GENERATOR

1. Type & cooling method Type Cooling method QFSN-300-2 Stator winding and terminal bushing are water inner-cooled, rotor winding is hydrogen inner-cooled and stator core hydrogen cooled 0.31 MPa (g) or 3.1 KSC 353 MVA 300 MW 20 KV 10189 A 3000 RPM 50 Hz 98.85% 38 C 2 times 2510 A 302 V Normal 46 C , Max 48 C 45~ 50 C

Rated H2 pressure 2. Basic technical data Rated capacity Rated capacity Rated stator voltage Rated stator current Rated speed Rated frequency Efficiency Cooling water inlet temperature Ceiling voltage Rated field current Rated field voltage ( 90 C) Cold H2 temperature Stator winding demineralized water inlet temperature 3. Parameter No load field current No load field voltage (75 C) Stator winding resistance (15 C)

Rotor winding resistance (15 C) Rotor winding self- inductance Stator winding capacitance to ground/ phase Direct axis sub-transient reactance (unsaturated) X du Direct axis sub-transient reactance (saturated) X d Quadrature axis sub-transient reactance (unsaturated) X qu Quadrature axis sub-transient reactance (saturated) X q Direct axis transient reactance (unsaturated) X du Direct axis transient reactance (saturated) X d Quadrature axis transient reactance (unsaturated) X qu Quadrature axis transient reactance (saturated) X q

987 A 113 V 0.00212 / PH 0.0923 0.857 H 0.209 F 17.4% 16% 17.2% 15.8 % 22.9 % 20.2 % 38.2 % 33.6 %

Direct axis synchronous reactance Xd Quadrature axis synchronous reactance Xq Negative phase-sequence (unsaturated) X2u Negative phase-sequence (saturated) X2 Zero phase-sequence (unsaturated) X0u Zero phase-sequence (saturated) X0 Direct axis transient open circuit time constant Tdo Quadrature axis transient open circuit time constant T q0 Direct axis transient short circuit time constant Td Quadrature axis transient short circuit time constant Tq Direct axis sub-transient open circuit time constant T d0 Quadrature axis sub- transient open circuit time constant Tq0 Direct axis sub-transient short circuit time constant T d Quadrature axis sub- transient short circuit time constant Tq

180 % 175 % 17.3% 15.9 % 7.93 % 7.53 8.6 s 0.956 s 0.965 s 0.184 s 0.044 s 0.074 s 0.035 s 0.035 s

4. The operation performance of H2 cooler Generator continuous operation capacity at rated H2 pressure, with 1/8 set of 4 coolers out of service Generator continuous operation capacity at rated H2 pressure, with 1/8 set of 4 coolers out of service, but not at the same corner Generator continuous operation capacity at rated H2 pressure, with 1/8 set of 4 coolers out of service, but at the same corner Generator is not recommended to be operated in the air, because the frication and windage loss will go high Volume of cooling water required Water pressure drop inside the cooler 5. Generator weight and critical speed Weight of the stator (including end bracket, coolers, bed plate and lead box) Max. transportation weight (stator, including transportation cover, but not including end bracket, coolers, bed plate and lead box) Generator rotor weight 262 t 210 t 318 MVA / 270 MW 282 MVA / 240 MW 212 MVA / 180 MW

4 x 110 m/h 56 KPa

53 t

Brushless exciter weight Sudden short circuit torque Generator rotor moment of inertia Equivalent to rotor flywheel moment Generator rotor critical speed

24.5 t 1400 t-m J= 8180 Kg-m GD= 32.7 t-m 1st 867 RPM 2nd 2256 RPM

.1 GENERATOR AND EXCITATION SYSTEM

3.1.1 GENERATOR MAKE TYPE CODE ACTIVE POWER APPARENT POWER STATOR VOLTAGE (U) STATOR CURRENT (I) POWER FACTOR (Pf) FREQUENCY (f) RATED SPEED (N) GUARANTEED EFFICIENCY AT MCR SHORT CIRCUIT RATIO NEGATIVE PHASE SEQUENCE CURRENT CAPABILITY STATOR PHASE CONNECTION DIRECTION OF ROTATION HYDROGEN PRESSURE TERMINAL MARKING VEIWED FROM SLIP RING END. (L TO R) STATOR WINDING RESISTANCE AT 200C PHASE U X PHASE V Y PHASE W Z ROTOR WINDING RESISTANCEAT 200C NO OF SLOTS WINDING TYPE

BHEL THRI - 930-38 P IS 5422, IEC-34.1 130 MW 162.5 MVA 10,500 + / - 5% Volts AT 47.5 Hz 8,935 Amps 0.8 Lag 50 Hz 3000 rpm 98.78 % 0.57 I2t not more than 10 sec DOUBLE STAR CW (Viewed from slip ring end) 3.0 kgf/cm2 PHASE : U V W NEUTRAL: X Y Z 0.000794677 ohms 0.000809157 ohms 0.000800924 ohms 0.08801328 ohms 48 LAP

MACHINE REACTANCE VALUES DIRECT AXIS TRANSIENT REACTANCE 1. SATURATED ( Xd) 2. UNSATURATED (Xdu) DIRECT AXIS SUB TRANSIENT REACTANCE. 1. SATURATED ( Xd) 2. UNSATURATED (Xdu) DIRECT AXIS SYNCHRONOUS REACTANCE 1. SATURATED (Xd) 2. UNSATURATED (Xdu) QUADRATURE AXIS SYNCHRONOUS REACTANCE NEGATIVE SEQUENCE REACTANCE (X2) SATURATED ZERO SEQUENCE REACTANCE (X0) MACHINE TIME CONSTANTS 1. DIRECT AXIS, TRANSIENT OPEN Ckt. (T do) 2. DIRECT AXIS, TRANSIENT CLOSED Ckt. (T d) 3. SUB TRANSIENT ( Td) FIELD TEST VOLTAGE CLASS OF INSULATION WEIGHT OF STATOR WEIGHT OF COOLERS & SHIELDS WEIGHT OF ROTOR STATOR CORE OUTER DIA STATOR CORE LENTH AIR GAP 3.1.2 EFFICIENCY OF TURBO GENERATOR PARAMETER 100% Load (130MW) FIELD CURRENT 2056 Amps FRICTION LOSSES 341.3 Kw CORE LOSSES 235 Kw STATOR Cu. LOSSES 575 Kw FIELD LOSSES 480 Kw TOTAL LOSSES 1631 Kw EFFICIENCY 98.76 % 3.1.3 STATIC EXCITATION SYSTEM MAKE TYPE ACCURACY OF EXCITATION CONTROL RANGE OF VOLTAGE CONTROL IN AUTO RANGE OF VOLTAGE CONTROL IN MANUAL RANGE REACTIVE CURRENT COMPENSATION FREQUENCY RANGE OF OPERATION TOTAL NO. OF PARALLEL THY. BRIDGES NO. OF REDUNDANT THYRISTOR BRIDGES PROTECTION CLASS EXCITATION EQUIPMENT RATING NO LOAD FIELD VOLTAGE (Ufo) NO LOAD FIELD CURRENT (Ifo) NOMINAL FIELD VOLTAGE (Ufn) NOMINAL FIELD CURRENT (Ifn) MAX. CONT. RATED FIELD VOLTAGE (Ufmax)

0.2064 P.U 0.2282 P.U 0.1512 P.U 0.1867 P.U 1.672 P.U 1.8971 P.U 1.8023 P.U 0.146 P.U 0.125 P.U 6.691 Sec 0.767 Sec 0.030 Sec 2500 Volts rms F 127 TONS 5 + 13 = 18 TONS 28 TONS 3780mm 6390 mm 62.5 mm

80% Load (104MW) 1812 Amps 341.3 Kw 235 Kw 370 Kw 379 Kw 1325.3 Kw 98.74 %

60% Load (78MW) 1573 Amps 341.3 Kw 235 Kw 205 Kw 291.1 Kw 1072.4 Kw 98.64 %

BHEL STATIC EXCITATION SYSTEM +/- 0.5% 90%UGN TO 110%UGN 75% IFO to 110% IFN 0 TO 15% 47 Hz TO 52 Hz 4NO. 2NO. IP31 FOR REG & FF IP20 FOR OTHER CUBICLES 77.8VDC 763.1ADC 239.9VDC 2039.3ADC 239.9VDC

MAX. CONT. RATED FIELD CURRENT (Ifmax) CEILING VOLTAGE (Ud) CEILING CURRENT (Id) DURATION OF FIELD FORCING STATION BATTERY SUPPLY

2039.3ADC 479.8VDC 3262.9ADC 2SEC 220 VDC

3.1.3 a). RECTIFIER TRANSFORMER: MAKE TYPE KVA RATING TAP NO HIGH VOLTAGE 1 11075 Volts 2 10763 Volts 3 10500 Volts 4 10238 Volts 5 9975 Volts PHASE TYPE OF COOLING PERCENTAGE IMPEDENCE FREQUENCY VECTOR GROUP MODE OF CONNECTION BETWEEN L.V TERMINALS & THYRISTOR CONVERTER INSULATION LEVEL DESIGN AMBIENT TEMP. TEMP. RISE ABOVE AMBIENT TEMP. WEIGHT OF TRANSFORMER

BHEL CAST COIL RESIN DRY TYPE 1500 KVA LOW VOLTAGE 400 Volts 400 Volts 400 Volts 400 Volts 400 Volts 3-PHASE AIR NATURAL 6% 50 Hz Dyn 5 CABLES 75 KVp / 26 KVrms 500C 900C 5000 kg

3.1.3 b) RECTIFIER ASSEMBLY: TYPE MAKE RATED RECTIFIED VOLTAGE RATED RECTIFIED CURRENT CEILING VOLTAGE RATING CEILING CURRENT RATING CEILING DUTY DURATION SCR BASE TEMP. AT RATED OUT PUT RATED PEAK INVERSE VOLTAGE OF SCR MAX. VOLTAGE DROP ACROSS RECTIFIER TYPE OF CONNECTION OVER VOLTAGE WITH STAND CAPACITY ON DC SIDE % SPARE CAPACITY OF RECTIFIERS ON THE BASIS OF GENERATED FULL LOAD EXCITATION FIELD SUPPRESSION ARRANGEMENT PROVIDED TOTAL LOSS IN EXCITATION SYSTEM AT RATED POWER 3.1.3 c) AUTOMATIC VOLTAGE REGULATOR: Temp. RANGE OF OPERATION ACCURACY DEAD BAND RESPONSE TIME AVR C.T RATIO AVR P.T RATIO AMBIENT TEMP. ALTITUDE

BHt 65 BHEL 239.9 Volts 2309.3 Amps 479.8 Volts DC 3262.9 Amps DC 10 Sec 1250C 1.95 Volts * 3-PHASE BRIDGE * 100% YES 20 Kw

* * * * 10,000 / 5 Amps 10,500 / 110 Volts 50 0C 1000 M

3.1.4 NEUTRAL GROUNDING SYSTEM 3.1.4 a) NEUTRAL GROUNDING TRANSFORMER KVA RATING 35 KVA VOLTAGE RATING 10.5 KV / 240 V PHASE 1 COOLING AN RATED DUTY CONTINUOUS TAPS OFF CKT, + / - 5% IN STEPS OF 2.5% ON HV SIDE 3.1.4 b) NEUTRAL GROUNDING RESISTOR RESISTANCE 0.61 OHM RATED CURRENT 240 AMP RATED DUTY 1 HOUR

3.1.5 SEAL OIL SYSTEM SEAL OIL SOURCE SEAL OIL PUMP-AC KIND OF PUMP TYPE SPEED CAPACITY DISCHARGE PRESSURE PUMP MOTOR RATING VOLTAGE /FREQUENCY CURRENT SPEED TYPE OF ENCLOSER NO OF PUMPS SEAL OIL PUMP-DC KIND OF PUMP TYPE SPEED CAPACITY DISCHARGE PRESSURE PUMP MOTOR MAKE RATING VOLTAGE /FREQUENCY CURRENT SPEED TYPE OF ENCLOSER NO. SEAL OIL LEVEL DETECTORS MAKE& TYPE PLACES OF LEVEL DETECTION

TURBINE OIL SCREW PUMP SNH 210-R46 (ALLWEILER) 16S-1 2.16 DM3 /S 12BAR 4.85KW 415V/50HZ 10.6A 16S-1 IP54 2 NOFULL CAPACITY SCREW PUMP SNH 210-R46 (ALLWEILER) 16 S-1 2.16 dm3 /S 12BAR CROMPTON GREAVES 5.6KW 220V DC 27A 16S-1 IP54 1 No FULL CAPACITY NIVOLARM-CONTROLLER SERIES 500 CAPACITANCE TYPE GENERATOR BRG TE PRECHAMBERS GENERATOR BRG EE PRECHAMBER SEAL OIL TANK SEAL OIL STORAGE TANK INTERMEDIATE OIL TANK

3.1.5 SEAL OIL SYSTEM (CONTD.) VACUUM PUMP MODEL TYPE RATED SUCTION CAPACITY WORKING CYCLES/ROTATION TOTAL PARTIAL VACUUM TOTAL ULTIMATE VACUUM WITH GASBALLAST OIL FILLING VACUUM PUMP MOTOR TYPE RATING VOLTAGE FREQUENCY CURRENT SPEED TYPE OF ENCLOSURE NO OF PUMPS BRG VAPOUR EXTRACTOR NO OF BRG VAP EXTS RATING VOLTAGE CURRENT SPEED Type of exhausters Volumetric flow rate SEAL OIL COOLER NO & CAP OF COOLERS OIL FLOW HEAT DISSIPATING CAP OIL INLET TEMP OIL OUTLET TEMP OIL PR DROP ( APPROX ) COOLING WATER FLOW WATER INLET TEMP WATER OUTLET TEMP WATER PR DROP SEAL OIL FILTER UNIT KIND VOL FLOW RATE DEG OF FILTRATION DP ACROSS FILTER NO OF FILTERS TRIVAC, SAB 1-STAGE, OILSEALED ROTARY SLIDING VANE PUMP 4.8 m3 / h 3 < 10 2 Torr < 6X101 Torr 0.8 1.2 dm3 AM80KY4 (AEG) 0.55 KW 415 V 50 HZ 0.5 A 25 S 1 IP54 1, FULL CAPACITY 2 (1-OP, 1-S /B) 0.75 KW 415 V 1.65 A 49 Hz Radial flow 380 m3/h AT 10 mbar 2, 100 % EACH 2.17 dm3 / S 90 KW 68 C 43 C 0.9 BAR 5.4 M3 / HR 36 C ( MAX ) 40 C 0.6 BAR SCREEN FILTER 2.16 dm3 / S 100 MICRONS 0.2 BAR (CLEAN) 1.2 BAR (100% FOULING) 2, EACH FULL CAPACITY

3.1.5. SEAL OIL SYSTEM (CONTD.) LUBRICATION CHART SEAL OIL PUMP-AC SEAL OIL PUMP-DC VACUUM PUMP BRG VAPOUR EXT SEAL OIL PUMP-AC MOTOR SEAL OIL PUMP-DC MOTOR VACUUM PUMP MOTOR GAS DRIER MOTOR BRG VAP EXT MOTOR 3.1.6 H2 SYSTEM H2 COOLED AREAS OF GEN TURBINE OIL TURBINE OIL SPECIAL OIL N62 LITHIUM SOAP GREASE KP3N TO DIN 51825 GREASE KP2N TO DIN 51825 GREASE KP2N TO DIN 51825 GREASE KP2N TO DIN 51825 GREASE KP2N TO DIN 51825 GREASE KP2N TO DIN 51825

POSSIBLE LOAD WITH ONE COOLER SECTION OUT LOCATION OF H2 BOTTLES BOTTLED H2 PRESSURE VOLUMETRIC FLOW RATE GENERATOR GAS VOLUME BOTTLE MATERIAL ON SITE STORAGE CAP GENERATOR H2 PRESSURE GENERATOR H2 PURITY MIN GENERATOR H2 PURITY LIMIT GENERATOR H2 LOSS MAX DP BETWEEN SEAL OIL & H2 H2 PRESSURE MEASUREMENT AT H2 BOTTLE AT H2 CASING 1 2 3

GEN STATOR WINDING GEN STATOR CORE GEN ROTOR 66 % OF GENERATOR OUTPUT 0 M TG BLDG GASEOUS 10 200 BAR (g) 40 60 DM3/S AT STP OR 144 216 m3/h 51 m3 STEEL 3O DAY OPN & FILL GR TO 99%PURITY (MIN) 3 BAR (g) 98 % 90 % 12 M3 / 24 HRS AT STP 1.5 BAR

AT H2 PRESSURE REDUCERS AT H2 GAS DRIER CHAMBER H2 PURITY MEASUREMENT ELECTRICAL TYPE AT FILLING & RATED SPEED MECHANICAL TYPE AT RATED SPEED ONLY SAMPLING TYPE AS PER NEED

DEHYDRATING FILTER LOCATION MOISTURE ABSORBENT REACTIVATION TEMP ELECT PURITY MEASURE SYS SILICA GEL / BLUE GEL 120 C

3.1.6 HYDROGEN SYSTEM (CONTD) HYDROGEN COOLER TYPE OF HEAT EXCHANGER NO OF COOLERS NO OF ELEMENTS NO OF PASSES HYDROGEN PRESSURE GAS FLOW THRU EACH ELEMENT HEAT DISSIPATING CAP COLD GAS TEMP HOT GAS TEMP GAS PRESSURE DROP COOLING WATER FLOW WATER INLET TEMP WATER OUTLET TEMP WATER PRESSURE DROP H2 DRIER TYPE MOTOR RATING VOLTAGE / CURRENT SPEED TYPE OF ENCLOSURE VOLUME OF ABSORBENT MATERIAL HEATER RATING REGENERATION AIR FLOW RATE REACTIVATION SOURCE H2 REQUIREMENT (IF GEN AT REST) REPLACEMENT OF CO2 AT START UP-PRESSURISING OPERATION-LOSSES OPERATION-PURITY MEASURE RECOMMENDED STOCK H2 BOTTLE VOLUMES H2 BOTTLE 40 H2 BOTTLE 50 8.70 (BOLL+KIRCH) 2BH 4100-OAC22-Z (SIEMENS) 1.1 KW 415 V / 2.5 A 48.5 Hz IP 54 20 dm3 2.5 KW 70 m3/h @120mbar HOT AIR 2.5 x GEN VOL OP.PR(BAR) X GEN VOL 0.5 M3/HR AT STP 20 DM3/HR AT STP 2 x STARTING FILLING PRESSURISING VOLUME 150 BAR 200 BAR 6 M3 AT STP 10 M3 AT STP TUBE-WATER&SHELL-H2 CROSS FLOW TYPE 2 2 / COOLER 2 FOR WATER SIDE 3 BAR 9 M3 / S 818.5 KW / COOLER 42 C 62.3 C 26 mm WC 95 M3 / HR / ELEMENT 36 C MAX 43.5 C 4 mm WC

AND

3.1.7 CO2 SYSTEM LOCATION OF CO2 BOTTLES SERVICE BOTTLED CO2 PRESSURE TEMPERATURE VOLUMETRIC FLOW RATE BOTTLE MATERIAL CO2 PURITY CO2 FLASH EVAPORATOR MODE OF HEATING RATING VOLTAGE HEAT TRANSFER LIQUID VOLUME OF HEAT TRANSFER LIQUID RELIEF VALVE ON HI PR. SIDE RELIEF VALVE ON LO PR. SIDE CO2 HEATER TUBE MATERIAL CO2 PR AFTER EXP VESSEL CO2 REQUIREMENT START UP SHUT DOWN RECOM STOCK-START UP RECOM STOCK-OPERATION CO2 BOTTLE VOLUMES CO2 BOTTLE 40 CO2 BOTTLE 45 CO2 BOTTLE 66.7 COMPRESSED AIR SYSTEM SERVICE SOURCE PRESSURE VOLUMETRIC FLOW RATE OIL/HYDROCARBON PRESENT PARTICLE SIZE DEW POINT AT LINE PR DEHYDRATING FILTER LOCATION MOISTURE ABSORBENT REACTIVATION TEMP AIR REQUIREMENT SHUT DOWN COMPRESSED AIR FILTER TYPE VOLUME OF ACTIVATED CARBON SERVICE HOURS THROUGHPUT

0 M TG BLDG PURGING OUT AIR / H2 LIQUID 1 2.5 BAR 20 30 C 4060 DM3/S AT STP OR 144216 m3/h STEEL 99.7 %

ELECTRICAL 18 KW (6 x 3 KW) 240 V MARLOTHERM 25 dm 80 BAR 8 BAR COPPER 7 25 PSI (g)

2 X GEN VOL 2 X GEN VOL 6 X GEN VOL 4 X GEN VOL 15 M3 AT STP 17 M3 AT STP 25.2 M3 AT STP PURGE OUT CO2 FROM GEN STATION AIR SYSTEM 6 9 BAR 40 60 dm3/S AT STP OR 144 216 m3/h MAX 1ppm V/V OR W/W MAX 5 microns MAX 10 C ELECT PURITY MEASURE SYS SILICA GEL / BLUE GEL 120 C 3 X GEN VOL AH 13 dm3 1500 2000 HOURS (APPROX) 80 m3/h AT 8 BAR

3.2 H.T.TRANSFORMER 3.2.1 STATION TRANSFORMER MAKE REFERENCE STANDARDS YEAR OF MANUR SERVICE INSTALLATION WINDINGS UNIT NO LOAD VOLTAGE H.V/L.V1/LV2 LINE CURRENT HV/LV/SV TYPE OF COOLING RATED POWER AT VARIOUS COOLING METHODS (OFAF/ONAF / ONAN) FOR HV/ LV1 / LV2 FREQUENCY /PHASE CONNECTION TYPE H.V. /L.V1./L.V2. VECTOR GROUP REFERENCE IMPEDANCE VOLT. AT RATED CURRENT FOR PRINCIPAL TAPPING AT 75C a) HV LV b) LV SV c) HV SV TYPE OF TAP CHANGER RANGE OF TAPPING IMPULSE VOLTAGE WITHSTAND LEVEL a) HV WINDING b) LV WINDING c) SV WINDING POWER FREQUENCY WITHSTAND VOLTAGE FOR ONE MINUTE (SEPARATE SOURCE / INDUCED OVER VOLTAGE) a) HV WINDING b) LV WINDING c) SV WINDING NO LOAD LOSSES AT RATED FREQUENCY AND 100% RATED VOLTAGE 110% RATED VOLTAGE LOAD LOSSES AT NORMAL RATIO, RATED CURRENT AND 75C TEMP. RISE OIL / WINDING EFFICIENCY AT 75C AND U.P.F FOR a) 110% FULL LOAD b) 75% FULL LOAD c) 50% FULL LOAD VOLTAGE REGULATION AT FULL LOAD AT 75C AND AT a) UNITY POWER FACTOR b) 0.8 POWER FACTOR (LAGGING) EXTERNAL SHORT CIRCUIT WITHSTAND CAPACITY BHEL JHANSI IS : 2026 1997 CONTINUOUS OUTDOOR 3 3 PHASE UNIT 220/6.9/6.9 KV 66.69 / 435.69 / 2094.33 A OFAF /ONAF /ONAN 50/25/25 MVA 8.33 / 6.25 MVA 50HZ/3PHASE STAR / STAR/ STAR YNyn0 yn0 13 % + IS TOLERANCE 7.5% APPROX. 21 % APPROX. ON LOAD ON HV WINDING + 5% TO 15 % IN STEPS OF 1.25% 950 KVp 60 KVp 75 KVp

50 KV / 395 KV 20 KV / 2 * NORMAL VOLTS 28 KV / 2 * NORMAL VOLTS 23.5 KW (FIRM) 35 KW APPROX. 102 KW (FIRM) (EXCLUDING COOLER LOSSES OF 2.5 KW) 50C / 55C 99.501 % (APPROX.) 99.571 % (APPROX.) 99.610 % (APPROX.) 1.253 % (APPROX.) 8.642 % (APPROX.) 20,000 MVA FOR HV 500 MVA FOR LV & SV

3.2.1 STATION TRANSFORMER (CONTD) TERMINALS OF TERTIARY WINDING BROUGHT OUT TO BUSHING TYPE OF MAGNETIC CIRCUIT TPYE OF CORE JOINTS TYPE OF WINDING a) HV WINDING b) LV WINDING c) SV WINDING TYPE OF INSULATION a) HV WINDING b) LV WINDING c) SV WINDING d) CORE TO ADJACENT WINDING e) BETWEEN WINDINGS HV TERMINAL ARRANGEMENT a) CT DETAILS b) CLEARANCE BETW PHASES IN AIR c) CLEARANCE TO EARTH IN AIR LV TERMINAL ARRANGEMENT a) CLEARANCE BTW PHASES IN AIR b) CLEARANCE TO EARTH IN AIR SV TERMINAL ARRANGEMENT a) CLEARANCE BTW PHASES IN AIR b) CLEARANCE TO EARTH IN AIR NEUTRAL TERMINAL ARRANGEMENT a) BUSHING CT b) NCT DETAILS HV BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 S. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE LV BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 S. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE NEUTRAL BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 S. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE

YES CORE FULLY MITRED PARTIAL INTERLEAVED DISC HELICAL HELICAL PAPER+Press board+OIL PAPER+Press board+OIL PAPER+Press board+OIL Press board cylinder+OIL Press board cylinder+OIL BUSHING WITH CTs 2000 mm (MIN.) 1820 mm (MIN.) WITHOUT CT 280 mm (MIN) 140 mm (MIN) WITHOUT CT 280 mm (MIN) 140 mm (MIN) HV NEUTRAL WITH CT LV NEUTRAL WITHOUT CT 245 KV / 800 A (MAX) 1050 KVp 460 KV 7600 mm (MIN) 17.5 KV / 3150 A 95 KVp 38 KV RMS 280 mm (MIN) 36 KV / 630 A 170 KVp 70 KV 375 mm

3.2.1 STATION TRANSFORMER (CONTD) HV NEUTRAL BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 s. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE MAXIMUM FLUX DENSITY (EXCEPT IN YOKE BOLT PORTION) a) RATED VOLTAGE b) 110% OF RATED VOLTAGE MAXIMUM CURRENT DENSITY a) HV b) LV c) SV MAGNETISING CURRENT AT RATED VOLTAGE & FREQ (% OF F.L CURRENT) TANK COVER WHEELS PRESSURE WITHSTAND a) TANK b) RADIATORS & OTHER FITTINGS VACUUM WITHSTAND a) TANK b) RADIATORS & OTHER FITTINGS COOLING FANS a) TYPE / RATING b) QUANTITY On load tap changer Make Type Rated voltage Rated current Number of steps Step voltage Rated voltage of drive motor Rated voltage of control circuit Time to complete one tap changing operation APPROXIMATE WEIGHT OF a) CORE b) WINDING c) TANK, FITTINGS & COOLERS d) OIL e) TOTAL WEIGHT (WITHOUT OIL) f) UNTANKING WT (CORE & WINDING) g) SHIP WTOF HEAVIEST PACKAGE

36 KV / 630 A 170 KVp 70 KV 750 mm 1.70 Wb / M.Sq. 1.87 Wb / M.Sq. 2.3 A / mm.Sq. 2.0 A / mm.Sq. 3.5 A / mm.Sq. <0.5 % BELL SHAPED FLANGED /BI-DIRECTIONAL 0.35 + NORMAL HEAD (KSC) 0.35 + NORMAL HEAD (KSC) 760 mmHg 760 mmHg IMPELLER TYPE / 0.55 KW PER FAN 4 RUNNING + 1 STANDBY BHEL M-III 350-60/C-10193W 60 KV SUITABLE FOR NEUTRAL END OF 220 KV 77.28 A rated, 350 A max. 16 1.590 KV 415 v, 3 ph , 50 Hz 110 v ,1 ph, 50hz 5 sec for electrical operation. 16,800 KG 12,000 KG 8,500 KG 23,500 KG 57,500 KG 32,000 KG 49,000 KG

3.2.1 STATION TRANSFORMER(CONTD) TOTAL QTY OF INSULATING OIL a) OIL IN TANK, TURRET, BUSHINGS, OLTC & CONSERVATOR UP TO 30C b) OIL IN CONSERVATOR BTWN HIGHEST & LOWEST VISIBLE LVL c) OIL IN COOLING EQUIPMENT TANK DIMENSIONS a) LENGTH b) BREADTH c) HEIGHT DEGREE OF PROTECTION OF M. BOX DETAILS OF TANK & OTHER MATERIAL a) THICKNESS OF TANK SIDE PLATES b) THICKNESS OF TANK BOTTOM PLATE c) THICKNESS OF TANK COVER PLATE d) THICKNESS OF RADIATOR SHEET e) THICKNESS OF CORE SHEET STEEL f) MIN. CLEARANCE HT. FOR LIFTING CORE & WDG FROM TANK g) MIN. CLEARANCE HT. FOR LIFTING HV BUSHING FROM TANK COVER NEUTRAL GROUNDING TRANSFORMER MAKE KVA RATING VOLTAGE RATING RATED DUTY TYPE NEUTRAL GROUNDING RESISTOR RESISTANCE CURRENT RATED DUTY TAPS

26,000 LITRES 21,000 LITRES 1300 LITRES 3700 LITRES 5800 mm 2300 mm 3200 mm IP 55 8 mm 16 mm 25 mm 1.2 mm 0.27 mm 7000 mm FROM GROUND LEVEL 4500 mm ABOVE TANK COVER EASTERN ELECTRIC 75 KVA 4000 / 400V CONTINUOUS OUTDOOR OIL FILLED 1.95 OHM 210 AMP CONTINUOUS OFF CKT AT 25%, 50%, 75%

3.2.2 INSULATING OIL PROPERTIES REFERENCE STANDARDS APPEARANCE DENSITY AT 29.5C KINEMATIC VISCOCITY AT 27C (MAX.) INTERFACIAL TENSION AT 27C (MIN) FLASH POINT (MIN.) POUR POINT (MAX.) NEUTRALISATION VALUE (TOTAL ACIDITY) (MAX) CORROSIVE SULPHUR ELECTRIC STRENGTH (BREAKDOWN VOLTAGE) (MIN) DIELECTRIC DISSIPATION FACTOR (TAN DELTA) AT 90C (MAX) WATER CONTENT (MAX) SPECIFIC RESISTANCE (MIN) AT 90C AT 27C OXIDATION STABILITY a) NEUTRALISATION VALUE (MAX) b) TOTAL SLUDGE AFTER OXIDATION (MAX) AGEING CHARACTERISTICS AFTER ACCELERATED AGEING (OPEN BREAKER METHOD WITH COPPER CATALYST) A) RESISTIVITY (MIN) AT 90C AT 27C B) TAN DELTA AT 90C (MAX) C) TOTAL ACIDITY (MAX) D) SLUDGE CONTENT BY WEIGHT MAX) PRESENCE OF OXIDATION INHIBITOR

IS: 335 CLEAR, TRANSPARENT & FREE FROM SUSPENDED MATTER OR SEDIMENTS 0.89 gm / cc 27 Cst 0.04 N / m 140C -6C 0.03 mg / KOH / g NON-CORROSIVE 60 kV (RMS) 0.002 15 ppm 35 * 1012 ohm-cm 1500 * 1012 ohm-cm 0.4 mg / KOH / g 0.10% mg / KOH / g

0.2 * 1012 ohm-cm 2.5 * 1012 ohm-cm 0.2 0.05 mg / KOH / g 0.05 % NIL

3.2.3 UNIT AUXILIARY TRANSFORMER MAKE REFERENCE STANDARDS YEAR OF MANUFACTURE SERVICE INSTALLATION WINDINGS UNIT NO LOAD VOLTAGE H.V/L.V LINE CURRENT H.V. / L.V. TYPE OF COOLING RATING H.V PHASE / FREQUENCY TYPE OF CONNECTION H.V./L.V. VECTOR GROUP REFERENCE IMPEDANCE VOLTAGE AT RATED CURRENT FOR PRINCIPAL TAPPING AT 75C TYPE OF TAP CHANGER RANGE OF TAPPING IMPULSE VOLTAGE WITHSTAND LEVEL a) HV WINDING b) LV WINDING POWER FREQUENCY WITHSTAND VOLTAGE FOR ONE MINUTE a) HV WINDING b) LV WINDING NO LOAD LOSSES AT RATED FREQ. AND 100% RATED VOLTAGE 110% RATED VOLTAGE LOAD LOSSES AT NORMAL RATIO, RATED CURRENT AND 75C TEMP. RISE OIL / WINDING EFFICIENCY AT 75C AND U.P.F FOR a) 110% FULL LOAD b) 75% FULL LOAD c) 50% FULL LOAD VOLT. REGN. AT F.L AT 75C AND AT a) UNITY POWER FACTOR b) 0.8 POWER FACTOR (LAGGING) EXTERNAL SHORT CIRCUIT WITHSTAND CAPACITY TYPE OF MAGNETIC CIRCUIT TPYE OF CORE JOINTS TYPE OF WINDING a) HV WINDING b) LV WINDING TYPE OF INSULATION a) HV WINDING b) LV WINDING c) CORE TO ADJACENT WINDING d) BETWEEN WINDINGS HV TERMINAL ARRANGEMENT a) CLEARANCE BETW PHASES IN AIR b) CLEARANCE TO EARTH IN AIR

BHEL JHANSI IS : 2026 1996 CONTINUOUS OUTDOOR TWO 3 PHASE UNIT 20/6.9 KV 880.815/1340.370 AMP ONAN 16 M.V.A 3 PHASE / 50 HZ DELTA/STAR Dyn11 7.5 % + IS TOLERANCE OFF CIRCUIT ON HV WINDING +/- 5% IN STEPS OF 2.5% 75 KVp 60 KVp 28 KV 20 KV 15.50 KW 23.52 KW 68.0 KW 50C / 55C 99.48 99.55 99.60 0.705 % 4.997 % 1000 MVA CORE FULLY MITRED DISC HELICAL PAPER+Press board+OIL PAPER+Press board+OIL Press board cylinder+OIL Press board cylinder+OIL BUSHING WITHOUT CTs 280 mm 140 mm

3.2.3 UNIT AUXILIARY TRANSFORMER(CONTD) LV TERMINAL ARRANGEMENT a) CT DETAILS (RATIO, ACC. CL, VA, TYPE b) CLEARANCE BTW PHASES IN AIR c) CLEARANCE TO EARTH IN AIR NEUTRAL TERMINAL ARRANGEMENT HV BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 s. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE LV BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 s. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE NEUTRAL BUSHINGS a) RATED VOLTAGE CLASS / CURRENT b) 1.2 / 50 s. IMPULSE WITHSTAND c) 1 MIN POWER FREQUENCY WITHSTAND (DRY & WET) VOLTAGE d) MIN. CREEPAGE DISTANCE MAXIMUM FLUX DENSITY a) RATED VOLTAGE b) 110% OF RATED VOLTAGE MAXIMUM CURRENT DENSITY a) HV b) LV MAGNETISING CURRENT AT RATED VOLTAGE & FREQ (% OF F.L CURRENT) TANK COVER PRESSURE WITHSTAND * a) TANK b) RADIATORS & OTHER FITTINGS APPROXIMATE WEIGHT OF a) CORE & WINDING b) TANK, FITTINGS & COOLERS c) OIL d) TOTAL WEIGHT (WITHOUT OIL) e) UNTANKING WT (CORE & WDG) TOTAL QTY OF INSULATING OIL TRANS PORT WT TANK DIMENSIONS a) LENGTH b) BREADTH c) HEIGHT DEGREE OF PROTECTION OF M. BOX

WTI CT PROVIDED 1340.37 / 2.7 2.5 2.3 2.1, 10VA, RING 280 mm 140 mm BUSHING WITHOUT CT 17.5 KV / 1000 A 95 KVp 38 KV 25 mm 17.5 KV / 2000 A 95 KVp 38 KV 25 mm 17.5 KV / 1000 A 95 KVp 38 KV 25 mm 1.70 Wb / M.Sq. 1.87 Wb / M.Sq. 2.5 A / mm.Sq. 2.5 A / mm.Sq. <0.5 % CONVENTIONAL 760 mmHg 760 mmHg * TESTED FOR 735 mmHg AS PER CBIP SPEC., CL.NO. 17.3.2 15,500 KG 13,325 KG 16,890 KG 42,970 KG 16,890 KG 19,940 LITRES 32932 K.G. 2800 mm 1600 mm 2490 mm IP 55

3.2.3 UNIT AUXILIARY TRANSFORMER(CONTD) DETAILS OF TANK & OTHER MATERIAL a) THICKNESS OF TANK SIDE PLATES b) THICKNESS OF TANK BOTTOM PLATE c) THICKNESS OF TANK COVER PLATE d) THICKNESS OF RADIATOR SHEET e) THICKNESS OF CORE SHEET STEEL f) MIN. CLEARANCE HT. FOR LIFTING CORE & WDG FROM TANK g) MIN. CLEARANCE HT. FOR LIFTING HV BUSHING FROM TANK COVER NEUTRAL GROUNDING TRANSFORMER MAKE KVA RATING VOLTAGE RATING RATED DUTY TYPE NEUTRAL GROUNDING RESISTOR RESISTANCE CURRENT RATED DUTY TAPS 8 mm 14 mm 16 mm 1.25 mm 0.27 mm 6600 mm 5600 mm EASTERN ELECTRIC 40 KVA 4000 / 400V CONTINUOUS OUTDOOR OIL FILLED 3.9 OHM 105 AMP CONTINUOUS OFF CKT AT 25%, 50%, 75%

3.2.4 a) GENERATOR TRANSFORMER DESCRIPTION Manufacturer REFERENCE STANDARDS YEAR OF MANUFACTURE Service Installation Type Of Transformer UNIT No Of Winding No Of Phase Rated No Load Voltage A)HV Winding B)LV Winding Type Of Cooling Rated Power at various cooling method A)ONAN B)ONAF C)OFAF Rated Frequency Winding Connection HV Winding LV Winding VECTOR GROUP REFERENCE Impedance voltage at rated current For the principal tapping at 750c HV- LV Type of tap changer On which winding Total range of tapping Size of tapping step OLTC details a)operation b)type of control c)Remote tap position indicator included IMPULSE VOLTAGE WITHSTAND LEVEL a) HV WINDING b) LV WINDING POWER FREQUENCY WITHSTAND VOLTAGE FOR ONE MINUTE a) HV WINDING b) LV WINDING NO LOAD LOSSES AT RATED FREQUENCY AND 100% RATED VOLTAGE 110% RATED VOLTAGE LOAD LOSSES AT NORMAL RATIO, RATED CURRENT AND 75C Guaranteed max temp rise of a)Oil by thermometer b)winding by resistance for ONAN/ONAF/OFAF

PARTICULARS BHEL Jhansi IS : 2026 PT.I,II, III & IV 1996 Continuous Out Door Generator 3 PHASE UNIT Two Three 230kv 10.5kv ONAN/ONAF/OFAF 97.8 MVA 130.4 MVA 163.0 MVA 50 Hz Star Delta YNd1 12.5% 10% On load HV +5% to 15% 1.25% Automatic/parallel Remote/local Yes 1) Digital for control desk 2) 4 to 70mA out for CRT 950 KVp 75 KVp 50,395 KV ABOVE EARTH 28 KV 91.0 KW (FIRM) 140 KW (APPROX) 475 KW (FIRM) EXCLUDING AUX. COOLER LOSS OF 21 KW APPROX. 500c 550c

3.2.4 a) GENERATOR TRANSFORMER (CONTD.) EFFICIENCY AT 750c & unity power factor for a) 110% full load b) 75% full load 99.65% c) 50% full load 99.70% 99.74% Voltage regulation at full at 750c and at a) Unity power factor 1.01% b) At 0.8 power factor (lagging) 8.17% External short circuit with stand capacity 20000MVA as per IS: 2026 Pt. -I Type of Magnetic Circuit Core Type of core joints Fully mitred Type of winding a) HV Partially interleaved b) LV Helical Type of insulation a) HV winding Paper + press bd + oil b) LV winding Paper + press bd + oil c) Core top adjacent winding Press bd + oil Between winding Press bd + oil HV terminal arrangement Bushing with CT 245 kV, 800 A CT details (Ratio, Acc, C1, VA, type) 500/1 A, PS, Vk > 300 V, Ie = 15mA at Vk/2 Clearance between phases in air 2100 mm Clearance to earth in air 1900 LV terminal arrangement Isolated phase bus duct Bushing with CT Porcelain with CT Clearance between phases in air 280 mm Clearance to earth in air 140 mm Neutral terminal arrangement Bushing with CT Porcelain with CT NCT details (Ratio, Acc, C1, VA, type) Core 1: 500/1 A, PS, VK > 300 V, Ie = 15mA at Vk Core 2: 500/1,5P20, 20V HV bushing Rated voltage class 245KV Rated current 800 A 1.2/50 micro sec impulse withstand 1050 KVp 1-minute P.F withstand (dry & wet) voltage 460 KV Min. creepage distance 7600 mm LV bushing Rated voltage class 24KV Rated current 10,000 A 1.2/50 micro sec impulse withstand 125 KVp 1-minute P.F withstand (dry & wet) voltage 50 KV Min. creepage distance 375 mm

3.2.4 a) GENERATOR TRANSFORMER (CONTD.) Neutral bushing Rated voltage class 36KV Rated current 630 A 1.2/50 micro sec impulse withstand 170 KVp 1-minute P.F withstand (dry & wet) voltage 70 KV Min. creepage distance 750 mm At rated voltage Maximum flux density 1.7 wb/m.sq. At 110% rated voltage Max. flux density 1.87 wb/m.sq. HV Max. current density 3.5 amp / mm.sq. HV tap Max. current density 3.8 amp / mm.sq. L V Max. current density 3.5 amp / mm.sq. Magnetising current at normal voltage & < 0.5 % frequency(%of full load current) Tank cover bell shaped DEGREE OF PROTECTION OF M. BOX IP 55 Wheels Flanged, bi-directional Pressure withstand Tank 0.35+normal head KSC Radiators & other fittings 0.35+normal head KSC. Conservator without air cell 0.175 kg/cm.sq. Vacuum withstand Tank 760 mm of Hg Radiators & other fittings 760 mm of Hg Cooling fans Type Impeller Quantity 3(6+1)= 21 total including 3 no. spare Rating 1.2 Kw each Cooling oil pumps Quantity 3(1+1)=6 no. Rating 2 Kw On load tap changer Make BHEL Type M-III 600-110/C-10139W Rated voltage 110 KV Rated current 482 A rated, 600 A max. Number of steps 16 Step voltage 1.660 KV Rated voltage of drive motor 415 v, 3 ph , 50 Hz Rated voltage of control circuit 110 v ,1 ph, 50hz Time to complete one tap changing operation 6 sec- for electrical operation. APPROXIMATE WEIGHT OF a) CORE & WINDING 92,800 KG b) TANK, FITTINGS & COOLERS 62,020 KG c) OIL 44,880 KG d) TOTAL WEIGHT (WITHOUT OIL) 154,820 KG e) UNTANKING WT (CORE & WINDING) 13,000 KG f) SHIP WT OF HEAVIEST PACKAGE 111,100 KG Quantity of insulation oil 50,430 litres Oil in tank turret ,bushings, OLTC and 37,605 litres conservator upto 30 deg c. Oil in cooling equipment 12,825 litres

3.2.4 a) GENERATOR TRANSFORMER (CONTD.) Tank Dimensions Length Breadth Height DETAILS OF TANK & OTHER MATERIAL a) THICKNESS OF TANK SIDE PLATES b) THICKNESS OF TANK BOTTOM PLATE c) THICKNESS OF TANK COVER PLATE d) THICKNESS OF RADIATOR SHEET e) THICKNESS OF CORE SHEET STEEL f) MIN. CLEARANCE HT. FOR LIFTING CORE & WDG FROM TANK g) MIN. CLEARANCE HT. FOR LIFTING HV BUSHING FROM TANK COVER 3.2.4 b) GENERATOR TRANSFORMER DESCRIPTION Manufacturer REFERENCE STANDARDS YEAR OF MANUFACTURE Service Installation Type Of Transformer UNIT No Of Winding No Of Phase Rated No Load Voltage A)HV Winding B)LV Winding Type Of Cooling CAPACITY CURRENT HV/LV CUARANTEED TEMP RISE OIL /WDG BIL (KVp) HV/LV CONNECTION & SYMBOL NEUTRAL GROUNDING TYPE OF CONSERVATOR TYPE OF TANK TYPE OF TAP CHANGER LOCATION OF TAP CHANGER TYPE OF BUSHING HV LV HV-N TOTAL OIL UNTANKING MASS CORE COIL UNTANKING MASS BELL TOTAL MASS TAP CHANGER MAKE TYPE

6300 mm 2610 mm 3330 mm 8 mm 16 mm 20 mm 1.25 mm 0.27 mm 9500 mm 10500 mm

PARTICULARS CGL IS : 2026 PT.I,II, III & IV 2001 Continuous Out Door Generator 3 PHASE UNIT Two Three 230kv 10.5kv ONAN/ONAF/OFAF 97.8/130.4/163 MVA 407.1A /8962.6A 50C / 55C 950/75 STAR/DELTA Ynd1 HV SOLIDLY EARTHED COPS Air cell inside the conservator BELL ON LOAD, MAKE: BHEL M III 500 Y 60-C 10.19.3W IN-TANK 245 KV / 800 A CONDENSER TYPE 24 KV / 10 KA High Current Bushing 36 KV / 630 A PORCELAIN TYPE 50000 kg 85000 kg 12000 kg 178000 kg BHEL M III 600

3.3 SWITCHYARD PARAMETERS 3.3.1 GENERAL DETAILS Operating voltage Basic impulse Rated current Abort time current & duration Dynamic rating Minimum clearance 1- phase to phase 2- phase to earth 3- live point to ground 4- section clearance Conductor Shield wire Insulator String 1. Type 2. Total Creepage Distance 3 Electromechanical Strength 4.Voltage Class 5. Impulse withstand of string (KV) 6. Number per string Withstand Voltage one min. power frequency (dry) one min. power frequency (wet) 1.2/50 microsec. impulse (dry) 1.2/50 microsec. impulse (wet) Maximum design tension at 16 0 c for conductor -All bay buses in the switch yard Circuit conductors for GT & ST bays. Interconnection conductors to steel plant s/y Shield wire Bus post insulator. type Ultimate cantilever strength Total creep distance Voltage class Withstand voltage . One min. power frequency (dry) One min. power frequency (wet) 1.2/50 micro sec. Impulse(dry) 1.2/50 micro sec. Impulse(wet) Normal 220 kv Highest-- 245kv 1050 peak 1600 amps 40ka for 1 sec. 100 ka peak 2100 mm 2100 mm 5500 mm 5000 mm Normal 400 kv Highest-- 420kv 1425 peak 2000 amps 40ka for 1 sec. 150 ka peak 4100 mm 3500 mm 8000 mm 6500 mm

Anti Fog type 31 mm/KV 1050 13 Suspension / 14 tension.

Anti Fog type 31 mm/KV 1550 23 Suspension / 25 tension.

31 mm/ KV

31 mm/ KV

3.3.2 ISOLATOR Application Type of break Voltage Frequency Rated current for site conditions Short time current Rated peak short circuit current Insulation level Phase spacing Operating device Creepage distance Minimum cantilever strength Aux. Supply l Interlocks with circuit breaker 3.3.3 SF6 CIRCUIT BREAKER

OUT DOOR S/Y 220 KV Single break, centre break 245 KV 50 Hz 1600 A 40 KA for 1 second 1050 KVP Manual and Motor driven 31 mm/ KV 600 Kg 220v, D.C for control and interlock; 415v A.C, 3 phase for motor drive. Bolt interlock and Electrical Interlock

OUT DOOR S/Y 400 KV pantograph 420 KV 50 Hz 2000 A 40 KA for 1 second 1425 KVP Manual and Motor driven 31 mm/ KV 800 Kg 220v, D.C for control and interlock; 415v A.C, 3 phase for motor drive. Bolt interlock and Electrical Interlock

Type Make QUANTITY Rated Voltage Rated current Short circuit breaking current & duration Making current Operating duty First pole clear factor Impulse with stand voltage One minute power frequency withstand voltage Line charging current breaking Cable charging current breaking Over voltage factor while switching off above currents Type of operating mechanism Operating mechanism to be suitable for Control voltage Pole No. of trip coils per pole Phase to phase phasing Insulation level Minimum cantilever strength Creepage distance Total break time (Max) Total make time (Max) SF6 Gas pressure nominal Pneumatic air pr. trip Blocking Pneumatic air pr. Blocking Pneumatic air pressure low alarm

SF6 outdoor 220 KV

SF6 outdoor 400 KV

245 KV 1600 A 40KA for 1 sec. 100 kAp 0-0.3 Sec-CO-3 min CO

420 KV 2000 A 40KA for 1 sec. 100 kAp 0-0.3 Sec-CO-3 min CO

220V DC Single

220V DC Single

1050 KVP 600 Kg 31 mm/ KV 60 milli secs 100 milli Secs.

1425 KVP 800 Kg 31 mm/ KV 40 milli secs 150 milli Secs.

SF6 Gas pressure low alarm SF6 Gas pressure blocking Pneumatic air pressure

3.3.4 CURRENT TRANSFORMER Type Make Nominal voltage & frequency Highest system voltage No of cores Generator transformer bay STN. Transformer bay Short time thermal rating Dynamic rating Class of insulation Impulse with stand voltage KVP One min. power frequency with stand Creepage distance Applicable Standards Insulating oil 3.3.5 CAPACITOR VOLTAGE TRANSFORMER Application Nominal/highest voltage/frequency Coefficient of Earthing Rated pr. Voltage Rated sec. Voltage No. of sec. Wdg. Accuracy class Rated voltage factor Class of wdg . insulation Rated capacitance HF capacitance Pr. Capacitance Sec. Capacitance Voltage factor Burden High frequency range Minimum cantilever strength 1.2/50 micro sec impulse with stand voltage 1 min. power freq. With stand vol. Method of connection 3.3.6 LIGHTNING ARRESTER MAKE Type Nominal Rated arrester voltage/operating voltage Nominal discharge. Current of 8/20 micro sec. Impulse current withstand Duty cycle High current short duration 4/10 micro wave Residual volts corresponding to steep current impulse Lightning impulse Switching impulse Min. symmetrical fault current

Outdoor, Oil filled hermetically sealed 220 KV 220 KV & 50 Hz 245 KV

Outdoor, Oil filled hermetically sealed 400 KV 400 KV & 50 Hz 420 KV

40 ka for 1 sec. 100 KAp 1050 KVp 31 mm/ KV

40 ka for 1 sec. 100 KAp 1425 KVp 31 mm/ KV

Out door 220/245kv/50 Hz 220kv/3 110v / 3, 110v / 3

Out door 400/420kv/50 Hz 400kv/3 110v / 3, 110v / 3

1. 2 continuous & 1.5 for 30s. Oil immersed class A

1. 2 continuous & 1.5 for 30s. Oil immersed class A

600 Kg 1050 kv Star/Star/open Delta

800 Kg 1425kv Star/Star/Star

220 KV Out door gapless 220 KV 198kv 10 kA Class 3

400 KV Out door gapless 400 KV 360 KV 20 kA Class 4

40 ka

40 ka

3.4 220KV MAIN STEP DOWN STATION NUMBER OF BAYS KPTCL LINE BAYS JSWSL CPP-2 LINE BAY BUS COUPLER BAY BUS TRANSFER BAY TRANSFORMER BAYS 11 NOS 2 NOS 1 NO 1 NO 1 NO 6 NOS ABB E L F SL 4-1 11 NOS 245 KV 2000 A 50 HZ 1050KV 40 KA 40KA/ 3 SEC 125A O-0.3S-CO-3MIN-CO 1.3 7 BAR 6.2 / 6.0 BAR 220 VDC 240 VAC 22 BAR 18 BAR 17.3/16.7/19 BAR 17.5/16.9/19.2 BAR 19.5 / 20.5 BAR ELGI 2NOS/ 240V, 1PHASE, 50 HZ

3.4.1 SF6 CIRCUIT BREAKER MAKE TYPE QUANTITY RATED VOLTAGE RATED CURRENT FREQUENCY LIGHTING IMPULSE WITHSTAND VOLTAGE SHORT CIRCUIT BREAKING CURRENT S.C WITHSTANDING CURRENT/DURATION LINE CHARGING BREAKING CURRENT OPERATING SEQUENCE FIRST POLE TO CLEAR FACTOR SF6 GAS PR AT 20 DEGREE C (ABS) ALARM / BLOCKING PR (SF6) CLOSING & OPENING DEVICE SUPPLY VOLTAGE AUX CIRCUIT SUPPLY VOLTAGE AIR PR ALARM PR FOR AIR BLOCKING PR FOR CLOSE/TRIP/RECLOSE (AIR) DE-BLOCKING PR. FOR CLOSE / TRIP / RECLOSE (AIR) COMPRESSOR START / STOP COMPRESSOR MAKE RECEIVER QUANTITY/ CAPACITY/BAY HEATER SUPPLY 3.4.2 ISOLATOR MAKE TYPE MECHANISM RATED VOLTAGE RATED CURRENT CONTROL SUPPLY MOTOR VOLTAGE MOTOR HP DEGREE OF PROTECTION 3.4.3 EARTH SWITCH MAKE TYPE MECHANISM RATED VOLTAGE BIL WT

AMEI POWER LTD DOUBLE BREAK MOTOR OPERATED 245 KV 2000A 220V DC 415V AC, 3 PHASE 0.5 IP 55

ELPRO HCB MANUAL 245 KV 1050 KVp 200 KG

3.4.4 LIGHTNING / SURGE ARRESTOR MAKE DESIGNATION Rated arrester voltage/operating voltage NOMINAL DISCHARGE CURRENT LINE DISCHARGE CLASS MAX RESIDUAL VOLTAGE KV CREST AT 10KA REF CURRENT REF VOLTAGE KV RMS/PK PARTIAL DISCHARGE AT COVX 1. 05 KV RMS SPECIFICATION REFERRED SURGE MONITOR TYPE / MAKE 3.4.5 CURRENT TRANSFORMER MAKE TYPE RATED TRANSFORMATION RATIO RATED / HIGHEST SYSTEM VOLTAGE S.C RATING NO. OF CORES CORE DETAILS CORE NO 1 2 3 BURDEN (VA) * * 75 ACC CLASS PS PS 0. 5 ALF/ISF * * 10-5-5 KPV(VOLTS) 2000-1000-625 * LeXe@VK(ma) * 15-30-50 Rsec @75 C * 8-4-2.5 3.4.6 CAPACITOR VOLTAGE TRANSFORMER MAKE TYPE RATED TRANSFORMATION RATIO RATED / HIGHEST SYSTEM VOLTAGE 1a 1n RATED OUTPUT 150 ACC CLASS 3P THERMAL OP TOTAL SIM. BURDEN / CLASS FREQUENCY EQU CAPACITANCE OF COUPLING CAPACITOR INSULATION LEVEL TOTAL WEIGHT

WS INDUSTRIES SMX 198kv/168 kv 10 KA (crest) 3 550 3 mA (peak) 218 KV (MIN) 50 pC (MAX) IEC 99-4 03/WS INDUSTRIES

CROMPTON GREAVES IOSK 1600 800 500 / 1 A 220 / 245 KV 40 KA / 1SEC 6 NO 4 5 * * PS PS * * 2000-1000-625 15-30-50 8-4-2.5 6 40 0. 5 10-5-5 * * *

CROMPTON GREAVES CVE 245 //1050 / 50 (220000/ 3)/ (110/3) 220 / 245 KV 2a 2n 3a 3n 4a 4n 200 100 400 0. 5 3P 0.5 750 VA 400 VA / 0.5 50 HZ 8800 pF +10%, -5% 220/460/1050 KV 685 +/- 10% Kg

3.4.7 80 MVA TRANSFORMERS MAKE QUANTITY MVA COOLING MVA HV/LV1/LV2 RATED VOLTAGE KV RATED CURRENT A BIL (KVP) NO OF PHASES FREQUENCY VECTOR GROUP TAPPING TEMP RISE WINDING TEMP TEMP RISE OIL TEMP TOTAL OIL NO LOAD LOSS LOAD LOSS AUX LOSS SHORT TIME RATING OLTC MAKE TYPE SUPPLY VOLTAGE CONTROL VOLTAGE FOR 1 TAP CHANGE COOLING PUMP MAKE TYPE RPM DUTY VOLTAGE CLASS HEDA HP/ KW CURRENT

CROMPTON GREAVES 2 NOS 50/63/80 ONAN/ONAF/OFAF 80/40/40 HV LV1 LV2 220 34.5 34.5 209.90 669.40 669.40 950 170 170 3 50 YNd11d11 Tap From 5% To -20% In Steps Of 1.25%On Hv 50 40 33700 LTS 63620W 153190W 7880W 5SEC MR, GERMANY D111400Y60/60 12.23.3W 415 V ,50 HZ , 1 PHASE 110 V AC 33 REV CGL IL 3A 1425 S1 415,50 HZ , 1 PHASE F 3 2 / 1. 5 3.2

3.4.8 50 MVA TRANSFORMERS Make TYPE STANDARD TYPE OF COOLING RATED MVA HV / LV RATED VOLTAGE AT NO LOAD HV/LV RATED CURRENT HV/LV VECTOR GROUP PHASES MAX AMBIENT TEMP TOP OIL TEMP RISE WINDING TEMP RISE SYMMETRICAL S.C CURRENT MAX SHORT CIRCUIT DURATION INSULATION LEVEL HV LV KV 395 28 KVP 950 75 INSULATING OIL 31,820 LTS RATIO ACC BURDEN HVN 200/1 5P20 15 (2 CORE) 200/1 PS * LVN 3000/1 PS * (2CORE) 400/1 5P15 * LV 1312/1 0.5 15 OLTC

NGEF ONTR 50000/220E IS 2026 ONAN 50/50 220/11 KV 131.2 / 2624.3 A YNyn0d11 3 50 C 40 C 50 C 7.87* In 5 SEC HV NEU LV NEU 38 28 95 75 VK * >=300 >=600 * * RCT@75C * * <=2 <=2 * NGEF

STAB.WG 20 60

PROTECTION BACK UP E/F REF REF BACK UP E/F LDC

3.4.9a) 130 MVA TRANSFORMER STANDARDS APPLICABLE MAKE YEAR OF MANUFACTURE MVA HV/LV1/LV2 COOLING TYPE OF COOLING MVA HV MVA IV MVA LV RATED VOLTAGE KV RATED CURRENT A BIL (KVP) NO OF PHASES FREQUENCY VECTOR GROUP NO. OF TAPS TAPPING TEMP RISE WINDING TEMP TEMP RISE OIL TEMP WT OF CORE & WDG WT OF BELL TANK TOTAL OIL TOTAL MASS NO LOAD CURRENT NO LOAD LOSS LOAD LOSS AT PRINCIPAL TAP AND 75C % IMPEDANCE AT PRINCIPAL TAP AND 75C HV-IV HV-LV IV-LV REGULATION AT U.P.F EFFICIENCY AT U.P.F RESISTANCE / PHASE @ 75C (HV / IV/ LV) OHMS FANS RATING PUMPS RATING NOISE LEVEL OLTC MAKE TYPE TRANSITION RESISTANCE MOTOR

IS 2026 CROMPTON GREAVES 2003 130 / 80 / 50 OFAF/ONAF/ONAN ONAN ONAF OFAF 82.5 102.375 130 50 63 80 31.25 39.375 50 HV IV LV 220 34.5 11.5 341.162 1338.8 2510.3 950 170 95 3 50 Ynd11yn0 21 +10% To -15% In Steps Of 1.25%On HV 50C 40C 96800 kg 18400 kg 57300 kg 207000 kg 1 % OF F.L.C (I.S TOL.) 68 KW 380 KW AT TAP-9 (MAX)

15.46% 30.15% 47.11% 0.388 99.85 0.49701 / 0.03229 / 0.00394 10 NO.S 700 W 4 NO.S 3.72 KW 89 dB EASUN M III 600 Y 72.5 / C 12.23.3W 5.1 OHMS 12.23 KW

3.4.9b) 130 MVA TRANSFORMER STANDARDS APPLICABLE MAKE YEAR OF MANUFACTURE MVA HV/LV1/LV2 COOLING TYPE OF COOLING MVA HV MVA LV1 MVA LV2 RATED CURRENT HV RATED CURRENT LV1 & LV2 RATED VOLTAGE KV BIL (KVP) AC (P.F) (KVP) NO OF PHASES FREQUENCY VECTOR GROUP NO. OF TAPS TAPPING TEMP RISE WINDING TEMP TEMP RISE OIL TEMP WT OF CORE & WDG WT OF TANK & FITTINGS WT / QTY OF OIL TOTAL MASS TRANSPORT WT (GAS FILLED) NO LOAD LOSS LOAD LOSS AT NOMINAL TAP % IMPEDANCE AT PRINCIPAL TAP AND 75C HV-LV1 & HV-LV2 LV1-LV2 HV-LV1+LV2 RESISTANCE / PHASE @ 75C (HV / LV1/ LV2) OHMS FANS RATING PUMPS RATING NOISE LEVEL OLTC MAKE TYPE

IS 2026 ABB 2005 130 / 102.2 / 81.25 OFAF/ONAF/ONAN ONAN ONAF OFAF 81.25 102.2 130 40.625 51.367 65 40.625 51.367 65 213.23 269.52 341.16 679.93 859.67 1087.76 HV LV1 LV2 240 34.5 34.5 950 170 170 395 70 70 3 50 Ynd11d11 21 +5% To -20% In Steps Of 1.25%On HV neutral 50C 40C 87000 kg 57500 kg 50900 kg / 57200 LTS 195400 kg 108700 KG 68.5 KW at TAP-5 305 KW AT TAP-5 8% 15% 9.2% 0.4603 / 0.0455 / 0.0451 16 NO.S 410 W, 1400 RPM, 415 V 4 NO.S 1.1 KW, 800 RPM, 415 V 69 dB EASUN-MR M III 600 123 / C 10.23.3W

3.4.10 NGT NO OF PHASE MAKE TYPE STANDARD FREQUENCY RATED NO LOAD VOLTAGE HV/ LV RATED CURRENT HV/ LV RATED KVA POWER FREQ TEST VOLTS HV/ LV IMPULSE VOLTAGE TYPE OF COOLING VECTOR GROUP MAX AMB /TOP OIL /Wdg TEMP IMPEDANCE VOLTAGE AT 500 KVA UNTANKING MASS TOTAL MASS TRANSPORT MASS VOLUME OF OIL NCT HV LV ZERO SEQUENCE IMPEDANCE / PHASE EARTH FAULT CURRENT 3.4.11 ABT METERS MAKE TYPE CLASS APPLICABLE STANDARDS SUPPLY VOLTAGE PF REF TEMP CT RATIO PT RATIO PULSE RATE MF

3 NGEF 0NTU-PT 500/33 IS:2026/IS:3151 50Hz 33 KV / 433 V 8.75A/666.7 A 500 70 KV / 3 KVRMS 170 KVP ONAN ZN Yn11 45 /45 /55 oC 33 KV /433 Vbase 8.75 T 15.2 T 14.0 T 4045 Lts 50 /1-1-1 A, 15 VA 3 core 500 / 5 A ,800 /5 A ,15 VA 2 Core 4.8 OHMS 7000 A FOR 5 SEC IN NEUTRAL

L & T WITH ABT FEATURES ER 300P-PRIDE ELECTRONIC TRIVECTOR METER 0.2S IEC 687 3, 4WIRE/110V/1A/ 50 HZ +1 TO 1 23 C 600/1A 220 kV /110 V 50,000/UNIT 1200000

3.5 SWITCH GEAR SYSTEM 3.5.1 SWITCH GEAR 6.6 KV NOMINAL VOLTAGE PHASE AND FREQUENCY SYS NEUTRAL EARTHING MAX. SYSTEM VOLTAGE ONE MINUTE POWER FREQUENCY WITH STAND VOLTAGE 1.2 / 50 MICRO SEC IMPULSE WITHSTAND VOLTAGE MAX TEMPERATURE OF BUS BAR , DROPPERS, CONNECTORS & CONTACTS AT CONTINUOUS CURRENT RATING UNDER SITE REF. AMBIENT TEMPERATURE MATERIAL OF BUS BARS DEGREE OF PROTECTION MATERIAL OF EARTHING BUS CLEARANCE IN AIR OF LIVE PARTS VACUUM BREAKER APPLICABLE STANDARDS TYPE RATED VOLTAGE RATED NORMAL CURRENT RATED FREQUENCY RATED SHORT CIRCUIT BREAKING CURRENT RATED SHORT CIRCUIT MAKING CURRENT RATED SHORT TIME WITH STAND CURRENT RATED DURATION OF S.C RATED OPERATING TIME RATED BREAK TIME RATED CLOSING TIME RATED OPERATING SEQUENCE RATED IMPULSE WITH STAND VOLTAGE RATED 1 MIN P.F WITHSTAND VOLTAGE AUXILIARY CONTROL SUPPLY FOR A. CLOSE/ TRIP COIL/ SPRING CHARGE B. SPACE HEATER & LIGHTING TRIP FREE OPERATING MECHANISM TYPE

6.6KV 3PH, 50HZ NON EFFECTIVELY EARTHED 7.2 kV 27 kV rms 60 kV peak 85 C

COPPER BUS BAR -IPH 4 OTHERS IPH 6 GALV STEEL PHASE TO PHASE 127 mm PHASE TO EARTH -77mm INDOOR METALCLAD IS 13118 & IS 3427 IEC 298 , & IEC 56 VM 12 7.2 k v 630/1250/2500 A 50 Hz 40 kA rms 100 kA peak 40 kA rms 1 TO 3 sec 60+/- 5 ms 80 +/- 5 ms 75 +/- 5ms O - 0.3 sec CO 3min CO 75 kv peak 28/35 kv rms 220 V DC 240V, 1PH MOTOR CHARGED SPRING MANUAL TRIP AND CLOSE FACILITY IS PROVIDED

3.5.1 SWITCH GEAR 6.6 KV(CONTD) INCOMER TO 6.6KV STATION SWGR RATING 2500AMPS BUS DUCT 2500 AMPS CT DETAILS RATIO CORE-I O/P CLASS CORE-II O/P CLASS CORE-III O/P CLASS AUX VOLTAGE DETAILS RATIO O/P CLASS AMMETER SCALE BUS PT 6.6KV STN SWGR VT DETAILS RATIO SEC O/P ACCURAC AUX VT DETAILS VOLT METER SCALE FEEDER PT VT DETAILS RATIO SEC O/P ACCURAC AUX VT DETAILS VOLT METER SCALE TIE TO UNIT BOARD RATING CT DETAILS

2500/1-1-1A 10VA 5P20 20VA 1ISF<5 VK>= <TORCT+180>V IE<= 30 mA AT VK/2 PS 400/110V 35VA 0.5/3P 0-2500AMPS 6600 V / 110 V / 3 3 100 VA, 0.5/3P 50 VA, .3P RATIO O /P CLASS 0 8 KV 6600 V / 110 V / 3 3 100 VA, 0.5/3P RATIO O /P CLASS 0 8 KV 110 V 3 110 V / 110 V 10 VA, .5

110 V 3 110 V / 110 V 10 VA, 0.5

1250A RATIO 1200 / 1 1A O/P CORE I 10 VA , 5P20 CLASS CORE II 20 VA , ISF < 5 AMMETER SCALE 0-1200A MOTOR FEEDER ( C.W PUMP 1350 Kw ) RATING 630 A CT DETAILS RATIO 200/1-1A CORE-I O/P CLASS 15VA 5P20 CORE-II O/P CLASS 20VA 1ISF<5 CORE-IIIO/P CLASS VK >= (25 + 15 RCT) IE<= 30 ma AT VK/2 PS DIFF. CT RATIO 200/1A DETAILS O/P CLASS VK >= (25 + 15 RCT) IE<= 30 ma AT VK/2 PS AMMETER SCALE 0-200/1200A

3.5.1 SWITCH GEAR 6.6 KV(CONTD) UNIT INCOMER, TIE WITH STATION RATING 1250AMPS CT DETAILS RATIO CORE-I O/P CLASS CORE-II O/P CLASS AUX RATIO VOLTAGE O/P DETAILS CLASS AMMETER SCALE DIFF CT DETAILS IF 1A CORE 1 RATIO CORE II RATIO

1200/1-1A 10VA 5P20 20VA 1 ISF<5 400/110V 35VA 0.5/3P 0-1200AMPS 1200/1A , CALLS PS VK >= 70RCT + 180 V IE <= 30 ma AT VK /2 4000/1 A , CLASS PS VK >= 20 RCT + 215 V IE < = 30 ma AT VK/ 2

3.6 BATTERY, DCDB, UPS, & DG 3.6.1 BATTERY CHARGERS MAKE QUANTITY MODEL INPUT OUTPUT REGULATION RIPPLE CURRENT LIMIT POWER FACTOR EFFICIENCY SOFT START SCR RATING COOLING AMBIENT FLOAT VOLTAGE SET AT FACTORY EQUALIZE VOLTAGE SET AT FACTORY EQUALIZE TIMER/SWITCH LOW DC VOLTAGE ALARM FACTORY SET HIGH DC VOLTAGE SHUTDOWN FACTORY SET LOW DC CURRENT FACTORY SET 3.6.2 TRANSFORMERS MAKE KVA PRIMARY SUPPLY SECONDARY IMPEDENCE INSULATION CLASS TEMPERATURE RISE TAPS CONSTANT POWER MFG CO 5+1 PORTABLE CHARGER 2 IN SWITCHYARD 1 EACH IN STATION, UNIT # 1, UNIT # 2 USG-415-3ph 220 200, 50Hz 415VAC +/- 10 %, 3ph, 50Hz +/- 5% 220VDC, 200ADC(NOMINAL) +/- 0.5 FROM 0 100% LOAD WITH +/-10% INPUT VOLTAGE 1% (WITH BATTERY CONNECTED) 115% AT FULL VOLTAGE (SET AT 110%) >/= 0.75 85 - 92% CURRENT WALK IN TO PROTECT EQUIPMENT FROM HIGH INRUSH CURRENT SILICON 800 P.I.V CONVECTION COOLED(FAN ASSISTED) 0 50 OC 243.0V 256.3V 0 72 hrs (MANUAL INTIATE) 198.0V 269.5V 230A

REX 101.6 415V DELTA 50/60Hz 3ph ISO 266V DELTA 4% @ 350C 220 1100C 7

3.6.3 220 V DC DRY BATTERIES MAKE TYPE LIFE SPECIFIC GRAVITY FLOAT VOLTAGE POST TYPE VENT TYPE NO. OF UNITS IN SERIES UNIT#1& UNIT#2 MODEL CAPACITY Battery charger COMMON MODEL CAPACITY Battery charger SWITCHYARD MODEL CAPACITY Battery charger

YUASA EXIDE LEAD ACID BATTERIES 20 yrs AT 25C UNDER FLOAT SERVICE 1.215 2.25VPC 2 POSITIVE POSTS & 2 NEGETIVE POSTS FLAME ARRESTOR FUSED ALUMINA 55 (110 CELLS) 2GC 21 1650 AH 51 KW, 200 A 2GC 19 1535 AH 24.3 KW, 150 A 2GC 17 1410 AH 24.3 KW, 300 A

3.6.4 DC SWITCHBOARD MAKE CLEVELAND SWITCHBOARD CO. NO. OF BOARDS 4 SENSITIVE GND RELAY MAKE GEC TYPE NGV29A INSTANTANEOUS VOLTAGE RELAY MAKE GEC TYPE PJV11 MCC CUTTLER HAMMER FREEDOM 2100 AIR BRK DE-ION CKT BKR MAKE WESTINGHOUSE 3.6.5 UPS MAKE RECTIFIER / CHARGER INVERTER LINE REGULATOR BATTERY SYSTEM AC OUTPUT SYNC DISCONNECT STATIC SWITCH TRANSFER

CYBEREX 415VAC, 3PH, 50HZ, 300A DC 210 280VDC, 60KW 415VAC, 1PH, 50HZ, 60KW EXIDE DX-9 110VAC, 1PH, 50HZ, 60KW + / - 1 HZ FROM 50HZ + / - 10% OF NOMINAL VOLTAGE

3.6.6 DG SET NOs. MAKE TYPE RATING PRIME / STANDBY P.F VOLTAGE INSULATION CLASS TEMP. RISE PHASE FREQUENCY RPM DIESEL ENGINE MODEL NO. OF CYLINDERS COMPRESSION RATIO RATING PRIME / STANDBY FUEL CONSUMPTION COOLING SYSTEM TYPE FAN TYPE FAN AIR FLOW ENGINE COOLANT STARTING MOTOR VOLTAGE BATTERY TYPE

2 SPECTRUM DETROIT DIESEL 350DS 287KW / 315KW 0.8 415V H 80C OVER 50C AMBIENT 3 50HZ 1500 8083-7405 8 17:1 454 / 500BHP 90LPH UNIT MOUNTED RADIATOR BLOWER 14805CFM 50% ETHYLENE GLYCOL & WATER 24VDC LEAD ACID

3.7 L.T TRANSFORMERS 3.7.1 L.T TRANSFORMER DESIGNATION & LOCATION Designation Rating Description Location 1 DAT 01 1 DAT 02 2 DAT 01 2 DAT 02 1 DBT 01 1 DBT 02 2 DBT 01 2 DBT 02 0 DAT 01 0 DAT 02 0 DBT 01 0 DBT 02 0 DCT 01 0 DCT 02 2000 KVA (Dry Type) 1500 KVA (Oil cooled) 2000 KVA (Oil cooled) Station service Transformer Turbine building, B-C bay 0.0m Elev. Station switch gear room Western side of ESP electrical control room CW Pump house switch gear room 1500 KVA (Oil cooled) E.P. Service Transformer Eastern side of ESP electrical control room 1500KVA (Dry Type) Unit auxiliary Service Transformer TG building, B-C bay 10.5m Ele. Unit #1 MCC Room TG building, B-C bay 10.5m Ele. Unit #2 MCC Room

Cooling tower Service x fmr

3.7.2 2000 KVA DRY TYPE TRAX'MER Make Type Enclosure Recommended surrounding KVA rating Primary voltage Secondary voltage Impedance Temperature rise Cooling class No. of phase Frequency Polarity Conductor Insulating medium Insulation class Primary BIL Secondary BIL Tap changer type Additional tap voltages Wdg resistance at 23.9oc Weight (core & coil) Weight (total) No load loss at 100% rated volts Exciting current 100% rated volts Losses at 23.9oc & rated current % Load & corr efficiency P.F & corresponding Regulation I2R losses Stray losses Full load loss Total losses Neutl. gr. resist. Max fault current

Dynapower Corporation Ultracast dry type cast type cast coil trax'mer NEMA standardized Indoor ( 30oc Avg. with 40oc peak in a day) 2000 kVA 6600 volts 433 Y/ 250 volts 7.416 % 70oc AA 3 50 Hz Dyn1 Primary Copper, Secondary Copper Dupont Nomex in Epoxy Resin F 60 kV 10 kV Off load 2 @ 2.5% FCAN & 2 @ 2.5 0.09 (HV) 0.505 (LV) 15000 LBS 18500 LBS 3664 watts 0.316 % 13568 watts Load 100% 75% 50% 25% 99.15 99.25 99.30 99.1 (%) P.f. 1.0 lag 1.0 lag 1.0 lag 1.0 lag Regl 0.68% 3.38% 4.97% 6.74% 11998 W 3196 W 15195 w 18859 w 350 ohms 1 amp

3.7.3 1500 KVA DRY TYPE Trax'mer Make Type KVA rating Primary voltage Secondary voltage Impedance Temperature rise Cooling class No. of phase Frequency Polarity Insulation class Primary BIL Secondary BIL Tap changer type Weight (core & coil) Weight (total) Neutl. gr. resist. Max fault current

Dynapower Corporation Ultracast dry type cast type cast coil trax'mer 1500 kVA 6600 volts 433 Y/ 230 volts 5.809 % 70oc AA 3 50 Hz DyN1 F 60 kV 10 kV Off load 15000 LBS 18500 LBS 350 ohms 1 amp

3.7.4 1500 KVA OIL COOLED TRAX'MER Make ABB Type Silicon fluid insulated unit substation Trax'mer Surrounding Outdoor (40oc avg ambient with 50oc peak ) KVA rating 1500 / 1680 Temperature rise 45/55oc Primary voltage 6600 volts Secondary voltage 433 Y/250 volts Impedance 7.89 % Cooling class OA Polarity Dyn1 Insulating medium Silicon fluid, Insuladur insulation Primary full wave impulse test 75 Kv Sec. Full wave impulse test 30kV Tap changer type Off load Additional tap volts/Amps at 433 V/ Tap No. Connects Volts HV Amp. HV 2240.1A on LV side 1 4 to 5 6930 140.0 2 3 to 5 6765 143.4 3 3 to 6 6600 146.9 4 2 to 6 6435 150.8 5 2 to 7 6270 154.7 Liquid level at 25oc 8.69 below highest manhole flange Rise in level /10oc rise 0.30 Vol. Liquid 425 Gallon Weight (core & coil) 5857 lbs Weight (case) 4295 lbs Weight (liquid) 3187 lbs Weight (total) 13339 lbs Operating Pr. 6.5PSI(sealed air fluid preserving system) Design Pr. 8.0 PSI Neutl. gr. resist. 350 ohms Max fault current 1 amp 3.7.5 2000 KVA OIL COOLED TRAX'MER Make ABB Type Silicon fluid insulated unit substation Trax'mer Surrounding Outdoor (40oc avg ambient with 50oc peak ) KVA rating 2000 / 2240 kVA Temperature rise 45/55oc Primary voltage 6600 volts Secondary voltage 433 Y/250 volts Impedance 7.62 % Cooling class OA No. of phase 3 Frequency 50 Hz

Polarity Insulating medium Primary full wave impulse test Sec. full wave impulse test Tap changer type Additional tap volts/Amps at 433 V/ 2986.6A on LV side

Liquid level at 25oc Rise in level /10oc rise Vol. Liquid Weight (core & coil) Weight (case) Weight (liquid) Weight (total) Operating Pr. Design Pr. Neutl. gr. resist. Max fault current 3.7.6 415 /240 V TRAX'MER KVA Rating HV side voltage /current LV side voltage /current Frequency Temperature rise Weight Connection HV side

DyN1 Silicon fluid, Insuladur insulation 75 kV 30kV Off load Tap No. Connects Volts HV Amp. HV 1 4 to 5 6930 186.6 2 3 to 5 6765 191.2 3 3 to 6 6600 196.0 4 2 to 6 6435 200.9 5 2 to 7 6270 206.3 9.78 below highest manhole flange 0.33 477 Gallon 6954 lbs 4847 lbs 3377 lbs 15378 lbs 6.5 PSI(limited by sealed air fluid preservation) 8.0 PSI 350 ohms 1 amp 3kVA 415 v/ 7.2 A 240 v / 13 A 50 / 60 Hz 80oc 60lbs H1 H2 H1 H3 H1 H4 H1 H5 H1 H6 X1 X2

Connection LV side 3.7.7 415 /110 V TRAX'MER KVA Rating HV side voltage /current LV side voltage /current Frequency Temperature rise Weight Connection HV side

394 volts 405 volts 415 volts 425 volts 435 volts 240 volts

Connection LV side 3.7.8 415 /24 V TRAX'MER KVA Rating HV side voltage /current LV side voltage /current Frequency Temperature rise Weight Connection HV side

2 kVA 415 v/ 5 A 110 v / 18 A 50 / 60 Hz 80oc 60 lbs H1 H2 H1 H3 H1 H4 H1 H5 H1 H6 X1 X2

394 volts 405 volts 415 volts 425 volts 435 volts 110 volts

Connection LV side

5 kVA 415 v/ 12 A 240 v / 24 A 50 / 60 Hz 80oc 60 lbs H1 H2 H1 H3 H1 H4 H1 H5 H1 H6 X1 X2

394 volts 405 volts 415 volts 425 volts 435 volts 24 volts

3.7.9 415 / 240 or 110 or 24 VOLTS TRAX'MER Trax'mer Application 415 / 240 volt Distribution panel MCC/Motor HTR MCC/Motor HTR 1HB 415 / 110 volt Test control Bus Test control Bus 1HB 415 / 24 volt Motor winding HTR Motor winding HTR 3.7.10 LDBS DATA Designation Charged from OLA OTA OLB OLC OTB OLD OLL OLG OSA OLP OLH OSB OLQ OLE OSC OLR OLF OSD OLS OSW OLM 1KB OLN 2KB OLU (DC) 0FA OLW (DC)

KVA Rating 100 100 100 100 50 100 50 100 50 100 50 100 50 50 50

Lighting area

3.7.11 LDB TRANSFORMER TYPE Rating Voltage (Pri/Sec) Current Phase Frequency No. of switches Switch fuse unit Type of cooling Impedance volts Vector group Insulation level Total weight Insulation class Max. temp rise of winding Off load Tap

TYPE Rating Voltage (Pri/Sec) Current Phase Frequency No. of switches Switch fuse unit Type of cooling Impedance volts Vector group Insulation level Total weight Insulation class Max. temp rise of winding Off load Tap

F-12 50 kVA 415 V/433 V 69.56 A/ 66.67 A 3/3 50 Hz 12 100 A AN 3.25 % DyN11 Primary 3 kV 350 kg F 70oc at 50oc amb. Tap No % 1 -5 2 -2.5 3 0 4 +2.5 5 +5 H-24 100 kVA 415 V/433 V 139.1A/133.4 A 3/3 50 Hz 24 250 A (Incomer) AN 3.69 % DyN11 Primary 3 kV 375 kg F 70oc at 50oc amb. Tap No % 1 -5 2 -2.5 3 0 4 +2.5 5 +5

Secondary 3kV

Volts HV 395 405 415 425 435

Volts LV 433 433 433 433 433

Secondary 3 kV

Volts HV 395 405 415 425 435

Volts LV 433 433 433 433 433