TECHNICAL PARTICULARS  

FOR 33kV / 132kV, 28 MVA POWER


  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
ANNEXURE‐II 

A. POWER TRANSFORMER: 

Sr. No.  Particulars  VTL Reply 


1.0  General   
1.1  Service  Continuous 
1.2  Make  Voltamp Transformers Ltd, Vadodara. 
1.3  Type   Power Transformers / Outdoor type. 
1.4  Number of windings per phase  Two Winding 
1.5  Number of phases  3 Phase 
1.6  Reference Standard  IEC:60076 
2.0  Rating   
2.1  Type of cooling  ONAN 
2.2  Rated output  28 MVA 
2.3  Rated Voltage   
  LV  33 KV 
  HV  132 KV 
2.4  Rated Current   
  LV  489.87 Amps 
  HV  122.47 Amps 
2.5  Rated Frequency  50 Hz 
2.6  Connection   
  LV  Star 
  HV  Star 
2.7  Vector Group Reference  YNyn0 
2.8  Voltage Withstand Time   
  a) 110% of rated voltage  Continuous 
  b) 120% of rated voltage  60 sec 
  c) 125% of rated voltage  60 sec 
  d) 130% of rated voltage  30 sec 
  e) 140% of rated voltage  5 sec 
  f) 150% of rated voltage  2 sec 
2.9  Over fluxing Capability   
  a) For Over fluxing Factor 1.10  Continuous 
  b) For Over fluxing Factor 1.20  60 sec  
  c) For Over fluxing Factor 1.25  60 sec 
  d) For Over fluxing Factor 1.30  30 sec 
  e) For Over fluxing Factor 1.40  5 sec 
  f) For Over fluxing Factor 1.50  2 sec 
2.10  Noise Level of transformer  73 DB 
3.0  Temperature   
3.1  Design Ambient Temperature  40°C 
3.2  Maximum temperature rise over ambient   
  a) Of top oil by thermometer  50°C 
  b) Of winding by resistance  55°C 
Maximum continuous over loading capacity of 
3.3  transformer without exceeding the specified winding  As per IEC 60354  
temperature 
Page 1 of 7 
TECHNICAL PARTICULARS  
FOR 33kV / 132kV, 28 MVA POWER
  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
Sr. No.  Particulars  VTL Reply 
4.0  Insulation Level   
4.1  HV winding / HV neutral  HV  HVN 
  i) Lightning Impulse withstand voltage  650 KVp  95 KVp 
  ii) Power frequency withstand voltage  275 KVrms  38 KVrms 
4.2  LV winding   
  i) Lightning Impulse withstand voltage  170 KVp 
  ii) Power frequency withstand voltage  70 KVrms 
4.3  HV Bushings   
  i) Lightning Impulse withstand voltage  650 KVp 
  ii) Power frequency withstand voltage   275 KVrms 
4.4  LV Bushings   
  i) Lightning Impulse withstand voltage   170 KVp 
  ii) Power frequency withstand voltage   70 KVrms 
4.5  HV Neutral Bushings   
  i) Lightning Impulse withstand voltage   250 KVp 
  ii) Power frequency withstand voltage   95 KVrms 
Separate source power frequency voltage withstand 
4.6 
HV/LV winding  As per IEC 60076. 
4.7  Inducted over voltage withstand HV/LV winding 
Full wave lightning impulse withstand voltage  HV – 650 KVp; LV/LVN – 170 KVp;  
4.8 
(Winding)  HVN – 95 KVp. 
Impedances at Nominal Tap at Rated 
5.0   
Frequency and 75° C winding temperature 
5.1  Percentage Impedance  10 % ( ±7.5% Tol. ) 
5.2  Percentage Reactance  9.986% 
5.3  Resistance (per phase in ohms)  0.536% 
90% to 110% of measured positive 
5.4  Zero sequence Impedance 
sequence impedance. 
5.5  Capacitance of windings   
  i) HV ‐ Earth 
Value shall be provided at the time of final 
  ii) LV ‐ Earth 
inspection. 
  iii) HV ‐ LV 
6.0  Guaranteed Losses   
6.1  No load loss at rated voltage & frequency  25 KW (Max.) 
6.2  Full load loss at nominal tap at 75 deg C winding temp.  150 KW (Max.) 
7.0  Efficiency at 75°C winding Temperature   At 0.8 PF  At unity PF 
7.1  At full load            99.22 %  99.38% 
7.2  At 3/4 full load            99.35 %  99.48% 
7.3  At 1/2 load  99.45 %  99.56% 
7.4  At 1/4 load  99.36 %  99.51% 
7.5  Maximum Efficiency  99.46 %  99.564% 
7.6  Load at which the max. efficiency occurs  40.825% 
Regulation at full load at 75°C winding 
8.0   
temperature 
8.1  At unity power factor  1.034% 
8.2  At 0.8 power factor lagging  6.714% 
Page 2 of 7 
TECHNICAL PARTICULARS  
FOR 33kV / 132kV, 28 MVA POWER
  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
Sr. No.  Particulars  VTL Reply 
9.0  No load current   
9.1  At 90% rated voltage  0.50% of FLRC (Approx.) 
9.2  At 100% rated voltage  0.75% of FLRC (Approx.) 
9.3  At 110% rated voltage  1.5% of FLRC (Approx.) 
9.4  At 125% rated voltage  3% of FLRC (Approx.) 
9.5  At 140% rated voltage  4% of FLRC (Approx.) 
10.0  Approximate Maximum Flux Density   
10.1  At 90% rated voltage  1.55 Tesla 
10.2  At 110% rated voltage  1.9 Tesla 
10.3  At 125% rated voltage  2.15 Tesla 
10.4  At 140% rated voltage  2.41 Tesla 
11.0  Maximum Current Density at rated load   
11.1  HV winding  < 3.5 A/mm² @ Normal tap. 
11.2  LV winding  < 3.5 A/mm². 
12.0  Withstand Time without injury for   
Single  phase  to  ground  short  circuit  at  terminal 
12.1  2 sec 
with rated voltage maintained on other side 
Three phase dead short circuit at terminal with 
12.2  2 sec 
rated voltage maintained on other side 
13.0  Radiator   
13.1  Number of Radiator banks   12 Nos. radiators 

13.2  Whether radiator banks are detachable  Detachable type radiator provided. 


13.3  Standards to which radiators shall be adhered to  As per IEEMA 
13.4  Make  Refer attached make list. 
13.5  Radiator fin thickness  1 mm 
13.6  Whether radiator banks are detachable  Detachable type radiator provided. 
14.0  Details of  Tank   
14.1  Material  Mild Steel 
14.2  Paint shade  Polyurethane, RAL ‐ 7035 
14.3  Thickness of sides  8 mm (Approx.) 
14.4  Thickness of bottom  10 mm (Approx.) 
14.5  Thickness of cover  16 mm (Approx.) 
14.6  Tank Designed for   
  i) Vacuum  735 mm of Hg + atmospheric pressure. 
  ii) Pressure  Normal head of oil + 0.35 Kg/sq. cm. 
15.0  Core   
15.1  Make  AK steel/POSCO / JFE/Nippon 
15.2  Type (core or shell )  Core 
15.3  Core material  CRGO 
15.4  Thickness of lamination  0.27 mm Approx. 
15.5  Insulation of lamination  Carlite 
15.6  Equivalent cross sectional area    2376 cm² (Apprx.) 
16.0  Coils   
16.1  Type of coil   
  a) HV  Disc winding 
Page 3 of 7 
TECHNICAL PARTICULARS  
FOR 33kV / 132kV, 28 MVA POWER
  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
Sr. No.  Particulars  VTL Reply 
  b) LV  Disc winding 
16.2  Conductor Material  Electrolytic Copper 
16.3  Insulating Material   
  a) HV Turn  Oil impregnated paper 
  b) LV Turn  Oil impregnated paper 
  c) HV ‐ LV  Press board and Transformer oil 
  d) HV ‐ Earth  Press board and Transformer oil 
  e) LV ‐ Earth  Press board and Transformer oil 
Whether HV Winding is provided with uniform 
16.4  No , HV winding with Graded insulation. 
insulation 
17  WINDING   
17.1  Type of winding   
  i) HV  Disc winding 
  ii) LV   Disc winding 
  iii) Tap   Disc winding 
17.2  Conductor area   
  i) HV   35 mm² (Apprx.) 
  ii) LV   140 mm² (Apprx.) 
17.3  Max. current density under short circuit   
  i) HV  10 times of rated current density 
  ii) LV  10 times of rated current density 
HV‐ 4 to 6 times of FLRC.  
17.4  Magnetizing inrush current 
LV‐ 6 to 8 times of FLRC. 
0.75% of FLRC at normal voltage & 
17.5  No load current 
frequency 
17.6  Leakage reactance   
  i) HV 
%X: 9.986% 
  ii) LV 
17.7  DC resistance at 75⁰C   
  i) HV  1.48 Ω (+3 % Tol.) 
  ii) LV  0.069 Ω (+3 % Tol.) 
17.8  Air core reactance of HV winding  20% (Apprx.) 
18.0  Tap Changer   
18.1  Make  Alwaye 
18.2  Type & Model  Off Circuit Tap Changer 
18.3  Location  HV Winding 
18.4  Voltage class & current  66 KV, 200 A 
18.5  Number of steps  8 steps , 9 Positions 
18.6  Range  +10% to ‐10% @ 2.5% 
18.7  Step voltage  1905 V 
18.8  Rated short circuit current   
  i) Dynamic   
3 KArms for 2 sec , 7.5 KApeak 
  ii) Thermal   
 
18.9  Withstand time for short circuit 
 

Page 4 of 7 
TECHNICAL PARTICULARS  
FOR 33kV / 132kV, 28 MVA POWER
  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
Sr. No.  Particulars  VTL Reply 
  i) Dynamic   
3 KArms for 2 sec , 7.5 KApeak 
  ii) Thermal   
18.10  No. of revolutions to complete one step   N.A. as Off Circuit Tap Changer. 
Insulation level of the connecting leads between  Suitable to withstand specified test 
18.11 
tap changer & transformer winding  voltage. 
19.0  Insulating Oil  (EHV Grade)   
19.1  Approximate volume   14945 Ltrs. (Approx.) 
19.2  10% excess oil furnished  Provided 
19.3  Oil conforms to  IEC 60296, Class‐1 
19.4  Oil preservation system provided  Conservator with silicagel breather 
19.5  Quantity of oil   
  a) In main tank 
  b) For topping of main tank         14945Ltrs. (Apprx.) 
  c) For conservator, radiator, pipe work etc. 
  d) Total Oil   13300 Kg. (Apprx.) 
  e) 10% extra oil  Provided. 
  f) Total oil to be dispatched  Total Oil + 10% extra oil 
  g) Oil to be dispatched in main tank  Shall be provided at the time of dispatch. 
  h) Total Oil to be dispatched in barrels  10% extra oil shall be dispatched in barrels 
  i) Each barrel contains   Shall be provided at the time of dispatch. 
  j) Total No. of barrels to be dispatched  Shall be provided at the time of dispatch. 
20.0  Bushings  HV  HV Neutral  LV/LVN 
20.1  Make  Refer 3GA‐23421 Drawing. 
OIP 
20.2  Type  Condenser  Porcelain  Porcelain 
Type 
20.3  Reference Standard  Relevant IEC std. 
20.4  Voltage Class  145 KV  52 KV  36 KV 
20.5  Type of atmosphere  Polluted  Polluted  Polluted 
20.6  Creepage Distance  25 mm/KV  25 mm/KV  25mm/KV 
20.7  Weight in kg (Approx.)  118 kg  29 kg  25 kg 
20.8  Mounting of bushing  Top  Top  Top 
20.9  Rated current of bushing  800 A  1000 A  1000 A 
20.10  Free space required for bushing removal       6300mm  1500mm  1500mm 
21.0  Minimum Clearance   
21.1  Between Phases  HV  LV 
  a) In air  1500 mm  320 mm 
  b) In oil  Suitable to withstand test voltage 
21.2  Between Phase and earth  HV  LV 
  a) In air  1300 mm  320 mm 
  b) In oil  Suitable to withstand test voltage 
22.0  Terminal Connections   
22.1  HV  Bare Bushing with terminal connector.  

Page 5 of 7 
TECHNICAL PARTICULARS  
FOR 33kV / 132kV, 28 MVA POWER
  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
Sr. No.  Particulars  VTL Reply 
22.2  LV  Bare Bushing with terminal connector. 
22.3  HV / LV Neutral  Bare Bushing 
23.0  Marshalling Box   
23.1  Material of construction  CRCA 
23.2  Thickness  2 mm (Approx.) 
23.3  Degree of protection  IP:55 
23.4  Paint shade  RAL:7035 
24.0  Terminal Blocks   
24.1  Make  Elmex 
24.2  Type  Stud  
24.3  20% spare terminals furnished  Yes 
25.0  Wiring   
25.1  Cable Type  Stranded 
25.2  Voltage grade  1100 V 
25.3  Conductor   
  a) Size for control circuit  2.5 sq. mm 
  b) Size for auxiliary AC power circuit  2.5 sq. mm 
  c) Size for CT circuit  4.0 sq. mm 
  d) Material  Copper 
  e) Stranded or not  Stranded 
26.0  Ratings of Trip and Alarm contacts  As per OEM standard. 
27.0  Details of Conservator   
Approx. 10% of cold oil in tank and 
27.1  Volume of conservator 
radiators. 
27.2  Volume of oil between the highest and lowest levels  Approx. 7.5% of the total cold oil. 
28.0  Pressure Release Device   
Minimum pressure the device is set to 
28.1  0.42 Kg/sq. cm to 0.70 Kg/sq. cm. 
operate/rupture 
28.2  No. of pressure relief devices provided  2 Nos. 
28.3  Trip contacts provided  Yes 
 
29.0  Neutral bushing CT   
 
29.1  Make    
29.2  Type   
29.3  CT ratio  NCT details will be incorporated after 
29.4  No. of core  checking the feasibility from supplier. 
29.5  Accuracy class 
29.6  Resistance of CT secondary winding 
29.7  Knee point voltage 
29.8  Magnetizing current at Vk / 2 
29.9  Insulation level 
Maximum temperature rise of top oil beyond 
29.10  N.A 
design ambient temperature 
30.0  Line terminal connector   
30.1  Material for terminal connector bodys  Bi‐Metallic 

Page 6 of 7 
TECHNICAL PARTICULARS  
FOR 33kV / 132kV, 28 MVA POWER
  TRANSFORMER
  VTL Ref.: 23421/GTP/Rev.0      Date: 18.07.2020 
Sr. No.  Particulars  VTL Reply 
Less than M12 ‐ SS : 316  
30.2  Material for nuts, bolts, washers etc. 
Above M12 ‐ HDZ 
31  Support/mounting/fixing structures & accessories   
31.1  Material for support/mounting structure  Mild steel 
Material for foundation bolt, nuts, washers 
31.2  Mild steel 
& base plate 
Material for all other nut, bolt, washers etc. for 
31.3  SS‐316  
mounting/fixing 
31.4  Thickness of galvanization  610 gm/m²  
31.5  Galvanization standard  IS:1461 & IS:4759.  
L : 6900 x B : 5450 x H : 5600mm (± 5% 
32.0  Approximate Overall Dimensions (L x B x  H) 
Tol.) 
33.0  Approximate Weights   
33.1  Core and coil   23800 Kgs. (Apprx.) 
33.2  Tank and fittings   15000 Kgs. (Apprx.) 
33.3  Oil   13300 Kgs. (Apprx.) 
33.4   Total Weight   52100Kgs. (Apprx.) 
34.0  Shipping Data   
34.1  Weight of the heaviest package with N2 filling   33000 Kgs. (Apprx.) 
L : 5500 x B : 2700 x H : 3300mm (±2.5% 
34.2  Dimension of the largest package (LXBXH) 
Tol.) 
Proposed method of transformer transportation (oil 
35.0   N2 filled. 
filled or Nitrogen filled) 
If Vacuum filling required, if so state absolute 
36.0  As per CBIP. 
pressure 
 

Note: Percentage Efficiency & Regulation are subject to Guaranteed Losses and Impedance. It can vary by change in 
Impedance within agreed Tolerance.   

FOR VOLTAMP TRANSFORMERS LIMITED. 

 