C. Sizing Calculation
1. For Continuous load demand
Sl. No. Feeder Load (kVA)
1. Desalination plant Load 2800
2. IREl Incoming plant Load 5000
3. Spare Capacity (20% of connected 1560
load)
Total 9360 kVA
It is desired to restrict the earth fault current between FLC and twice the FLC of the
transformer.
12500
FLC is = = 656 𝐴
11 𝑥 √3
To match with the existing system the maximum fault current is chosen as 1200 A
6350
So value of the NGR required is = 1200 = 5.29 𝑜ℎ𝑚
Conclusion:
a. The transformers selected are 2 nos. of 132/11 kV Oil immersed 10/12.5 MVA
(ONAN/ONAF) transformer in the 2 100% configuration. During the normal operation,
both the transformers shall share the total load equally in the ratio 1:1.
b. The value of NGR is 5.29 ohms.