You are on page 1of 4

CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0310

ANALYSIS OF A CLOSED LOOP CONTROL FOR CURRENT UNBALANCE


COMPENSATION BASED ON AC/AC CONVERTERS
Pompeo MARINO Giuliano RAIMONDO Giuseppe TORRE
Seconda Università degli Studi di Napoli – Italy Seconda Università degli Studi di Napoli – Italy Seconda Università degli Studi di Napoli – Italy
pompeo.marino@unina2.it raimondogiuliano@inwind.it giuseppe.torre@unina2.it

ABSTRACT capacitor and inductor. Considering a situation as in Figure


1, where an ohmic-inductive load cause unbalance in a
In this paper a stability analysis method for unbalance three-phase grid, a control law is defined in order to
compensation system based on AC-Chopper is proposed. rebalance the line currents system.
Employing Ac-Choppers and Steinmetz theory it’s possible
to obtain a dynamic compensation system. This system’s
performance and stability are not depending only on the ea (t ) Rl L ia (t ) Ia R
cause of unbalance but also on grid parameters such as eb (t ) Rl L ib (t ) Ib R
line impedances and other connected loads. If a quasi-static ec (t ) Rl L ic (t ) Ic R
sinusoidal steady-state approximation is hypothesized, Rs
through the multivariable control theory it’s possible to is (t )
Ls

study the compensation system stability propriety in


relation with grid parameters.
*
Iind

*
I inv =0

INTRODUCTION
*
Icap

In three-phase power systems the generated voltages are


sinusoidal and equal in magnitude, with the individual Figure 1 Compensation Scheme
phases 120 degree apart. However, the resulting power
system at the distribution end and the point of utilization can In [4], m easuring the rms current value and the current
be unbalanced for several reasons. The nature of the phase of the unbalanced RL load a feed-forward action is
unbalance includes unequal voltage magnitudes at the used to compensate the symmetrical inverse component
fundamental system frequency (under-voltages and over- generated in the line currents. Due to uncertainties presence,
voltages), fundamental phase angle deviation, and unequal the only feed-forward action is not able to completely re-
levels of harmonic distortion between the phases. A major balance the system current, so in addition, a closed-loop
cause of voltage unbalance is the uneven distribution of control is used. In this work an analysis of the this control is
single-phase loads, that can be continuously changing across performed focusing on the system modelling and on the
a three-phase power system. Example problem areas can be stability study.
traction, where some technical reasons encourage the
adoption of a single-phase feeding system. The single-phase
railway system usually causes unbalance problems due to PROBLEM DESCRIPTION
large unbalanced traction loads. These unbalance may cause
As shown in Figure 1, the line impedance presence in
extra losses, motor overheating and malfunction of
addition to an unbalanced current system leads to
electronic devices. The results are unacceptable if they
unbalanced voltage supply. Complete modelling of all
affect the power system behaviour significantly.
effects present on the grid is quite complex. Therefore, in
International standards give limits for the unbalance ratio <
order to a better comprehension of the results, before
2% for LV and MV systems and <1% for HV systems. A
studying the detailed model of the system, intermediate
solution to mitigate the unbalances is the so-called
simplified model will be considered and described in the
“Steinmetz Circuit” [1] [2]that consists of a capacitor and
next sections.
an inductor properly rated in order to compensate the
current inverse-sequence component. This solution is not
able to compensate a dynamic unbalance. In [3][4] an
SYSTEM MODELING
unbalance compensation technique based on Ac/Ac The aim of this section is to obtain an equivalent model
regulators has been proposed. Studying the validity range of scheme for system in Figure 1. The multivariable system
each Steinmetz Circuits it is possible to obtain a variable obtained is reported in Figure 2. The system’s input are the
compensation net by employing AC-choppers [5] instead of real and imaginary part of the desired inverse component

CIRED2009 Session 2 Paper No 0310


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0310

phasor for ia(t), ib(t), ic(t) (normally the two reference values state have to be hypothesized. In this way the grid is
are zero but it’s also possible to consider a different value described as a static 2x2 matrix N with 2 disturbs d1 and
that is acceptable for the standard, limiting the Ac-Chopper
input current). Outputs are real and imaginary part of the d 2 acting at the output.
inverse component present on the three-phase system. Each ea (t ) Rl L ia (t ) R
part of the scheme is discussed in the next paragraphs.
eb (t ) Rl L ib (t ) R
Controller
ec (t ) Rl L ic (t ) R
In Figure 2, the controller is represented with matrix C
iC (t ) iL (t ) Rs
and Beq . The first matrix contains the K ( s ) controller
Ls
transfer functions on the principle diagonal. In this paper a is (t )
classic PI controller has been considered as reported in (1)
Ki
K (s) = K p + (1) Figure 3 – Grid model circuit
s
Matrix Beq explicitly reported in Figure 2 is introduced in This approximation is acceptable if I cap , I ind variations are
[4] and it’s a linear combination of the controller output that slow in such a way that the grid behaviour can be
* *
gives references I cap and I ind . considered as a succession of sinusoidal steady-states. This
is true if the Ac-Choppers rms-input current control is slow
Variable Impedance respect to the grid dynamics. Regarding the grid model,
As reported in [4], the variable impedance control is a rms- three cases will be studied. First, in case (a) line impedances
will be neglected and will not be considered. In this way
input-current control. Gc contains on the principal diagonal
voltage supply is considered always balanced. In case (b)
the closed-loop transfer function of the variable impedance the presence of line impedance and the effect of unbalanced
system. It’s possible to consider G ( s ) a first order transfer voltage on three-phase load R is been considered. In case
function as in (2) (c), a further non-ideality in introduced considering the Ac-
1 Choppers input currents not perfectly inductive and
G(s) = (2)
1 + sτ capacitive, with -90° and +90° phase shift respect to the
on condition that time constant τ is relatively big in order to voltage, and two phase error α and β are introduced.
first order system approximation. Next paragraph will show
that the G ( s ) passband has to be small enough to guarantee Case (a)
the validity of the grid used model. Matrix N a and disturbs d1 and d2 are reported in (3)

Re* {I inv }  1 
 Is

( 3 sin φ + cos φ 

)
 −2 0   d1a   2 3 
a  
d1 N =  =  (3)
e1 (t )
C Beq Gc N
Re {I inv }
 3
− −
3  d 2a   I s ( 3 cos φ − sin φ  )
 K (s ) 0   −2 0  G ( s ) 0   N11 N12   6 3   
 0
 K ( s)   
 1 − 3
 0
 G ( s )  N
 21 N 22 
Im { I inv }
 2 3 
e2 (t )
Where I s = I s ∠φ is the unbalanced load current phasor.
d2
If (4) is supposed
Im* {I inv }
L0 ( s ) = K ( s ) G ( s ) (4)

Figure 2 – forward path


Forward path matrix of the system is calculated in (5)
Grid modelling  L0 ( s ) 0 
La = N a ⋅ Gc ⋅ Beq ⋅ C =   (5)
L0 ( s ) 
With aim of obtaining a grid model, the equivalent circuit
reported in Figure 3 is considered. The variable capacitive  0
and inductive impedances are schematized as current
It’s important to note that matrix N a outputs are real and
generators. In this way, the grid can be seen as a system
imaginary parts of the inverse component injected by the
with input I cap , I ind (Ac-Chopper rms input current value)
Ac-Choppers compensation net. Disturbs d1 and d2 are
and output the real and imaginary part of the inverse
real and imaginary parts of the inverse component related to
component I inv . In order to define the symmetrical the unbalancing. The aim of the control is to reject these
component decomposition, a quasi static sinusoidal steady- disturbs.

CIRED2009 Session 2 Paper No 0310


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0310

All the theory about the unbalance compensation control is Case (a)
reported in [4]. Next cases will present a more complex a
formulation due to the presence of the line impedance and Due to the diagonal structure of L , the eigenvalues are
easily calculated and reported in (11).
the I cap and I ind phase displacements. Anyway the physical
λ1a ( s ) = λ2a ( s ) = λ a ( s ) = L0 ( s ) (11)
sense of the terms remain the same.
Case (b)
Case (b)

( )
Considering the line impedance, Matrix N and disturbs d1
and d2 are function of all grid parameters. λ1,2
b
( s ) = k ⋅ L0 ( s ) ⋅ λ1,2 M b =
(12)
(
 d b R , L, R , L , R
 1 l s s ) = L0 ( s ) ⋅ k ⋅ ( R + Rl ± jω L )
N b ( Rl , L, R )  b  (6)
(
 d 2 Rl , L, Rs , Ls , R ) Case c)

Assuming (7), the forward path is reported in (8) λ1,2


c
( )
( s ) = k ⋅ L0 ( s ) ⋅ λ1,2 M c (13)

R
k= In case (a), the eigenvalues λ1 and λ2 are coincident and
(ω L ) + ( R + Rl )
2 2
equal to L0 ( s ) . Therefore, the system characteristic loci’s
(7)
R + R ωL  and L0 ( s ) have the same Nyquist diagram.
Mb =  l 
 −ω L Rl + R 
In case (b) and (c) eigenvalues can be written as in (14).
= L0 ( s ) ⋅ Ab e ± jφ
b
λ1,2
b

Lb = N b ⋅ Gc ⋅ Beq ⋅ C = k L0 ( s ) M b (8) (14)


= L0 ( s ) ⋅ Ac e ± jφ
c
λ1,2
c

It’s possible to note that matrix M b structure is such that it’s Where:
R
always non-singular (except in case of all zero element). Ab =
(ω L ) + ( R + Rl )
2 2
Case (c)
In this case line impedance and unbalanced voltage effect  ωL 
are considered. Moreover, input current Ac-Choppers phase φ b = atan   (15)
shift have been introduced. Using particular α and β values  R + Rl 
it’s possible to model power losses in the converters and
phase deviation due to any input filter.
Ac = Ac ( Rl , L, Rs , Ls , R, α , β )
φ c = φ c ( Rl , L, Rs , Ls , R, α , β )
 d1c ( Rl , L, Rs , Ls , R ) Due to the complexity, Ac and φ c are not reported here.
N c ( Rl , L, Rs , Ls , R, α , β )   (9)
 d 2c ( Rl , L, Rs , Ls , R ) From (14) and (15), it’s possible to affirm that both in case
As in the previous case, it’s possible to determine a matrix (b) and case (c), system’s characteristic loci are an
M c such that the forward path is: amplified and rotated version of L0 ( s ) Nyquist diagram as
shown in Figure 4.

Lc = N c ⋅ Gc ⋅ Beq ⋅ C = k L0 ( s ) M c (10)
Im

Re
STABILITY ANALYSIS
In this paragraph a stability analysis methodology for
A L0 e jφ
systems (5), (8) e (10) will be proposed. The stability is
studied considering is the generalized Nyquist criteria [6].
For each case, the eigenvalues of the system matrix are L0 A L0 e − jφ
calculated and the Nyquist diagram is evaluated.
Figure 4 - Nyquist diagram of Characteristic Loci

CIRED2009 Session 2 Paper No 0310


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0310

In order to verify the system stability, the characteristic


loci’s phase margins have to be positive. It’s clear that the Parameter Value Unit
stability is dependent on L0 ( s ) structure and on the entity Phase Voltage (RMS) 63 kV
Line Frequency 50 Hz
of A and φ . In case (b), in (15) it’s shown that A and φ Line Resistance Rl 1.4 Ω
Line Inductance L 25 mH
are strongly dependent on R. Therefore it’s interesting to Unbalanced Load Rs 40 Ω
study the stability when that parameter is varying. In case Unbalanced Load Ls 0.26 H
(c) the analysis is more complicated, and fixed the AC/chopper control time costant τ 1 s
controller structure, line impedances and the unbalance Range for grid load R [0 20] Ω
entity, the varying parameters are R, α and β . Therefore Range for AC/Chipper phase
[0 20] degree
displacement α and β
an iterative algorithm is needed and it’s shown in the next
Controller 1 Kp=0.5 Ki=1
session. Controller 2 Kp=1 Ki=10
90 Table I
80

70
CONCLUSIONS
60 Ψm Controller 1
degree

max φ c
50
Ψm Controller 2 In this paper, a method for the stability analysis of an
40 unbalance compensation control is been proposed. If a
phasorial model of the grid can be considered, using the
30
generalized Nyquist criteria and an iterative numerical
20
0 0.5 1 1.5 2 2.5
analysis, it’s possible to study the compensation control
R / |Z| stability for a chosen variation range of parameters. This
Figure 5 - Numerical results iterative analysis strategy is a trial-and-error criteria for the
controller design.
Numerical stability analysis
In order to evaluate numerically the stability varying R, α
and β , first a variation ranges have to be chosen. These
REFERENCES
ranges and all parameters considered in the numerical
analysis are reported in table I. Since L0 ( s ) present an [1] M. ChindriS, A. Cziker, S. Stefanescu, 2001
infinite gain margin, it’s possible to study the stability “Symmetrizing Steinmetz Circuitry”, CIRED 2001
evaluating only the phase margin. The analysis steps are the Amsterdam (Netherlands) , June 2001.
following:
[2] L. Sainz, J. Pedra, M. Caro,”Steinmetz circuit
1. Parameters Rl , L, Rs , Ls , K p , Ki are fixed influence on the electric system harmonic response”,
2. A value of R is chosen Power Delivery, IEEE Transactions on Volume 20,
Issue 2, April 2005 Page(s): 1143 – 1150.
3. φmax = max φ c is evaluated
α ,β
[3] B. Cougo, T. Meynard, “A Solution for Three-Phase
4. Phase margin ψ m  AC L0 ( s )  in calculated System Unbalance Based on PWM AC Choppers”,
IECON 2006 ,Paris (France), November 2006.
5. If φmax < ψ m then the closed-loop in stable
6. Repeating from 2, varying R , the numerical [4] P. Ladoux, P. Marino, G. Torre, 2008, "Power quality
stability can be performed. improvement by means of AC/AC choppers",
SPEEDAM 2008 , Ischia, On page(s): 77-8.
Numerical results are reported in Figure 5. Two controllers
are considered. The first stable for all R values, the other [5] L. Lowinsky, P. Ladoux, Y. Chéron, S. Alvarez: 3
one stable only for some values. MVAR Single Phase STATCOM based on AC Chopper
It is possible to observe that increasing R , and so Topology. PCIM 2008 – Nurnberg (Germany), May
decreasing the power drawn by the loads connected to the 2008.
three-phase grid, stability properties are improved. Vice
versa, low values of R are critical. In Figure 5, on the x- [6] J.M. Maciejowski, 1989, Multivariable Feedback
axis the values of R is normalized on the line impedance Design, Wokingham, England.
module.

CIRED2009 Session 2 Paper No 0310

You might also like