_VIP_QUALITY_4 1507 SW PFSO event_Protection GOOSE Virtual input 4 Quality bit Quality VIP 4 * * * * * * *
DDB_VIP_QUALITY_5 1508 SW PFSO event_Protection GOOSE Virtual input 5 Quality bit Quality VIP 5 * * * * * * *
DDB_VIP_QUALITY_6 1509 SW PFSO event_Protection GOOSE Virtual input 6 Quality bit Quality VIP 6 * * * * * * *
DDB_VIP_QUALITY_7 1510 SW PFSO event_Protection GOOSE Virtual input 7 Quality bit Quality VIP 7 * * * * * * *
DDB_VIP_QUALITY_8 1511 SW PFSO event_Protection GOOSE Virtual input 8 Quality bit Quality VIP 8 * * * * * * *
DDB_VIP_QUALITY_9 1512 SW PFSO event_Protection GOOSE Virtual input 9 Quality bit Quality VIP 9 * * * * * * *
DDB_VIP_QUALITY_10 1513 SW PFSO event_Protection GOOSE Virtual input 10 Quality bit Quality VIP 10 * * * * * * *
DDB_VIP_QUALITY_11 1514 SW PFSO event_Protection GOOSE Virtual input 11 Quality bit Quality VIP 11 * * * * * * *
DDB_VIP_QUALITY_12 1515 SW PFSO event_Protection GOOSE Virtual input 12 Quality bit Quality VIP 12 * * * * * * *
DDB_VIP_QUALITY_13 1516 SW PFSO event_Protection GOOSE Virtual input 13 Quality bit Quality VIP 13 * * * * * * *
DDB_VIP_QUALITY_14 1517 SW PFSO event_Protection GOOSE Virtual input 14 Quality bit Quality VIP 14 * * * * * * *
DDB_VIP_QUALITY_15 1518 SW PFSO event_Protection GOOSE Virtual input 15 Quality bit Quality VIP 15 * * * * * * *
DDB_VIP_QUALITY_16 1519 SW PFSO event_Protection GOOSE Virtual input 16 Quality bit Quality VIP 16 * * * * * * *
DDB_VIP_QUALITY_17 1520 SW PFSO event_Protection GOOSE Virtual input 17 Quality bit Quality VIP 17 * * * * * * *
DDB_VIP_QUALITY_18 1521 SW PFSO event_Protection GOOSE Virtual input 18 Quality bit Quality VIP 18 * * * * * * *
DDB_VIP_QUALITY_19 1522 SW PFSO event_Protection GOOSE Virtual input 19 Quality bit Quality VIP 19 * * * * * * *
DDB_VIP_QUALITY_20 1523 SW PFSO event_Protection GOOSE Virtual input 20 Quality bit Quality VIP 20 * * * * * * *
DDB_VIP_QUALITY_21 1524 SW PFSO event_Protection GOOSE Virtual input 21 Quality bit Quality VIP 21 * * * * * * *
DDB_VIP_QUALITY_22 1525 SW PFSO event_Protection GOOSE Virtual input 22 Quality bit Quality VIP 22 * * * * * * *
DDB_VIP_QUALITY_23 1526 SW PFSO event_Protection GOOSE Virtual input 23 Quality bit Quality VIP 23 * * * * * * *
DDB_VIP_QUALITY_24 1527 SW PFSO event_Protection GOOSE Virtual input 24 Quality bit Quality VIP 24 * * * * * * *
DDB_VIP_QUALITY_25 1528 SW PFSO event_Protection GOOSE Virtual input 25 Quality bit Quality VIP 25 * * * * * * *
DDB_VIP_QUALITY_26 1529 SW PFSO event_Protection GOOSE Virtual input 26 Quality bit Quality VIP 26 * * * * * * *
DDB_VIP_QUALITY_27 1530 SW PFSO event_Protection GOOSE Virtual input 27 Quality bit Quality VIP 27 * * * * * * *
DDB_VIP_QUALITY_28 1531 SW PFSO event_Protection GOOSE Virtual input 28 Quality bit Quality VIP 28 * * * * * * *
DDB_VIP_QUALITY_29 1532 SW PFSO event_Protection GOOSE Virtual input 29 Quality bit Quality VIP 29 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 97 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_VIP_QUALITY_30 1533 SW PFSO event_Protection GOOSE Virtual input 30 Quality bit Quality VIP 30 * * * * * * *
DDB_VIP_QUALITY_31 1534 SW PFSO event_Protection GOOSE Virtual input 31 Quality bit Quality VIP 31 * * * * * * *
DDB_VIP_QUALITY_32 1535 SW PFSO event_Protection GOOSE Virtual input 32 Quality bit Quality VIP 32 * * * * * * *
DDB_VIP_QUALITY_33 1536 SW PFSO event_Protection GOOSE Virtual input 33 Quality bit Quality VIP 33 * * * * * * *
DDB_VIP_QUALITY_34 1537 SW PFSO event_Protection GOOSE Virtual input 34 Quality bit Quality VIP 34 * * * * * * *
DDB_VIP_QUALITY_35 1538 SW PFSO event_Protection GOOSE Virtual input 35 Quality bit Quality VIP 35 * * * * * * *
DDB_VIP_QUALITY_36 1539 SW PFSO event_Protection GOOSE Virtual input 36 Quality bit Quality VIP 36 * * * * * * *
DDB_VIP_QUALITY_37 1540 SW PFSO event_Protection GOOSE Virtual input 37 Quality bit Quality VIP 37 * * * * * * *
DDB_VIP_QUALITY_38 1541 SW PFSO event_Protection GOOSE Virtual input 38 Quality bit Quality VIP 38 * * * * * * *
DDB_VIP_QUALITY_39 1542 SW PFSO event_Protection GOOSE Virtual input 39 Quality bit Quality VIP 39 * * * * * * *
DDB_VIP_QUALITY_40 1543 SW PFSO event_Protection GOOSE Virtual input 40 Quality bit Quality VIP 40 * * * * * * *
DDB_VIP_QUALITY_41 1544 SW PFSO event_Protection GOOSE Virtual input 41 Quality bit Quality VIP 41 * * * * * * *
DDB_VIP_QUALITY_42 1545 SW PFSO event_Protection GOOSE Virtual input 42 Quality bit Quality VIP 42 * * * * * * *
DDB_VIP_QUALITY_43 1546 SW PFSO event_Protection GOOSE Virtual input 43 Quality bit Quality VIP 43 * * * * * * *
DDB_VIP_QUALITY_44 1547 SW PFSO event_Protection GOOSE Virtual input 44 Quality bit Quality VIP 44 * * * * * * *
DDB_VIP_QUALITY_45 1548 SW PFSO event_Protection GOOSE Virtual input 45 Quality bit Quality VIP 45 * * * * * * *
DDB_VIP_QUALITY_46 1549 SW PFSO event_Protection GOOSE Virtual input 46 Quality bit Quality VIP 46 * * * * * * *
DDB_VIP_QUALITY_47 1550 SW PFSO event_Protection GOOSE Virtual input 47 Quality bit Quality VIP 47 * * * * * * *
DDB_VIP_QUALITY_48 1551 SW PFSO event_Protection GOOSE Virtual input 48 Quality bit Quality VIP 48 * * * * * * *
DDB_VIP_QUALITY_49 1552 SW PFSO event_Protection GOOSE Virtual input 49 Quality bit Quality VIP 49 * * * * * * *
DDB_VIP_QUALITY_50 1553 SW PFSO event_Protection GOOSE Virtual input 50 Quality bit Quality VIP 50 * * * * * * *
DDB_VIP_QUALITY_51 1554 SW PFSO event_Protection GOOSE Virtual input 51 Quality bit Quality VIP 51 * * * * * * *
DDB_VIP_QUALITY_52 1555 SW PFSO event_Protection GOOSE Virtual input 52 Quality bit Quality VIP 52 * * * * * * *
DDB_VIP_QUALITY_53 1556 SW PFSO event_Protection GOOSE Virtual input 53 Quality bit Quality VIP 53 * * * * * * *
DDB_VIP_QUALITY_54 1557 SW PFSO event_Protection GOOSE Virtual input 54 Quality bit Quality VIP 54 * * * * * * *
DDB_VIP_QUALITY_55 1558 SW PFSO event_Protection GOOSE Virtual input 55 Quality bit Quality VIP 55 * * * * * * *
DDB_VIP_QUALITY_56 1559 SW PFSO event_Protection GOOSE Virtual input 56 Quality bit Quality VIP 56 * * * * * * *
DDB_VIP_QUALITY_57 1560 SW PFSO event_Protection GOOSE Virtual input 57 Quality bit Quality VIP 57 * * * * * * *
DDB_VIP_QUALITY_58 1561 SW PFSO event_Protection GOOSE Virtual input 58 Quality bit Quality VIP 58 * * * * * * *
DDB_VIP_QUALITY_59 1562 SW PFSO event_Protection GOOSE Virtual input 59 Quality bit Quality VIP 59 * * * * * * *
DDB_VIP_QUALITY_60 1563 SW PFSO event_Protection GOOSE Virtual input 60 Quality bit Quality VIP 60 * * * * * * *
DDB_VIP_QUALITY_61 1564 SW PFSO event_Protection GOOSE Virtual input 61 Quality bit Quality VIP 61 * * * * * * *
DDB_VIP_QUALITY_62 1565 SW PFSO event_Protection GOOSE Virtual input 62 Quality bit Quality VIP 62 * * * * * * *
DDB_VIP_QUALITY_63 1566 SW PFSO event_Protection GOOSE Virtual input 63 Quality bit Quality VIP 63 * * * * * * *
DDB_VIP_QUALITY_64 1567 SW PFSO event_Protection GOOSE Virtual input 64 Quality bit Quality VIP 64 * * * * * * *
DDB_UNUSED 1568 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1569 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1570 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1571 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1572 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1573 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1574 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1575 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1576 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1577 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1578 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1579 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1580 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1581 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1582 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1583 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1584 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1585 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1586 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1587 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1588 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1589 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1590 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1591 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1592 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1593 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1594 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1595 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1596 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1597 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1598 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1599 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 98 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_VIP_PUB_PRES_1 1600 SW PFSO event_Protection GOOSE Virtual input 1 publisher bit PubPres VIP 1 * * * * * * *
DDB_VIP_PUB_PRES_2 1601 SW PFSO event_Protection GOOSE Virtual input 2 publisher bit PubPres VIP 2 * * * * * * *
DDB_VIP_PUB_PRES_3 1602 SW PFSO event_Protection GOOSE Virtual input 3 publisher bit PubPres VIP 3 * * * * * * *
DDB_VIP_PUB_PRES_4 1603 SW PFSO event_Protection GOOSE Virtual input 4 publisher bit PubPres VIP 4 * * * * * * *
DDB_VIP_PUB_PRES_5 1604 SW PFSO event_Protection GOOSE Virtual input 5 publisher bit PubPres VIP 5 * * * * * * *
DDB_VIP_PUB_PRES_6 1605 SW PFSO event_Protection GOOSE Virtual input 6 publisher bit PubPres VIP 6 * * * * * * *
DDB_VIP_PUB_PRES_7 1606 SW PFSO event_Protection GOOSE Virtual input 7 publisher bit PubPres VIP 7 * * * * * * *
DDB_VIP_PUB_PRES_8 1607 SW PFSO event_Protection GOOSE Virtual input 8 publisher bit PubPres VIP 8 * * * * * * *
DDB_VIP_PUB_PRES_9 1608 SW PFSO event_Protection GOOSE Virtual input 9 publisher bit PubPres VIP 9 * * * * * * *
DDB_VIP_PUB_PRES_10 1609 SW PFSO event_Protection GOOSE Virtual input 10 publisher bit PubPres VIP 10 * * * * * * *
DDB_VIP_PUB_PRES_11 1610 SW PFSO event_Protection GOOSE Virtual input 11 publisher bit PubPres VIP 11 * * * * * * *
DDB_VIP_PUB_PRES_12 1611 SW PFSO event_Protection GOOSE Virtual input 12 publisher bit PubPres VIP 12 * * * * * * *
DDB_VIP_PUB_PRES_13 1612 SW PFSO event_Protection GOOSE Virtual input 13 publisher bit PubPres VIP 13 * * * * * * *
DDB_VIP_PUB_PRES_14 1613 SW PFSO event_Protection GOOSE Virtual input 14 publisher bit PubPres VIP 14 * * * * * * *
DDB_VIP_PUB_PRES_15 1614 SW PFSO event_Protection GOOSE Virtual input 15 publisher bit PubPres VIP 15 * * * * * * *
DDB_VIP_PUB_PRES_16 1615 SW PFSO event_Protection GOOSE Virtual input 16 publisher bit PubPres VIP 16 * * * * * * *
DDB_VIP_PUB_PRES_17 1616 SW PFSO event_Protection GOOSE Virtual input 17 publisher bit PubPres VIP 17 * * * * * * *
DDB_VIP_PUB_PRES_18 1617 SW PFSO event_Protection GOOSE Virtual input 18 publisher bit PubPres VIP 18 * * * * * * *
DDB_VIP_PUB_PRES_19 1618 SW PFSO event_Protection GOOSE Virtual input 19 publisher bit PubPres VIP 19 * * * * * * *
DDB_VIP_PUB_PRES_20 1619 SW PFSO event_Protection GOOSE Virtual input 20 publisher bit PubPres VIP 20 * * * * * * *
DDB_VIP_PUB_PRES_21 1620 SW PFSO event_Protection GOOSE Virtual input 21 publisher bit PubPres VIP 21 * * * * * * *
DDB_VIP_PUB_PRES_22 1621 SW PFSO event_Protection GOOSE Virtual input 22 publisher bit PubPres VIP 22 * * * * * * *
DDB_VIP_PUB_PRES_23 1622 SW PFSO event_Protection GOOSE Virtual input 23 publisher bit PubPres VIP 23 * * * * * * *
DDB_VIP_PUB_PRES_24 1623 SW PFSO event_Protection GOOSE Virtual input 24 publisher bit PubPres VIP 24 * * * * * * *
DDB_VIP_PUB_PRES_25 1624 SW PFSO event_Protection GOOSE Virtual input 25 publisher bit PubPres VIP 25 * * * * * * *
DDB_VIP_PUB_PRES_26 1625 SW PFSO event_Protection GOOSE Virtual input 26 publisher bit PubPres VIP 26 * * * * * * *
DDB_VIP_PUB_PRES_27 1626 SW PFSO event_Protection GOOSE Virtual input 27 publisher bit PubPres VIP 27 * * * * * * *
DDB_VIP_PUB_PRES_28 1627 SW PFSO event_Protection GOOSE Virtual input 28 publisher bit PubPres VIP 28 * * * * * * *
DDB_VIP_PUB_PRES_29 1628 SW PFSO event_Protection GOOSE Virtual input 29 publisher bit PubPres VIP 29 * * * * * * *
DDB_VIP_PUB_PRES_30 1629 SW PFSO event_Protection GOOSE Virtual input 30 publisher bit PubPres VIP 30 * * * * * * *
DDB_VIP_PUB_PRES_31 1630 SW PFSO event_Protection GOOSE Virtual input 31 publisher bit PubPres VIP 31 * * * * * * *
DDB_VIP_PUB_PRES_32 1631 SW PFSO event_Protection GOOSE Virtual input 32 publisher bit PubPres VIP 32 * * * * * * *
DDB_VIP_PUB_PRES_33 1632 SW PFSO event_Protection GOOSE Virtual input 33 publisher bit PubPres VIP 33 * * * * * * *
DDB_VIP_PUB_PRES_34 1633 SW PFSO event_Protection GOOSE Virtual input 34 publisher bit PubPres VIP 34 * * * * * * *
DDB_VIP_PUB_PRES_35 1634 SW PFSO event_Protection GOOSE Virtual input 35 publisher bit PubPres VIP 35 * * * * * * *
DDB_VIP_PUB_PRES_36 1635 SW PFSO event_Protection GOOSE Virtual input 36 publisher bit PubPres VIP 36 * * * * * * *
DDB_VIP_PUB_PRES_37 1636 SW PFSO event_Protection GOOSE Virtual input 37 publisher bit PubPres VIP 37 * * * * * * *
DDB_VIP_PUB_PRES_38 1637 SW PFSO event_Protection GOOSE Virtual input 38 publisher bit PubPres VIP 38 * * * * * * *
DDB_VIP_PUB_PRES_39 1638 SW PFSO event_Protection GOOSE Virtual input 39 publisher bit PubPres VIP 39 * * * * * * *
DDB_VIP_PUB_PRES_40 1639 SW PFSO event_Protection GOOSE Virtual input 40 publisher bit PubPres VIP 40 * * * * * * *
DDB_VIP_PUB_PRES_41 1640 SW PFSO event_Protection GOOSE Virtual input 41 publisher bit PubPres VIP 41 * * * * * * *
DDB_VIP_PUB_PRES_42 1641 SW PFSO event_Protection GOOSE Virtual input 42 publisher bit PubPres VIP 42 * * * * * * *
DDB_VIP_PUB_PRES_43 1642 SW PFSO event_Protection GOOSE Virtual input 43 publisher bit PubPres VIP 43 * * * * * * *
DDB_VIP_PUB_PRES_44 1643 SW PFSO event_Protection GOOSE Virtual input 44 publisher bit PubPres VIP 44 * * * * * * *
DDB_VIP_PUB_PRES_45 1644 SW PFSO event_Protection GOOSE Virtual input 45 publisher bit PubPres VIP 45 * * * * * * *
DDB_VIP_PUB_PRES_46 1645 SW PFSO event_Protection GOOSE Virtual input 46 publisher bit PubPres VIP 46 * * * * * * *
DDB_VIP_PUB_PRES_47 1646 SW PFSO event_Protection GOOSE Virtual input 47 publisher bit PubPres VIP 47 * * * * * * *
DDB_VIP_PUB_PRES_48 1647 SW PFSO event_Protection GOOSE Virtual input 48 publisher bit PubPres VIP 48 * * * * * * *
DDB_VIP_PUB_PRES_49 1648 SW PFSO event_Protection GOOSE Virtual input 49 publisher bit PubPres VIP 49 * * * * * * *
DDB_VIP_PUB_PRES_50 1649 SW PFSO event_Protection GOOSE Virtual input 50 publisher bit PubPres VIP 50 * * * * * * *
DDB_VIP_PUB_PRES_51 1650 SW PFSO event_Protection GOOSE Virtual input 51 publisher bit PubPres VIP 51 * * * * * * *
DDB_VIP_PUB_PRES_52 1651 SW PFSO event_Protection GOOSE Virtual input 52 publisher bit PubPres VIP 52 * * * * * * *
DDB_VIP_PUB_PRES_53 1652 SW PFSO event_Protection GOOSE Virtual input 53 publisher bit PubPres VIP 53 * * * * * * *
DDB_VIP_PUB_PRES_54 1653 SW PFSO event_Protection GOOSE Virtual input 54 publisher bit PubPres VIP 54 * * * * * * *
DDB_VIP_PUB_PRES_55 1654 SW PFSO event_Protection GOOSE Virtual input 55 publisher bit PubPres VIP 55 * * * * * * *
DDB_VIP_PUB_PRES_56 1655 SW PFSO event_Protection GOOSE Virtual input 56 publisher bit PubPres VIP 56 * * * * * * *
DDB_VIP_PUB_PRES_57 1656 SW PFSO event_Protection GOOSE Virtual input 57 publisher bit PubPres VIP 57 * * * * * * *
DDB_VIP_PUB_PRES_58 1657 SW PFSO event_Protection GOOSE Virtual input 58 publisher bit PubPres VIP 58 * * * * * * *
DDB_VIP_PUB_PRES_59 1658 SW PFSO event_Protection GOOSE Virtual input 59 publisher bit PubPres VIP 59 * * * * * * *
DDB_VIP_PUB_PRES_60 1659 SW PFSO event_Protection GOOSE Virtual input 60 publisher bit PubPres VIP 60 * * * * * * *
DDB_VIP_PUB_PRES_61 1660 SW PFSO event_Protection GOOSE Virtual input 61 publisher bit PubPres VIP 61 * * * * * * *
DDB_VIP_PUB_PRES_62 1661 SW PFSO event_Protection GOOSE Virtual input 62 publisher bit PubPres VIP 62 * * * * * * *
DDB_VIP_PUB_PRES_63 1662 SW PFSO event_Protection GOOSE Virtual input 63 publisher bit PubPres VIP 63 * * * * * * *
DDB_VIP_PUB_PRES_64 1663 SW PFSO event_Protection GOOSE Virtual input 64 publisher bit PubPres VIP 64 * * * * * * *
DDB_UNUSED 1664 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1665 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1666 SW UNUSED NO_RESPONSE Unused
470234511.xls
Relay Menu Database DDBSignals
Page 99 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_UNUSED 1667 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1668 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1669 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1670 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1671 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1672 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1673 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1674 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1675 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1676 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1677 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1678 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1679 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1680 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1681 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1682 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1683 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1684 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1685 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1686 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1687 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1688 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1689 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1690 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1691 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1692 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1693 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1694 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1695 SW UNUSED NO_RESPONSE Unused
DDB_GOOSEOUT_1 1696 PSL GOOSEOUT event_Protection Virtual Output 01 Virtual Output01 * * * * * * *
DDB_GOOSEOUT_2 1697 PSL GOOSEOUT event_Protection Virtual Output 02 Virtual Output02 * * * * * * *
DDB_GOOSEOUT_3 1698 PSL GOOSEOUT event_Protection Virtual Output 03 Virtual Output03 * * * * * * *
DDB_GOOSEOUT_4 1699 PSL GOOSEOUT event_Protection Virtual Output 04 Virtual Output04 * * * * * * *
DDB_GOOSEOUT_5 1700 PSL GOOSEOUT event_Protection Virtual Output 05 Virtual Output05 * * * * * * *
DDB_GOOSEOUT_6 1701 PSL GOOSEOUT event_Protection Virtual Output 06 Virtual Output06 * * * * * * *
DDB_GOOSEOUT_7 1702 PSL GOOSEOUT event_Protection Virtual Output 07 Virtual Output07 * * * * * * *
DDB_GOOSEOUT_8 1703 PSL GOOSEOUT event_Protection Virtual Output 08 Virtual Output08 * * * * * * *
DDB_GOOSEOUT_9 1704 PSL GOOSEOUT event_Protection Virtual Output 09 Virtual Output09 * * * * * * *
DDB_GOOSEOUT_10 1705 PSL GOOSEOUT event_Protection Virtual Output 10 Virtual Output10 * * * * * * *
DDB_GOOSEOUT_11 1706 PSL GOOSEOUT event_Protection Virtual Output 11 Virtual Output11 * * * * * * *
DDB_GOOSEOUT_12 1707 PSL GOOSEOUT event_Protection Virtual Output 12 Virtual Output12 * * * * * * *
DDB_GOOSEOUT_13 1708 PSL GOOSEOUT event_Protection Virtual Output 13 Virtual Output13 * * * * * * *
DDB_GOOSEOUT_14 1709 PSL GOOSEOUT event_Protection Virtual Output 14 Virtual Output14 * * * * * * *
DDB_GOOSEOUT_15 1710 PSL GOOSEOUT event_Protection Virtual Output 15 Virtual Output15 * * * * * * *
DDB_GOOSEOUT_16 1711 PSL GOOSEOUT event_Protection Virtual Output 16 Virtual Output16 * * * * * * *
DDB_GOOSEOUT_17 1712 PSL GOOSEOUT event_Protection Virtual Output 17 Virtual Output17 * * * * * * *
DDB_GOOSEOUT_18 1713 PSL GOOSEOUT event_Protection Virtual Output 18 Virtual Output18 * * * * * * *
DDB_GOOSEOUT_19 1714 PSL GOOSEOUT event_Protection Virtual Output 19 Virtual Output19 * * * * * * *
DDB_GOOSEOUT_20 1715 PSL GOOSEOUT event_Protection Virtual Output 20 Virtual Output20 * * * * * * *
DDB_GOOSEOUT_21 1716 PSL GOOSEOUT event_Protection Virtual Output 21 Virtual Output21 * * * * * * *
DDB_GOOSEOUT_22 1717 PSL GOOSEOUT event_Protection Virtual Output 22 Virtual Output22 * * * * * * *
DDB_GOOSEOUT_23 1718 PSL GOOSEOUT event_Protection Virtual Output 23 Virtual Output23 * * * * * * *
DDB_GOOSEOUT_24 1719 PSL GOOSEOUT event_Protection Virtual Output 24 Virtual Output24 * * * * * * *
DDB_GOOSEOUT_25 1720 PSL GOOSEOUT event_Protection Virtual Output 25 Virtual Output25 * * * * * * *
DDB_GOOSEOUT_26 1721 PSL GOOSEOUT event_Protection Virtual Output 26 Virtual Output26 * * * * * * *
DDB_GOOSEOUT_27 1722 PSL GOOSEOUT event_Protection Virtual Output 27 Virtual Output27 * * * * * * *
DDB_GOOSEOUT_28 1723 PSL GOOSEOUT event_Protection Virtual Output 28 Virtual Output28 * * * * * * *
DDB_GOOSEOUT_29 1724 PSL GOOSEOUT event_Protection Virtual Output 29 Virtual Output29 * * * * * * *
DDB_GOOSEOUT_30 1725 PSL GOOSEOUT event_Protection Virtual Output 30 Virtual Output30 * * * * * * *
DDB_GOOSEOUT_31 1726 PSL GOOSEOUT event_Protection Virtual Output 31 Virtual Output31 * * * * * * *
DDB_GOOSEOUT_32 1727 PSL GOOSEOUT event_Protection Virtual Output 32 Virtual Output32 * * * * * * *
DDB_GOOSEOUT_33 1728 PSL GOOSEOUT event_Protection Virtual Output 33 Virtual Output33 * * * * * * *
DDB_GOOSEOUT_34 1729 PSL GOOSEOUT event_Protection Virtual Output 34 Virtual Output34 * * * * * * *
DDB_GOOSEOUT_35 1730 PSL GOOSEOUT event_Protection Virtual Output 35 Virtual Output35 * * * * * * *
DDB_GOOSEOUT_36 1731 PSL GOOSEOUT event_Protection Virtual Output 36 Virtual Output36 * * * * * * *
DDB_GOOSEOUT_37 1732 PSL GOOSEOUT event_Protection Virtual Output 37 Virtual Output37 * * * * * * *
DDB_GOOSEOUT_38 1733 PSL GOOSEOUT event_Protection Virtual Output 38 Virtual Output38 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 100 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_GOOSEOUT_39 1734 PSL GOOSEOUT event_Protection Virtual Output 39 Virtual Output39 * * * * * * *
DDB_GOOSEOUT_40 1735 PSL GOOSEOUT event_Protection Virtual Output 40 Virtual Output40 * * * * * * *
DDB_GOOSEOUT_41 1736 PSL GOOSEOUT event_Protection Virtual Output 41 Virtual Output41 * * * * * * *
DDB_GOOSEOUT_42 1737 PSL GOOSEOUT event_Protection Virtual Output 42 Virtual Output42 * * * * * * *
DDB_GOOSEOUT_43 1738 PSL GOOSEOUT event_Protection Virtual Output 43 Virtual Output43 * * * * * * *
DDB_GOOSEOUT_44 1739 PSL GOOSEOUT event_Protection Virtual Output 44 Virtual Output44 * * * * * * *
DDB_GOOSEOUT_45 1740 PSL GOOSEOUT event_Protection Virtual Output 45 Virtual Output45 * * * * * * *
DDB_GOOSEOUT_46 1741 PSL GOOSEOUT event_Protection Virtual Output 46 Virtual Output46 * * * * * * *
DDB_GOOSEOUT_47 1742 PSL GOOSEOUT event_Protection Virtual Output 47 Virtual Output47 * * * * * * *
DDB_GOOSEOUT_48 1743 PSL GOOSEOUT event_Protection Virtual Output 48 Virtual Output48 * * * * * * *
DDB_GOOSEOUT_49 1744 PSL GOOSEOUT event_Protection Virtual Output 49 Virtual Output49 * * * * * * *
DDB_GOOSEOUT_50 1745 PSL GOOSEOUT event_Protection Virtual Output 50 Virtual Output50 * * * * * * *
DDB_GOOSEOUT_51 1746 PSL GOOSEOUT event_Protection Virtual Output 51 Virtual Output51 * * * * * * *
DDB_GOOSEOUT_52 1747 PSL GOOSEOUT event_Protection Virtual Output 52 Virtual Output52 * * * * * * *
DDB_GOOSEOUT_53 1748 PSL GOOSEOUT event_Protection Virtual Output 53 Virtual Output53 * * * * * * *
DDB_GOOSEOUT_54 1749 PSL GOOSEOUT event_Protection Virtual Output 54 Virtual Output54 * * * * * * *
DDB_GOOSEOUT_55 1750 PSL GOOSEOUT event_Protection Virtual Output 55 Virtual Output55 * * * * * * *
DDB_GOOSEOUT_56 1751 PSL GOOSEOUT event_Protection Virtual Output 56 Virtual Output56 * * * * * * *
DDB_GOOSEOUT_57 1752 PSL GOOSEOUT event_Protection Virtual Output 57 Virtual Output57 * * * * * * *
DDB_GOOSEOUT_58 1753 PSL GOOSEOUT event_Protection Virtual Output 58 Virtual Output58 * * * * * * *
DDB_GOOSEOUT_59 1754 PSL GOOSEOUT event_Protection Virtual Output 59 Virtual Output59 * * * * * * *
DDB_GOOSEOUT_60 1755 PSL GOOSEOUT event_Protection Virtual Output 60 Virtual Output60 * * * * * * *
DDB_GOOSEOUT_61 1756 PSL GOOSEOUT event_Protection Virtual Output 61 Virtual Output61 * * * * * * *
DDB_GOOSEOUT_62 1757 PSL GOOSEOUT event_Protection Virtual Output 62 Virtual Output62 * * * * * * *
DDB_GOOSEOUT_63 1758 PSL GOOSEOUT event_Protection Virtual Output 63 Virtual Output63 * * * * * * *
DDB_GOOSEOUT_64 1759 PSL GOOSEOUT event_Protection Virtual Output 64 Virtual Output64 * * * * * * *
DDB_UNUSED 1760 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1761 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1762 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1763 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1764 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1765 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1766 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1767 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1768 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1769 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1770 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1771 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1772 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1773 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1774 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1775 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1776 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1777 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1778 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1779 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1780 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1781 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1782 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1783 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1784 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1785 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1786 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1787 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1788 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1789 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1790 SW UNUSED NO_RESPONSE Unused
DDB_UNUSED 1791 SW UNUSED NO_RESPONSE Unused
DDB_PSLINT_1 1792 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 1 * * * * * * *
DDB_PSLINT_2 1793 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 2 * * * * * * *
DDB_PSLINT_3 1794 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 3 * * * * * * *
DDB_PSLINT_4 1795 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 4 * * * * * * *
DDB_PSLINT_5 1796 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 5 * * * * * * *
DDB_PSLINT_6 1797 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 6 * * * * * * *
DDB_PSLINT_7 1798 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 7 * * * * * * *
DDB_PSLINT_8 1799 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 8 * * * * * * *
DDB_PSLINT_9 1800 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 9 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 101 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_PSLINT_10 1801 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 10 * * * * * * *
DDB_PSLINT_11 1802 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 11 * * * * * * *
DDB_PSLINT_12 1803 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 12 * * * * * * *
DDB_PSLINT_13 1804 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 13 * * * * * * *
DDB_PSLINT_14 1805 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 14 * * * * * * *
DDB_PSLINT_15 1806 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 15 * * * * * * *
DDB_PSLINT_16 1807 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 16 * * * * * * *
DDB_PSLINT_17 1808 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 17 * * * * * * *
DDB_PSLINT_18 1809 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 18 * * * * * * *
DDB_PSLINT_19 1810 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 19 * * * * * * *
DDB_PSLINT_20 1811 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 20 * * * * * * *
DDB_PSLINT_21 1812 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 21 * * * * * * *
DDB_PSLINT_22 1813 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 22 * * * * * * *
DDB_PSLINT_23 1814 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 23 * * * * * * *
DDB_PSLINT_24 1815 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 24 * * * * * * *
DDB_PSLINT_25 1816 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 25 * * * * * * *
DDB_PSLINT_26 1817 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 26 * * * * * * *
DDB_PSLINT_27 1818 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 27 * * * * * * *
DDB_PSLINT_28 1819 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 28 * * * * * * *
DDB_PSLINT_29 1820 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 29 * * * * * * *
DDB_PSLINT_30 1821 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 30 * * * * * * *
DDB_PSLINT_31 1822 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 31 * * * * * * *
DDB_PSLINT_32 1823 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 32 * * * * * * *
DDB_PSLINT_33 1824 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 33 * * * * * * *
DDB_PSLINT_34 1825 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 34 * * * * * * *
DDB_PSLINT_35 1826 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 35 * * * * * * *
DDB_PSLINT_36 1827 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 36 * * * * * * *
DDB_PSLINT_37 1828 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 37 * * * * * * *
DDB_PSLINT_38 1829 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 38 * * * * * * *
DDB_PSLINT_39 1830 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 39 * * * * * * *
DDB_PSLINT_40 1831 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 40 * * * * * * *
DDB_PSLINT_41 1832 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 41 * * * * * * *
DDB_PSLINT_42 1833 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 42 * * * * * * *
DDB_PSLINT_43 1834 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 43 * * * * * * *
DDB_PSLINT_44 1835 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 44 * * * * * * *
DDB_PSLINT_45 1836 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 45 * * * * * * *
DDB_PSLINT_46 1837 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 46 * * * * * * *
DDB_PSLINT_47 1838 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 47 * * * * * * *
DDB_PSLINT_48 1839 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 48 * * * * * * *
DDB_PSLINT_49 1840 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 49 * * * * * * *
DDB_PSLINT_50 1841 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 50 * * * * * * *
DDB_PSLINT_51 1842 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 51 * * * * * * *
DDB_PSLINT_52 1843 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 52 * * * * * * *
DDB_PSLINT_53 1844 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 53 * * * * * * *
DDB_PSLINT_54 1845 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 54 * * * * * * *
DDB_PSLINT_55 1846 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 55 * * * * * * *
DDB_PSLINT_56 1847 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 56 * * * * * * *
DDB_PSLINT_57 1848 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 57 * * * * * * *
DDB_PSLINT_58 1849 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 58 * * * * * * *
DDB_PSLINT_59 1850 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 59 * * * * * * *
DDB_PSLINT_60 1851 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 60 * * * * * * *
DDB_PSLINT_61 1852 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 61 * * * * * * *
DDB_PSLINT_62 1853 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 62 * * * * * * *
DDB_PSLINT_63 1854 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 63 * * * * * * *
DDB_PSLINT_64 1855 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 64 * * * * * * *
DDB_PSLINT_65 1856 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 65 * * * * * * *
DDB_PSLINT_66 1857 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 66 * * * * * * *
DDB_PSLINT_67 1858 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 67 * * * * * * *
DDB_PSLINT_68 1859 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 68 * * * * * * *
DDB_PSLINT_69 1860 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 69 * * * * * * *
DDB_PSLINT_70 1861 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 70 * * * * * * *
DDB_PSLINT_71 1862 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 71 * * * * * * *
DDB_PSLINT_72 1863 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 72 * * * * * * *
DDB_PSLINT_73 1864 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 73 * * * * * * *
DDB_PSLINT_74 1865 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 74 * * * * * * *
DDB_PSLINT_75 1866 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 75 * * * * * * *
DDB_PSLINT_76 1867 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 76 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 102 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_PSLINT_77 1868 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 77 * * * * * * *
DDB_PSLINT_78 1869 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 78 * * * * * * *
DDB_PSLINT_79 1870 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 79 * * * * * * *
DDB_PSLINT_80 1871 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 80 * * * * * * *
DDB_PSLINT_81 1872 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 81 * * * * * * *
DDB_PSLINT_82 1873 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 82 * * * * * * *
DDB_PSLINT_83 1874 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 83 * * * * * * *
DDB_PSLINT_84 1875 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 84 * * * * * * *
DDB_PSLINT_85 1876 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 85 * * * * * * *
DDB_PSLINT_86 1877 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 86 * * * * * * *
DDB_PSLINT_87 1878 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 87 * * * * * * *
DDB_PSLINT_88 1879 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 88 * * * * * * *
DDB_PSLINT_89 1880 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 89 * * * * * * *
DDB_PSLINT_90 1881 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 90 * * * * * * *
DDB_PSLINT_91 1882 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 91 * * * * * * *
DDB_PSLINT_92 1883 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 92 * * * * * * *
DDB_PSLINT_93 1884 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 93 * * * * * * *
DDB_PSLINT_94 1885 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 94 * * * * * * *
DDB_PSLINT_95 1886 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 95 * * * * * * *
DDB_PSLINT_96 1887 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 96 * * * * * * *
DDB_PSLINT_97 1888 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 97 * * * * * * *
DDB_PSLINT_98 1889 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 98 * * * * * * *
DDB_PSLINT_99 1890 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 99 * * * * * * *
DDB_PSLINT_100 1891 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 100 * * * * * * *
DDB_PSLINT_101 1892 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 101 * * * * * * *
DDB_PSLINT_102 1893 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 102 * * * * * * *
DDB_PSLINT_103 1894 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 103 * * * * * * *
DDB_PSLINT_104 1895 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 104 * * * * * * *
DDB_PSLINT_105 1896 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 105 * * * * * * *
DDB_PSLINT_106 1897 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 106 * * * * * * *
DDB_PSLINT_107 1898 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 107 * * * * * * *
DDB_PSLINT_108 1899 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 108 * * * * * * *
DDB_PSLINT_109 1900 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 109 * * * * * * *
DDB_PSLINT_110 1901 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 110 * * * * * * *
DDB_PSLINT_111 1902 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 111 * * * * * * *
DDB_PSLINT_112 1903 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 112 * * * * * * *
DDB_PSLINT_113 1904 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 113 * * * * * * *
DDB_PSLINT_114 1905 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 114 * * * * * * *
DDB_PSLINT_115 1906 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 115 * * * * * * *
DDB_PSLINT_116 1907 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 116 * * * * * * *
DDB_PSLINT_117 1908 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 117 * * * * * * *
DDB_PSLINT_118 1909 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 118 * * * * * * *
DDB_PSLINT_119 1910 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 119 * * * * * * *
DDB_PSLINT_120 1911 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 120 * * * * * * *
DDB_PSLINT_121 1912 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 121 * * * * * * *
DDB_PSLINT_122 1913 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 122 * * * * * * *
DDB_PSLINT_123 1914 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 123 * * * * * * *
DDB_PSLINT_124 1915 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 124 * * * * * * *
DDB_PSLINT_125 1916 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 125 * * * * * * *
DDB_PSLINT_126 1917 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 126 * * * * * * *
DDB_PSLINT_127 1918 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 127 * * * * * * *
DDB_PSLINT_128 1919 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 128 * * * * * * *
DDB_PSLINT_129 1920 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 129 * * * * * * *
DDB_PSLINT_130 1921 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 130 * * * * * * *
DDB_PSLINT_131 1922 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 131 * * * * * * *
DDB_PSLINT_132 1923 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 132 * * * * * * *
DDB_PSLINT_133 1924 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 133 * * * * * * *
DDB_PSLINT_134 1925 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 134 * * * * * * *
DDB_PSLINT_135 1926 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 135 * * * * * * *
DDB_PSLINT_136 1927 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 136 * * * * * * *
DDB_PSLINT_137 1928 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 137 * * * * * * *
DDB_PSLINT_138 1929 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 138 * * * * * * *
DDB_PSLINT_139 1930 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 139 * * * * * * *
DDB_PSLINT_140 1931 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 140 * * * * * * *
DDB_PSLINT_141 1932 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 141 * * * * * * *
DDB_PSLINT_142 1933 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 142 * * * * * * *
DDB_PSLINT_143 1934 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 143 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 103 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_PSLINT_144 1935 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 144 * * * * * * *
DDB_PSLINT_145 1936 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 145 * * * * * * *
DDB_PSLINT_146 1937 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 146 * * * * * * *
DDB_PSLINT_147 1938 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 147 * * * * * * *
DDB_PSLINT_148 1939 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 148 * * * * * * *
DDB_PSLINT_149 1940 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 149 * * * * * * *
DDB_PSLINT_150 1941 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 150 * * * * * * *
DDB_PSLINT_151 1942 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 151 * * * * * * *
DDB_PSLINT_152 1943 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 152 * * * * * * *
DDB_PSLINT_153 1944 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 153 * * * * * * *
DDB_PSLINT_154 1945 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 154 * * * * * * *
DDB_PSLINT_155 1946 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 155 * * * * * * *
DDB_PSLINT_156 1947 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 156 * * * * * * *
DDB_PSLINT_157 1948 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 157 * * * * * * *
DDB_PSLINT_158 1949 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 158 * * * * * * *
DDB_PSLINT_159 1950 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 159 * * * * * * *
DDB_PSLINT_160 1951 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 160 * * * * * * *
DDB_PSLINT_161 1952 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 161 * * * * * * *
DDB_PSLINT_162 1953 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 162 * * * * * * *
DDB_PSLINT_163 1954 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 163 * * * * * * *
DDB_PSLINT_164 1955 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 164 * * * * * * *
DDB_PSLINT_165 1956 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 165 * * * * * * *
DDB_PSLINT_166 1957 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 166 * * * * * * *
DDB_PSLINT_167 1958 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 167 * * * * * * *
DDB_PSLINT_168 1959 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 168 * * * * * * *
DDB_PSLINT_169 1960 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 169 * * * * * * *
DDB_PSLINT_170 1961 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 170 * * * * * * *
DDB_PSLINT_171 1962 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 171 * * * * * * *
DDB_PSLINT_172 1963 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 172 * * * * * * *
DDB_PSLINT_173 1964 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 173 * * * * * * *
DDB_PSLINT_174 1965 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 174 * * * * * * *
DDB_PSLINT_175 1966 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 175 * * * * * * *
DDB_PSLINT_176 1967 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 176 * * * * * * *
DDB_PSLINT_177 1968 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 177 * * * * * * *
DDB_PSLINT_178 1969 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 178 * * * * * * *
DDB_PSLINT_179 1970 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 179 * * * * * * *
DDB_PSLINT_180 1971 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 180 * * * * * * *
DDB_PSLINT_181 1972 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 181 * * * * * * *
DDB_PSLINT_182 1973 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 182 * * * * * * *
DDB_PSLINT_183 1974 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 183 * * * * * * *
DDB_PSLINT_184 1975 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 184 * * * * * * *
DDB_PSLINT_185 1976 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 185 * * * * * * *
DDB_PSLINT_186 1977 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 186 * * * * * * *
DDB_PSLINT_187 1978 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 187 * * * * * * *
DDB_PSLINT_188 1979 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 188 * * * * * * *
DDB_PSLINT_189 1980 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 189 * * * * * * *
DDB_PSLINT_190 1981 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 190 * * * * * * *
DDB_PSLINT_191 1982 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 191 * * * * * * *
DDB_PSLINT_192 1983 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 192 * * * * * * *
DDB_PSLINT_193 1984 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 193 * * * * * * *
DDB_PSLINT_194 1985 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 194 * * * * * * *
DDB_PSLINT_195 1986 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 195 * * * * * * *
DDB_PSLINT_196 1987 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 196 * * * * * * *
DDB_PSLINT_197 1988 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 197 * * * * * * *
DDB_PSLINT_198 1989 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 198 * * * * * * *
DDB_PSLINT_199 1990 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 199 * * * * * * *
DDB_PSLINT_200 1991 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 200 * * * * * * *
DDB_PSLINT_201 1992 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 201 * * * * * * *
DDB_PSLINT_202 1993 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 202 * * * * * * *
DDB_PSLINT_203 1994 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 203 * * * * * * *
DDB_PSLINT_204 1995 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 204 * * * * * * *
DDB_PSLINT_205 1996 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 205 * * * * * * *
DDB_PSLINT_206 1997 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 206 * * * * * * *
DDB_PSLINT_207 1998 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 207 * * * * * * *
DDB_PSLINT_208 1999 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 208 * * * * * * *
DDB_PSLINT_209 2000 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 209 * * * * * * *
DDB_PSLINT_210 2001 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 210 * * * * * * *
470234511.xls
Relay Menu Database DDBSignals
Page 104 of 163
Element Name Ordinal Source Type Response Fn Description English Text M1 M2 M3 M4 M5 M6 M7
DDB_PSLINT_211 2002 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 211 * * * * * * *
DDB_PSLINT_212 2003 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 212 * * * * * * *
DDB_PSLINT_213 2004 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 213 * * * * * * *
DDB_PSLINT_214 2005 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 214 * * * * * * *
DDB_PSLINT_215 2006 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 215 * * * * * * *
DDB_PSLINT_216 2007 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 216 * * * * * * *
DDB_PSLINT_217 2008 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 217 * * * * * * *
DDB_PSLINT_218 2009 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 218 * * * * * * *
DDB_PSLINT_219 2010 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 219 * * * * * * *
DDB_PSLINT_220 2011 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 220 * * * * * * *
DDB_PSLINT_221 2012 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 221 * * * * * * *
DDB_PSLINT_222 2013 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 222 * * * * * * *
DDB_PSLINT_223 2014 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 223 * * * * * * *
DDB_PSLINT_224 2015 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 224 * * * * * * *
DDB_PSLINT_225 2016 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 225 * * * * * * *
DDB_PSLINT_226 2017 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 226 * * * * * * *
DDB_PSLINT_227 2018 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 227 * * * * * * *
DDB_PSLINT_228 2019 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 228 * * * * * * *
DDB_PSLINT_229 2020 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 229 * * * * * * *
DDB_PSLINT_230 2021 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 230 * * * * * * *
DDB_PSLINT_231 2022 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 231 * * * * * * *
DDB_PSLINT_232 2023 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 232 * * * * * * *
DDB_PSLINT_233 2024 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 233 * * * * * * *
DDB_PSLINT_234 2025 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 234 * * * * * * *
DDB_PSLINT_235 2026 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 235 * * * * * * *
DDB_PSLINT_236 2027 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 236 * * * * * * *
DDB_PSLINT_237 2028 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 237 * * * * * * *
DDB_PSLINT_238 2029 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 238 * * * * * * *
DDB_PSLINT_239 2030 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 239 * * * * * * *
DDB_PSLINT_240 2031 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 240 * * * * * * *
DDB_PSLINT_241 2032 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 241 * * * * * * *
DDB_PSLINT_242 2033 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 242 * * * * * * *
DDB_PSLINT_243 2034 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 243 * * * * * * *
DDB_PSLINT_244 2035 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 244 * * * * * * *
DDB_PSLINT_245 2036 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 245 * * * * * * *
DDB_PSLINT_246 2037 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 246 * * * * * * *
DDB_PSLINT_247 2038 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 247 * * * * * * *
DDB_PSLINT_248 2039 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 248 * * * * * * *
DDB_PSLINT_249 2040 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 249 * * * * * * *
DDB_PSLINT_250 2041 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 250 * * * * * * *
DDB_PSLINT_251 2042 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 251 * * * * * * *
DDB_PSLINT_252 2043 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 252 * * * * * * *
DDB_PSLINT_253 2044 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 253 * * * * * * *
DDB_PSLINT_254 2045 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 254 * * * * * * *
DDB_PSLINT_255 2046 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 255 * * * * * * *
DDB_PSLINT_256 2047 PSL PSLINT NO_RESPONSE PSL Internal connection PSL Int. 256 * * * * * * *
470234511.xls
Relay Menu Database Events
Page 105 of 163

Event record specification for Courier and Modbus interfaces


Event Model Courier Events: Modbus Events:
Event Event Type Modbus Additional
Name P341(3x) P342 P343 P344 P345 P341(7x) Options Cell Ref Extraction Text Value (Binary Flag) Bit (See G13) Event Value 3x10008 Register Event Index 3x10011 Data
Column 3x10007 3x10010 3x10012
Opto-Isolated Status Input Events * * * * * * 0020 Status Input user label + ON/OFF 32 bit binary flag value 5 32 bit binary flag value 311025 0 0
Relay Contact Output Events * * * * * * 0021 Relay Contact user label + ON/OFF 32 bit binary flag value 4 32 bit binary flag value 311023 0 0
Alarm Status 1 Events (alarms 1 - 32):
Not Used * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000000001 0 - 00000000000000000000000000000001 30011 Bit 15=state, bits 0-14=0 0
F out of Range * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000000010 1 2 or 3 00000000000000000000000000000010 30011 Bit 15=state, bits 0-14=1 0
SG-DDB Invalid * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000000100 2 2 or 3 00000000000000000000000000000100 30011 Bit 15=state, bits 0-14=2 0
Prot'n Disabled * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000001000 3 2 or 3 00000000000000000000000000001000 30011 Bit 15=state, bits 0-14=3 0
VT Fail Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000010000 4 2 or 3 00000000000000000000000000010000 30011 Bit 15=state, bits 0-14=4 0
CT-1 Fail Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000000100000 5 2 or 3 00000000000000000000000000100000 30011 Bit 15=state, bits 0-14=5 0
CB Fail * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000001000000 6 0 or 1 00000000000000000000000001000000 30011 Bit 15=state, bits 0-14=6 0
I^ Maint Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000010000000 7 2 or 3 00000000000000000000000010000000 30011 Bit 15=state, bits 0-14=7 0
I^ Maint Lockout * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000000100000000 8 2 or 3 00000000000000000000000100000000 30011 Bit 15=state, bits 0-14=8 0
CB OPs Maint * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000001000000000 9 2 or 3 00000000000000000000001000000000 30011 Bit 15=state, bits 0-14=9 0
CB OPs Lock * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000010000000000 10 2 or 3 00000000000000000000010000000000 30011 Bit 15=state, bits 0-14=10 0
CB Time Maint * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000000100000000000 11 2 or 3 00000000000000000000100000000000 30011 Bit 15=state, bits 0-14=11 0
CB Time Lockout * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000001000000000000 12 2 or 3 00000000000000000001000000000000 30011 Bit 15=state, bits 0-14=12 0
Fault Freq Lock * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000010000000000000 13 2 or 3 00000000000000000010000000000000 30011 Bit 15=state, bits 0-14=13 0
CB Status Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000000000000100000000000000 14 0 or 1 00000000000000000100000000000000 30011 Bit 15=state, bits 0-14=14 0
CB Trip Fail * * * * * * 0022 Alarm Name + ON/OFF 00000000000000001000000000000000 15 0 or 1 00000000000000001000000000000000 30011 Bit 15=state, bits 0-14=15 0
CB Close Fail * * * * * * 0022 Alarm Name + ON/OFF 00000000000000010000000000000000 16 0 or 1 00000000000000010000000000000000 30011 Bit 15=state, bits 0-14=16 0
Man CB Unhealthy * * * * * * 0022 Alarm Name + ON/OFF 00000000000000100000000000000000 17 0 or 1 00000000000000100000000000000000 30011 Bit 15=state, bits 0-14=17 0
NPS thermal Alm * * * * 0022 Alarm Name + ON/OFF 00000000000001000000000000000000 18 0 or 1 00000000000001000000000000000000 30011 Bit 15=state, bits 0-14=18 0
Thermal Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000000010000000000000000000 19 0 or 1 00000000000010000000000000000000 30011 Bit 15=state, bits 0-14=19 0
V/Hz Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000000100000000000000000000 20 0 or 1 00000000000100000000000000000000 30011 Bit 15=state, bits 0-14=20 0
Field Fail Alarm * * * * * * 0022 Alarm Name + ON/OFF 00000000001000000000000000000000 21 0 or 1 00000000001000000000000000000000 30011 Bit 15=state, bits 0-14=21 0
RTD Thermal Alm * * * * * * 0022 Alarm Name + ON/OFF 00000000010000000000000000000000 22 0 or 1 00000000010000000000000000000000 30011 Bit 15=state, bits 0-14=22 0
RTD Open Cct * * * * * * 0022 Alarm Name + ON/OFF 00000000100000000000000000000000 23 0 or 1 00000000100000000000000000000000 30011 Bit 15=state, bits 0-14=23 0
RTD short Cct * * * * * * 0022 Alarm Name + ON/OFF 00000001000000000000000000000000 24 0 or 1 00000001000000000000000000000000 30011 Bit 15=state, bits 0-14=24 0
RTD Data Error * * * * * * 0022 Alarm Name + ON/OFF 00000010000000000000000000000000 25 0 or 1 00000010000000000000000000000000 30011 Bit 15=state, bits 0-14=25 0
RTD Board Fail * * * * * * 0022 Alarm Name + ON/OFF 00000100000000000000000000000000 26 0 or 1 00000100000000000000000000000000 30011 Bit 15=state, bits 0-14=26 0
Freq Prot Alm * * * * * * 0022 Alarm Name + ON/OFF 00001000000000000000000000000000 27 0 or 1 00001000000000000000000000000000 30011 Bit 15=state, bits 0-14=27 0
Voltage Prot Alm * * * * * * 0022 Alarm Name + ON/OFF 00010000000000000000000000000000 28 0 or 1 00010000000000000000000000000000 30011 Bit 15=state, bits 0-14=28 0
CT-2 Fail Alarm * * * 0022 Alarm Name + ON/OFF 00100000000000000000000000000000 29 2 or 3 00100000000000000000000000000000 30011 Bit 15=state, bits 0-14=29 0
64S R<1 Alarm * 0022 Alarm Name + ON/OFF 01000000000000000000000000000000 30 0 or 1 01000000000000000000000000000000 30011 Bit 15=state, bits 0-14=30 0
64S Fail Alarm * 0022 Alarm Name + ON/OFF 10000000000000000000000000000000 31 2 or 3 10000000000000000000000000000000 30011 Bit 15=state, bits 0-14=31 0
Alarm Status 2 Events (alarms 33 - 64):
CL Card I/P Fail * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000000001 0 0 or 1 00000000000000000000000000000001 30013 Bit 15=state, bits 0-14=32 0
CL Card O/P Fail * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000000010 1 0 or 1 00000000000000000000000000000010 30013 Bit 15=state, bits 0-14=33 0
CL Input 1 Alarm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000000100 2 0 or 1 00000000000000000000000000000100 30013 Bit 15=state, bits 0-14=34 0
CL Input 2 Alarm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000001000 3 0 or 1 00000000000000000000000000001000 30013 Bit 15=state, bits 0-14=35 0
CL Input 3 Alarm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000010000 4 0 or 1 00000000000000000000000000010000 30013 Bit 15=state, bits 0-14=36 0
CL Input 4 Alarm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000000100000 5 0 or 1 00000000000000000000000000100000 30013 Bit 15=state, bits 0-14=37 0
CLI1 I< Fail Alm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000001000000 6 0 or 1 00000000000000000000000001000000 30013 Bit 15=state, bits 0-14=38 0
CLI2 I< Fail Alm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000010000000 7 0 or 1 00000000000000000000000010000000 30013 Bit 15=state, bits 0-14=39 0
CLI3 I< Fail Alm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000000100000000 8 0 or 1 00000000000000000000000100000000 30013 Bit 15=state, bits 0-14=40 0
CLI4 I< Fail Alm * * * * * * CLIO 0051 Alarm Name + ON/OFF 00000000000000000000001000000000 9 0 or 1 00000000000000000000001000000000 30013 Bit 15=state, bits 0-14=41 0
64R R<1 Alarm * * * * 0051 Alarm Name + ON/OFF 00000000000000000000010000000000 10 0 or 1 00000000000000000000010000000000 30013 Bit 15=state, bits 0-14=42 0
64R CL I/P Fail * * * * 0051 Alarm Name + ON/OFF 00000000000000000000100000000000 11 0 or 1 00000000000000000000100000000000 30013 Bit 15=state, bits 0-14=43 0
CT Para Mismatch * * * 0051 Alarm Name + ON/OFF 00000000000000000001000000000000 12 0 or 1 00000000000000000001000000000000 30013 Bit 15=state, bits 0-14=44 0
Amb T Fail Alm * 0051 Alarm Name + ON/OFF 00000000000000000001000000000000 12 0 or 1 00000000000000000001000000000000 30013 Bit 15=state, bits 0-14=44 0
LOL Alarm * * * * 0051 Alarm Name + ON/OFF 00000000000000000010000000000000 13 0 or 1 00000000000000000010000000000000 30013 Bit 15=state, bits 0-14=45 0
Wind V Fail Alm * 0051 Alarm Name + ON/OFF 00000000000000000010000000000000 13 0 or 1 00000000000000000010000000000000 30013 Bit 15=state, bits 0-14=45 0
FAA Alarm * * * * 0051 Alarm Name + ON/OFF 00000000000000000100000000000000 14 0 or 1 00000000000000000100000000000000 30013 Bit 15=state, bits 0-14=46 0
Wind D Fail Alm * 0051 Alarm Name + ON/OFF 00000000000000000100000000000000 14 0 or 1 00000000000000000100000000000000 30013 Bit 15=state, bits 0-14=46 0
Thru Fault Alm * * * * 0051 Alarm Name + ON/OFF 00000000000000001000000000000000 15 0 or 1 00000000000000001000000000000000 30013 Bit 15=state, bits 0-14=47 0
Solar R Fail Alm * 0051 Alarm Name + ON/OFF 00000000000000001000000000000000 15 0 or 1 00000000000000001000000000000000 30013 Bit 15=state, bits 0-14=47 0
Cct Fail Alarm * * * * 0051 Alarm Name + ON/OFF 00000000000000010000000000000000 16 0 or 1 00000000000000010000000000000000 30013 Bit 15=state, bits 0-14=48 0
Tol Pretrip Alm * * * * * 0051 Alarm Name + ON/OFF 00000000000000100000000000000000 17 0 or 1 00000000000000100000000000000000 30013 Bit 15=state, bits 0-14=49 0
CT Fail Alarm * * * * 0051 Alarm Name + ON/OFF 00000000000001000000000000000000 18 0 or 1 00000000000001000000000000000000 30013 Bit 15=state, bits 0-14=50 0
Man No Checksync * * * * * * 0051 Alarm Name + ON/OFF 00000000000010000000000000000000 19 0 or 1 00000000000010000000000000000000 30013 Bit 15=state, bits 0-14=51 0
System Split Alm * * * * * * 0051 Alarm Name + ON/OFF 00000000000100000000000000000000 20 0 or 1 00000000000100000000000000000000 30013 Bit 15=state, bits 0-14=52 0
MR User Alarm 11 * * * * * * 0051 Alarm Name + ON/OFF 00000000001000000000000000000000 21 0 or 1 00000000001000000000000000000000 30013 Bit 15=state, bits 0-14=53 0
MR User Alarm 10 * * * * * * 0051 Alarm Name + ON/OFF 00000000010000000000000000000000 22 0 or 1 00000000010000000000000000000000 30013 Bit 15=state, bits 0-14=54 0
MR User Alarm 9 * * * * * * 0051 Alarm Name + ON/OFF 00000000100000000000000000000000 23 0 or 1 00000000100000000000000000000000 30013 Bit 15=state, bits 0-14=55 0
MR User Alarm 8 * * * * * * 0051 Alarm Name + ON/OFF 00000001000000000000000000000000 24 0 or 1 00000001000000000000000000000000 30013 Bit 15=state, bits 0-14=56 0
MR User Alarm 7 * * * * * * 0051 Alarm Name + ON/OFF 00000010000000000000000000000000 25 0 or 1 00000010000000000000000000000000 30013 Bit 15=state, bits 0-14=57 0
MR User Alarm 6 * * * * * * 0051 Alarm Name + ON/OFF 00000100000000000000000000000000 26 0 or 1 00000100000000000000000000000000 30013 Bit 15=state, bits 0-14=58 0
MR User Alarm 5 * * * * * * 0051 Alarm Name + ON/OFF 00001000000000000000000000000000 27 0 or 1 00001000000000000000000000000000 30013 Bit 15=state, bits 0-14=59 0
SR User Alarm 4 * * * * * * 0051 Alarm Name + ON/OFF 00010000000000000000000000000000 28 2 or 3 00010000000000000000000000000000 30013 Bit 15=state, bits 0-14=60 0
SR User Alarm 3 * * * * * * 0051 Alarm Name + ON/OFF 00100000000000000000000000000000 29 2 or 3 00100000000000000000000000000000 30013 Bit 15=state, bits 0-14=61 0
SR User Alarm 2 * * * * * * 0051 Alarm Name + ON/OFF 01000000000000000000000000000000 30 2 or 3 01000000000000000000000000000000 30013 Bit 15=state, bits 0-14=62 0
SR User Alarm 1 * * * * * * 0051 Alarm Name + ON/OFF 10000000000000000000000000000000 31 2 or 3 10000000000000000000000000000000 30013 Bit 15=state, bits 0-14=63 0
Alarm Status 3 Events (alarms 65 - 96):
Battery Fail * * * * * * 0052 Alarm Name + ON/OFF 00000000000000000000000000000001 0 2 or 3 00000000000000000000000000000001 30015 Bit 15=state, bits 0-14=64 0
Field Volt Fail * * * * * * 0052 Alarm Name + ON/OFF 00000000000000000000000000000010 1 2 or 3 00000000000000000000000000000010 30015 Bit 15=state, bits 0-14=65 0
Rear Comm 2 Fail InterMiCOM 0052 Alarm Name + ON/OFF 00000000000000000000000000000100 2 2 or 3 00000000000000000000000000000100 30015 Bit 15=state, bits 0-14=66 0
GOOSE IED Absent * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000000001000 3 2 or 3 00000000000000000000000000001000 30015 Bit 15=state, bits 0-14=67 0
NIC Not Fitted * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000000010000 4 2 or 3 00000000000000000000000000010000 30015 Bit 15=state, bits 0-14=68 0
NIC No Response * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000000100000 5 2 or 3 00000000000000000000000000100000 30015 Bit 15=state, bits 0-14=69 0
NIC Fatal Error * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000001000000 6 2 or 3 00000000000000000000000001000000 30015 Bit 15=state, bits 0-14=70 0
NIC Soft. Reload * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000010000000 7 2 or 3 00000000000000000000000010000000 30015 Bit 15=state, bits 0-14=71 0
Bad TCP/IP Cfg. * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000000100000000 8 2 or 3 00000000000000000000000100000000 30015 Bit 15=state, bits 0-14=72 0
Bad OSI Config. * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000001000000000 9 2 or 3 00000000000000000000001000000000 30015 Bit 15=state, bits 0-14=73 0
470234511.xls
Relay Menu Database Events
Page 106 of 163

Event record specification for Courier and Modbus interfaces


Event Model Courier Events: Modbus Events:
Event Event Type Modbus Additional
Name P341(3x) P342 P343 P344 P345 P341(7x) Options Cell Ref Extraction Text Value (Binary Flag) Bit (See G13) Event Value 3x10008 Register Event Index 3x10011 Data
Column 3x10007 3x10010 3x10012
NIC Link Fail * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000010000000000 10 2 or 3 00000000000000000000010000000000 30015 Bit 15=state, bits 0-14=74 0
NIC SW Mis-Match * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000000100000000000 11 2 or 3 00000000000000000000100000000000 30015 Bit 15=state, bits 0-14=75 0
IP Addr Conflict * * * * * * UCA2 0052 Alarm Name + ON/OFF 00000000000000000001000000000000 12 2 or 3 00000000000000000001000000000000 30015 Bit 15=state, bits 0-14=76 0
Unused 0052 Alarm Name + ON/OFF 00000000000000000010000000000000 13 - 00000000000000000010000000000000 30015 Bit 15=state, bits 0-14=77 0
Unused 0052 Alarm Name + ON/OFF 00000000000000000100000000000000 14 - 00000000000000000100000000000000 30015 Bit 15=state, bits 0-14=78 0
Unused 0052 Alarm Name + ON/OFF 00000000000000001000000000000000 15 - 00000000000000001000000000000000 30015 Bit 15=state, bits 0-14=79 0
Unused 0052 Alarm Name + ON/OFF 00000000000000010000000000000000 16 - 00000000000000010000000000000000 30015 Bit 15=state, bits 0-14=80 0
Unused 0052 Alarm Name + ON/OFF 00000000000000100000000000000000 17 - 00000000000000100000000000000000 30015 Bit 15=state, bits 0-14=81 0
Unused 0052 Alarm Name + ON/OFF 00000000000001000000000000000000 18 - 00000000000001000000000000000000 30015 Bit 15=state, bits 0-14=82 0
Unused 0052 Alarm Name + ON/OFF 00000000000010000000000000000000 19 - 00000000000010000000000000000000 30015 Bit 15=state, bits 0-14=83 0
Unused 0052 Alarm Name + ON/OFF 00000000000100000000000000000000 20 - 00000000000100000000000000000000 30015 Bit 15=state, bits 0-14=84 0
Unused 0052 Alarm Name + ON/OFF 00000000001000000000000000000000 21 - 00000000001000000000000000000000 30015 Bit 15=state, bits 0-14=85 0
Unused 0052 Alarm Name + ON/OFF 00000000010000000000000000000000 22 - 00000000010000000000000000000000 30015 Bit 15=state, bits 0-14=86 0
Unused 0052 Alarm Name + ON/OFF 00000000100000000000000000000000 23 - 00000000100000000000000000000000 30015 Bit 15=state, bits 0-14=87 0
Unused 0052 Alarm Name + ON/OFF 00000001000000000000000000000000 24 - 00000001000000000000000000000000 30015 Bit 15=state, bits 0-14=88 0
Unused 0052 Alarm Name + ON/OFF 00000010000000000000000000000000 25 - 00000010000000000000000000000000 30015 Bit 15=state, bits 0-14=89 0
Unused 0052 Alarm Name + ON/OFF 00000100000000000000000000000000 26 - 00000100000000000000000000000000 30015 Bit 15=state, bits 0-14=90 0
Unused 0052 Alarm Name + ON/OFF 00001000000000000000000000000000 27 - 00001000000000000000000000000000 30015 Bit 15=state, bits 0-14=91 0
Unused 0052 Alarm Name + ON/OFF 00010000000000000000000000000000 28 - 00010000000000000000000000000000 30015 Bit 15=state, bits 0-14=92 0
Unused 0052 Alarm Name + ON/OFF 00100000000000000000000000000000 29 - 00100000000000000000000000000000 30015 Bit 15=state, bits 0-14=93 0
Unused 0052 Alarm Name + ON/OFF 01000000000000000000000000000000 30 - 01000000000000000000000000000000 30015 Bit 15=state, bits 0-14=94 0
Unused 0052 Alarm Name + ON/OFF 10000000000000000000000000000000 31 - 10000000000000000000000000000000 30015 Bit 15=state, bits 0-14=95 0
Protection Events * * * * * * 0F26 - 0F5F DDB Signal Name + ON/OFF 32bit Binary Flag of the revelant packed DDB 6 32 bit binary flag value 311035 to 311149 Bit 15=state, bits 0-14=DDB ID 0
Fault Records * * * * * * B000 Fault Record 8 0 0 0 1
Maintenance Record * * * * * * B100 Maint Record 9 0 0 0 2
470234511.xls
Relay Menu Database Events
Page 107 of 163

Event record specification for Courier and Modbus interfaces


Event Model Courier Events: Modbus Events:
Event Event Type Modbus Additional
Name P341(3x) P342 P343 P344 P345 P341(7x) Options Cell Ref Extraction Text Value (Binary Flag) Bit (See G13) Event Value 3x10008 Register Event Index 3x10011 Data
Column 3x10007 3x10010 3x10012
General Events:
Alarm log cleared * * * * * * FFFF Alarms Cleared 0 7 0 0 0 0
Event log cleared * * * * * * 0B01 Events Cleared 1 7 1 0 0 0
Fault log cleared * * * * * * 0B02 Faults Cleared 2 7 2 0 0 0
Maintenance log cleared * * * * * * 0B03 Maint Cleared 3 7 3 0 0 0
Front panel user interface password unlocked * * * * * * 0002 PW Unlocked UI 4 7 4 0 0 0
Front panel user interface password invalid * * * * * * 0002 PW Invalid UI 5 7 5 0 0 0
Front panel user interface password level 1 modified * * * * * * 00D2 PW1 Modified UI 6 7 6 0 0 0
Front panel user interface password level 2 modified * * * * * * 00D3 PW2 Modified UI 7 7 7 0 0 0
Front panel user interface password expired * * * * * * 0002 PW Expired UI 8 7 8 0 0 0
Front port password unlocked * * * * * * 0002 PW Unlocked F 9 7 9 0 0 0
Front port password invalid * * * * * * 0002 PW Invalid F 10 7 10 0 0 0
Front port password level 1 modified * * * * * * 00D2 PW1 Modified F 11 7 11 0 0 0
Front port password level 2 modified * * * * * * 00D3 PW2 Modified F 12 7 12 0 0 0
Front port password expired * * * * * * 0002 PW Expired F 13 7 13 0 0 0
Rear port 1 password unlocked * * * * * * 0002 PW Unlocked R 14 7 14 0 0 0
Rear port 1 password invalid * * * * * * 0002 PW Invalid R 15 7 15 0 0 0
Rear port 1 password level 1 modified * * * * * * 00D2 PW1 Modified R 16 7 16 0 0 0
Rear port 1 password level 2 modified * * * * * * 00D3 PW2 Modified R 17 7 17 0 0 0
Rear port 1 password expired * * * * * * 0002 PW Expired R 18 7 18 0 0 0
IRIG-B Active * * * * * * IRIB-B 0805 IRIG-B Active 19 7 19 0 0 0
IRIG-B Inactive * * * * * * IRIB-B 0805 IRIG-B Inactive 20 7 20 0 0 0
Time Synchronisation * * * * * * 0801 Time Synch 21 7 21 0 0 0
Control & Support Setting change * * * * * * FFFF C&S Changed 22 7 22 0 0 0
Disturbance Recorder Setting change * * * * * * 0C01 Dist Changed 23 7 23 0 0 0
Protection Group 1 setting change * * * * * * 0905 Group 1 Changed 24 7 24 0 0 0
Protection Group 2 setting change * * * * * * 0905 Group 2 Changed 25 7 25 0 0 0
Protection Group 3 setting change * * * * * * 0905 Group 3 Changed 26 7 26 0 0 0
Protection Group 4 setting change * * * * * * 0905 Group 4 Changed 27 7 27 0 0 0
Active Group Changed * * * * * * 0904 Act Grp Changed 28 + (New active group * 65536) 7 28 + (New active group * 65536) 0 0 0
Front panel indications reset * * * * * * 01FF Indication Reset 29 7 29 0 0 0
Power on * * * * * * FFFF Power On 30 7 30 0 0 0
Bad GOOSE Scheme Logic (UCA2 Only) * * * * * * UCA2 FFFF Bad GOOSE Logic 31 7 31 0 0 0
Bad Masks (UCA2 Only) * * * * * * UCA2 FFFF Bad Masks 32 7 32 0 0 0
Bad Reporting Deadbands (UCA2 Only) * * * * * * UCA2 FFFF Bad Deadbands 33 7 33 0 0 0
Bad Device Identity (UCA2 Only) * * * * * * UCA2 FFFF Bad DI Object 34 7 34 0 0 0
Rear port 2 card failure * * * * * * RP2 FFFF Rear Comm 2 Fail 35 7 35 0 0 0
Rear port 2 password unlocked * * * * * * RP2 0002 PW Unlocked R2 36 7 36 0 0 0
Rear port 2 password invalid * * * * * * RP2 0002 PW Invalid R2 37 7 37 0 0 0
Rear port 2 password level 1 modified * * * * * * RP2 00D2 PW1 Modified R2 38 7 38 0 0 0
Rear port 2 password level 2 modified * * * * * * RP2 00D3 PW2 Modified R2 39 7 39 0 0 0
Rear port 2 password expired * * * * * * RP2 0002 PW Expired R2 40 7 40 0 0 0
Fibre-optic port not fitted * * * * * * Fibre iface FFFF No Fibre Card 41 7 41 0 0 0
Ethernet link fail * * * * * * UCA2 FFFF NIC Link Fail 42 7 42 0 0 0
Disturbance Records cleared * * * * * * 0B30 Dist Rec Cleared 43 7 43 0 0 0
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 108 of 163

IEC 60870-5-103 Device Profile


Vendor Name: Schneider Electric
Device Name: P340 Generator Protection
Models Covered: P341****3**70**
Compatibility Level: 2
Physical Layer
Electrical Interface: EIA485
Number of loads: 1 for one protection equipment
Optical Interface (Order option) Plastic fibre BFOC/2.5 type connector
Transmission speed: 9600 or 19200bps (User Setting)
Application Layer
Common address of ASDU = Link Address

Compatible Range Information numbers in Monitor Direction


ASDU COT FUN Inf Description GI Model Number Interpretation DDB
TYPE No. P341(3x) P342 P343 P344 P345 P341(7x) Ordinal
System Functions
8 10 255 0 End of General Interrogration * * * * *
6 8 255 0 Time Synchronisation * * * * *
5 3 224 2 Reset FCB * * * * *
5 4 224 3 Reset CU * * * * *
5 5 224 4 Start/Restart * * * * *
5 6 224 5 Power On * * * * *
Note: Indentification message in ASDU 5: "MiCOM P" + 16bit model + 8bit major version + 1 character minor version e.g. "MiCOM P" + 343 + 32 + 'A'

Status Indications
1,7,9,11,12,20,2
1 224 16 Auto-recloser active *
1
1,7,9,11,12,20,2
1 224 17 Tele-protection active *
1
1,7,9,11,12,20,2
1 224 18 Protection active *
1
1 1,7,11,12,20, 21 224 19 LED Reset * * * * * * * Reset Indications
1 9,11 224 20 Monitor direction blocked * * * * * * * 391
1 9,11 224 21 Test mode * * * * * * * Protection Disabled 677
1 9,11 224 22 Local parameter setting *
1,7,9,11,12,20,2
1 224 23 Characteristic 1 * * * * * * * PG1 Changed
1
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 109 of 163

1,7,9,11,12,20,2
1 224 24 Characteristic 2 * * * * * * * PG2 Changed
1
1,7,9,11,12,20,2
1 224 25 Characteristic 3 * * * * * * * PG3 Changed
1
1,7,9,11,12,20,2
1 224 26 Characteristic 4 * * * * * * * PG4 Changed
1
1 1,7,9,11 224 27 Auxillary input 1 * * * * * * * Opto Input 1 32
1 1,7,9,11 224 28 Auxillary input 2 * * * * * * * Opto Input 2 33
1 1,7,9,11 224 29 Auxillary input 3 * * * * * * * Opto Input 3 34
1 1,7,9,11 224 30 Auxillary input 4 * * * * * * * Opto Input 4 35

Supervision Indications
1 1,7,9 224 32 Measurand supervision I *
1 1,7,9 224 33 Measurand supervision V *
1 1,7,9 224 35 Phase sequence supervision *
1 1,7,9 224 36 Trip circuit supervision *
1 1,7,9 224 37 I>> back-up supervision *
1 1,7,9 224 38 VT fuse failure * * * * * * * VTS Indication 292
1 1,7,9 224 39 Teleprotection disturbed *
1 1,7,9 224 46 Group warning *
1 1,7,9 224 47 Group alarm *

Earth Fault Indications


1 1,7,9 224 48 Earth Fault L1 *
1 1,7,9 224 49 Earth Fault L2 *
1 1,7,9 224 50 Earth Fault L3 *
1 1,7,9 224 51 Earth Fault Fwd *
1 1,7,9 224 52 Earth Fault Rev *
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 110 of 163

Fault Indications
2 1,7,9 224 64 Start /pickup L1 * * * * * * * 1st Stage O/C Start A 1041
2 1,7,9 224 65 Start /pickup L2 * * * * * * * 1st Stage O/C Start B 1042
2 1,7,9 224 66 Start /pickup L3 * * * * * * * 1st Stage O/C Start C 1043
2 1,7,9 224 67 Start /pickup N * * * * * * * 1st Stage EF Start 1008
2 1,7 224 68 General Trip * * * * * * * Any Trip 674
2 1,7 224 69 Trip L1 * * * * * * * 1st Stage O/C Trip A 801
2 1,7 224 70 Trip L2 * * * * * * * 1st Stage O/C Trip B 802
2 1,7 224 71 Trip L3 * * * * * * * 1st Stage O/C Trip C 803
2 1,7 224 72 Trip I>> (back up)
4 1,7 224 73 Fault Location in ohms
2 1,7 224 74 Fault forward
2 1,7 224 75 Fault reverse
2 1,7 224 76 Teleprotection signal sent
2 1,7 224 77 Teleprotection signal received
2 1,7 224 78 Zone 1
2 1,7 224 79 Zone 2
2 1,7 224 80 Zone 3
2 1,7 224 81 Zone 4
2 1,7 224 82 Zone 5
2 1,7 224 83 Zone 6
2 1,7,9 224 84 General Start * * * * * * * Any Start 992
2 1,7 224 85 Breaker Failure * * * * * * * Breaker Fail Any Trip 358
2 1,7 224 86 Trip measuring system L1
2 1,7 224 87 Trip measuring system L2
2 1,7 224 88 Trip measuring system L3
2 1,7 224 89 Trip measuring system E
2 1,7 224 90 Trip I> * * * * * * * 1st Stage O/C Trip 3ph 800
2 1,7 224 91 Trip I>> * * * * * * * 2nd Stage O/C Trip 3ph 804
2 1,7 224 92 Trip IN> * * * * * * * 1st Stage EF Trip 768
2 1,7 224 93 Trip IN>> * * * * * * * 2nd Stage EF Trip 769

Auto-Reclose Indications
1 1,7 224 128 CB 'on' by A/R
1 1,7 224 129 CB 'on' by long time A/R
1 1,7,9 224 130 AR blocked *

Measurands
3.1 2,7 224 144 Measurand I
3.2 2,7 224 145 Measurands I,V
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 111 of 163

3.3 2,7 224 146 Measurands I,V,P,Q


3.4 2,7 224 147 Measurands IN,VEN
Measurands
9 2,7 224 148 * * * * * Note unavailable measurands sent as invalid
IL1,2,3,VL1,2,3,P,Q,f

Generic Functions
10 42,43 224 240 Read Headings
Read attributes of all entries of a
10 42,43 224 241
group
10 42,43 224 243 Read directory of entry
1,2,7,9,11,12,
10 224 244 Real attribute of entry *
42,43
10 10 224 245 End of GGI
10 41,44 224 249 Write entry with confirm
10 40,41 224 250 Write entry with execute
10 40 224 251 Write entry aborted

Compatible Range Information numbers in Control Direction


ASDU COT FUN Inf Description GI Model Number Interpretation DDB
TYPE No. P341(3x) P342 P343 P344 P345 P341(7x) Ordinal
System Functions
7 9 255 0 Init General Interrogation * * * * * *
6 8 255 0 Time Synchronisation * * * * * *

General Commands
20 20 224 16 Auto-recloser on/off Autoreclose in Service
20 20 224 17 Teleprotection on/off
20 20 224 18 Protection on/off
20 20 224 19 LED Reset * * * * * * Reset Indications and Latches
20 20 224 23 Activate characteristic 1 * * * * * * Activate Setting Group 1
20 20 224 24 Activate characteristic 2 * * * * * * Activate Setting Group 2
20 20 224 25 Activate characteristic 3 * * * * * * Activate Setting Group 3
20 20 224 26 Activate characteristic 4 * * * * * * Activate Setting Group 4
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 112 of 163

Generic Functions
Read headings of all defined
21 42 224 240 * * * * * * * Measurements1/2/3/4
groups
Read single attribute of all entries
21 42 224 241 * * * * * * * Measurements1/2/3/5
of a group
21 42 224 243 Read directory of single entry * * * * * * * Measurements1/2/3/6
21 42 224 244 Read attribute of sngle entry * * * * * * * Measurements1/2/3/7
Generic General Interrogation
21 9 224 245
(GGI)
10 40 224 248 Write entry
10 40 224 249 Write with confirm
10 40 224 250 Write with execute
10 40 224 251 Write entry abort

Basic Application Functions


Test Mode * * * * * * *
Blocking of monitor direction * * * * * * *
Disturbance data * * * * * * *
Generic services * * * * * * * * * Measurements1/2/3/7
Private data * * * * * * *

Miscellaneous Max. MVAL = times rated value


Measurands 1.2 2.4
Current L1 *
Current L2 *
Current L3 *
Voltage L1-E *
Voltage L2-E *
Voltage L3-E *
Active Power P *
Reactive Power Q *
Frequency F *
Voltage L1-L2

Private Range Information numbers in Monitor Direction


ASDU COT FUN Inf Display Text (English) GI Model Number DDB Signal Description DDB
TYPE No. P341(3x) P342 P343 P344 P345 P341(7x) Ordinal
1 1,7,9 226 0 see 4B01 * * * * * * * Output Relay 1 0
1 1,7,9 226 1 see 4B02 * * * * * * * Output Relay 2 1
1 1,7,9 226 2 see 4B03 * * * * * * * Output Relay 3 2
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 113 of 163

1 1,7,9 226 3 see 4B04 * * * * * * * Output Relay 4 3


1 1,7,9 226 4 see 4B05 * * * * * * * Output Relay 5 4
1 1,7,9 226 5 see 4B06 * * * * * * * Output Relay 6 5
1 1,7,9 226 6 see 4B07 * * * * * * * Output Relay 7 6
1 1,7,9 226 7 see 4B08 * * * * * * * Output Relay 8 7
1 1,7,9 226 8 see 4B09 * * * * * * * Output Relay 9 8
1 1,7,9 226 9 see 4B0A * * * * * * * Output Relay 10 9
1 1,7,9 226 10 see 4B0B * * * * * * * Output Relay 11 10
1 1,7,9 226 11 see 4B0C * * * * * * * Output Relay 12 11
1 1,7,9 226 12 see 4B0D * * * * * * * Output Relay 13 12
1 1,7,9 226 13 see 4B0E * * * * * * * Output Relay 14 13
1 1,7,9 226 14 see 4B0F * * * * * * * Output Relay 15 14
1 1,7,9 226 15 see 4B10 * * * * * * * Output Relay 16 15
1 1,7,9 226 16 see 4B11 * * * * * * * Output Relay 17 16
1 1,7,9 226 17 see 4B12 * * * * * * * Output Relay 18 17
1 1,7,9 226 18 see 4B13 * * * * * * * Output Relay 19 18
1 1,7,9 226 19 see 4B14 * * * * * * * Output Relay 20 19
1 1,7,9 226 20 see 4B15 * * * * * * * Output Relay 21 20
1 1,7,9 226 21 see 4B16 * * * * * * * Output Relay 22 21
1 1,7,9 226 22 see 4B17 * * * * * * * Output Relay 23 22
1 1,7,9 226 23 see 4B18 * * * * * * * Output Relay 24 23
1 1,7,9 226 24 see 4B19 * * * * Output Relay 25 24
1 1,7,9 226 25 see 4B1A * * * * Output Relay 26 25
1 1,7,9 226 26 see 4B1B * * * * Output Relay 27 26
1 1,7,9 226 27 see 4B1C * * * * Output Relay 28 27
1 1,7,9 226 28 see 4B1D * * * * Output Relay 29 28
1 1,7,9 226 29 see 4B1E * * * * Output Relay 30 29
1 1,7,9 226 30 see 4B1F * * * * Output Relay 31 30
1 1,7,9 226 31 see 4B20 * * * * Output Relay 32 31
1 1,7,9,11 224 27 see 4A01 * * * * * * * Opto Isolator Input 1 32
1 1,7,9,11 224 28 see 4A02 * * * * * * * Opto Isolator Input 2 33
1 1,7,9,11 224 29 see 4A03 * * * * * * * Opto Isolator Input 3 34
1 1,7,9,11 224 30 see 4A04 * * * * * * * Opto Isolator Input 4 35
1 1,7,9,11 226 36 see 4A05 * * * * * * * Opto Isolator Input 5 36
1 1,7,9,11 226 37 see 4A06 * * * * * * * Opto Isolator Input 6 37
1 1,7,9,11 226 38 see 4A07 * * * * * * * Opto Isolator Input 7 38
1 1,7,9,11 226 39 see 4A08 * * * * * * * Opto Isolator Input 8 39
1 1,7,9,11 226 40 see 4A09 * * * * * * * Opto Isolator Input 9 40
1 1,7,9,11 226 41 see 4A0A * * * * * * * Opto Isolator Input 10 41
1 1,7,9,11 226 42 see 4A0B * * * * * * * Opto Isolator Input 11 42
1 1,7,9,11 226 43 see 4A0C * * * * * * * Opto Isolator Input 12 43
1 1,7,9,11 226 44 see 4A0D * * * * * * * Opto Isolator Input 13 44
1 1,7,9,11 226 45 see 4A0E * * * * * * * Opto Isolator Input 14 45
1 1,7,9,11 226 46 see 4A0F * * * * * * * Opto Isolator Input 15 46
1 1,7,9,11 226 47 see 4A10 * * * * * * * Opto Isolator Input 16 47
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 114 of 163

1 1,7,9,11 226 48 see 4A11 * * * * * * * Opto Isolator Input 17 48


1 1,7,9,11 226 49 see 4A12 * * * * * * * Opto Isolator Input 18 49
1 1,7,9,11 226 50 see 4A13 * * * * * * * Opto Isolator Input 19 50
1 1,7,9,11 226 51 see 4A14 * * * * * * * Opto Isolator Input 20 51
1 1,7,9,11 226 52 see 4A15 * * * * * * * Opto Isolator Input 21 52
1 1,7,9,11 226 53 see 4A16 * * * * * * * Opto Isolator Input 22 53
1 1,7,9,11 226 54 see 4A17 * * * * * * * Opto Isolator Input 23 54
1 1,7,9,11 226 55 see 4A18 * * * * * * * Opto Isolator Input 24 55
1 1,7,9,11 226 56 see 4A19 * * * * Opto Isolator Input 25 56
1 1,7,9,11 226 57 see 4A1A * * * * Opto Isolator Input 26 57
1 1,7,9,11 226 58 see 4A1B * * * * Opto Isolator Input 27 58
1 1,7,9,11 226 59 see 4A1C * * * * Opto Isolator Input 28 59
1 1,7,9,11 226 60 see 4A1D * * * * Opto Isolator Input 29 60
1 1,7,9,11 226 61 see 4A1E * * * * Opto Isolator Input 30 61
1 1,7,9,11 226 62 see 4A1F * * * * Opto Isolator Input 31 62
1 1,7,9,11 226 63 see 4A20 * * * * Opto Isolator Input 32 63
226 160 Relay Cond 1 * * * * * * Relay Conditioner 1 64
226 161 Relay Cond 2 * * * * * * Relay Conditioner 2 65
226 162 Relay Cond 3 * * * * * * Relay Conditioner 3 66
226 163 Relay Cond 4 * * * * * * Relay Conditioner 4 67
226 164 Relay Cond 5 * * * * * * Relay Conditioner 5 68
226 165 Relay Cond 6 * * * * * * Relay Conditioner 6 69
226 166 Relay Cond 7 * * * * * * Relay Conditioner 7 70
226 167 Relay Cond 8 * * * * * * Relay Conditioner 8 71
226 168 Relay Cond 9 * * * * * * Relay Conditioner 9 72
226 169 Relay Cond 10 * * * * * * Relay Conditioner 10 73
226 170 Relay Cond 11 * * * * * * Relay Conditioner 11 74
226 171 Relay Cond 12 * * * * * * Relay Conditioner 12 75
226 172 Relay Cond 13 * * * * * * Relay Conditioner 13 76
226 173 Relay Cond 14 * * * * * * Relay Conditioner 14 77
226 174 Relay Cond 15 * * * * * * Relay Conditioner 15 78
226 175 Relay Cond 16 * * * * * * Relay Conditioner 16 79
226 176 Relay Cond 17 * * * * * * Relay Conditioner 17 80
226 177 Relay Cond 18 * * * * * * Relay Conditioner 18 81
226 178 Relay Cond 19 * * * * * * Relay Conditioner 19 82
226 179 Relay Cond 20 * * * * * * Relay Conditioner 20 83
226 180 Relay Cond 21 * * * * * * Relay Conditioner 21 84
226 181 Relay Cond 22 * * * * * * Relay Conditioner 22 85
226 182 Relay Cond 23 * * * * * * Relay Conditioner 23 86
226 183 Relay Cond 24 * * * * * * Relay Conditioner 24 87
226 184 Relay Cond 25 * * * Relay Conditioner 25 88
226 185 Relay Cond 26 * * * Relay Conditioner 26 89
226 186 Relay Cond 27 * * * Relay Conditioner 27 90
226 187 Relay Cond 28 * * * Relay Conditioner 28 91
226 188 Relay Cond 29 * * * Relay Conditioner 29 92
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 115 of 163

226 189 Relay Cond 30 * * * Relay Conditioner 30 93


226 190 Relay Cond 31 * * * Relay Conditioner 31 94
226 191 Relay Cond 32 * * * Relay Conditioner 32 95
226 96 LED1 Red * * * Tri-LED - 1 - Red 96
226 97 LED1 Grn * * * Tri-LED - 1 - Green 97
226 98 LED2 Red * * * Tri-LED - 2 - Red 98
226 99 LED2 Grn * * * Tri-LED - 2 - Green 99
226 100 LED3 Red * * * Tri-LED - 3 - Red 100
226 101 LED3 Grn * * * Tri-LED - 3 - Green 101
226 102 LED4 Red * * * Tri-LED - 4 - Red 102
226 103 LED4 Grn * * * Tri-LED - 4 - Green 103
226 104 LED5 Red * * * Tri-LED - 5 - Red 104
226 105 LED5 Grn * * * Tri-LED - 5 - Green 105
226 106 LED6 Red * * * Tri-LED - 6 - Red 106
226 107 LED6 Grn * * * Tri-LED - 6 - Green 107
226 108 LED7 Red * * * Tri-LED - 7 - Red 108
226 109 LED7 Grn * * * Tri-LED - 7 - Green 109
226 110 LED8 Red * * * Tri-LED - 8 - Red 110
226 111 LED8 Grn * * * Tri-LED - 8 - Green 111
226 112 FnKey LED1 Red * * * Tri-LED - 9 - Red 112
226 113 FnKey LED1 Grn * * * Tri-LED - 9 - Green 113
226 114 FnKey LED2 Red * * * Tri-LED - 10 - Red 114
226 115 FnKey LED2 Grn * * * Tri-LED - 10 - Green 115
226 116 FnKey LED3 Red * * * Tri-LED - 11 - Red 116
226 117 FnKey LED3 Grn * * * Tri-LED - 11 - Green 117
226 118 FnKey LED4 Red * * * Tri-LED - 12 - Red 118
226 119 FnKey LED4 Grn * * * Tri-LED - 12 - Green 119
226 120 FnKey LED5 Red * * * Tri-LED - 13 - Red 120
226 121 FnKey LED5 Grn * * * Tri-LED - 13 - Green 121
226 122 FnKey LED6 Red * * * Tri-LED - 14 - Red 122
226 123 FnKey LED6 Grn * * * Tri-LED - 14 - Green 123
226 124 FnKey LED7 Red * * * Tri-LED - 15 - Red 124
226 125 FnKey LED7 Grn * * * Tri-LED - 15 - Green 125
226 126 FnKey LED8 Red * * * Tri-LED - 16 - Red 126
226 127 FnKey LED8 Grn * * * Tri-LED - 16 - Green 127
226 128 FnKey LED9 Red * * * Tri-LED - 17 - Red 128
226 129 FnKey LED9 Grn * * * Tri-LED - 17 - Green 129
226 130 FnKey LED10 Red * * * Tri-LED - 18 - Red 130
226 131 FnKey LED10 Grn * * * Tri-LED - 18 - Green 131
226 132 132
226 133 133
226 134 134
226 135 135
226 136 136
226 137 137
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 116 of 163

226 138 138


226 139 139
226 140 140
226 141 141
226 142 142
226 143 143
226 144 144
226 145 145
226 146 146
226 147 147
226 148 148
226 149 149
226 150 150
226 151 151
226 152 152
226 153 153
226 154 154
226 155 155
226 156 156
226 157 157
226 158 158
226 159 159
226 192 LED1 Con R * * * Tri-LED Conditioner - 1 - Red 160
226 193 LED1 Con G * * * Tri-LED Conditioner- 1 - Green 161
226 194 LED2 Con R * * * Tri-LED Conditioner - 2 - Red 162
226 195 LED2 Con G * * * Tri-LED Conditioner - 2 - Green 163
226 196 LED3 Con R * * * Tri-LED Conditioner - 3 - Red 164
226 197 LED3 Con G * * * Tri-LED Conditioner - 3 - Green 165
226 198 LED4 Con R * * * Tri-LED Conditioner - 4 - Red 166
226 199 LED4 Con G * * * Tri-LED Conditioner - 4 - Green 167
226 200 LED5 Con R * * * Tri-LED Conditioner - 5 - Red 168
226 201 LED5 Con G * * * Tri-LED Conditioner - 5 - Green 169
226 202 LED6 Con R * * * Tri-LED Conditioner - 6 - Red 170
226 203 LED6 Con G * * * Tri-LED Conditioner - 6 - Green 171
226 204 LED7 Con R * * * Tri-LED Conditioner - 7 - Red 172
226 205 LED7 Con G * * * Tri-LED Conditioner - 7 - Green 173
226 206 LED8 Con R * * * Tri-LED Conditioner - 8 - Red 174
226 207 LED8 Con G * * * Tri-LED Conditioner - 8 - Green 175
226 208 FnKey LED1 ConR * * * Tri-LED Conditioner - 9 - Red 176
226 209 FnKey LED1 ConG * * * Tri-LED Conditioner - 9 - Green 177
226 210 FnKey LED2 ConR * * * Tri-LED Conditioner - 10 - Red 178
226 211 FnKey LED2 ConG * * * Tri-LED Conditioner - 10 - Green 179
226 212 FnKey LED3 ConR * * * Tri-LED Conditioner - 11 - Red 180
226 213 FnKey LED3 ConG * * * Tri-LED Conditioner - 11 - Green 181
226 214 FnKey LED4 ConR * * * Tri-LED Conditioner - 12 - Red 182
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 117 of 163

226 215 FnKey LED4 ConG * * * Tri-LED Conditioner - 12 - Green 183


226 216 FnKey LED5 ConR * * * Tri-LED Conditioner - 13 - Red 184
226 217 FnKey LED5 ConG * * * Tri-LED Conditioner - 13 - Green 185
226 218 FnKey LED6 ConR * * * Tri-LED Conditioner - 14 - Red 186
226 219 FnKey LED6 ConG * * * Tri-LED Conditioner - 14 - Green 187
226 220 FnKey LED7 ConR * * * Tri-LED Conditioner - 15 - Red 188
226 221 FnKey LED7 ConG * * * Tri-LED Conditioner - 15 - Green 189
226 222 FnKey LED8 ConR * * * Tri-LED Conditioner - 16 - Red 190
226 223 FnKey LED8 ConG * * * Tri-LED Conditioner - 16 - Green 191
226 224 FnKey LED9 ConR * * * Tri-LED Conditioner - 17 - Red 192
226 225 FnKey LED9 ConG * * * Tri-LED Conditioner - 17 - Green 193
226 226 FnKey LED10 ConR * * * Tri-LED Conditioner - 18 - Red 194
226 227 FnKey LED10 ConG * * * Tri-LED Conditioner - 18 - Green 195
226 228 196
226 229 197
226 230 198
226 231 199
226 232 200
226 233 201
226 234 202
226 235 203
226 236 204
226 237 205
226 238 206
226 239 207
226 240 208
226 241 209
226 242 210
226 243 211
226 244 212
226 245 213
226 246 214
226 247 215
226 248 216
226 249 217
226 250 218
226 251 219
226 252 220
226 253 221
226 254 222
226 255 223
226 64 LED 1 * * * LED 1 224
226 65 LED 2 * * * LED 2 225
226 66 LED 3 * * * LED 3 226
226 67 LED 4 * * * LED 4 227
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 118 of 163

226 68 LED 5 * * * LED 5 228


226 69 LED 6 * * * LED 6 229
226 70 LED 7 * * * LED 7 230
226 71 LED 8 * * * LED 8 231
226 72 LED Cond IN 1 * * * LED Conditioner IN 1 232
226 73 LED Cond IN 2 * * * LED Conditioner IN 2 233
226 74 LED Cond IN 3 * * * LED Conditioner IN 3 234
226 75 LED Cond IN 4 * * * LED Conditioner IN 4 235
226 76 LED Cond IN 5 * * * LED Conditioner IN 5 236
226 77 LED Cond IN 6 * * * LED Conditioner IN 6 237
226 78 LED Cond IN 7 * * * LED Conditioner IN 7 238
226 79 LED Cond IN 8 * * * LED Conditioner IN 8 239
226 80 240
226 81 241
226 82 242
226 83 243
226 84 244
226 85 245
226 86 246
226 87 247
226 88 248
226 89 249
226 90 250
226 91 251
226 92 252
226 93 253
226 94 254
226 95 255
230 0 Function Key 1 * * * Function Key 1 256
230 1 Function Key 2 * * * Function Key 2 257
230 2 Function Key 3 * * * Function Key 3 258
230 3 Function Key 4 * * * Function Key 4 259
230 4 Function Key 5 * * * Function Key 5 260
230 5 Function Key 6 * * * Function Key 6 261
230 6 Function Key 7 * * * Function Key 7 262
230 7 Function Key 8 * * * Function Key 8 263
230 8 Function Key 9 * * * Function Key 9 264
230 9 Function Key 10 * * * Function Key 10 265
230 10 266
230 11 267
230 12 268
230 13 269
230 14 270
230 15 271
230 16 272
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 119 of 163

230 17 273
230 18 274
230 19 275
230 20 276
230 21 277
230 22 278
230 23 279
230 24 280
230 25 281
230 26 282
230 27 283
230 28 284
230 29 285
230 30 286
230 31 287
227 0 Timer out 1 * * * * * * Auxiliary Timer out 1 288
227 1 Timer out 2 * * * * * * Auxiliary Timer out 2 289
227 2 Timer out 3 * * * * * * Auxiliary Timer out 3 290
227 3 Timer out 4 * * * * * * Auxiliary Timer out 4 291
227 4 Timer out 5 * * * * * * Auxiliary Timer out 5 292
227 5 Timer out 6 * * * * * * Auxiliary Timer out 6 293
227 6 Timer out 7 * * * * * * Auxiliary Timer out 7 294
227 7 Timer out 8 * * * * * * Auxiliary Timer out 8 295
227 8 Timer out 9 * * * * * * Auxiliary Timer out 9 296
227 9 Timer out 10 * * * * * * Auxiliary Timer out 10 297
227 10 Timer out 11 * * * * * * Auxiliary Timer out 11 298
227 11 Timer out 12 * * * * * * Auxiliary Timer out 12 299
227 12 Timer out 13 * * * * * * Auxiliary Timer out 13 300
227 13 Timer out 14 * * * * * * Auxiliary Timer out 14 301
227 14 Timer out 15 * * * * * * Auxiliary Timer out 15 302
227 15 Timer out 16 * * * * * * Auxiliary Timer out 16 303
230 32 304
230 33 305
230 34 306
230 35 307
230 36 308
230 37 309
230 38 310
230 39 311
230 40 312
230 41 313
230 42 314
230 43 315
230 44 316
230 45 317
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 120 of 163

230 46 318
230 47 319
227 16 Timer in 1 * * * * * * Auxiliary Timer in 1 320
227 17 Timer in 2 * * * * * * Auxiliary Timer in 2 321
227 18 Timer in 3 * * * * * * Auxiliary Timer in 3 322
227 19 Timer in 4 * * * * * * Auxiliary Timer in 4 323
227 20 Timer in 5 * * * * * * Auxiliary Timer in 5 324
227 21 Timer in 6 * * * * * * Auxiliary Timer in 6 325
227 22 Timer in 7 * * * * * * Auxiliary Timer in 7 326
227 23 Timer in 8 * * * * * * Auxiliary Timer in 8 327
227 24 Timer in 9 * * * * * * Auxiliary Timer in 9 328
227 25 Timer in 10 * * * * * * Auxiliary Timer in 10 329
227 26 Timer in 11 * * * * * * Auxiliary Timer in 11 330
227 27 Timer in 12 * * * * * * Auxiliary Timer in 12 331
227 28 Timer in 13 * * * * * * Auxiliary Timer in 13 332
227 29 Timer in 14 * * * * * * Auxiliary Timer in 14 333
227 30 Timer in 15 * * * * * * Auxiliary Timer in 15 334
227 31 Timer in 16 * * * * * * Auxiliary Timer in 16 335
230 48 336
230 49 337
230 50 338
230 51 339
230 52 340
230 53 341
230 54 342
230 55 343
230 56 344
230 57 345
230 58 346
230 59 347
230 60 348
230 61 349
230 62 350
230 63 351
230 64 352
1 1,7,9 227 50 F out of Range * * * * * * * Frequency Out of Range 353
1 1,7,9 227 34 SG-DDB Invalid * * * * * * * Setting Group selection by DDB inputs invalid 354
1 9,11 224 21 Prot'n Disabled * * * * * * * Test Mode Enabled 355
1 1,7,9 224 38 VT Fail Alarm * * * * * * * VTS VT Fail Alarm 356
1 1,7,9 227 37 CT-1 Fail Alarm * * * * * * * CTS-1 CT-1 Fail Alarm 357
2 1,7 224 85 CB Fail Alarm * * * * * * Breaker Fail Any Trip 358
1 1,7,9 227 39 I^ Maint Alarm * * * * * * * Broken Current Maintenance Alarm 359
1 1,7,9 227 40 I^ Lockout Alarm * * * * * * * Broken Current Lockout Alarm 360
1 1,7,9 227 41 CB Ops Maint * * * * * * * Number of CB Operations Maintenance Alarm 361
1 1,7,9 227 42 CB Ops Lockout * * * * * * * Number of CB Operations Maintenance Lockout 362
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 121 of 163

1 1,7,9 227 43 CB Op Time Maint * * * * * * * Excessive CB Operation Time Maintenance Alarm 363
1 1,7,9 227 44 CB Op Time Lock * * * * * * * Excessive CB Operation Time Lockout Alarm 364
1 1,7,9 227 45 Fault Freq Lock * * * * * * * Excessive Fault Frequency Lockout Alarm 365
1 1,7,9 227 46 CB Status Alarm * * * * * * * CB Status Alarm 366
1 1,7,9 227 47 Man CB Trip Fail * * * * * * * CB Failed to Trip 367
1 1,7,9 227 48 Man CB Cls Fail * * * * * * * CB Failed to Close 368
1 1,7,9 227 49 Man CB Unhealthy * * * * * * * Control CB Unhealthy 369
1 1,7,9 232 1 NPS Thermal Alm * * * * * Negative Phase Sequence thermal Alarm 370
1 1,7,9 227 51 Thermal Alarm * * * * * * * Thermal Overload Alarm 371
1 1,7,9 227 52 V/Hz Alarm * * * * * Volts Per Hz Alarm 372
1 1,7,9 227 53 Field Fail Alarm * * * * * Field Failure Alarm 373
1 1,7,9 227 54 RTD Thermal Alm * * * * * RTD Thermal Alarm 374
1 1,7,9 227 55 RTD Open Cct * * * * * RTD Open Circuit Failure 375
1 1,7,9 227 56 RTD short Cct * * * * * RTD Short Circuit Failure 376
1 1,7,9 227 57 RTD Data Error * * * * * RTD Data Inconsistency Error 377
1 1,7,9 227 58 RTD Board Fail * * * * * RTD Board Failure 378
1 1,7,9 227 59 Freq Prot Alm * * * * * * * Frequency Protection Alarm 379
1 1,7,9 227 60 Voltage Prot Alm * * * * * * * Voltage Protection Alarm 380
1 1,7,9 227 61 CT-2 Fail Alarm * * * * CTS-2 CT-2 Fail Alarm 381
1 1,7,9 227 62 64S R<1 Alarm * * 64S 100% St EF Under Resistance Stage 1 Alarm 382
1 1,7,9 227 63 64S Fail Alarm * * 64S Injection Fail Alarm 383
1 1,7,9 227 64 CL Card I/P Fail * * * * * * * CLIO Input Board Failure 384
1 1,7,9 227 65 CL Card O/P Fail * * * * * * * CLIO Output Board Failure 385
1 1,7,9 227 66 CL Input 1 Alarm * * * * * * * Current Loop Input 1 Alarm 386
1 1,7,9 227 67 CL Input 2 Alarm * * * * * * * Current Loop Input 2 Alarm 387
1 1,7,9 227 68 CL Input 3 Alarm * * * * * * * Current Loop Input 3 Alarm 388
1 1,7,9 227 69 CL Input 4 Alarm * * * * * * * Current Loop Input 4 Alarm 389
1 1,7,9 227 70 CLI1 I< Fail Alm * * * * * * * Current Loop Input 1 Undercurrent Fail Alarm 390
1 1,7,9 227 71 CLI2 I< Fail Alm * * * * * * * Current Loop Input 2 Undercurrent Fail Alarm 391
1 1,7,9 227 72 CLI3 I< Fail Alm * * * * * * * Current Loop Input 3 Undercurrent Fail Alarm 392
1 1,7,9 227 73 CLI4 I< Fail Alm * * * * * * * Current Loop Input 4 Undercurrent Fail Alarm 393
1 1,7,9 227 74 64R R<1 Alarm * * * * * 64R Rotor EF Under Resistance Stage 1 Alarm 394
1 1,7,9 227 75 64R CL I/P Fail * * * * * 64R Rotor EF Current Loop Input Fail 395
1 1,7,9 227 76 CT Para Mismatch * * * * CT parameter mismatch alarm 396
1 1,7,9 227 76 Amb T Fail Alm * * DLR Input Ambient Temperature Fail alarm 396
1 1,7,9 227 77 LOL Alarm * * * * * Loss of Life Alarm 397
1 1,7,9 227 77 Wind V Fail Alm * * DLR Input Wind Velocity Fail alarm 397
1 1,7,9 227 78 FAA Alarm * * * * * Aging Acceleration Factor Alarm 398
1 1,7,9 227 78 Wind D Fail Alm * * DLR Input Wind Direction Fail alarm 398
1 1,7,9 227 79 Thru Fault Alm * * * * * Through Fault Alarm 399
1 1,7,9 227 79 Solar R Fail Alm * * DLR Input Solar Radiation Fail alarm 399
1 1,7,9 227 80 Cct Fail Alarm * * * * Circuitry Fault Alarm 400
1 1,7,9 227 81 Tol Pretrip Alm * * * * * Tol Pretrip Alm 401
1 1,7,9 230 152 CT Fail Alarm * * * * differential CTS 402
1 1,7,9 233 179 Man No Checksync * * * * * * * Manual close CB but do not satisfy CS condition 403
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 122 of 163

1 1,7,9 233 178 System Split * * * * * * * System Split Alarm 404


1 1,7,9 227 85 MR User Alarm 11 * * * * * * * User Definable Alarm 11 (Manual Reset) 405
1 1,7,9 227 86 MR User Alarm 10 * * * * * * * User Definable Alarm 10 (Manual Reset) 406
1 1,7,9 227 87 MR User Alarm 9 * * * * * * * User Definable Alarm 9 (Manual Reset) 407
1 1,7,9 227 88 MR User Alarm 8 * * * * * * * User Definable Alarm 8 (Manual Reset) 408
1 1,7,9 227 89 MR User Alarm 7 * * * * * * * User Definable Alarm 7 (Manual Reset) 409
1 1,7,9 227 90 MR User Alarm 6 * * * * * * * User Definable Alarm 6 (Manual Reset) 410
1 1,7,9 227 91 MR User Alarm 5 * * * * * * * User Definable Alarm 5 (Manual Reset) 411
1 1,7,9 227 92 SR User Alarm 4 * * * * * * * User Definable Alarm 4 (Self Reset) 412
1 1,7,9 227 93 SR User Alarm 3 * * * * * * * User Definable Alarm 3 (Self Reset) 413
1 1,7,9 227 94 SR User Alarm 2 * * * * * * * User Definable Alarm 2 (Self Reset) 414
1 1,7,9 227 95 SR User Alarm 1 * * * * * * * User Definable Alarm 1 (Self Reset) 415
1 1,7,9 229 32 Battery Fail * * * * * * * Battery Fail alarm indication 416
1 1,7,9 229 33 Field Volts Fail * * * * * * * Field Voltage Failure 417
229 34 Rear Comm 2 Fail * * * * * * InterMiCOM Second rear comm card failure indicati 418
229 35 GOOSE IED Absent * * * * * * Enrolled GOOSE IED absent alarm indication 419
229 36 NIC Not Fitted * * * * * * Network Interface Card not fitted/failed alarm 420
229 37 NIC No Response * * * * * * Network Interface Card not responding alarm 421
229 38 NIC Fatal Error * * * * * * Network Interface Card fatal error alarm indication 422
229 39 NIC Soft. Reload * * * * * * Network Interface Card software reload alarm 423
229 40 Bad TCP/IP Cfg. * * * * * * Bad TCP/IP Configuration Alarm 424
229 41 Bad OSI Config. * * * * * * Bad OSI Configuration Alarm 425
229 42 NIC Link Fail * * * * * * Network Interface Card link fail alarm indication 426
229 43 NIC SW Mis-Match * * * * * * Main card/NIC software mismatch alarm indication 427
229 44 IP Addr Conflict * * * * * * IP address conflict alarm indication 428
229 45 IM Loopback * * * * * * InterMiCOM Loop-back alarm indication 429
229 46 IM Message Fail * * * * * * InterMiCOM Message Fail alarm indication 430
229 47 IM Data CD Fail * * * * * * InterMiCOM DCD Fail alarm indication 431
229 48 IM Channel Fail * * * * * * InterMiCOM Channel Fail alarm indication 432
229 49 433
229 50 434
229 51 435
229 52 436
229 53 437
229 54 438
229 55 439
229 56 440
229 57 441
229 58 442
229 59 443
229 60 444
229 61 445
229 62 446
229 63 447
230 66 448
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 123 of 163

230 67 449
230 68 450
230 69 451
230 70 452
230 71 453
230 72 454
230 73 455
230 74 456
230 75 457
230 76 458
230 77 459
230 78 460
230 79 461
230 80 462
230 81 463
230 82 464
230 83 465
230 84 466
230 85 467
230 86 468
230 87 469
230 88 470
230 89 471
230 90 472
230 91 473
230 92 474
230 93 475
230 94 476
230 95 477
230 96 478
230 97 479
230 98 480
230 99 481
230 100 482
230 101 483
230 102 484
230 103 485
230 104 486
230 105 487
230 106 488
230 107 489
230 108 490
230 109 491
230 110 492
230 111 493
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 124 of 163

230 112 494


230 113 495
230 114 496
230 115 497
230 116 498
230 117 499
230 118 500
230 119 501
230 120 502
230 121 503
230 122 504
230 123 505
230 124 506
230 125 507
230 126 508
230 127 509
230 126 510
230 127 511
227 141 Gen Diff Block * * * Block Generator Differential protection 512
230 141 Xform Diff Block * * * Block Xformer Differential protection 513
2 1,7 230 148 Inhibit CTS * * * differential CTS 514
230 169 515
230 176 516
230 169 517
230 176 518
230 183 519
230 190 520
230 197 521
230 204 522
230 211 523
230 218 524
230 225 525
230 232 526
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 125 of 163

230 239 527


230 246 528
230 253 529
229 1 530
229 2 531
229 3 532
229 4 533
229 5 534
229 6 535
229 7 536
229 8 537
229 9 538
229 10 539
229 11 540
229 12 541
229 13 542
229 14 543
227 102 IN>1 Timer Blk * * * * * * Block Earth Fault Stage 1 time delay 544
227 103 IN>2 Timer Blk * * * * * * Block Earth Fault Stage 2 time delay 545
227 104 IN>3 Timer Blk * * Block Earth Fault Stage 3 time delay 546
227 105 IN>4 Timer Blk * * Block Earth Fault Stage 4 time delay 547
227 106 ISEF>1 Timer Blk * * * * * * Block SEF Stage 1 time delay 548
227 107 ISEF>2 Timer Blk * * Block SEF Stage 2 time delay 549
227 108 ISEF>3 Timer Blk * * Block SEF Stage 3 time delay 550
227 109 ISEF>4 Timer Blk * * Block SEF Stage 4 time delay 551
227 154 64S I>1 Inhibit * Inhibit 64S Overcurrent Protection 552
227 155 64S R<1 Inhibit * Inhibit 64S Under Impedance Stage 1 553
227 156 64S R<2 Inhibit * Inhibit 64S Under Impedance Stage 2 554
227 157 64S Filter On * Enable the 64S band pass filter permanently 555
230 132 64R R<1 Inhibit * * * * Inhibit 64R Under Impedance Stage 1 556
230 133 64R R<2 Inhibit * * * * Inhibit 64R Under Impedance Stage 2 557
231 27 558
231 28 559
231 29 560
231 30 561
231 31 562
231 32 563
231 33 564
231 34 565
231 35 566
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 126 of 163

231 36 567
231 37 568
231 38 569
231 39 570
231 40 571
231 41 572
231 42 573
231 43 574
231 44 575
227 98 I>1 Timer Block * * * * * * Block Phase Overcurrent Stage 1 time delay 576
227 99 I>2 Timer Block * * * * * * Block Phase Overcurrent Stage 2 time delay 577
227 100 I>3 Timer Block * * * * * * Block Phase Overcurrent Stage 3 time delay 578
227 101 I>4 Timer Block * * * * * * Block Phase Overcurrent Stage 4 time delay 579
231 249 580
231 250 581
227 147 I2> Inhibit * * * * * * Inhibit NPS Overcurrent protection 582
227 148 I2>1 Timer Block * * * * * * Block NPS Overcurrent Stage 1 Timer 583
227 149 I2>2 Timer Block * * * * * * Block NPS Overcurrent Stage 2 Timer 584
227 150 I2>3 Timer Block * * * * * * Block NPS Overcurrent Stage 3 Timer 585
227 151 I2>4 Timer Block * * * * * * Block NPS Overcurrent Stage 4 Timer 586
227 152 587
230 158 588
230 159 589
230 160 590
230 161 591
227 112 VN>1 Timer Blk * * * * * * Block Residual Over Voltage Stage 1 time delay 592
227 113 VN>2 Timer Blk * * * * * * Block Residual Over Voltage Stage 2 time delay 593
227 142 VN>3 Timer Block * * * * * * Block Residual Over Voltage Stage 3 Timer 594
227 143 VN>4 Timer Block * * * * * * Block Residual Over Voltage Stage 4 Timer 595
227 144 VN>5 Timer Block * * Block Residual Over Voltage Stage 5 Timer 596
227 145 VN>6 Timer Block * * Block Residual Over Voltage Stage 6 Timer 597
227 116 V>1 Timer Block * * * * * * Block Phase Over Voltage Stage 1 time delay 598
227 117 V>2 Timer Block * * * * * * Block Phase Over Voltage Stage 2 time delay 599
227 152 V2>1 Accelerate * * * * * * Accelerate NPS Over Voltage Stage 1 Start 600
227 114 V<1 Timer Block * * * * * * Block Phase Under Voltage Stage 1 time delay 601
227 115 V<2 Timer Block * * * * * * Block Phase Under Voltage Stage 2 time delay 602
227 152 603
230 174 604
230 175 605
230 176 606
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 127 of 163

230 177 607


227 96 VDepOC Timer Blk * * * * Voltage Dependant Overcurrent time delay 608
227 97 UnderZ Timer Blk * * * * Under Impedance time delay 609
227 124 610
227 125 611
227 126 612
227 127 613
227 128 614
227 129 615
227 130 616
227 131 617
227 132 618
224 22 619
227 82 620
227 158 621
227 159 622
227 32 623
229 14 Stop Freq Track * * * * * * Stop / Halt Frequency Tracking 624
227 153 V/Hz>1 Inhibit * * * * Inhibit Volts per Hz Stage 1 625
227 118 F<1 Timer Block * * * * * * Block Under Frequency Stage 1 Timer 626
227 119 F<2 Timer Block * * * * * * Block Under Frequency Stage 2 Timer 627
227 120 F<3 Timer Block * * * * * * Block Under Frequency Stage 3 Timer 628
227 121 F<4 Timer Block * * * * * * Block Under Frequency Stage 4 Timer 629
227 122 F>1 Timer Block * * * * * * Block Over Frequency Stage 1 Timer 630
227 123 F>2 Timer Block * * * * * * Block Over Frequency Stage 2 Timer 631
227 146 Turbine F Inh * * * * Inhibit Turbine Abnormal Frequency Protection 632
230 153 df/dt> Inhibit * * * * * * df/dt> Inhibit 633
230 154 df/dt>1 Tmr Blk * * * * * * df/dt>1 Tmr Blk 634
230 155 df/dt>2 Tmr Blk * * * * * * df/dt>2 Tmr Blk 635
230 156 df/dt>3 Tmr Blk * * * * * * df/dt>3 Tmr Blk 636
230 157 df/dt>4 Tmr Blk * * * * * * df/dt>4 Tmr Blk 637
230 190 638
230 191 639
227 133 Reset I2 Thermal * * * * Reset NPS Thermal State 640
227 134 Reset ThermalO/L * * * * * * Reset Thermal Overload State 641
230 134 DLR I>1 Inhibit * Inhibit DLR Stage 1 642
230 135 DLR I>2 Inhibit * Inhibit DLR Stage 2 643
230 136 DLR I>3 Inhibit * Inhibit DLR Stage 3 644
230 137 DLR I>4 Inhibit * Inhibit DLR Stage 4 645
230 138 DLR I>5 Inhibit * Inhibit DLR Stage 5 646
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 128 of 163

230 139 DLR I>6 Inhibit * Inhibit DLR Stage 6 647


230 140 DLR Scheme Inh * Scheme Logic Inhibit 648
227 135 Reset XThermal * * * * Reset Xformer Thermal Overload State 649
2 1,7 232 38 Frcd Air Cool * * * * Select forced air cooling 650
2 1,7 232 39 Frcd Oil Cool * * * * Select forced oil cooling 651
227 192 TFR De-energised * * * * Xformer De-energised Status 652
227 177 653
227 178 654
227 179 655
227 137 CL Input 1 Blk * * * * * * Block Current Loop Input 1 protection 656
227 138 CL Input 2 Blk * * * * * * Block Current Loop Input 2 protection 657
227 139 CL Input 3 Blk * * * * * * Block Current Loop Input 3 protection 658
227 140 CL Input 4 Blk * * * * * * Block Current Loop Input 4 protection 659
231 45 660
231 46 661
227 185 662
224 92 663
224 93 664
227 188 665
227 189 666
227 190 667
227 191 668
227 192 669
227 193 670
227 194 671
227 32 Fault REC TRIG * * * * * * Fault Record Trigger Input 672
227 192 673
2 1,7 224 68 Any Trip * * * * * * Any Trip 674
1 1,7,9 230 130 SG Select x1 * * * * * * Setting Group Selector x1 (bit 0) 675
1 1,7,9 230 131 SG Select 1x * * * * * * Setting Group Selector 1x (bit 1) 676
227 159 Test Mode * * * * * * Initiate Test Mode 677
227 110 Init Trip CB * * * * * * Logic Input Trip CB 678
227 111 Init Close CB * * * * * * Logic Input Close CB 679
227 124 Ext. Trip 3ph * * * * * * External Trip 3ph 680
227 125 CB Aux 3ph(52-A) * * * * * * 52-A (3 phase) 681
227 126 CB Aux 3ph(52-B) * * * * * * 52-B (3 phase) 682
227 127 CB Healthy * * * * * * CB Healthy 683
227 128 MCB/VTS * * * * * * MCB/VTS opto 684
1 9, 11 224 20 Monitor Blocked * * * * * * * IEC60870-5-103 Monitor Blocking 685
1 9, 11 227 136 Command Blocked * * * * * * * IEC60870-5-103 Command Blocking 686
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 129 of 163

227 158 Time Synch * * * * * * Time synchronise to nearest minute on 0-1 change 687
227 129 Reset Close Dly * * * * * * Reset Manual CB Close Time Delay 688
227 130 Reset Relays/LED * * * * * * Reset Latched Relays & LED’s 689
227 131 Reset Lockout * * * * * * Reset Lockout Opto Input 690
227 132 Reset All Values * * * * * * Reset CB Maintenance Values 691
230 178 RP1 Read Only * * * * * * Remote Read Only 1 DDB 692
230 179 RP2 Read Only * * * * * * Remote Read Only 2 DDB 693
230 180 NIC Read Only * * * * * * Remote Read Only NIC DDB 694
230 182 103 MonitorBlock * * * * * * Monitor Block 695
230 183 103 CommandBlock * * * * * * Command Block 696
233 180 * * * * * * in order to make this version compatible with the pa 697
233 181 * * * * * * in order to make this version compatible with the pa 698
233 182 * * * * * * in order to make this version compatible with the pa 699
233 183 * * * * * * in order to make this version compatible with the pa 700
233 184 * * * * * * in order to make this version compatible with the pa 701
233 185 * * * * * * in order to make this version compatible with the pa 702
233 186 * * * * * * in order to make this version compatible with the pa 703
224 90 704
224 69 705
224 70 706
224 71 707
224 91 708
227 226 709
227 227 710
227 228 711
227 229 712
227 230 713
227 231 714
227 232 715
227 233 716
227 234 717
227 235 718
227 236 719
227 239 720
227 240 721
227 241 722
227 242 723
227 169 724
227 170 725
227 171 726
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 130 of 163

227 172 727


227 244 728
227 245 729
227 246 730
227 247 731
227 248 732
227 249 733
227 250 734
227 251 735
2 1,7 227 162 Gen Diff Trip * * * Generator Differential Trip 3ph 736
2 1,7 227 163 Gen Diff Trip A * * * Generator Differential Trip A 737
2 1,7 227 164 Gen Diff Trip B * * * Generator Differential Trip B 738
2 1,7 227 165 Gen Diff Trip C * * * Generator Differential Trip C 739
2 1,7 232 2 Xform Dif Trp * * * Xformer Differential Trip 3ph 740
2 1,7 232 3 Xform Dif Trp A * * * Xformer Differential Trip A 741
2 1,7 232 4 Xform Dif Trp B * * * Xformer Differential Trip B 742
2 1,7 232 5 Xform Dif Trp C * * * Xformer Differential Trip C 743
2 1,7 232 6 Xform Bias Trp A * * * Xformer Differential Low Set Trip A 744
2 1,7 232 7 Xform Bias Trp B * * * Xformer Differential Low Set Trip B 745
2 1,7 232 8 Xform Bias Trp C * * * Xformer Differential Low Set Trip C 746
2 1,7 232 9 Xform HS1 Trp A * * * Xformer Differential HS1 Trip A 747
2 1,7 232 10 Xform HS1 Trp B * * * Xformer Differential HS1Trip B 748
2 1,7 232 11 Xform HS1 Trp C * * * Xformer Differential HS1Trip C 749
2 1,7 232 12 Xform HS2 Trp A * * * Xformer Differential HS2 Trip A 750
2 1,7 232 13 Xform HS2 Trp B * * * Xformer Differential HS2Trip B 751
2 1,7 232 14 Xform HS2 Trp C * * * Xformer Differential HS2Trip C 752
231 129 753
231 130 754
231 131 755
231 132 756
231 133 757
231 134 758
231 135 759
231 136 760
231 137 761
231 138 762
231 139 763
231 140 764
231 141 765
231 142 766
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 131 of 163

231 143 767


2 1,7 224 92 IN>1 Trip * * * * * * 1st Stage EF Trip 768
2 1,7 224 93 IN>2 Trip * * * * * * 2nd Stage EF Trip 769
2 1,7 227 188 IN>3 Trip * * 3rd Stage EF Trip 770
2 1,7 227 189 IN>4 Trip * * 4th Stage EF Trip 771
2 1,7 227 190 IREF> Trip * * * * * * REF Trip 772
2 1,7 227 191 ISEF>1 Trip * * * * * * 1st Stage SEF Trip 773
2 1,7 227 192 ISEF>2 Trip * * 2nd Stage SEF Trip 774
2 1,7 227 193 ISEF>3 Trip * * 3rd Stage SEF Trip 775
2 1,7 227 194 ISEF>4 Trip * * 4th Stage SEF Trip 776
2 1,7 227 160 100%StEF3H Trip * * * 100% Stator Earth Fault (3rd harmonic) Trip 777
2 1,7 228 19 64S I>1 Trip * 64S 100% Stator Earth Fault Overcurrent Trip 778
2 1,7 228 20 64S R<2 Trip * 64S 100% St EF Under Resistance Stage 2 Trip 779
2 1,7 228 21 64R R<2 Trip * * * * 64R Rotor Earth Fault Under Resistance Stage 2 Tr 780
231 144 781
231 145 782
231 146 783
231 147 784
231 148 785
231 149 786
231 150 787
231 151 788
231 152 789
231 153 790
231 154 791
231 155 792
231 156 793
231 157 794
231 158 795
231 159 796
231 160 797
231 161 798
231 162 799
2 1,7 224 90 I>1 Trip * * * * * * 1st Stage O/C Trip 3ph 800
2 1,7 224 69 I>1 Trip A * * * * * * 1st Stage O/C Trip A 801
2 1,7 224 70 I>1 Trip B * * * * * * 1st Stage O/C Trip B 802
2 1,7 224 71 I>1 Trip C * * * * * * 1st Stage O/C Trip C 803
2 1,7 224 91 I>2 Trip * * * * * * 2nd Stage O/C Trip 3ph 804
2 1,7 227 226 I>2 Trip A * * * * * * 2nd Stage O/C Trip A 805
2 1,7 227 227 I>2 Trip B * * * * * * 2nd Stage O/C Trip B 806
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 132 of 163

2 1,7 227 228 I>2 Trip C * * * * * * 2nd Stage O/C Trip C 807
2 1,7 227 229 I>3 Trip * * * * * * 3rd Stage O/C Trip 3ph 808
2 1,7 227 230 I>3 Trip A * * * * * * 3rd Stage O/C Trip A 809
2 1,7 227 231 I>3 Trip B * * * * * * 3rd Stage O/C Trip B 810
2 1,7 227 232 I>3 Trip C * * * * * * 3rd Stage O/C Trip C 811
2 1,7 227 233 I>4 Trip * * * * * * 4th Stage O/C Trip 3ph 812
2 1,7 227 234 I>4 Trip A * * * * * * 4th Stage O/C Trip A 813
2 1,7 227 235 I>4 Trip B * * * * * * 4th Stage O/C Trip B 814
2 1,7 227 236 I>4 Trip C * * * * * * 4th Stage O/C Trip C 815
231 163 816
231 164 817
231 165 818
231 166 819
231 167 820
231 168 821
231 169 822
231 170 823
2 1,7 228 11 I2>1 Trip * * * * * * NPS Overcurrent Stage 1 Trip 824
2 1,7 228 12 I2>2 Trip * * * * * * NPS Overcurrent Stage 2 Trip 825
2 1,7 228 13 I2>3 Trip * * * * * * NPS Overcurrent Stage 3 Trip 826
2 1,7 228 14 I2>4 Trip * * * * * * NPS Overcurrent Stage 4 Trip 827
2 1,7 227 237 Bfail1 Trip 3ph * * * * * * tBF1 Trip 3ph 828
2 1,7 227 238 Bfail2 Trip 3ph * * * * * * tBF2 Trip 3ph 829
231 171 830
231 172 831
2 1,7 227 195 VN>1 Trip * * * * * * 1st Stage Residual O/V Trip 832
2 1,7 227 196 VN>2 Trip * * * * * * 2nd Stage Residual O/V Trip 833
2 1,7 228 0 VN>3 Trip * * * * * * Residual O/V Stage 3 Trip 834
2 1,7 228 1 VN>4 Trip * * * * * * Residual O/V Stage 4 Trip 835
2 1,7 228 2 VN>5 Trip * * Residual O/V Stage 5 Trip 836
2 1,7 228 3 VN>6 Trip * * Residual O/V Stage 6 Trip 837
2 1,7 227 205 V>1 Trip * * * * * * 1st Stage Phase O/V Trip 3ph 838
2 1,7 227 206 V>1 Trip A/AB * * * * * * 1st Stage Phase O/V Trip A/AB 839
2 1,7 227 207 V>1 Trip B/BC * * * * * * 1st Stage Phase O/V Trip B/BC 840
2 1,7 227 208 V>1 Trip C/CA * * * * * * 1st Stage Phase O/V Trip C/CA 841
2 1,7 227 209 V>2 Trip * * * * * * 2nd Stage Phase O/V Trip 3ph 842
2 1,7 227 210 V>2 Trip A/AB * * * * * * 2nd Stage Phase O/V Trip A/AB 843
2 1,7 227 211 V>2 Trip B/BC * * * * * * 2nd Stage Phase O/V Trip B/BC 844
2 1,7 227 212 V>2 Trip C/CA * * * * * * 2nd Stage Phase O/V Trip C/CA 845
2 1,7 228 15 V2>1 Trip * * * * * * NPS Over Voltage Stage 1 Trip 846
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 133 of 163

2 1,7 227 197 V<1 Trip * * * * * * 1st Stage Phase U/V Trip 3ph 847
2 1,7 227 198 V<1 Trip A/AB * * * * * * 1st Stage Phase U/V Trip A/AB 848
2 1,7 227 199 V<1 Trip B/BC * * * * * * 1st Stage Phase U/V Trip B/BC 849
2 1,7 227 200 V<1 Trip C/CA * * * * * * 1st Stage Phase U/V Trip C/CA 850
2 1,7 227 201 V<2 Trip * * * * * * 2nd Stage Phase U/V Trip 3ph 851
2 1,7 227 202 V<2 Trip A/AB * * * * * * 2nd Stage Phase U/V Trip A/AB 852
2 1,7 227 203 V<2 Trip B/BC * * * * * * 2nd Stage Phase U/V Trip B/BC 853
2 1,7 227 204 V<2 Trip C/CA * * * * * * 2nd Stage Phase U/V Trip C/CA 854
231 173 855
231 174 856
231 175 857
231 176 858
231 177 859
231 178 860
231 179 861
231 180 862
231 181 863
2 1,7 227 166 Field Fail1 Trip * * * * Field Failure Stage 1 Trip 864
2 1,7 227 167 Field Fail2 Trip * * * * Field Failure Stage 2 Trip 865
2 1,7 227 241 PSlipz Z1 Trip * * * Pole Slip (Impedance) Zone1 Trip 866
2 1,7 227 242 PSlipz Z2 Trip * * * Pole Slip (Impedance) Zone2 Trip 867
2 1,7 227 169 V Dep OC Trip * * * * Voltage Dependant Overcurrent Trip 3ph 868
2 1,7 227 170 V Dep OC Trip A * * * * Voltage Dependant Overcurrent Trip A 869
2 1,7 227 171 V Dep OC Trip B * * * * Voltage Dependant Overcurrent Trip B 870
2 1,7 227 172 V Dep OC Trip C * * * * Voltage Dependant Overcurrent Trip C 871
2 1,7 227 244 Z<1 Trip * * * * Under Impedance 3Phase Stage 1 Trip 872
2 1,7 227 245 Z<1 Trip A * * * * Under Impedance Phase A Stage 1 Trip 873
2 1,7 227 246 Z<1 Trip B * * * * Under Impedance Phase B Stage 1 Trip 874
2 1,7 227 247 Z<1 Trip C * * * * Under Impedance Phase C Stage 1 Trip 875
2 1,7 227 248 Z<2 Trip * * * * Under Impedance 3Phase Stage 2 Trip 876
2 1,7 227 249 Z<2 Trip A * * * * Under Impedance Phase A Stage 2 Trip 877
2 1,7 227 250 Z<2 Trip B * * * * Under Impedance Phase B Stage 2 Trip 878
2 1,7 227 251 Z<2 Trip C * * * * Under Impedance Phase C Stage 2 Trip 879
2 1,7 227 161 DeadMachine Trip * * * Dead Machine Protection Trip 880
2 1,7 228 4 S2>1 Trip * * * * NPS Overpower Stage 1 trip 881
2 1,7 227 219 Power1 Trip * * * * * * Power Stage 1 Trip 882
2 1,7 227 220 Power2 Trip * * * * * * Power Stage 2 Trip 883
2 1,7 227 239 SPower1 Trip * * * * * * Sensitive A Phase Power Stage 1 Trip 884
2 1,7 227 240 SPower2 Trip * * * * * * Sensitive A Phase Power Stage 2 Trip 885
228 54 886
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 134 of 163

228 55 887
228 56 888
228 57 889
228 58 890
228 59 891
228 60 892
228 61 893
228 62 894
228 63 895
228 54 896
228 55 897
228 56 898
228 57 899
228 58 900
228 54 901
228 54 902
228 55 903
228 56 904
228 57 905
228 58 906
228 59 907
228 60 908
228 61 909
228 62 910
228 63 911
2 1,7 227 173 V/Hz>1 Trip * * * * 1st Stage Volts per Hz Trip 912
2 1,7 228 16 V/Hz>2 Trip * * * * Volts per Hz Stage 2 Trip 913
2 1,7 228 17 V/Hz>3 Trip * * * * Volts per Hz Stage 3 Trip 914
2 1,7 228 18 V/Hz>4 Trip * * * * Volts per Hz Stage 4 Trip 915
2 1,7 227 213 F<1 Trip * * * * * * Under Frequency Stage 1 Trip 916
2 1,7 227 214 F<2 Trip * * * * * * Under Frequency Stage 2 Trip 917
2 1,7 227 215 F<3 Trip * * * * * * Under Frequency Stage 3 Trip 918
2 1,7 227 216 F<4 Trip * * * * * * Under Frequency Stage 4 Trip 919
2 1,7 227 217 F>1 Trip * * * * * * Over Frequency Stage 1 Trip 920
2 1,7 227 218 F>2 Trip * * * * * * Over Frequency Stage 2 Trip 921
2 1,7 228 5 Freq Band1 Trip * * * * Turbine Abnormal Frequency Band 1 Trip 922
2 1,7 228 6 Freq Band2 Trip * * * * Turbine Abnormal Frequency Band 2 Trip 923
2 1,7 228 7 Freq Band3 Trip * * * * Turbine Abnormal Frequency Band 3 Trip 924
2 1,7 228 8 Freq Band4 Trip * * * * Turbine Abnormal Frequency Band 4 Trip 925
2 1,7 228 9 Freq Band5 Trip * * * * Turbine Abnormal Frequency Band 5 Trip 926
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 135 of 163

2 1,7 228 10 Freq Band6 Trip * * * * Turbine Abnormal Frequency Band 6 Trip 927
2 1,7 232 15 Trip df/dt>1 * * * * * * df/dt>1 Trip 928
2 1,7 232 16 Trip df/dt>2 * * * * * * df/dt>2 Trip 929
2 1,7 232 17 Trip df/dt>3 * * * * * * df/dt>3 Trip 930
2 1,7 232 18 Trip df/dt>4 * * * * * * df/dt>4 Trip 931
232 19 932
2 1,7 227 185 V Shift Trip * * Voltage Vector Shift Trip 933
230 216 934
230 217 935
1 1,7,9 230 218 df/dt>1 Under F * * * * * * Rate Of Change Of Frequency Stage 1 Under Freq 936
1 1,7,9 230 219 df/dt>1 Over F * * * * * * Rate Of Change Of Frequency Stage 1 Over Frequ 937
230 220 938
230 221 939
230 222 940
230 223 941
231 238 942
231 239 943
2 1,7 227 168 NPS Thermal Trip * * * * Negative Phase Sequence Thermal Trip 944
2 1,7 227 243 Thermal O/L Trip * * * * * * Thermal Overload Trip 945
2 1,7 232 20 Hot Spot>1 Trip * * * * Hot Spot>1 Trip 946
2 1,7 232 21 Hot Spot>2 Trip * * * * Hot Spot>2 Trip 947
2 1,7 232 22 Hot Spot>3 Trip * * * * Hot Spot>3 Trip 948
2 1,7 232 23 Top Oil>1 Trip * * * * Top Oil>1 Trip 949
2 1,7 232 24 Top Oil>2 Trip * * * * Top Oil>2 Trip 950
2 1,7 232 25 Top Oil>3 Trip * * * * Top Oil>3 Trip 951
2 1,7 228 23 DLR I>1 Trip * DLR Ampacity prot. stage 1 trip 952
2 1,7 228 24 DLR I>2 Trip * DLR Ampacity prot. stage 2 trip 953
2 1,7 228 25 DLR I>3 Trip * DLR Ampacity prot. stage 3 trip 954
2 1,7 228 26 DLR I>4 Trip * DLR Ampacity prot. stage 4 trip 955
2 1,7 228 27 DLR I>5 Trip * DLR Ampacity prot. stage 5 trip 956
2 1,7 228 28 DLR I>6 Trip * DLR Ampacity prot. stage 6 trip 957
232 40 958
232 41 959
231 240 960
231 241 961
231 243 962
229 177 963
231 242 964
231 244 965
231 245 966
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 136 of 163

231 246 967


231 247 968
231 238 969
231 239 970
231 240 971
231 241 972
231 242 973
231 243 974
228 207 975
2 1,7 227 174 RTD 1 Trip * * * * RTD 1 Trip 976
2 1,7 227 175 RTD 2 Trip * * * * RTD 2 Trip 977
2 1,7 227 176 RTD 3 Trip * * * * RTD 3 Trip 978
2 1,7 227 177 RTD 4 Trip * * * * RTD 4 Trip 979
2 1,7 227 178 RTD 5 Trip * * * * RTD 5 Trip 980
2 1,7 227 179 RTD 6 Trip * * * * RTD 6 Trip 981
2 1,7 227 180 RTD 7 Trip * * * * RTD 7 Trip 982
2 1,7 227 181 RTD 8 Trip * * * * RTD 8 Trip 983
2 1,7 227 182 RTD 9 Trip * * * * RTD 9 Trip 984
2 1,7 227 183 RTD 10 Trip * * * * RTD 10 Trip 985
2 1,7 227 184 Any RTD Trip * * * * Any RTD Trip 986
2 1,7 227 252 CL Input 1 Trip * * * * * * Current Loop Input 1 Trip 987
2 1,7 227 253 CL Input 2 Trip * * * * * * Current Loop Input 2 Trip 988
2 1,7 227 254 CL Input 3 Trip * * * * * * Current Loop Input 3 Trip 989
2 1,7 227 255 CL Input 4 Trip * * * * * * Current Loop Input 4 Trip 990
228 223 991
2 1,7,9 224 84 Any Start * * * * * * * Any Start 992
2 1,7,9 233 0 Xform Bias StrtA * * * Xformer Differential Start A 993
2 1,7,9 233 1 Xform Bias StrtB * * * Xformer Differential Start B 994
2 1,7,9 233 2 Xform Bias StrtC * * * Xformer Differential Start C 995
231 182 996
231 183 997
231 184 998
231 185 999
231 186 1000
231 187 1001
231 188 1002
231 189 1003
231 190 1004
231 191 1005
231 192 1006
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 137 of 163

231 193 1007


2 1,7,9 224 67 IN>1 Start * * * * * * * 1st Stage EF Start 1008
2 1,7,9 228 102 IN>2 Start * * * * * * * 2nd Stage EF Start 1009
2 1,7,9 228 103 IN>3 Start * * * 3rd Stage EF Start 1010
2 1,7,9 228 104 IN>4 Start * * * 4th Stage EF Start 1011
2 1,7,9 228 105 ISEF>1 Start * * * * * * * 1st Stage SEF Start 1012
2 1,7,9 228 106 ISEF>2 Start * * * 2nd Stage SEF Start 1013
2 1,7,9 228 107 ISEF>3 Start * * * 3rd Stage SEF Start 1014
2 1,7,9 228 108 ISEF>4 Start * * * 4th Stage SEF Start 1015
2 1,7,9 228 109 100%StEF3H Start * * * * 100% Stator Earth Fault (3rd harmonic) Start 1016
2 1,7,9 228 174 64S I< Start * * 64S 100% Stator Earth Fault Undercurrent Start 1017
2 1,7,9 228 175 64S V< Start * * 64S 100% Stator Earth Fault Undervoltage Start 1018
2 1,7,9 228 176 64S I>1 Start * * 64S 100% Stator Earth Fault Overcurrent Start 1019
2 1,7,9 228 177 64S Start R<1Alm * * 64S 100% St EF Under Resistance Stg 1 Alm Start 1020
2 1,7,9 228 178 64S R<2 Start * * 64S 100% St EF Under Resistance Stg 2 Trip Start 1021
2 1,7,9 228 184 64R Start R<1Alm * * * * * 64R Rotor EF Under Resistance Stg 1 Alm Start 1022
2 1,7,9 228 185 64R R<2 Start * * * * * 64R Rotor EF Under Resistance Stg 2 Trip Start 1023
231 194 1024
231 195 1025
231 196 1026
231 197 1027
231 198 1028
231 199 1029
231 200 1030
231 201 1031
231 202 1032
231 203 1033
231 204 1034
231 205 1035
231 206 1036
231 207 1037
231 208 1038
231 209 1039
2 1,7,9 228 85 I>1 Start * * * * * * * 1st Stage O/C Start 3ph 1040
2 1,7,9 224 64 I>1 Start A * * * * * * * 1st Stage O/C Start A 1041
2 1,7,9 224 65 I>1 Start B * * * * * * * 1st Stage O/C Start B 1042
2 1,7,9 224 66 I>1 Start C * * * * * * * 1st Stage O/C Start C 1043
2 1,7,9 228 89 I>2 Start * * * * * * * 2nd Stage O/C Start 3ph 1044
2 1,7,9 228 90 I>2 Start A * * * * * * * 2nd Stage O/C Start A 1045
2 1,7,9 228 91 I>2 Start B * * * * * * * 2nd Stage O/C Start B 1046
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 138 of 163

2 1,7,9 228 92 I>2 Start C * * * * * * * 2nd Stage O/C Start C 1047


2 1,7,9 228 93 I>3 Start * * * * * * * 3rd Stage O/C Start 3ph 1048
2 1,7,9 228 94 I>3 Start A * * * * * * * 3rd Stage O/C Start A 1049
2 1,7,9 228 95 I>3 Start B * * * * * * * 3rd Stage O/C Start B 1050
2 1,7,9 228 96 I>3 Start C * * * * * * * 3rd Stage O/C Start C 1051
2 1,7,9 228 97 I>4 Start * * * * * * * 4th Stage O/C Start 3ph 1052
2 1,7,9 228 98 I>4 Start A * * * * * * * 4th Stage O/C Start A 1053
2 1,7,9 228 99 I>4 Start B * * * * * * * 4th Stage O/C Start B 1054
2 1,7,9 228 100 I>4 Start C * * * * * * * 4th Stage O/C Start C 1055
231 210 1056
231 211 1057
231 212 1058
231 213 1059
231 214 1060
231 215 1061
231 216 1062
231 217 1063
2 1,7,9 228 166 I2>1 Start * * * * * * * NPS Overcurrent Stage 1 Start 1064
2 1,7,9 228 167 I2>2 Start * * * * * * * NPS Overcurrent Stage 2 Start 1065
2 1,7,9 228 168 I2>3 Start * * * * * * * NPS Overcurrent Stage 3 Start 1066
2 1,7,9 228 169 I2>4 Start * * * * * * * NPS Overcurrent Stage 4 Start 1067
228 119 IA< Start * * * * * * Fast under current: Phase A 1068
228 120 IB< Start * * * * * * Fast under current: Phase B 1069
228 121 IC< Start * * * * * * Fast under current: Phase C 1070
228 122 ISEF< Start * * * * * * ISEF< Operate 1071
228 123 IN< Start * * * * IN< Operate 1072
2 1,7,9 228 116 I> BlockStart * * * I> Blocked O/C Start 1073
2 1,7,9 228 117 IN/SEF>Blk Start * * * IN/ISEF> Blocked O/C Start 1074
2 1,7 229 24 TF OC Start * * * * Through fault START 1075
229 177 1076
233 4 TF Recorder trig * * * * Through fault TRIGGER 1077
231 218 1078
231 219 1079
231 220 1080
231 221 1081
231 222 1082
231 223 1083
231 224 1084
231 225 1085
231 226 1086
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 139 of 163

231 227 1087


2 1,7,9 228 65 VN>1 Start * * * * * * * 1st Stage Residual O/V Start 1088
2 1,7,9 228 66 VN>2 Start * * * * * * * 2nd Stage Residual O/V Start 1089
2 1,7,9 228 154 VN>3 Start * * * * * * * Residual O/V Stage 3 Start 1090
2 1,7,9 228 155 VN>4 Start * * * * * * * Residual O/V Stage 4 Start 1091
2 1,7,9 228 156 VN>5 Start * * * Residual O/V Stage 5 Start 1092
2 1,7,9 228 157 VN>6 Start * * * Residual O/V Stage 6 Start 1093
2 1,7,9 228 75 V>1 Start * * * * * * * 1st Stage Phase O/V Start 3ph 1094
2 1,7,9 228 76 V>1 Start A/AB * * * * * * * 1st Stage Phase O/V Start A/AB 1095
2 1,7,9 228 77 V>1 Start B/BC * * * * * * * 1st Stage Phase O/V Start B/BC 1096
2 1,7,9 228 78 V>1 Start C/CA * * * * * * * 1st Stage Phase O/V Start C/CA 1097
2 1,7,9 228 79 V>2 Start * * * * * * * 2nd Stage Phase O/V Start 3ph 1098
2 1,7,9 228 80 V>2 Start A/AB * * * * * * * 2nd Stage Phase O/V Start A/AB 1099
2 1,7,9 228 81 V>2 Start B/BC * * * * * * * 2nd Stage Phase O/V Start B/BC 1100
2 1,7,9 228 82 V>2 Start C/CA * * * * * * * 2nd Stage Phase O/V Start C/CA 1101
2 1,7,9 228 170 V2>1 Start * * * * * * * NPS Over Voltage Stage 1 Start 1102
2 1,7,9 228 67 V<1 Start * * * * * * * 1st Stage Phase U/V Start 3ph 1103
2 1,7,9 228 68 V<1 Start A/AB * * * * * * * 1st Stage Phase U/V Start A/AB 1104
2 1,7,9 228 69 V<1 Start B/BC * * * * * * * 1st Stage Phase U/V Start B/BC 1105
2 1,7,9 228 70 V<1 Start C/CA * * * * * * * 1st Stage Phase U/V Start C/CA 1106
2 1,7,9 228 71 V<2 Start * * * * * * * 2nd Stage Phase U/V Start 3ph 1107
2 1,7,9 228 72 V<2 Start A/AB * * * * * * * 2nd Stage Phase U/V Start A/AB 1108
2 1,7,9 228 73 V<2 Start B/BC * * * * * * * 2nd Stage Phase U/V Start B/BC 1109
2 1,7,9 228 74 V<2 Start C/CA * * * * * * * 2nd Stage Phase U/V Start C/CA 1110
231 228 1111
231 229 1112
231 230 1113
231 231 1114
231 232 1115
231 233 1116
231 234 1117
231 235 1118
231 236 1119
2 1,7,9 228 125 FFail1 Start * * * * * Field Failure Stage 1 Start 1120
2 1,7,9 228 126 FFail2 Start * * * * * Field Failure Stage 2 Start 1121
2 1,7,9 228 133 PSlipz Z1 Start * * * * Pole Slip (Impedance) Zone1 Start 1122
2 1,7,9 228 134 PSlipz Z2 Start * * * * Pole Slip (Impedance) Zone2 Start 1123
2 1,7,9 228 135 PSlipz LensStart * * * * Pole Slip (impedance) Lens Start 1124
2 1,7,9 228 136 PSlipz BlindStrt * * * * Pole Slip (impedance) Blinder Start 1125
2 1,7,9 228 137 PSlipz ReactStrt * * * * Pole Slip (impedance) Reactance Line Start 1126
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 140 of 163

2 1,7,9 228 127 V Dep OC Start * * * * * Voltage Dependant Overcurrent Start 3Ph 1127
2 1,7,9 228 128 V Dep OC Start A * * * * * Voltage Dependant Overcurrent Start A 1128
2 1,7,9 228 129 V Dep OC Start B * * * * * Voltage Dependant Overcurrent Start B 1129
2 1,7,9 228 130 V Dep OC Start C * * * * * Voltage Dependant Overcurrent Start C 1130
2 1,7,9 228 138 Z<1 Start * * * * * Under Impedance 3Phase Stage 1 Start 1131
2 1,7,9 228 139 Z<1 Start A * * * * * Under Impedance Phase A Stage 1 Start 1132
2 1,7,9 228 140 Z<1 Start B * * * * * Under Impedance Phase B Stage 1 Start 1133
2 1,7,9 228 141 Z<1 Start C * * * * * Under Impedance Phase C Stage 1 Start 1134
2 1,7,9 228 142 Z<2 Start * * * * * Under Impedance 3Phase Stage 2 Start 1135
2 1,7,9 228 143 Z<2 Start A * * * * * Under Impedance Phase A Stage 2 Start 1136
2 1,7,9 228 144 Z<2 Start B * * * * * Under Impedance Phase B Stage 2 Start 1137
2 1,7,9 228 145 Z<2 Start C * * * * * Under Impedance Phase C Stage 2 Start 1138
2 1,7,9 228 158 S2>1 Start * * * * * NPS Overpower Stage 1 Start 1139
2 1,7,9 228 83 Power1 Start * * * * * * * Power Stage 1 Start 1140
2 1,7,9 228 84 Power2 Start * * * * * * * Power Stage 2 Start 1141
2 1,7,9 228 131 SPower1 Start * * * * * * * Sensitive A Phase Power Stage 1 Start 1142
2 1,7,9 228 132 SPower2 Start * * * * * * * Sensitive A Phase Power Stage 2 Start 1143
228 216 1144
228 217 1145
228 218 1146
228 219 1147
228 220 1148
228 221 1149
228 222 1150
228 223 1151
228 219 1152
228 220 1153
228 221 1154
228 222 1155
228 223 1156
228 219 1157
228 220 1158
228 221 1159
228 222 1160
228 223 1161
228 219 1162
228 219 1163
228 220 1164
228 221 1165
228 222 1166
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 141 of 163

228 223 1167


2 1,7,9 228 124 V/Hz>1 Start * * * * * 1st Stage Volts per Hz Start 1168
2 1,7,9 228 171 V/Hz>2 Start * * * * * Volts per Hz Stage 2 Start 1169
2 1,7,9 228 172 V/Hz>3 Start * * * * * Volts per Hz Stage 3 Start 1170
2 1,7,9 228 173 V/Hz>4 Start * * * * * Volts per Hz Stage 4 Start 1171
2 1,7,9 228 110 F<1 Start * * * * * * * Under Frequency Stage 1 Start 1172
2 1,7,9 228 111 F<2 Start * * * * * * * Under Frequency Stage 2 Start 1173
2 1,7,9 228 112 F<3 Start * * * * * * * Under Frequency Stage 3 Start 1174
2 1,7,9 228 113 F<4 Start * * * * * * * Under Frequency Stage 4 Start 1175
2 1,7,9 228 114 F>1 Start * * * * * * * Over Frequency Stage 1 Start 1176
2 1,7,9 228 115 F>2 Start * * * * * * * Over Frequency Stage 2 Start 1177
2 1,7,9 228 160 Freq Band1 Start * * * * * Turbine Abnormal Frequency Band 1 Start 1178
2 1,7,9 228 161 Freq Band2 Start * * * * * Turbine Abnormal Frequency Band 2 Start 1179
2 1,7,9 228 162 Freq Band3 Start * * * * * Turbine Abnormal Frequency Band 3 Start 1180
2 1,7,9 228 163 Freq Band4 Start * * * * * Turbine Abnormal Frequency Band 4 Start 1181
2 1,7,9 228 164 Freq Band5 Start * * * * * Turbine Abnormal Frequency Band 5 Start 1182
2 1,7,9 228 165 Freq Band6 Start * * * * * Turbine Abnormal Frequency Band 6 Start 1183
2 1,7,9 233 5 Start df/dt>1 * * * * * * df/dt>1 Start 1184
2 1,7,9 233 6 Start df/dt>2 * * * * * * df/dt>2 Start 1185
2 1,7,9 233 7 Start df/dt>3 * * * * * * df/dt>3 Start 1186
2 1,7,9 233 8 Start df/dt>4 * * * * * * df/dt>4 Start 1187
228 118 1188
230 250 1189
230 251 1190
230 252 1191
230 253 1192
230 254 1193
230 255 1194
230 255 1195
231 252 1196
231 253 1197
231 254 1198
231 255 1199
2 1,7,9 228 199 Hot Spot>1 Start * * * * HotSpot>1 Start 1200
2 1,7,9 228 200 Hot Spot>2 Start * * * * HotSpot>2 Start 1201
2 1,7,9 228 201 Hot Spot>3 Start * * * * HotSpot>3 Start 1202
2 1,7,9 228 202 Top Oil>1 start * * * * Top Oil>1 Start 1203
2 1,7,9 228 203 Top Oil>2 start * * * * Top Oil>2 Start 1204
2 1,7,9 228 204 Top Oil>3 start * * * * Top Oil>3 Start 1205
2 1,7,9 228 186 DLR I>1 Start * * DLR Trip 1 Start 1206
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 142 of 163

2 1,7,9 228 187 DLR I>2 Start * * DLR Trip 2 Start 1207
2 1,7,9 228 188 DLR I>3 Start * * DLR Trip 3 Start 1208
2 1,7,9 228 189 DLR I>4 Start * * DLR Trip 4 Start 1209
2 1,7,9 228 190 DLR I>5 Start * * DLR Trip 5 Start 1210
2 1,7,9 228 191 DLR I>6 Start * * DLR Trip 6 Start 1211
232 26 1212
232 27 1213
232 28 1214
232 29 1215
231 113 1216
231 114 1217
231 115 1218
231 116 1219
231 117 1220
231 118 1221
231 119 1222
231 120 1223
231 121 1224
231 122 1225
231 123 1226
231 124 1227
231 125 1228
231 126 1229
231 127 1230
231 128 1231
2 1,7,9 228 146 CLI1 Alarm Start * * * * * * * Current Loop Input 1 Alarm Start 1232
2 1,7,9 228 147 CLI2 Alarm Start * * * * * * * Current Loop Input 2 Alarm Start 1233
2 1,7,9 228 148 CLI3 Alarm Start * * * * * * * Current Loop Input 3 Alarm Start 1234
2 1,7,9 228 149 CLI4 Alarm Start * * * * * * * Current Loop Input 4 Alarm Start 1235
2 1,7,9 228 150 CLI1 Trip Start * * * * * * * Current Loop Input 1 Trip Start 1236
2 1,7,9 228 151 CLI2 Trip Start * * * * * * * Current Loop Input 2 Trip Start 1237
2 1,7,9 228 152 CLI3 Trip Start * * * * * * * Current Loop Input 3 Trip Start 1238
2 1,7,9 228 153 CLI4 Trip Start * * * * * * * Current Loop Input 4 Trip Start 1239
232 30 1240
232 31 1241
232 32 1242
232 33 1243
232 34 1244
232 35 1245
232 36 1246
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 143 of 163

232 37 1247
1 1,7,9 228 224 VTS Fast Block * * * * * * * VTS Fast Block 1248
1 1,7,9 228 225 VTS Slow Block * * * * * * * VTS Slow Block 1249
228 250 VTS Acc Ind * * * * * * VTS Accelerate Indication 1250
228 251 VTS Volt Dep * * * * * * Any Voltage Dependent 1251
228 252 VTS IA> * * * * * * Ia Over Threshold 1252
228 253 VTS IB> * * * * * * Ib Over Threshold 1253
228 254 VTS IC> * * * * * * Ic Over Threshold 1254
228 255 VTS VA> * * * * * * Va Over Threshold 1255
229 0 VTS VB> * * * * * * Vb Over Threshold 1256
229 1 VTS VC> * * * * * * Vc Over Threshold 1257
229 2 VTS I2> * * * * * * I2 Over Threshold 1258
229 3 VTS V2> * * * * * * V2 Over Threshold 1259
229 4 VTS IA delta> * * * * * * Superimposed Ia Over Threshold 1260
229 5 VTS IB delta> * * * * * * Superimposed Ib Over Threshold 1261
229 6 VTS IC delta> * * * * * * Superimposed Ic Over Threshold 1262
1 1,7,9 228 226 CTS-1 Block * * * * * * * CTS-1 Block 1263
1 1,7,9 229 19 CTS-2 Block * * * * CTS-2 Block 1264
230 149 CTS BLK * * * differential CTS 1265
230 150 CTS CT1 * * * differential CTS 1266
230 151 CTS CT2 * * * differential CTS 1267
231 251 1268
1 1,7,9 233 9 CctFail Blk A * * * Circuitry Fault Alarm A 1269
1 1,7,9 233 10 CctFail Blk B * * * Circuitry Fault Alarm B 1270
1 1,7,9 233 11 CctFail Blk C * * * Circuitry Fault Alarm C 1271
1 1,7,9 233 12 2nd Har Blk A * * * 2nd Harmonic A 1272
1 1,7,9 233 13 2nd Har Blk B * * * 2nd Harmonic B 1273
1 1,7,9 233 14 2nd Har Blk C * * * 2nd Harmonic C 1274
1 1,7,9 233 15 5nd Har Blk A * * * 5th Har Blk A 1275
1 1,7,9 233 16 5nd Har Blk B * * * 5th Har Blk B 1276
1 1,7,9 233 17 5nd Har Blk C * * * 5th Har Blk C 1277
1 1,7,9 228 227 Control Trip * * * * * * * Control Trip 1278
1 1,7,9 228 228 Control Close * * * * * * * Control Close 1279
1 1,7,9 228 229 Close in Prog * * * * * * * Control Close in Progress 1280
1 1,7,9 228 241 Lockout Alarm * * * * * * * Composite Lockout Alarm 1281
1 1,7,9 228 242 CB Open 3 ph * * * * * * * 3 ph CB Open 1282
1 1,7,9 228 243 CB Closed 3 ph * * * * * * * 3 ph CB Closed 1283
1 1,7,9 228 245 All Poles Dead * * * * * * * All Poles Dead 1284
1 1,7,9 228 246 Any Pole Dead * * * * * * * Any Pole Dead 1285
1 1,7,9 228 247 Pole Dead A * * * * * * * Phase A Pole Dead 1286
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 144 of 163

1 1,7,9 228 248 Pole Dead B * * * * * * * Phase B Pole Dead 1287


1 1,7,9 228 249 Pole Dead C * * * * * * * Phase C Pole Dead 1288
229 7 BFail SEF Trip-1 * * * * * * CBF Current Prot SEF Stage Trip 1289
229 8 BFail Non I Tr-1 * * * * * * CBF Non Current Prot Stage Trip 1290
229 9 BFail SEF Trip * * * * * * CBF Current Prot SEF Trip 1291
229 10 BFail Non I Trip * * * * * * CBF Non Current Prot Trip 1292
229 11 Freq High * * * * * * Freq High 1293
229 12 Freq Low * * * * * * Freq Low 1294
229 13 Freq Not found * * * * * * Freq Not Found 1295
230 181 1296
1 1,7,9 229 20 64S F Band Block * * 64S 100% Stator Earth Fault - System frequency in 1297
1 1,7,9 229 21 64S Fail * * 64S 100% Stator Earth Fault - Injection failure 1298
1 1,7,9 228 230 Reconnection * * * Reconnection Time Delay Output 1299
229 15 Recon LOM-1 * * Reconnect LOM (Unqualified) 1300
229 16 Recon Disable-1 * * Reconnect Disable (Unqualified) 1301
229 17 Recon LOM * * Reconnect LOM 1302
229 18 Recon Disable * * Reconnect Disable 1303
1 1,7,9 228 231 RTD 1 Alarm * * * * * RTD 1 Alarm 1304
1 1,7,9 228 232 RTD 2 Alarm * * * * * RTD 2 Alarm 1305
1 1,7,9 228 233 RTD 3 Alarm * * * * * RTD 3 Alarm 1306
1 1,7,9 228 234 RTD 4 Alarm * * * * * RTD 4 Alarm 1307
1 1,7,9 228 235 RTD 5 Alarm * * * * * RTD 5 Alarm 1308
1 1,7,9 228 236 RTD 6 Alarm * * * * * RTD 6 Alarm 1309
1 1,7,9 228 237 RTD 7 Alarm * * * * * RTD 7 Alarm 1310
1 1,7,9 228 238 RTD 8 Alarm * * * * * RTD 8 Alarm 1311
1 1,7,9 228 239 RTD 9 Alarm * * * * * RTD 9 Alarm 1312
1 1,7,9 228 240 RTD 10 Alarm * * * * * RTD 10 Alarm 1313
231 248 Blk Rmt. CB Ops * * * * * * Blocks remote CB Trip/Close commands when asse 1314
228 37 1315
228 38 1316
228 39 1317
228 40 1318
228 41 1319
228 36 1320
228 37 1321
228 38 1322
228 39 1323
228 40 1324
228 41 1325
228 42 1326
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 145 of 163

228 43 1327
229 25 Live Gen * * * * * * Live Gen 1328
229 26 Dead Gen * * * * * * Dead Gen 1329
229 27 Live Bus * * * * * * Live Bus 1330
229 28 Dead Bus * * * * * * Dead Bus 1331
229 29 Check Sync 1 OK * * * * * * Check Sync 1 OK 1332
229 30 Check Sync 2 OK * * * * * * Check Sync 2 OK 1333
228 44 1334
231 0 SysChks Inactive * * * * * * SysChks Inactive 1335
231 1 CS1 Enabled * * * * * * CS1 Enabled 1336
231 2 CS2 Enabled * * * * * * CS2 Enabled 1337
231 3 SysSplit Enabled * * * * * * SysSplit Enabled 1338
2 1,7 231 4 CS1 Slipfreq> * * * * * * Check Synch 1 Slip > Setting 1339
231 5 CS1 Slipfreq< * * * * * * Check Synch 1 Slip < Setting 1340
2 1,7 231 6 CS2 Slipfreq> * * * * * * Check Synch 2 Slip > Setting 1341
231 7 CS2 Slipfreq< * * * * * * Check Synch 2 Slip < Setting 1342
231 8 CS Vgen< * * * * * * Gen volts less than CS undervoltage setting 1343
231 9 CS Vbus< * * * * * * Bus volts less than CS undervoltage setting 1344
231 10 CS Vgen> * * * * * * Gen volts greater than CS overvoltage setting 1345
231 11 CS Vbus> * * * * * * Bus volts greater than CS overvoltage setting 1346
231 12 Freq Low * * * * * * Gen freq less than CS underfreq setting 1347
231 13 Freq High * * * * * * Gen freq greater than CS overfreq setting 1348
231 14 CS Vgen>Vbus * * * * * * Gen volts greater than (bus volts + CS diff voltage s 1349
231 15 CS Vgen<Vbus * * * * * * Bus volts greater than (line volts + CS diff voltage se 1350
231 16 CS1 Fgen>Fbus * * * * * * Gen freq greater than (bus freq + CS1 slip freq setti 1351
231 17 CS1 Fgen<Fbus * * * * * * Bus freq greater than (line freq + CS1 slip freq setti 1352
231 18 CS1 Ang Not OK + * * * * * * Gen angle in range (CS1 ang setting to +180 deg) 1353
231 19 CS1 Ang Not OK - * * * * * * Gen angle in range (-CS1 ang setting to -180 deg) 1354
231 20 CS2 Fgen>Fbus * * * * * * Gen freq greater than (bus freq + CS2 slip freq setti 1355
231 21 CS2 Fgen<Fbus * * * * * * Bus freq greater than (gen freq + CS2 slip freq setti 1356
231 22 CS2 Ang Not OK + * * * * * * Gen angle in range (CS2 angle setting to +180 deg) 1357
231 23 CS2 Ang Not OK - * * * * * * Gen angle in range (-CS2 angle setting to -180 deg) 1358
231 24 CS Ang Rot ACW * * * * * * Gen/Bus phase angle is rotating anti-clockwise 1359
231 25 CS Ang Rot CW * * * * * * Gen/Bus phase angle is rotating clockwise 1360
231 26 CS Guard Enabled * * * * * * Check Synch Guard on 1361
230 26 Man Check Synch * * * * * * Manual check synchronization conditions are satisfi 1362
230 27 CS Guard Enable * * * * * * Check Synch Guard input 1363
227 83 1364
227 84 1365
228 38 1366
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 146 of 163

228 39 1367
228 40 1368
228 41 1369
228 42 1370
228 43 1371
228 44 1372
228 45 1373
228 46 1374
228 47 1375
1 9,11,12,20,21 229 64 Control Input 1 * * * * * * * Control Input 1 1376
1 9,11,12,20,21 229 65 Control Input 2 * * * * * * * Control Input 2 1377
1 9,11,12,20,21 229 66 Control Input 3 * * * * * * * Control Input 3 1378
1 9,11,12,20,21 229 67 Control Input 4 * * * * * * * Control Input 4 1379
1 9,11,12,20,21 229 68 Control Input 5 * * * * * * * Control Input 5 1380
1 9,11,12,20,21 229 69 Control Input 6 * * * * * * * Control Input 6 1381
1 9,11,12,20,21 229 70 Control Input 7 * * * * * * * Control Input 7 1382
1 9,11,12,20,21 229 71 Control Input 8 * * * * * * * Control Input 8 1383
1 9,11,12,20,21 229 72 Control Input 9 * * * * * * * Control Input 9 1384
1 9,11,12,20,21 229 73 Control Input 10 * * * * * * * Control Input 10 1385
1 9,11,12,20,21 229 74 Control Input 11 * * * * * * * Control Input 11 1386
1 9,11,12,20,21 229 75 Control Input 12 * * * * * * * Control Input 12 1387
1 9,11,12,20,21 229 76 Control Input 13 * * * * * * * Control Input 13 1388
1 9,11,12,20,21 229 77 Control Input 14 * * * * * * * Control Input 14 1389
1 9,11,12,20,21 229 78 Control Input 15 * * * * * * * Control Input 15 1390
1 9,11,12,20,21 229 79 Control Input 16 * * * * * * * Control Input 16 1391
1 9,11,12,20,21 229 80 Control Input 17 * * * * * * * Control Input 17 1392
1 9,11,12,20,21 229 81 Control Input 18 * * * * * * * Control Input 18 1393
1 9,11,12,20,21 229 82 Control Input 19 * * * * * * * Control Input 19 1394
1 9,11,12,20,21 229 83 Control Input 20 * * * * * * * Control Input 20 1395
1 9,11,12,20,21 229 84 Control Input 21 * * * * * * * Control Input 21 1396
1 9,11,12,20,21 229 85 Control Input 22 * * * * * * * Control Input 22 1397
1 9,11,12,20,21 229 86 Control Input 23 * * * * * * * Control Input 23 1398
1 9,11,12,20,21 229 87 Control Input 24 * * * * * * * Control Input 24 1399
1 9,11,12,20,21 229 88 Control Input 25 * * * * * * * Control Input 25 1400
1 9,11,12,20,21 229 89 Control Input 26 * * * * * * * Control Input 26 1401
1 9,11,12,20,21 229 90 Control Input 27 * * * * * * * Control Input 27 1402
1 9,11,12,20,21 229 91 Control Input 28 * * * * * * * Control Input 28 1403
1 9,11,12,20,21 229 92 Control Input 29 * * * * * * * Control Input 29 1404
1 9,11,12,20,21 229 93 Control Input 30 * * * * * * * Control Input 30 1405
1 9,11,12,20,21 229 94 Control Input 31 * * * * * * * Control Input 31 1406
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 147 of 163

1 9,11,12,20,21 229 95 Control Input 32 * * * * * * * Control Input 32 1407


1 1,7,9 229 96 Virtual Input 01 * * * * * * * Virtual Input 01 1408
1 1,7,9 229 97 Virtual Input 02 * * * * * * * Virtual Input 02 1409
1 1,7,9 229 98 Virtual Input 03 * * * * * * * Virtual Input 03 1410
1 1,7,9 229 99 Virtual Input 04 * * * * * * * Virtual Input 04 1411
1 1,7,9 229 100 Virtual Input 05 * * * * * * * Virtual Input 05 1412
1 1,7,9 229 101 Virtual Input 06 * * * * * * * Virtual Input 06 1413
1 1,7,9 229 102 Virtual Input 07 * * * * * * * Virtual Input 07 1414
1 1,7,9 229 103 Virtual Input 08 * * * * * * * Virtual Input 08 1415
1 1,7,9 229 104 Virtual Input 09 * * * * * * * Virtual Input 09 1416
1 1,7,9 229 105 Virtual Input 10 * * * * * * * Virtual Input 10 1417
1 1,7,9 229 106 Virtual Input 11 * * * * * * * Virtual Input 11 1418
1 1,7,9 229 107 Virtual Input 12 * * * * * * * Virtual Input 12 1419
1 1,7,9 229 108 Virtual Input 13 * * * * * * * Virtual Input 13 1420
1 1,7,9 229 109 Virtual Input 14 * * * * * * * Virtual Input 14 1421
1 1,7,9 229 110 Virtual Input 15 * * * * * * * Virtual Input 15 1422
1 1,7,9 229 111 Virtual Input 16 * * * * * * * Virtual Input 16 1423
1 1,7,9 229 112 Virtual Input 17 * * * * * * * Virtual Input 17 1424
1 1,7,9 229 113 Virtual Input 18 * * * * * * * Virtual Input 18 1425
1 1,7,9 229 114 Virtual Input 19 * * * * * * * Virtual Input 19 1426
1 1,7,9 229 115 Virtual Input 20 * * * * * * * Virtual Input 20 1427
1 1,7,9 229 116 Virtual Input 21 * * * * * * * Virtual Input 21 1428
1 1,7,9 229 117 Virtual Input 22 * * * * * * * Virtual Input 22 1429
1 1,7,9 229 118 Virtual Input 23 * * * * * * * Virtual Input 23 1430
1 1,7,9 229 119 Virtual Input 24 * * * * * * * Virtual Input 24 1431
1 1,7,9 229 120 Virtual Input 25 * * * * * * * Virtual Input 25 1432
1 1,7,9 229 121 Virtual Input 26 * * * * * * * Virtual Input 26 1433
1 1,7,9 229 122 Virtual Input 27 * * * * * * * Virtual Input 27 1434
1 1,7,9 229 123 Virtual Input 28 * * * * * * * Virtual Input 28 1435
1 1,7,9 229 124 Virtual Input 29 * * * * * * * Virtual Input 29 1436
1 1,7,9 229 125 Virtual Input 30 * * * * * * * Virtual Input 30 1437
1 1,7,9 229 126 Virtual Input 31 * * * * * * * Virtual Input 31 1438
1 1,7,9 229 127 Virtual Input 32 * * * * * * * Virtual Input 32 1439
1 1,7,9 233 18 Virtual Input 33 * * * * * * Virtual Input 33 1440
1 1,7,9 233 19 Virtual Input 34 * * * * * * Virtual Input 34 1441
1 1,7,9 233 20 Virtual Input 35 * * * * * * Virtual Input 35 1442
1 1,7,9 233 21 Virtual Input 36 * * * * * * Virtual Input 36 1443
1 1,7,9 233 22 Virtual Input 37 * * * * * * Virtual Input 37 1444
1 1,7,9 233 23 Virtual Input 38 * * * * * * Virtual Input 38 1445
1 1,7,9 233 24 Virtual Input 39 * * * * * * Virtual Input 39 1446
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 148 of 163

1 1,7,9 233 25 Virtual Input 40 * * * * * * Virtual Input 40 1447


1 1,7,9 233 26 Virtual Input 41 * * * * * * Virtual Input 41 1448
1 1,7,9 233 27 Virtual Input 42 * * * * * * Virtual Input 42 1449
1 1,7,9 233 28 Virtual Input 43 * * * * * * Virtual Input 43 1450
1 1,7,9 233 29 Virtual Input 44 * * * * * * Virtual Input 44 1451
1 1,7,9 233 30 Virtual Input 45 * * * * * * Virtual Input 45 1452
1 1,7,9 233 31 Virtual Input 46 * * * * * * Virtual Input 46 1453
1 1,7,9 233 32 Virtual Input 47 * * * * * * Virtual Input 47 1454
1 1,7,9 233 33 Virtual Input 48 * * * * * * Virtual Input 48 1455
1 1,7,9 233 34 Virtual Input 49 * * * * * * Virtual Input 49 1456
1 1,7,9 233 35 Virtual Input 50 * * * * * * Virtual Input 50 1457
1 1,7,9 233 36 Virtual Input 51 * * * * * * Virtual Input 51 1458
1 1,7,9 233 37 Virtual Input 52 * * * * * * Virtual Input 52 1459
1 1,7,9 233 38 Virtual Input 53 * * * * * * Virtual Input 53 1460
1 1,7,9 233 39 Virtual Input 54 * * * * * * Virtual Input 54 1461
1 1,7,9 233 40 Virtual Input 55 * * * * * * Virtual Input 55 1462
1 1,7,9 233 41 Virtual Input 56 * * * * * * Virtual Input 56 1463
1 1,7,9 233 42 Virtual Input 57 * * * * * * Virtual Input 57 1464
1 1,7,9 233 43 Virtual Input 58 * * * * * * Virtual Input 58 1465
1 1,7,9 233 44 Virtual Input 59 * * * * * * Virtual Input 59 1466
1 1,7,9 233 45 Virtual Input 60 * * * * * * Virtual Input 60 1467
1 1,7,9 233 46 Virtual Input 61 * * * * * * Virtual Input 61 1468
1 1,7,9 233 47 Virtual Input 62 * * * * * * Virtual Input 62 1469
1 1,7,9 233 48 Virtual Input 63 * * * * * * Virtual Input 63 1470
1 1,7,9 233 49 Virtual Input 64 * * * * * * Virtual Input 64 1471
234 1 1472
234 2 1473
234 3 1474
234 4 1475
234 5 1476
234 6 1477
234 7 1478
234 8 1479
234 9 1480
234 10 1481
234 11 1482
234 12 1483
234 13 1484
234 14 1485
234 15 1486
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 149 of 163

234 16 1487
234 17 1488
234 18 1489
234 19 1490
234 20 1491
234 21 1492
234 22 1493
234 23 1494
234 24 1495
234 25 1496
234 26 1497
234 27 1498
234 28 1499
234 29 1500
234 30 1501
234 31 1502
234 32 1503
234 33 Quality VIP 1 * * * * * * GOOSE Virtual input 1 Quality bit 1504
234 34 Quality VIP 2 * * * * * * GOOSE Virtual input 2 Quality bit 1505
234 35 Quality VIP 3 * * * * * * GOOSE Virtual input 3 Quality bit 1506
234 36 Quality VIP 4 * * * * * * GOOSE Virtual input 4 Quality bit 1507
234 37 Quality VIP 5 * * * * * * GOOSE Virtual input 5 Quality bit 1508
234 38 Quality VIP 6 * * * * * * GOOSE Virtual input 6 Quality bit 1509
234 39 Quality VIP 7 * * * * * * GOOSE Virtual input 7 Quality bit 1510
234 40 Quality VIP 8 * * * * * * GOOSE Virtual input 8 Quality bit 1511
234 41 Quality VIP 9 * * * * * * GOOSE Virtual input 9 Quality bit 1512
234 42 Quality VIP 10 * * * * * * GOOSE Virtual input 10 Quality bit 1513
234 43 Quality VIP 11 * * * * * * GOOSE Virtual input 11 Quality bit 1514
234 44 Quality VIP 12 * * * * * * GOOSE Virtual input 12 Quality bit 1515
234 45 Quality VIP 13 * * * * * * GOOSE Virtual input 13 Quality bit 1516
234 46 Quality VIP 14 * * * * * * GOOSE Virtual input 14 Quality bit 1517
234 47 Quality VIP 15 * * * * * * GOOSE Virtual input 15 Quality bit 1518
234 48 Quality VIP 16 * * * * * * GOOSE Virtual input 16 Quality bit 1519
234 49 Quality VIP 17 * * * * * * GOOSE Virtual input 17 Quality bit 1520
234 50 Quality VIP 18 * * * * * * GOOSE Virtual input 18 Quality bit 1521
234 51 Quality VIP 19 * * * * * * GOOSE Virtual input 19 Quality bit 1522
234 52 Quality VIP 20 * * * * * * GOOSE Virtual input 20 Quality bit 1523
234 53 Quality VIP 21 * * * * * * GOOSE Virtual input 21 Quality bit 1524
234 54 Quality VIP 22 * * * * * * GOOSE Virtual input 22 Quality bit 1525
234 55 Quality VIP 23 * * * * * * GOOSE Virtual input 23 Quality bit 1526
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 150 of 163

234 56 Quality VIP 24 * * * * * * GOOSE Virtual input 24 Quality bit 1527


234 57 Quality VIP 25 * * * * * * GOOSE Virtual input 25 Quality bit 1528
234 58 Quality VIP 26 * * * * * * GOOSE Virtual input 26 Quality bit 1529
234 59 Quality VIP 27 * * * * * * GOOSE Virtual input 27 Quality bit 1530
234 60 Quality VIP 28 * * * * * * GOOSE Virtual input 28 Quality bit 1531
234 61 Quality VIP 29 * * * * * * GOOSE Virtual input 29 Quality bit 1532
234 62 Quality VIP 30 * * * * * * GOOSE Virtual input 30 Quality bit 1533
234 63 Quality VIP 31 * * * * * * GOOSE Virtual input 31 Quality bit 1534
234 64 Quality VIP 32 * * * * * * GOOSE Virtual input 32 Quality bit 1535
234 65 Quality VIP 33 * * * * * * GOOSE Virtual input 33 Quality bit 1536
234 66 Quality VIP 34 * * * * * * GOOSE Virtual input 34 Quality bit 1537
234 67 Quality VIP 35 * * * * * * GOOSE Virtual input 35 Quality bit 1538
234 68 Quality VIP 36 * * * * * * GOOSE Virtual input 36 Quality bit 1539
234 69 Quality VIP 37 * * * * * * GOOSE Virtual input 37 Quality bit 1540
234 70 Quality VIP 38 * * * * * * GOOSE Virtual input 38 Quality bit 1541
234 71 Quality VIP 39 * * * * * * GOOSE Virtual input 39 Quality bit 1542
234 72 Quality VIP 40 * * * * * * GOOSE Virtual input 40 Quality bit 1543
234 73 Quality VIP 41 * * * * * * GOOSE Virtual input 41 Quality bit 1544
234 74 Quality VIP 42 * * * * * * GOOSE Virtual input 42 Quality bit 1545
234 75 Quality VIP 43 * * * * * * GOOSE Virtual input 43 Quality bit 1546
234 76 Quality VIP 44 * * * * * * GOOSE Virtual input 44 Quality bit 1547
234 77 Quality VIP 45 * * * * * * GOOSE Virtual input 45 Quality bit 1548
234 78 Quality VIP 46 * * * * * * GOOSE Virtual input 46 Quality bit 1549
234 79 Quality VIP 47 * * * * * * GOOSE Virtual input 47 Quality bit 1550
234 80 Quality VIP 48 * * * * * * GOOSE Virtual input 48 Quality bit 1551
234 81 Quality VIP 49 * * * * * * GOOSE Virtual input 49 Quality bit 1552
234 82 Quality VIP 50 * * * * * * GOOSE Virtual input 50 Quality bit 1553
234 83 Quality VIP 51 * * * * * * GOOSE Virtual input 51 Quality bit 1554
234 84 Quality VIP 52 * * * * * * GOOSE Virtual input 52 Quality bit 1555
234 85 Quality VIP 53 * * * * * * GOOSE Virtual input 53 Quality bit 1556
234 86 Quality VIP 54 * * * * * * GOOSE Virtual input 54 Quality bit 1557
234 87 Quality VIP 55 * * * * * * GOOSE Virtual input 55 Quality bit 1558
234 88 Quality VIP 56 * * * * * * GOOSE Virtual input 56 Quality bit 1559
234 89 Quality VIP 57 * * * * * * GOOSE Virtual input 57 Quality bit 1560
234 90 Quality VIP 58 * * * * * * GOOSE Virtual input 58 Quality bit 1561
234 91 Quality VIP 59 * * * * * * GOOSE Virtual input 59 Quality bit 1562
234 92 Quality VIP 60 * * * * * * GOOSE Virtual input 60 Quality bit 1563
234 93 Quality VIP 61 * * * * * * GOOSE Virtual input 61 Quality bit 1564
234 94 Quality VIP 62 * * * * * * GOOSE Virtual input 62 Quality bit 1565
234 95 Quality VIP 63 * * * * * * GOOSE Virtual input 63 Quality bit 1566
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 151 of 163

234 96 Quality VIP 64 * * * * * * GOOSE Virtual input 64 Quality bit 1567


234 97 1568
234 98 1569
234 99 1570
234 100 1571
234 101 1572
234 102 1573
234 103 1574
234 104 1575
234 105 1576
234 106 1577
234 107 1578
234 108 1579
234 109 1580
234 110 1581
234 111 1582
234 112 1583
234 113 1584
234 114 1585
234 115 1586
234 116 1587
234 117 1588
234 118 1589
234 119 1590
234 120 1591
234 121 1592
234 122 1593
234 123 1594
234 124 1595
234 125 1596
234 126 1597
234 127 1598
234 128 1599
234 129 PubPres VIP 1 * * * * * * GOOSE Virtual input 1 publisher bit 1600
234 130 PubPres VIP 2 * * * * * * GOOSE Virtual input 2 publisher bit 1601
234 131 PubPres VIP 3 * * * * * * GOOSE Virtual input 3 publisher bit 1602
234 132 PubPres VIP 4 * * * * * * GOOSE Virtual input 4 publisher bit 1603
234 133 PubPres VIP 5 * * * * * * GOOSE Virtual input 5 publisher bit 1604
234 134 PubPres VIP 6 * * * * * * GOOSE Virtual input 6 publisher bit 1605
234 135 PubPres VIP 7 * * * * * * GOOSE Virtual input 7 publisher bit 1606
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 152 of 163

234 136 PubPres VIP 8 * * * * * * GOOSE Virtual input 8 publisher bit 1607
234 137 PubPres VIP 9 * * * * * * GOOSE Virtual input 9 publisher bit 1608
234 138 PubPres VIP 10 * * * * * * GOOSE Virtual input 10 publisher bit 1609
234 139 PubPres VIP 11 * * * * * * GOOSE Virtual input 11 publisher bit 1610
234 140 PubPres VIP 12 * * * * * * GOOSE Virtual input 12 publisher bit 1611
234 141 PubPres VIP 13 * * * * * * GOOSE Virtual input 13 publisher bit 1612
234 142 PubPres VIP 14 * * * * * * GOOSE Virtual input 14 publisher bit 1613
234 143 PubPres VIP 15 * * * * * * GOOSE Virtual input 15 publisher bit 1614
234 144 PubPres VIP 16 * * * * * * GOOSE Virtual input 16 publisher bit 1615
234 145 PubPres VIP 17 * * * * * * GOOSE Virtual input 17 publisher bit 1616
234 146 PubPres VIP 18 * * * * * * GOOSE Virtual input 18 publisher bit 1617
234 147 PubPres VIP 19 * * * * * * GOOSE Virtual input 19 publisher bit 1618
234 148 PubPres VIP 20 * * * * * * GOOSE Virtual input 20 publisher bit 1619
234 149 PubPres VIP 21 * * * * * * GOOSE Virtual input 21 publisher bit 1620
234 150 PubPres VIP 22 * * * * * * GOOSE Virtual input 22 publisher bit 1621
234 151 PubPres VIP 23 * * * * * * GOOSE Virtual input 23 publisher bit 1622
234 152 PubPres VIP 24 * * * * * * GOOSE Virtual input 24 publisher bit 1623
234 153 PubPres VIP 25 * * * * * * GOOSE Virtual input 25 publisher bit 1624
234 154 PubPres VIP 26 * * * * * * GOOSE Virtual input 26 publisher bit 1625
234 155 PubPres VIP 27 * * * * * * GOOSE Virtual input 27 publisher bit 1626
234 156 PubPres VIP 28 * * * * * * GOOSE Virtual input 28 publisher bit 1627
234 157 PubPres VIP 29 * * * * * * GOOSE Virtual input 29 publisher bit 1628
234 158 PubPres VIP 30 * * * * * * GOOSE Virtual input 30 publisher bit 1629
234 159 PubPres VIP 31 * * * * * * GOOSE Virtual input 31 publisher bit 1630
234 160 PubPres VIP 32 * * * * * * GOOSE Virtual input 32 publisher bit 1631
234 161 PubPres VIP 33 * * * * * * GOOSE Virtual input 33 publisher bit 1632
234 162 PubPres VIP 34 * * * * * * GOOSE Virtual input 34 publisher bit 1633
234 163 PubPres VIP 35 * * * * * * GOOSE Virtual input 35 publisher bit 1634
234 164 PubPres VIP 36 * * * * * * GOOSE Virtual input 36 publisher bit 1635
234 165 PubPres VIP 37 * * * * * * GOOSE Virtual input 37 publisher bit 1636
234 166 PubPres VIP 38 * * * * * * GOOSE Virtual input 38 publisher bit 1637
234 167 PubPres VIP 39 * * * * * * GOOSE Virtual input 39 publisher bit 1638
234 168 PubPres VIP 40 * * * * * * GOOSE Virtual input 40 publisher bit 1639
234 169 PubPres VIP 41 * * * * * * GOOSE Virtual input 41 publisher bit 1640
234 170 PubPres VIP 42 * * * * * * GOOSE Virtual input 42 publisher bit 1641
234 171 PubPres VIP 43 * * * * * * GOOSE Virtual input 43 publisher bit 1642
234 172 PubPres VIP 44 * * * * * * GOOSE Virtual input 44 publisher bit 1643
234 173 PubPres VIP 45 * * * * * * GOOSE Virtual input 45 publisher bit 1644
234 174 PubPres VIP 46 * * * * * * GOOSE Virtual input 46 publisher bit 1645
234 175 PubPres VIP 47 * * * * * * GOOSE Virtual input 47 publisher bit 1646
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 153 of 163

234 176 PubPres VIP 48 * * * * * * GOOSE Virtual input 48 publisher bit 1647
234 177 PubPres VIP 49 * * * * * * GOOSE Virtual input 49 publisher bit 1648
234 178 PubPres VIP 50 * * * * * * GOOSE Virtual input 50 publisher bit 1649
234 179 PubPres VIP 51 * * * * * * GOOSE Virtual input 51 publisher bit 1650
234 180 PubPres VIP 52 * * * * * * GOOSE Virtual input 52 publisher bit 1651
234 181 PubPres VIP 53 * * * * * * GOOSE Virtual input 53 publisher bit 1652
234 182 PubPres VIP 54 * * * * * * GOOSE Virtual input 54 publisher bit 1653
234 183 PubPres VIP 55 * * * * * * GOOSE Virtual input 55 publisher bit 1654
234 184 PubPres VIP 56 * * * * * * GOOSE Virtual input 56 publisher bit 1655
234 185 PubPres VIP 57 * * * * * * GOOSE Virtual input 57 publisher bit 1656
234 186 PubPres VIP 58 * * * * * * GOOSE Virtual input 58 publisher bit 1657
234 187 PubPres VIP 59 * * * * * * GOOSE Virtual input 59 publisher bit 1658
234 188 PubPres VIP 60 * * * * * * GOOSE Virtual input 60 publisher bit 1659
234 189 PubPres VIP 61 * * * * * * GOOSE Virtual input 61 publisher bit 1660
234 190 PubPres VIP 62 * * * * * * GOOSE Virtual input 62 publisher bit 1661
234 191 PubPres VIP 63 * * * * * * GOOSE Virtual input 63 publisher bit 1662
234 192 PubPres VIP 64 * * * * * * GOOSE Virtual input 64 publisher bit 1663
234 193 1664
234 194 1665
234 195 1666
234 196 1667
234 197 1668
234 198 1669
234 199 1670
234 200 1671
234 201 1672
234 202 1673
234 203 1674
234 204 1675
234 205 1676
234 206 1677
234 207 1678
234 208 1679
234 209 1680
234 210 1681
234 211 1682
234 212 1683
234 213 1684
234 214 1685
234 215 1686
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 154 of 163

234 216 1687


234 217 1688
234 218 1689
234 219 1690
234 220 1691
234 221 1692
234 222 1693
234 223 1694
234 224 1695
1 1,7,9 229 128 Virtual Output01 * * * * * * * Virtual Output 01 1696
1 1,7,9 229 129 Virtual Output02 * * * * * * * Virtual Output 02 1697
1 1,7,9 229 130 Virtual Output03 * * * * * * * Virtual Output 03 1698
1 1,7,9 229 131 Virtual Output04 * * * * * * * Virtual Output 04 1699
1 1,7,9 229 132 Virtual Output05 * * * * * * * Virtual Output 05 1700
1 1,7,9 229 133 Virtual Output06 * * * * * * * Virtual Output 06 1701
1 1,7,9 229 134 Virtual Output07 * * * * * * * Virtual Output 07 1702
1 1,7,9 229 135 Virtual Output08 * * * * * * * Virtual Output 08 1703
1 1,7,9 229 136 Virtual Output09 * * * * * * * Virtual Output 09 1704
1 1,7,9 229 137 Virtual Output10 * * * * * * * Virtual Output 10 1705
1 1,7,9 229 138 Virtual Output11 * * * * * * * Virtual Output 11 1706
1 1,7,9 229 139 Virtual Output12 * * * * * * * Virtual Output 12 1707
1 1,7,9 229 140 Virtual Output13 * * * * * * * Virtual Output 13 1708
1 1,7,9 229 141 Virtual Output14 * * * * * * * Virtual Output 14 1709
1 1,7,9 229 142 Virtual Output15 * * * * * * * Virtual Output 15 1710
1 1,7,9 229 143 Virtual Output16 * * * * * * * Virtual Output 16 1711
1 1,7,9 229 144 Virtual Output17 * * * * * * * Virtual Output 17 1712
1 1,7,9 229 145 Virtual Output18 * * * * * * * Virtual Output 18 1713
1 1,7,9 229 146 Virtual Output19 * * * * * * * Virtual Output 19 1714
1 1,7,9 229 147 Virtual Output20 * * * * * * * Virtual Output 20 1715
1 1,7,9 229 148 Virtual Output21 * * * * * * * Virtual Output 21 1716
1 1,7,9 229 149 Virtual Output22 * * * * * * * Virtual Output 22 1717
1 1,7,9 229 150 Virtual Output23 * * * * * * * Virtual Output 23 1718
1 1,7,9 229 151 Virtual Output24 * * * * * * * Virtual Output 24 1719
1 1,7,9 229 152 Virtual Output25 * * * * * * * Virtual Output 25 1720
1 1,7,9 229 153 Virtual Output26 * * * * * * * Virtual Output 26 1721
1 1,7,9 229 154 Virtual Output27 * * * * * * * Virtual Output 27 1722
1 1,7,9 229 155 Virtual Output28 * * * * * * * Virtual Output 28 1723
1 1,7,9 229 156 Virtual Output29 * * * * * * * Virtual Output 29 1724
1 1,7,9 229 157 Virtual Output30 * * * * * * * Virtual Output 30 1725
1 1,7,9 229 158 Virtual Output31 * * * * * * * Virtual Output 31 1726
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 155 of 163

1 1,7,9 229 159 Virtual Output32 * * * * * * * Virtual Output 32 1727


1 1,7,9 233 50 Virtual Output33 * * * * * * Virtual Output 33 1728
1 1,7,9 233 51 Virtual Output34 * * * * * * Virtual Output 34 1729
1 1,7,9 233 52 Virtual Output35 * * * * * * Virtual Output 35 1730
1 1,7,9 233 53 Virtual Output36 * * * * * * Virtual Output 36 1731
1 1,7,9 233 54 Virtual Output37 * * * * * * Virtual Output 37 1732
1 1,7,9 233 55 Virtual Output38 * * * * * * Virtual Output 38 1733
1 1,7,9 233 56 Virtual Output39 * * * * * * Virtual Output 39 1734
1 1,7,9 233 57 Virtual Output40 * * * * * * Virtual Output 40 1735
1 1,7,9 233 58 Virtual Output41 * * * * * * Virtual Output 41 1736
1 1,7,9 233 59 Virtual Output42 * * * * * * Virtual Output 42 1737
1 1,7,9 233 60 Virtual Output43 * * * * * * Virtual Output 43 1738
1 1,7,9 233 61 Virtual Output44 * * * * * * Virtual Output 44 1739
1 1,7,9 233 62 Virtual Output45 * * * * * * Virtual Output 45 1740
1 1,7,9 233 63 Virtual Output46 * * * * * * Virtual Output 46 1741
1 1,7,9 233 64 Virtual Output47 * * * * * * Virtual Output 47 1742
1 1,7,9 233 65 Virtual Output48 * * * * * * Virtual Output 48 1743
1 1,7,9 233 66 Virtual Output49 * * * * * * Virtual Output 49 1744
1 1,7,9 233 67 Virtual Output50 * * * * * * Virtual Output 50 1745
1 1,7,9 233 68 Virtual Output51 * * * * * * Virtual Output 51 1746
1 1,7,9 233 69 Virtual Output52 * * * * * * Virtual Output 52 1747
1 1,7,9 233 70 Virtual Output53 * * * * * * Virtual Output 53 1748
1 1,7,9 233 71 Virtual Output54 * * * * * * Virtual Output 54 1749
1 1,7,9 233 72 Virtual Output55 * * * * * * Virtual Output 55 1750
1 1,7,9 233 73 Virtual Output56 * * * * * * Virtual Output 56 1751
1 1,7,9 233 74 Virtual Output57 * * * * * * Virtual Output 57 1752
1 1,7,9 233 75 Virtual Output58 * * * * * * Virtual Output 58 1753
1 1,7,9 233 76 Virtual Output59 * * * * * * Virtual Output 59 1754
1 1,7,9 233 77 Virtual Output60 * * * * * * Virtual Output 60 1755
1 1,7,9 233 78 Virtual Output61 * * * * * * Virtual Output 61 1756
1 1,7,9 233 79 Virtual Output62 * * * * * * Virtual Output 62 1757
1 1,7,9 233 80 Virtual Output63 * * * * * * Virtual Output 63 1758
1 1,7,9 233 81 Virtual Output64 * * * * * * Virtual Output 64 1759
234 225 1760
234 226 1761
234 227 1762
234 228 1763
234 229 1764
234 230 1765
234 231 1766
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 156 of 163

234 232 1767


234 233 1768
234 234 1769
234 235 1770
234 236 1771
234 237 1772
234 238 1773
234 239 1774
234 240 1775
234 241 1776
234 242 1777
234 243 1778
234 244 1779
234 245 1780
234 246 1781
234 247 1782
234 248 1783
234 249 1784
234 250 1785
234 251 1786
234 252 1787
234 253 1788
234 254 1789
234 255 1790
231 237 1791
229 160 PSL Int. 1 * * * * * * PSL Internal connection 1792
229 161 PSL Int. 2 * * * * * * PSL Internal connection 1793
229 162 PSL Int. 3 * * * * * * PSL Internal connection 1794
229 163 PSL Int. 4 * * * * * * PSL Internal connection 1795
229 164 PSL Int. 5 * * * * * * PSL Internal connection 1796
229 165 PSL Int. 6 * * * * * * PSL Internal connection 1797
229 166 PSL Int. 7 * * * * * * PSL Internal connection 1798
229 167 PSL Int. 8 * * * * * * PSL Internal connection 1799
229 168 PSL Int. 9 * * * * * * PSL Internal connection 1800
229 169 PSL Int. 10 * * * * * * PSL Internal connection 1801
229 170 PSL Int. 11 * * * * * * PSL Internal connection 1802
229 171 PSL Int. 12 * * * * * * PSL Internal connection 1803
229 172 PSL Int. 13 * * * * * * PSL Internal connection 1804
229 173 PSL Int. 14 * * * * * * PSL Internal connection 1805
229 174 PSL Int. 15 * * * * * * PSL Internal connection 1806
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 157 of 163

229 175 PSL Int. 16 * * * * * * PSL Internal connection 1807


229 176 PSL Int. 17 * * * * * * PSL Internal connection 1808
229 177 PSL Int. 18 * * * * * * PSL Internal connection 1809
229 178 PSL Int. 19 * * * * * * PSL Internal connection 1810
229 179 PSL Int. 20 * * * * * * PSL Internal connection 1811
229 180 PSL Int. 21 * * * * * * PSL Internal connection 1812
229 181 PSL Int. 22 * * * * * * PSL Internal connection 1813
229 182 PSL Int. 23 * * * * * * PSL Internal connection 1814
229 183 PSL Int. 24 * * * * * * PSL Internal connection 1815
229 184 PSL Int. 25 * * * * * * PSL Internal connection 1816
229 185 PSL Int. 26 * * * * * * PSL Internal connection 1817
229 186 PSL Int. 27 * * * * * * PSL Internal connection 1818
229 187 PSL Int. 28 * * * * * * PSL Internal connection 1819
229 188 PSL Int. 29 * * * * * * PSL Internal connection 1820
229 189 PSL Int. 30 * * * * * * PSL Internal connection 1821
229 190 PSL Int. 31 * * * * * * PSL Internal connection 1822
229 191 PSL Int. 32 * * * * * * PSL Internal connection 1823
229 192 PSL Int. 33 * * * * * * PSL Internal connection 1824
229 193 PSL Int. 34 * * * * * * PSL Internal connection 1825
229 194 PSL Int. 35 * * * * * * PSL Internal connection 1826
229 195 PSL Int. 36 * * * * * * PSL Internal connection 1827
229 196 PSL Int. 37 * * * * * * PSL Internal connection 1828
229 197 PSL Int. 38 * * * * * * PSL Internal connection 1829
229 198 PSL Int. 39 * * * * * * PSL Internal connection 1830
229 199 PSL Int. 40 * * * * * * PSL Internal connection 1831
229 200 PSL Int. 41 * * * * * * PSL Internal connection 1832
229 201 PSL Int. 42 * * * * * * PSL Internal connection 1833
229 202 PSL Int. 43 * * * * * * PSL Internal connection 1834
229 203 PSL Int. 44 * * * * * * PSL Internal connection 1835
229 204 PSL Int. 45 * * * * * * PSL Internal connection 1836
229 205 PSL Int. 46 * * * * * * PSL Internal connection 1837
229 206 PSL Int. 47 * * * * * * PSL Internal connection 1838
229 207 PSL Int. 48 * * * * * * PSL Internal connection 1839
229 208 PSL Int. 49 * * * * * * PSL Internal connection 1840
229 209 PSL Int. 50 * * * * * * PSL Internal connection 1841
229 210 PSL Int. 51 * * * * * * PSL Internal connection 1842
229 211 PSL Int. 52 * * * * * * PSL Internal connection 1843
229 212 PSL Int. 53 * * * * * * PSL Internal connection 1844
229 213 PSL Int. 54 * * * * * * PSL Internal connection 1845
229 214 PSL Int. 55 * * * * * * PSL Internal connection 1846
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 158 of 163

229 215 PSL Int. 56 * * * * * * PSL Internal connection 1847


229 216 PSL Int. 57 * * * * * * PSL Internal connection 1848
229 217 PSL Int. 58 * * * * * * PSL Internal connection 1849
229 218 PSL Int. 59 * * * * * * PSL Internal connection 1850
229 219 PSL Int. 60 * * * * * * PSL Internal connection 1851
229 220 PSL Int. 61 * * * * * * PSL Internal connection 1852
229 221 PSL Int. 62 * * * * * * PSL Internal connection 1853
229 222 PSL Int. 63 * * * * * * PSL Internal connection 1854
229 223 PSL Int. 64 * * * * * * PSL Internal connection 1855
229 224 PSL Int. 65 * * * * * * PSL Internal connection 1856
229 225 PSL Int. 66 * * * * * * PSL Internal connection 1857
229 226 PSL Int. 67 * * * * * * PSL Internal connection 1858
229 227 PSL Int. 68 * * * * * * PSL Internal connection 1859
229 228 PSL Int. 69 * * * * * * PSL Internal connection 1860
229 229 PSL Int. 70 * * * * * * PSL Internal connection 1861
229 230 PSL Int. 71 * * * * * * PSL Internal connection 1862
229 231 PSL Int. 72 * * * * * * PSL Internal connection 1863
229 232 PSL Int. 73 * * * * * * PSL Internal connection 1864
229 233 PSL Int. 74 * * * * * * PSL Internal connection 1865
229 234 PSL Int. 75 * * * * * * PSL Internal connection 1866
229 235 PSL Int. 76 * * * * * * PSL Internal connection 1867
229 236 PSL Int. 77 * * * * * * PSL Internal connection 1868
229 237 PSL Int. 78 * * * * * * PSL Internal connection 1869
229 238 PSL Int. 79 * * * * * * PSL Internal connection 1870
229 239 PSL Int. 80 * * * * * * PSL Internal connection 1871
229 240 PSL Int. 81 * * * * * * PSL Internal connection 1872
229 241 PSL Int. 82 * * * * * * PSL Internal connection 1873
229 242 PSL Int. 83 * * * * * * PSL Internal connection 1874
229 243 PSL Int. 84 * * * * * * PSL Internal connection 1875
229 244 PSL Int. 85 * * * * * * PSL Internal connection 1876
229 245 PSL Int. 86 * * * * * * PSL Internal connection 1877
229 246 PSL Int. 87 * * * * * * PSL Internal connection 1878
229 247 PSL Int. 88 * * * * * * PSL Internal connection 1879
229 248 PSL Int. 89 * * * * * * PSL Internal connection 1880
229 249 PSL Int. 90 * * * * * * PSL Internal connection 1881
229 250 PSL Int. 91 * * * * * * PSL Internal connection 1882
229 251 PSL Int. 92 * * * * * * PSL Internal connection 1883
229 252 PSL Int. 93 * * * * * * PSL Internal connection 1884
229 253 PSL Int. 94 * * * * * * PSL Internal connection 1885
229 254 PSL Int. 95 * * * * * * PSL Internal connection 1886
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 159 of 163

231 48 PSL Int. 96 * * * * * * PSL Internal connection 1887


231 49 PSL Int. 97 * * * * * * PSL Internal connection 1888
231 50 PSL Int. 98 * * * * * * PSL Internal connection 1889
231 51 PSL Int. 99 * * * * * * PSL Internal connection 1890
231 52 PSL Int. 100 * * * * * * PSL Internal connection 1891
231 53 PSL Int. 101 * * * * * * PSL Internal connection 1892
231 54 PSL Int. 102 * * * * * * PSL Internal connection 1893
231 55 PSL Int. 103 * * * * * * PSL Internal connection 1894
231 56 PSL Int. 104 * * * * * * PSL Internal connection 1895
231 57 PSL Int. 105 * * * * * * PSL Internal connection 1896
231 58 PSL Int. 106 * * * * * * PSL Internal connection 1897
231 59 PSL Int. 107 * * * * * * PSL Internal connection 1898
231 60 PSL Int. 108 * * * * * * PSL Internal connection 1899
231 61 PSL Int. 109 * * * * * * PSL Internal connection 1900
231 62 PSL Int. 110 * * * * * * PSL Internal connection 1901
231 63 PSL Int. 111 * * * * * * PSL Internal connection 1902
231 64 PSL Int. 112 * * * * * * PSL Internal connection 1903
231 65 PSL Int. 113 * * * * * * PSL Internal connection 1904
231 66 PSL Int. 114 * * * * * * PSL Internal connection 1905
231 67 PSL Int. 115 * * * * * * PSL Internal connection 1906
231 68 PSL Int. 116 * * * * * * PSL Internal connection 1907
231 69 PSL Int. 117 * * * * * * PSL Internal connection 1908
231 70 PSL Int. 118 * * * * * * PSL Internal connection 1909
231 71 PSL Int. 119 * * * * * * PSL Internal connection 1910
231 72 PSL Int. 120 * * * * * * PSL Internal connection 1911
231 73 PSL Int. 121 * * * * * * PSL Internal connection 1912
231 74 PSL Int. 122 * * * * * * PSL Internal connection 1913
231 75 PSL Int. 123 * * * * * * PSL Internal connection 1914
231 76 PSL Int. 124 * * * * * * PSL Internal connection 1915
231 77 PSL Int. 125 * * * * * * PSL Internal connection 1916
231 78 PSL Int. 126 * * * * * * PSL Internal connection 1917
231 79 PSL Int. 127 * * * * * * PSL Internal connection 1918
231 80 PSL Int. 128 * * * * * * PSL Internal connection 1919
231 81 PSL Int. 129 * * * * * * PSL Internal connection 1920
231 82 PSL Int. 130 * * * * * * PSL Internal connection 1921
231 83 PSL Int. 131 * * * * * * PSL Internal connection 1922
231 84 PSL Int. 132 * * * * * * PSL Internal connection 1923
231 85 PSL Int. 133 * * * * * * PSL Internal connection 1924
231 86 PSL Int. 134 * * * * * * PSL Internal connection 1925
231 87 PSL Int. 135 * * * * * * PSL Internal connection 1926
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 160 of 163

231 88 PSL Int. 136 * * * * * * PSL Internal connection 1927


231 89 PSL Int. 137 * * * * * * PSL Internal connection 1928
231 90 PSL Int. 138 * * * * * * PSL Internal connection 1929
231 91 PSL Int. 139 * * * * * * PSL Internal connection 1930
231 92 PSL Int. 140 * * * * * * PSL Internal connection 1931
231 93 PSL Int. 141 * * * * * * PSL Internal connection 1932
231 94 PSL Int. 142 * * * * * * PSL Internal connection 1933
231 95 PSL Int. 143 * * * * * * PSL Internal connection 1934
231 96 PSL Int. 144 * * * * * * PSL Internal connection 1935
231 97 PSL Int. 145 * * * * * * PSL Internal connection 1936
231 98 PSL Int. 146 * * * * * * PSL Internal connection 1937
231 99 PSL Int. 147 * * * * * * PSL Internal connection 1938
231 100 PSL Int. 148 * * * * * * PSL Internal connection 1939
231 101 PSL Int. 149 * * * * * * PSL Internal connection 1940
231 102 PSL Int. 150 * * * * * * PSL Internal connection 1941
231 103 PSL Int. 151 * * * * * * PSL Internal connection 1942
231 104 PSL Int. 152 * * * * * * PSL Internal connection 1943
231 105 PSL Int. 153 * * * * * * PSL Internal connection 1944
231 106 PSL Int. 154 * * * * * * PSL Internal connection 1945
231 107 PSL Int. 155 * * * * * * PSL Internal connection 1946
231 108 PSL Int. 156 * * * * * * PSL Internal connection 1947
231 109 PSL Int. 157 * * * * * * PSL Internal connection 1948
231 110 PSL Int. 158 * * * * * * PSL Internal connection 1949
231 111 PSL Int. 159 * * * * * * PSL Internal connection 1950
231 112 PSL Int. 160 * * * * * * PSL Internal connection 1951
233 82 PSL Int. 161 * * * * * * PSL Internal connection 1952
233 83 PSL Int. 162 * * * * * * PSL Internal connection 1953
233 84 PSL Int. 163 * * * * * * PSL Internal connection 1954
233 85 PSL Int. 164 * * * * * * PSL Internal connection 1955
233 86 PSL Int. 165 * * * * * * PSL Internal connection 1956
233 87 PSL Int. 166 * * * * * * PSL Internal connection 1957
233 88 PSL Int. 167 * * * * * * PSL Internal connection 1958
233 89 PSL Int. 168 * * * * * * PSL Internal connection 1959
233 90 PSL Int. 169 * * * * * * PSL Internal connection 1960
233 91 PSL Int. 170 * * * * * * PSL Internal connection 1961
233 92 PSL Int. 171 * * * * * * PSL Internal connection 1962
233 93 PSL Int. 172 * * * * * * PSL Internal connection 1963
233 94 PSL Int. 173 * * * * * * PSL Internal connection 1964
233 95 PSL Int. 174 * * * * * * PSL Internal connection 1965
233 96 PSL Int. 175 * * * * * * PSL Internal connection 1966
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 161 of 163

233 97 PSL Int. 176 * * * * * * PSL Internal connection 1967


233 98 PSL Int. 177 * * * * * * PSL Internal connection 1968
233 99 PSL Int. 178 * * * * * * PSL Internal connection 1969
233 100 PSL Int. 179 * * * * * * PSL Internal connection 1970
233 101 PSL Int. 180 * * * * * * PSL Internal connection 1971
233 102 PSL Int. 181 * * * * * * PSL Internal connection 1972
233 103 PSL Int. 182 * * * * * * PSL Internal connection 1973
233 104 PSL Int. 183 * * * * * * PSL Internal connection 1974
233 105 PSL Int. 184 * * * * * * PSL Internal connection 1975
233 106 PSL Int. 185 * * * * * * PSL Internal connection 1976
233 107 PSL Int. 186 * * * * * * PSL Internal connection 1977
233 108 PSL Int. 187 * * * * * * PSL Internal connection 1978
233 109 PSL Int. 188 * * * * * * PSL Internal connection 1979
233 110 PSL Int. 189 * * * * * * PSL Internal connection 1980
233 111 PSL Int. 190 * * * * * * PSL Internal connection 1981
233 112 PSL Int. 191 * * * * * * PSL Internal connection 1982
233 113 PSL Int. 192 * * * * * * PSL Internal connection 1983
233 114 PSL Int. 193 * * * * * * PSL Internal connection 1984
233 115 PSL Int. 194 * * * * * * PSL Internal connection 1985
233 116 PSL Int. 195 * * * * * * PSL Internal connection 1986
233 117 PSL Int. 196 * * * * * * PSL Internal connection 1987
233 118 PSL Int. 197 * * * * * * PSL Internal connection 1988
233 119 PSL Int. 198 * * * * * * PSL Internal connection 1989
233 120 PSL Int. 199 * * * * * * PSL Internal connection 1990
233 121 PSL Int. 200 * * * * * * PSL Internal connection 1991
233 122 PSL Int. 201 * * * * * * PSL Internal connection 1992
233 123 PSL Int. 202 * * * * * * PSL Internal connection 1993
233 124 PSL Int. 203 * * * * * * PSL Internal connection 1994
233 125 PSL Int. 204 * * * * * * PSL Internal connection 1995
233 126 PSL Int. 205 * * * * * * PSL Internal connection 1996
233 127 PSL Int. 206 * * * * * * PSL Internal connection 1997
233 128 PSL Int. 207 * * * * * * PSL Internal connection 1998
233 129 PSL Int. 208 * * * * * * PSL Internal connection 1999
233 130 PSL Int. 209 * * * * * * PSL Internal connection 2000
233 131 PSL Int. 210 * * * * * * PSL Internal connection 2001
233 132 PSL Int. 211 * * * * * * PSL Internal connection 2002
233 133 PSL Int. 212 * * * * * * PSL Internal connection 2003
233 134 PSL Int. 213 * * * * * * PSL Internal connection 2004
233 135 PSL Int. 214 * * * * * * PSL Internal connection 2005
233 136 PSL Int. 215 * * * * * * PSL Internal connection 2006
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 162 of 163

233 137 PSL Int. 216 * * * * * * PSL Internal connection 2007


233 138 PSL Int. 217 * * * * * * PSL Internal connection 2008
233 139 PSL Int. 218 * * * * * * PSL Internal connection 2009
233 140 PSL Int. 219 * * * * * * PSL Internal connection 2010
233 141 PSL Int. 220 * * * * * * PSL Internal connection 2011
233 142 PSL Int. 221 * * * * * * PSL Internal connection 2012
233 143 PSL Int. 222 * * * * * * PSL Internal connection 2013
233 144 PSL Int. 223 * * * * * * PSL Internal connection 2014
233 145 PSL Int. 224 * * * * * * PSL Internal connection 2015
233 146 PSL Int. 225 * * * * * * PSL Internal connection 2016
233 147 PSL Int. 226 * * * * * * PSL Internal connection 2017
233 148 PSL Int. 227 * * * * * * PSL Internal connection 2018
233 149 PSL Int. 228 * * * * * * PSL Internal connection 2019
233 150 PSL Int. 229 * * * * * * PSL Internal connection 2020
233 151 PSL Int. 230 * * * * * * PSL Internal connection 2021
233 152 PSL Int. 231 * * * * * * PSL Internal connection 2022
233 153 PSL Int. 232 * * * * * * PSL Internal connection 2023
233 154 PSL Int. 233 * * * * * * PSL Internal connection 2024
233 155 PSL Int. 234 * * * * * * PSL Internal connection 2025
233 156 PSL Int. 235 * * * * * * PSL Internal connection 2026
233 157 PSL Int. 236 * * * * * * PSL Internal connection 2027
233 158 PSL Int. 237 * * * * * * PSL Internal connection 2028
233 159 PSL Int. 238 * * * * * * PSL Internal connection 2029
233 160 PSL Int. 239 * * * * * * PSL Internal connection 2030
233 161 PSL Int. 240 * * * * * * PSL Internal connection 2031
233 162 PSL Int. 241 * * * * * * PSL Internal connection 2032
233 163 PSL Int. 242 * * * * * * PSL Internal connection 2033
233 164 PSL Int. 243 * * * * * * PSL Internal connection 2034
233 165 PSL Int. 244 * * * * * * PSL Internal connection 2035
233 166 PSL Int. 245 * * * * * * PSL Internal connection 2036
233 167 PSL Int. 246 * * * * * * PSL Internal connection 2037
233 168 PSL Int. 247 * * * * * * PSL Internal connection 2038
233 169 PSL Int. 248 * * * * * * PSL Internal connection 2039
233 170 PSL Int. 249 * * * * * * PSL Internal connection 2040
233 171 PSL Int. 250 * * * * * * PSL Internal connection 2041
233 172 PSL Int. 251 * * * * * * PSL Internal connection 2042
233 173 PSL Int. 252 * * * * * * PSL Internal connection 2043
233 174 PSL Int. 253 * * * * * * PSL Internal connection 2044
233 175 PSL Int. 254 * * * * * * PSL Internal connection 2045
233 176 PSL Int. 255 * * * * * * PSL Internal connection 2046
470234511.xls
Relay Menu Database IEC 60870-5-103
Page 163 of 163

233 177 PSL Int. 256 * * * * * * PSL Internal connection 2047

You might also like