A. POWER TRANSFORMER:
Page 4 of 7
TECHNICAL PARTICULARS
FOR 33kV / 132kV, 28 MVA POWER
TRANSFORMER
VTL Ref.: 23421/GTP/Rev.0 Date: 18.07.2020
Sr. No. Particulars VTL Reply
i) Dynamic
3 KArms for 2 sec , 7.5 KApeak
ii) Thermal
18.10 No. of revolutions to complete one step N.A. as Off Circuit Tap Changer.
Insulation level of the connecting leads between Suitable to withstand specified test
18.11
tap changer & transformer winding voltage.
19.0 Insulating Oil (EHV Grade)
19.1 Approximate volume 14945 Ltrs. (Approx.)
19.2 10% excess oil furnished Provided
19.3 Oil conforms to IEC 60296, Class‐1
19.4 Oil preservation system provided Conservator with silicagel breather
19.5 Quantity of oil
a) In main tank
b) For topping of main tank 14945Ltrs. (Apprx.)
c) For conservator, radiator, pipe work etc.
d) Total Oil 13300 Kg. (Apprx.)
e) 10% extra oil Provided.
f) Total oil to be dispatched Total Oil + 10% extra oil
g) Oil to be dispatched in main tank Shall be provided at the time of dispatch.
h) Total Oil to be dispatched in barrels 10% extra oil shall be dispatched in barrels
i) Each barrel contains Shall be provided at the time of dispatch.
j) Total No. of barrels to be dispatched Shall be provided at the time of dispatch.
20.0 Bushings HV HV Neutral LV/LVN
20.1 Make Refer 3GA‐23421 Drawing.
OIP
20.2 Type Condenser Porcelain Porcelain
Type
20.3 Reference Standard Relevant IEC std.
20.4 Voltage Class 145 KV 52 KV 36 KV
20.5 Type of atmosphere Polluted Polluted Polluted
20.6 Creepage Distance 25 mm/KV 25 mm/KV 25mm/KV
20.7 Weight in kg (Approx.) 118 kg 29 kg 25 kg
20.8 Mounting of bushing Top Top Top
20.9 Rated current of bushing 800 A 1000 A 1000 A
20.10 Free space required for bushing removal 6300mm 1500mm 1500mm
21.0 Minimum Clearance
21.1 Between Phases HV LV
a) In air 1500 mm 320 mm
b) In oil Suitable to withstand test voltage
21.2 Between Phase and earth HV LV
a) In air 1300 mm 320 mm
b) In oil Suitable to withstand test voltage
22.0 Terminal Connections
22.1 HV Bare Bushing with terminal connector.
Page 5 of 7
TECHNICAL PARTICULARS
FOR 33kV / 132kV, 28 MVA POWER
TRANSFORMER
VTL Ref.: 23421/GTP/Rev.0 Date: 18.07.2020
Sr. No. Particulars VTL Reply
22.2 LV Bare Bushing with terminal connector.
22.3 HV / LV Neutral Bare Bushing
23.0 Marshalling Box
23.1 Material of construction CRCA
23.2 Thickness 2 mm (Approx.)
23.3 Degree of protection IP:55
23.4 Paint shade RAL:7035
24.0 Terminal Blocks
24.1 Make Elmex
24.2 Type Stud
24.3 20% spare terminals furnished Yes
25.0 Wiring
25.1 Cable Type Stranded
25.2 Voltage grade 1100 V
25.3 Conductor
a) Size for control circuit 2.5 sq. mm
b) Size for auxiliary AC power circuit 2.5 sq. mm
c) Size for CT circuit 4.0 sq. mm
d) Material Copper
e) Stranded or not Stranded
26.0 Ratings of Trip and Alarm contacts As per OEM standard.
27.0 Details of Conservator
Approx. 10% of cold oil in tank and
27.1 Volume of conservator
radiators.
27.2 Volume of oil between the highest and lowest levels Approx. 7.5% of the total cold oil.
28.0 Pressure Release Device
Minimum pressure the device is set to
28.1 0.42 Kg/sq. cm to 0.70 Kg/sq. cm.
operate/rupture
28.2 No. of pressure relief devices provided 2 Nos.
28.3 Trip contacts provided Yes
29.0 Neutral bushing CT
29.1 Make
29.2 Type
29.3 CT ratio NCT details will be incorporated after
29.4 No. of core checking the feasibility from supplier.
29.5 Accuracy class
29.6 Resistance of CT secondary winding
29.7 Knee point voltage
29.8 Magnetizing current at Vk / 2
29.9 Insulation level
Maximum temperature rise of top oil beyond
29.10 N.A
design ambient temperature
30.0 Line terminal connector
30.1 Material for terminal connector bodys Bi‐Metallic
Page 6 of 7
TECHNICAL PARTICULARS
FOR 33kV / 132kV, 28 MVA POWER
TRANSFORMER
VTL Ref.: 23421/GTP/Rev.0 Date: 18.07.2020
Sr. No. Particulars VTL Reply
Less than M12 ‐ SS : 316
30.2 Material for nuts, bolts, washers etc.
Above M12 ‐ HDZ
31 Support/mounting/fixing structures & accessories
31.1 Material for support/mounting structure Mild steel
Material for foundation bolt, nuts, washers
31.2 Mild steel
& base plate
Material for all other nut, bolt, washers etc. for
31.3 SS‐316
mounting/fixing
31.4 Thickness of galvanization 610 gm/m²
31.5 Galvanization standard IS:1461 & IS:4759.
L : 6900 x B : 5450 x H : 5600mm (± 5%
32.0 Approximate Overall Dimensions (L x B x H)
Tol.)
33.0 Approximate Weights
33.1 Core and coil 23800 Kgs. (Apprx.)
33.2 Tank and fittings 15000 Kgs. (Apprx.)
33.3 Oil 13300 Kgs. (Apprx.)
33.4 Total Weight 52100Kgs. (Apprx.)
34.0 Shipping Data
34.1 Weight of the heaviest package with N2 filling 33000 Kgs. (Apprx.)
L : 5500 x B : 2700 x H : 3300mm (±2.5%
34.2 Dimension of the largest package (LXBXH)
Tol.)
Proposed method of transformer transportation (oil
35.0 N2 filled.
filled or Nitrogen filled)
If Vacuum filling required, if so state absolute
36.0 As per CBIP.
pressure
Note: Percentage Efficiency & Regulation are subject to Guaranteed Losses and Impedance. It can vary by change in
Impedance within agreed Tolerance.
FOR VOLTAMP TRANSFORMERS LIMITED.
AUTHORISED SIGNATORY