Professional Documents
Culture Documents
Paper 0055
7
Number of cables
0
1978 1980 1982 1984 1986 1988 1990 1992 1994 1996
DIAGNOSTIC METHOD Year of installation
The measurements were carried out using the method called Figure 1. Year of installation for the cables included in the
dielectric spectroscopy [2]. VLF voltages in the range project.
between 0.5 U0 and 1.5 U0 and with frequencies typically
between 0.03 Hz and 0.3 Hz were applied, and the dielectric Unfortunately, it was not possible to assess the insulation
losses in the insulation were measured. condition of all these cables. Around 25 % of the cable
sections had been equipped with cable accessories that had
Based on the variation of the dielectric losses with voltage high losses and prevented the measurement of the losses in
and frequency, the cables were classified into four the cable insulation.
categories, corresponding to increasing levels of ageing:
• Good cables with low losses If a network owner wants to be able to carry out diagnostic
• Aged cables with voltage dependent losses measurements on XLPE cables, only cable accessories with
• Significantly aged cables with transition to leakage high DC resistance at voltages of 1.5 U0 to 2 U0 should be
current at the highest applied voltage level installed. So far, measurement of this DC resistance is not
• Bad cables with leakage current occurring at normal included in the type tests for accessories, but the customers
operating voltage. should ask the manufacturers to give this information and
choose among the types with high DC resistance.
Paper 0055
SHEATH CONDITION cables with leakage current 37 dry cured cables were
checked at least twice. In Figure 3, the results of the first
When testing the integrity of the cable sheaths it was found and the final assessment of the insulation condition of these
that the sheath currents in some of the cables were close to cables are shown. A significant deterioration of the
the limit values of I0=500 µA/km (PVC) and I0=10 µA/km insulation condition is seen in the figure. 16 out of the 37
(PE) given above. Therefore, the cables were divided into cables were found to have a poorer insulation condition at
three categories the last measurement than at the beginning of the 6-year
• 44 % of the cables had sheath currents below I0, period.
indicating an intact sheath
• 21 % of the cables had sheath currents between I0 and 25
10 I0 and may have a damaged sheath
• 35 % of the cables had sheath currents above 10 I0 and 20
First assessment
Final assessment
certainly have a damaged sheath.
Number of cables
15
In Figure 2 the sheath condition is shown for three groups of
cables with different time in operation. It is seen that there 10
70%
60%
in 2007 transition to leakage current was measured at 1.5 U0
Intact
50% Possibly damaged
(9 kV) and the leakage current response was maintained
40%
Damaged after lowering the voltage to U0 (6 kV) as shown in
30% Figure 4.
20%
10%
0%
1979-85 1986-90 1991-96
Year of installation
INSULATION CONDITION
In the years 2002 to 2007 some of the cables have been
selected for re-measurements. The selection was based on
the result of the first diagnostic measurements so that the
cables showing the clearest signs of ageing at the first
measurements in 2001 were investigated more often than
the cables with good insulation condition.
Paper 0055
100%
90%
80%
Percentage of cables
70%
60% Good
Aged
50%
Significantly aged
40% Bad
30%
20%
10%
0%
1979-85 1986-90 1991-96
Year of installation
100%
90%
80%
Percentage of cables
70%
60% Good
Aged
50%
Significantly aged
40% Bad
30%
20%
10%
0%
Intact Possibly damaged Damaged
Sheath condition Figure 7. Diagnostic measurements on a 10 kV cable in
Figure 6. Assessment of insulation condition for cables with three consecutive years: 2005 (top), 2006 (middle) and
varying sheath condition. 2007 (bottom).
Paper 0055
Several possible explanations for the fact that a damaged greatest change was observed for a cable installed in 1983.
sheath does not necessarily lead to poor insulation condition In 2001 this cable was found to be in good condition but in
could be given. As the cables have no radial water barrier, 2007 it showed signs of long water trees.
water with time will diffuse into the insulation, even if the
sheath is intact, and local variations in soil humidity will Of the tested cable sections at least 35 % had damaged
probably have a larger influence on the ageing process than sheaths. There seems to be no correlation between the
a hole in the sheath. number of years in service and the occurrence of sheath
damage, so probably the damaging of the sheaths mainly
Furthermore, the effects of a damaged sheath may be very occurs during the installation of the cables.
local and may only contribute moderately to the average
losses for the whole cable section. From the measurements, the insulation conditions for cables
with intact sheaths seem to be poorer than for cables with
INFLUENCE OF SOIL HUMIDITY damaged sheaths. This must, however, be a matter of
coincidence, and there may be some local deterioration of
It is known from laboratory measurements that if the the insulation which does not contribute enough to the total
insulation dries out, an XLPE cable with water trees does dielectric losses of the insulation to change the assessment
not any longer give the typical water tree response in of the insulation condition.
diagnostic measurements, as the water trees become less
conductive. In 2006 the summer in Denmark was extremely warm and
dry and this led to a drying of some of the cable sections.
In 2006 this phenomenon was observed for underground The dielectric losses in several of the investigated cables
cables still in service. The summer in Denmark in 2006 was were reduced and their insulation condition could not be
extremely hot and dry, and for some of the investigated assessed correctly. Measurements in 2007 on the same
cables this led to a large reduction in losses as shown in cables showed that most of them again had obtained their
Figure 7 on the previous page. “normal” dielectric losses, but some still seemed to be dry.
A year later, the losses for most of the cables had returned None of the tested cable sections has failed yet so it is still
to a level close to the values from 2005 (or earlier). unknown how fast the last part of the degradation of the
However, a few still had low losses when the final insulation will proceed. To get information on this the cable
measurements were carried out in 2007. sections will be followed also in the coming years.
As the growth of water trees is also stopped when the cables
REFERENCES
dry out, the dry summer of 2006 may have added a year or
more to the expected service life of some of the cables. [1] H. J. Jorgensen and J. S Christensen, 2003,
"Experience from diagnostic testing of MV XLPE
CONCLUSION cables", Proceedings CIRED 2003, Session 1, Paper
No. 75
The measurements have shown that 50 % of the cables are [2] S. Hvidsten, P. Werelius and J. Christensen, 2001,
still in good condition. 25 % show signs of slight ageing and “Evaluation of on-site dielectric response methods for
around 23 % are significantly aged. One cable (around 2 %) non-destructive testing of water treed MV XLPE
was found to have bad insulation condition with high risk of cables”, Proceedings CIRED 2001, vol. 1, paper 1.48.
failure in the case of an overvoltage occurring on the [3] J. T. Benjaminsen, 2001, Sheath Testing of MV
system. Polymer Cables. Background and Handbook,
TR A5484, SINTEF Energy Research, Trondheim,
In the 6-year project period the insulation condition was Norway.
found to deteriorate for more than 40 % of the cables. The