KARNATAKA POWER TRANSMISSION COR

Bid Enquiry No. KPTCL/CEE/T&P/400kV/Kadak


a. Establishing 2x500MVA, 400/220kV Substation at Kadakola in Mysuru Taluk & Districtb. Construction
LILO from existing 400kV Shanthigrama-Basthipura line to the proposed 400/220kV Kadakola sub-station
including Designing of 400kV Towers, Supply of all equipments/ Materials including Mandatory spares, Er
Commissioning.

GUARANTEED TECHNICAL PARTICULARS FOR STATIO


(Bidder should indicate the guaranteed technical data

Bidder's Name
1 Make
2 Name of Manufacturer
3 Place of Manufacture
4 Reference standard
5 Service (indoor/outdoor)
6 Voltage Ratio
7 Rating in kVA
8 Rated Frequency (Hz)
9 Number of phases
10 Vector group
11 a)      Core Material used and Grade
b)     Flux density
c)      Over fluxing without saturation (Curve to be furnished by the
manufacturer in support of his claim)
12 Maximum temperature rise of:
a)    Winding by resistance method (0C)
b)   Oil by thermometer (0C)
13 Magnetizing (No-load) current at :
a)    90%
b)   100%
c)    110%
14 Core loss in watts
a)    Normal voltage
b)   Maximum voltage
15 Resistance of windings at 200C (with 5% tolerance)
a)    HV Windings (ohms)
b)   LV Windings (ohms)
16 Full load losses (watt) at 750C
17 Total losses at 100% load at 750C
18 Total losses at 50% load at 750C
19 Current density used for : (Ampere/Sq.mm)
a)    HV Winding
b)   LV winding
20 a)   Clearances : mm (in oil)
a)    Core and LV
b)   LV & HV
c)    HV Phase to Phase
d)   End insulation clearance to earth
e)    Any point of winding to tank
ii)    Clearances : mm (in air)
a)    HV - Phase to Phase
Phase to Earth
b)   LV - Phase to Phase
Phase to Earth
21 Efficiency at 750C (@ Unity P.F. and 0.8 P.F.)
a)    125% load
b) 100% load
c) 75% load
d) 50% load
e) 25% load
22 Regulation at :
a)    Unity P.F. and
b)   0.8 P.F. at 750C
23 % Impedance at 750C
24 Tap changing gear:
a)    Make
b)   Type of tap changer
c)    Step voltage
d)   Total tap range (+) percent to (-) percent
e)    Tappings provided at
25 Permissible overloading
Noise level when energized at normal voltage and normal frequency at
26
no-load (db)
27 Insulation level in kV
a)    Nominal system voltage (NSV)
b)   Highest system voltage (HSV)
c)    Power frequency withstand voltage
d) Lightning impulse withstand voltage
28 Mass of : (kg)
a)    Core lamination (minimum)
b)   Windings (minimum)
c)    Tank and fittings
d)   Oil
e)    Oil quantity (minimum ) (litre)
f)     Total weight
29 Oil Data:
1.     Quantity for first filling (minimum) (litre)
2.     Grade of oil used
3.     Maker’s name
4.     BDV at the time of filling (kV)
5.     Water content at the time of filling (in PPM)
30 Transformer:
a)    Overall length x breadth x height (mm x mm x mm)
b)   Tank length x breadth x height
c)    Thickness of plates for
i) Side plate (min)
ii) Top and bottom plate (min)
d)     Conservator dimensions
31 Radiation:
a)      Heat dissipation by tank walls excluding top and bottom
b)     Heat dissipation by cooling tube
c)      Diameter and thickness of cooling tube
d)     Total radiating surface in square metre
e)      Whether calculation sheet for selecting cooling area to ensure
that the transformer is capable of giving continuous rated output
without exceeding temperature rise is enclosed.
32 Inter layer insulation provided in design for :
a)    Top and bottom layer
b)   In between all layer
c)    Details of end insulation
d)   Whether wedges are provided at 50% turns of the HV coil.
33 Insulation materials provided
a)    For conductors
i.       HV
ii.      LV
b)   For core
34 Material and size of the conductor used and current density
a)    HV Dia (mm) SWG
b)   LV i) Strip size
ii) No. of conductors in parallel
iii)  Total area of cross section (all particulars as required in
tender).
c)    Current density - HV
LV
d)   Material of winding conductor
35 Whether the name plate gives all particulars as required in tender
36 Particulars of bushings HV/LV
a)    Maker’s name
b)   Type
c)    Current Rating (Amps)/Voltage rating (kV)
d)   Dry power frequency withstand voltage (kV rms)
e)    Wet power frequency withstand voltage (kV rms)
f)     Lightning impulse withstand voltage (kVp)
g)    Creepage distance (mm)
37 Type of insulation used in
a)    HV windings
b)   LV windings
38 Type of insulation used on
a)    Core bolts
b)   Core bolt washers
c)    Core laminations
39 Vacuum to which the tank can be subjected without distortion (torr)
40 Weight of insulated conductor
a)    HV
b)   LV
41 a.    Weight of core
b.   Tolerance
42 Weight of complete Transformer for transport
Period for which this design of transformer has been in commercial
43
use.
Reactance of windings at 750C/ph
44
a.    HV b. LV
Resistance of windings at rated current and frequency
45
a. HV b. LV
Type & size of Gas operated relay and whether supervisory alarm and
46
trip contacts provided.
Temperature indicators
48 a)    Oil temperature b) Winding temperature
indicator indicator
i) Make & type
ii) Permissible setting ranges for alarm & trip
iii) No. of contacts
iv)  Current rating of each contact
49 Ratio and type of CT used for winding temperature
a)    Ratio
b)   Type
50 No. of Breathers provided (Nos.)
51 Type of dehydrating agent used for breathers
52 a)    Type , make and number of pressure relief device
b)   Minimum pressure at which the device operates, Kg/cm2
53 Valves - sizes and numbers required/fitted
a)    Drain cum sampling valve
b) Fitter valve
54 Characteristics of insulating oil to be used
a. Appearance
b.  Density (Max) at 20° C
c.  Kinematic viscosity (max)
d.  Interfacial tension
e.  Flash point (Min)
f. Neutralization value
i) Total acidity (Max)
ii) Inorganic acidity/Alkalinity
a.  Pour point (max)
b.  Corrosive sulphur
i. Electric strength (break down voltage (min) with 2.5mm gap)
i) New Unfiltered oil as in received condition.
ii) After filtration.
j. Dielectric dissipation factor (tan delta) at 90°C (Max)
k.  Water content (Max)
l. Specific Resistance (Min) (Resistivity)
i) At 90°C (min)
ii) At 27°C (min)
m. Oxidation Stability
i) Neutralization value after oxidation (Max.)
ii) Total sludge after oxidation (Max.)
n. Ageing characteristics after accelerated ageing (Open breaker method with
copper catalyst)
a)  Resistivity at 27°C
b)  Resistivity at 90°C
c)    Dielectric loss factor (tan delta) at 90°C
d)    Total acidity mg KOH/g
e)    Sludge Content (Max.)
o. Presence of oxidation inhibitor (Percent by weight)
Date of commencement of production of distribution transformer at the
55
factory of the supplier

Date

Place
TRANSMISSION CORPORATION LIMITED

/CEE/T&P/400kV/Kadakola/TTK/TLSS-1446
& Districtb. Construction of 400kV MC line with Twin Moose ACSR on MC towers by making double
kV Kadakola sub-station for a distance of 43.96km in Mysore Taluk & District.on Total Turnkey Basis
ng Mandatory spares, Erection (including Civil Works), of all materials/ equipments, Testing &

DRS - 17
ICULARS FOR STATION AUXILIARY TRANSFORMERS
uaranteed technical data of all equipments/materials )

1MVA 630kVA

VARDHMAN VARDHMAN
ELECTROMECH ELECTROMECH
JAIPUR JAIPUR
IS 1180 IS 1180
Outdoor Outdoor
33/0.433 11/0.433
1000 630
50 50
3 3
Dyn11 Dyn11
CRGO / M4 or better grade CRGO / M4 or better grade
1.69 1.69
1.9 1.9

55 55
50 50

1.2% At rated current 1.2% At rated current


1.5% At rated current 1.5% At rated current
1.7% At rated current 1.7% At rated current

As per clause No. 17&18 As per clause No. 17&18


As per clause No. 17&18 As per clause No. 17&18

9.14 Approx 1.542 Approx


0.00048 Approx 0.0000635 Approx
As per clause No. 17&18 As per clause No. 17&18
8277.5 1860
2999 5300

2.8 max 2.8 max


2.8 max 2.8 max

4mm Approx 4mm Approx


17mm Approx 10mm Approx
18mm Approx 10mm Approx
50mm Approx 25mm Approx
60mm Approx 30mm Approx

350 255
320 140
75 75
40 40

99.03 and 98.80 99.07 and 98.84


99.16 and 98.98 99.21 and 99.01
99.31 and 99.14 99.33 and 99.16
99.40 and 99.26 99.41 and 99.27
99.33 and 99.16 99.33 and 99.16

0.82 0.77
3.59 3.26
5 4.5

MAC Power/CTR Abhishek


OLTC OCTC
825 275
(+5 to -10)% (+5 to -10)%
HV Side HV Side
IS 6600 IS 6600
As per NEMA As per NEMA

33 kv 11 kv
36 kv 12 kv
70 kv 28 kv
170 kv 75 kv

1390 900
1765 646
1542 685
1315 550
1615 675
5152 2850

1615 675
As per IS 335 As per IS 335
Apar or Reputed make Apar or Reputed make
60 kv 60 kv
As per IS 335 As per IS 335

3425 x 2675 x 2640 2930 x 1990 x 2360


1525x615x1440 1280x530x1160

4 4
5 5

3080 Approx 2099.6 Approx


7222 6083
1mm 1mm
42.16 Sqmm 21.48 Sqmm
At th etime of Inspection At th etime of Inspection

Kraft paper Kraft paper


Kraft paper Kraft paper
Kraft paper Kraft paper
NA NA

TPC DPC
DPC DPC
Carlite Carlite

2.70mm 3.94mm
11.45 x 3.40 mm 12.80 x 4.35 mm
15 9
571.05 493.38

1.76 1.6
2.33 1.7
Copper Copper
Yes Yes

Adpro / Jaipur glass or Reputed Adpro / Jaipur glass or Reputed


make make
Porcelain Porcelain
250 Amp / 36 kv 250 Amp / 12 kv
70 28
70 28
170 75
18mm 18mm
TPC DPC
DPC DPC

Varnesh Varnesh
Varnesh Varnesh
Carlite Carlite
500 (As per IS) 500 (As per IS)

473 374
292 272
1390 900
As per IS (±10%) As per IS (±10%)
5200 3000
2018 2018

(a) 161.74 (b) 9.2 (a)25.64 (b) 13.24

(a) 9.14 (b)0.0048 (a)22.85 (b) 0.001


Gor - 1 Gor - 1

Voltech or Reputed make Voltech or Reputed make


90 & 95 90 & 95
2 2
5A 5A

20\2 60\2
WTI WTI
1 1
Silica Gel Silica Gel
1 1
0.56 0.56

25 25
25 25

As per IS 335 As per IS 335


As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335
As per IS 335 As per IS 335

2018 2018

Name

Designation

Name of the Company