280 280
"TOP VIEW"
C 1W 1V 1U "LEFT VIEW" C
05 08
06 09
D 10 D
11
1433
12
07
E 13
1 2 3 4 Drawing remain the property of PT. Bambang Djaja, Reproduction is not Allowed with any reasons. Sheet 1 of 1 Rev 0
Schedule of Particulars
SCHEDULE OF PARTICULARS
ELECTRICAL RATING :
Capacity : 630 kVA Frequency : 50 Hz
Number of Phase : 3 Phase For 1 Phase : CSP NON - CSP
Nominal Voltage (No Load) : HV Winding 20000 Volt LV winding 400 Volt
Full Load Current : HV Winding 18.19 Amp LV winding 909.33 Amp
Edition HV Tapping : + 2 x 2.5 %
- 4 x 2.5 %
Vector Group : Dyn5
Insulation Temp. Class : A
HV LV
Highest Voltage for Equipment : 24 kV 1.1 kV
Applied Test Voltage : 50 kV 3 kV
Lightning Impulse (BIL) : 125 kV - kV
Induced Voltage Test is applied 2 times of the rated voltage at 200 cycles per second for 30 seconds
(**) Weight and Dimension are approximate only and will vary according to the accessories supplied. Outline drawing will be
submitted to the customer later on.
1 2 3 4
NAME PLATE
A
118
130
C
Tap 1 : 21000 V
Tap 2 : 20500 V 1W 2w
1U
Tap 3 : 20000 V 2v
2w
1V 2v
Tap 4 : 19500 V 2u 2n
1W 1V 2u
Tap 5 : 19000 V 1U 2n
Tap 6 : 18500 V
Tap 7 : 18000 V
6 118 6
130
Projection : Scale :
- - - - -
- - - - A4
Drawing Number :
- - - -
F Rev. Modification Date Approved TR-C2LA7A41-ABAA
Drawing Title : Customer and destination : Drawn by :
- IRW
NAME PLATE Checked by :
SRT
Approved by :
Power Transformer | 630KVA| HV 20000 V | LV 400 V | Dyn5 | 50 Hz
Drawing remain the property of PT. Bambang Djaja, Reproduction is not Allowed with any reasons. Sheet 1 of 1
1 2 3 4
A VIEW
A
40
5 20 20
20
ø14
2 M12
70
8
7
76
9
B ITEM DESCRIPTION QTY
3
1 PORCELAIN 1
4 2 UPPER BOLT 1
3 CAP 1
5 4 GASKET 1
5 GASKET 1
A
1 D 6 GASKET 1
7 WASHER DIN 125 A 2
12 8 WASHER DIN 127 B 1
9 FULL NUT 3
10 WASHER DIN 125 A 4
C 14
L
11 PRESSBITS 4
12 FLANGE 1
13 13 FULL NUT 4
14 LOWER BOLT 1
10
11 VOLTAGE
IDENTIFICATION
TIGHTNESS
LIGHTNING IMPULSE (kV)
6 POWER
RATED VOLTAGE (kV)
LEE PROTECTED
LINE MIN. (mm)
D
TO STANDARD
(kV)
CREEPAGE
MIN. (mm)
ACCORDING
WET
DRY
Projection : Scale :
- - - - -
- - - -
Drawing Number :
A4
- - - -
ASHV.012.025
F Rev. Modification Date Approved
Drawing Title : Customer and destination : Drawn by :
- ADM
BUSHING 20NF-250 Checked by :
ARF
Approved by :
Distribution Transformer | Standard Accessories SRT
Drawing remain the property of PT. Bambang Djaja, Reproduction is not Allowed with any reasons. Sheet 1 of 1 Rev. 0
1 2 3 4
A VIEW
A C 60
E 17 26 17
26 17
2 Holes Ø14
60
6
D
3
13
12
11
B
4 A
2 ITEM DESCRIPTION QTY
5 1 UPPER PORCELAIN 1
D1 2 GASKET 1
7 3 BOLT 1
1 4 UPPER WASHER 1
5 MIDDLE WASHER 1
8 D2 6 FLAG DIN 43675 1
9 7 GASKET 1
8 GASKET 1
3
B
9 LOWER PORCELAIN 1
C 10 LOWER WASHER 1
10 11 FULL NUT 1
B 12 WASHER DIN 125 A 2
12 13 SCREW DIN 933 2
POWER
RATED VOLTAGE (kV)
LEE APROTECTED
ARCING DISTANCE
CREEPAGE
MIN. (mm)
D
ACCORDING
2 Holes Ø12
15
WET
DRY
15 30 15
60
Projection : Scale :
- - - - -
- - - -
Drawing Number :
A4
- - - -
ASLV.001.100
F Rev. Modification Date Approved
Drawing Title : Customer and destination : Drawn by :
- ADM
BUSHING DT1-1000 Checked by :
ARF
Approved by :
Distribution Transformer | Standard Accessories SRT
Drawing remain the property of PT. Bambang Djaja, Reproduction is not Allowed with any reasons. Sheet 1 of 1 Rev. 0