You are on page 1of 1

L 1

W
3
2W 2V 2U 2N 1U 1V 1W
7
35

2
36.5
65

H 6 MS
W/H
C/L

W/W

9
5

25
8

LV SIDE VIEW SIDE VIEW HV SIDE VIEW Core Assembly

Fittings
1 Core Clamping Channel 75x45 mm

2 Core Studs 12 mm 4 No
Overall Core Coil Assembly (CCA) Dimensions 3 M 12 Tie Rods 8 No
4
1 Height 650
4 End Packing 8 No PB
2 Width 280
5 Spacers B/W HV Coils 10 mm PB
3 Length 790
6 Phase Barrier 3 mm PB
7 Off Load Tap Changer 5 Positions
PLAN
Core Details 8 Foot Plates 12 mm
LV Winding Duct HV Winding 1 Window Height (W/H) 415
HV Winding Duct 2 Window Width (W/W) 155 Winding Deatils

3 Center Limb Distance(C/L) 265 1 Size of LV Strip (mm) 10.9 X3.92- 2R


LV Winding
4 Maximum Step (M.S) 110 2 Size of HV Conductor (mm) 1.67 mm
Duct Between HV and LV Windings
5 Core Diameter (Do) 117 3 LV Coil ID/OD 123 /182 mm
Core
6 No Off Steps 9 4 HV Coil ID/OD 202/256 mm

M/s Drawn MJR 13/05/2019


M/sGreentech Power Solutions NTS
Visakapatnam
Checked TM 13/05/2019 E:\weber documents\logo\w mahi anna.png

Used On
100 KVA , 11KV/433V, DYn11, 50 Hz Distribution
Approved TM 13/02/2019
transformer with OCTC
Title:
All information contained in this document is confidential and the property of Weberindia Infra Power (opc) Pvt Ltd. WEBERINDIA INFRA POWER (OPC) PVT LTD
Reproduction of these in any form is to be done with the specific permission of the Company General Assembly Drawing of CCA