Communication Terminal Board Installation Manual

Installation tool

1. . A Phillips screwdriver (diameter 6.0 mm).


2. . A small screwdriver (diameter 2. 5mm).

Installation method

Modbus PCB installation


1. In Figure 1: block 1 is the position of the fixed power terminal, and block 2 is the position of the fixed
plastic box.
2. Fix the power terminal with four screws as shown in Figure 2, and fix the plastic box with two screws;
Block 3 is the location of the fixed switching power supply board, and block 4 is the location of the fixed
Modbus communication board.
3. For the good hole position, fix the switching power supply board and the Modbus communication board
with screws as shown in Figure 3.
4. Wiring according to the wiring diagram of Figure 4: Connect the Modbus communication board and the
switching power supply board with a two-core shielded twisted pair cable at both ends of the board,
connect the switching power supply board to the power terminal with a power cable with one end of the
VH-3 A socket and the other end of the U-shaped terminal. Figure 5 is a physical wiring diagram.
5. The blue block in Figure 6 is grounded and copper screws are screwed; the red block is mounted on the
crimping cable and is fixed as shown.
6. The screws (4) in the red block of Figure 7 are fixed lids, and the holes (4) in the blue block are used to
secure the entire sheet metal box that needs to be installed upright.
Note:
1. The Modbus component requires a two-core shielded twisted pair cable, which is more than 0.75
mm2;
2. Modbus component needs to be installed in an indoor environment, using ambient temperature -20~
60°C;
3. The power supply voltage of the Modbus component power board is AC 220V/50Hz, the power
consumption is 1-2W;
4. Since the cover plate is a sheet metal piece, it cannot be installed horizontally to prevent the
condensation from dripping on the PBA board, and it needs to be installed upright;
5. The connection between the Modbus board and CMV-Mini main board is up to 800m;
6. The dimension of the components W*H*D: 280*60*121(mm).

Figure.1 Figure.2

Figure.3
T o o u td o o r
m a i n b o a rd

Outdoor

X Y E

SW2
SW11 ON
CN 30 ' J3 J2 J2 CN28 CN1 CN13
CN 13 CN 13

0
1 2 POWER

L N A B E K 1K2E O A E X Y E P Q E H 1H2E
CN1

ModBUS
communication

Figure.4 Figure.5

Figure.6 Figure.7

Error details

Note: The red light is the power light.

Error Error display Error description

1. Outdoor main board problem;


Slowly flashing yellow and green lights 2. Poor contact or missing connection of PQE
Cannot find indoor unit
(flashing once in 2 seconds) terminals.

1. Outdoor main board problem;


Quickly flashing yellow and green lights
Cannot find outdoor unit 2. MOUDBUS problem.
(flashing twice in 1 second)