Professional Documents
Culture Documents
Keywords: Fault passage indicator, Compensated network, Transient based fault detection
Abstract
A new fault monitoring and location system is available for load monitoring and fault detection of overhead distribution lines.
Acquisition units (AUs) are mounted on all three phases and communicate with a data collection unit (DCU) at the bottom of
the pole using short-range wireless communications. The DCU communicates with a remote master station through the mobile
network, thus forming a complete fault monitoring and location system for the distribution network. The system provides high
speed sampling of three-phase voltage and current signals through innovative sensors, the samples are synchronized through
communications by the DCU. When a fault occurs, disturbance records are sent by the AUs to the DCU, so that zero sequence
components can be calculated. This feature allows the system to detect high impedance earth faults. High speed sampling also
allows transients of the signals to be derived, so that the system can be applied to unearthed and compensated networks. For
such networks the earth fault current magnitude is insignificant, but there is a dominant transient signal which can be used to
identify the faulty line and the faulty section.
The technology used in this system and the transient-based fault detection technique are detailed in this paper. Staged fault tests
were performed on a feeder with compensated earthing. Actual site fault records were also obtained. The results are presented.
1
0
line current is not available. Four red LEDs provide 360 distribution network topology built-in. All the devices in the
visibility for fault indications. Current measurement is through field are mapped to the appropriate locations of the network.
Rogowski coil, whereas voltage measurement is derived from Under system healthy conditions, real-time line voltage and
an electric field sensor. It is a capacitive device as shown in the load current measurements of the monitored locations can
Figure 2, which captures the vertical electric field strength be displayed. Under fault conditions, the master station
from the phase conductor to ground by induction [2]. software receives waveforms from all the units which have
triggered. It then performs waveform comparison to decide on
Overhead Phase Conductor the faulty feeder and the faulty section. The fault section will
be indicated in the network diagram, as shown in Figure 4.
Contact capacitor
The server also provides a data transfer service which allows
Sampling Acquisition other PCs to access the on-line measurements and fault
capacitor unit location information.
Figure 2 Vertical electric field transducer producing the Collection Unit (n)
equivalent phase voltage
2
successful and the current has returned to its normal operating
value. From this, it can be determined that the line has a
transient short-circuit fault.
5 Earth fault detection for isolated and Figure 7 Voltage and current for faults on non-effective
compensated networks earthed system
A single-phase-to-earth fault for a non-solidly earthed system
The phenomenon of a single-phase-to earth fault occurring on
has the following characteristics:
a non-solidly earthed system is as follows:
a) The voltage of the faulted phase has a severe voltage
a) Before the single-phase-to-earth fault occurs, the zero-
depression.
sequence voltage and current are very small, caused only
b) A high frequency transient signal appears in the phase
by the unbalance of the system.
current. The fundamental magnitude of the phase current,
b) During the fault, the faulty phase voltage reduces in
however, may only have a small increase or may remain
magnitude, whereas the two healthy phases experience a
unchanged.
rise in voltage (maximum √3x Vn) , thus creating a zero-
sequence voltage. High frequency current transients also
occur on the faulty phase, with the instantaneous
magnitude reaching △I, which lasts for less than 20ms.
This also creates a transient zero sequence current.
c) After 20ms, the system moves from a transient condition
to a steady state condition, the transient current subsides,
the phase current now has only a small variation in
magnitude compared to its pre-fault state.
3
compensated 10kV network were also obtained. The results
are presented in the following sections.
As can be seen, the fault current is not very high, around 16A
Healthy Line
rms. There are voltage increases in the two healthy phases,
creating a significant zero sequence voltage.
Because of the high fault impedance, a lot of the fault
Healthy Line transients from the zero-sequence current are suppressed.
However, there is sufficient transient at the moment of fault
inception for the signal to be processed.
Faulty Line
6.2 Staged test for a solid earth fault
4
6.3 Actual earth fault on a compensated 10kV feeder
An actual earth fault has occurred on a utility’s compensated
10kV feeder with the device installed. There are obvious
transient signals present in the zero-sequence current. The A-
phase voltage has a severe depression, and there is a significant
zero sequence voltage. The cause of the fault is not yet known,
but is suspected to be due to tree contact, with arcs coming on
and then self-extinguished.
7 Conclusions
A new fault monitoring and location system is available for
distribution overhead lines. Apart from performing traditional
fault passage indicator functions, it has more advanced
Figure 12 Record from the second unit on a compensated test features allowing it to detect high impedance faults, and to be
feeder for solid fault applied to isolated and compensated networks. The design of
the system and the communications are explained in this paper.
The fault detection algorithms are also depicted. Actual fault
records from staged test and from the utility’s installation are
also shown.
8 References
[1] Calone, R., Cerretti, A., Fatica, A.: ‘Evolution of the fault
locator on MV distribution network: from simple stand alone
device, to a sophisticated strategic component of the smart grid
control system’, Proc. of CIRED 2011, Frankfurt, June 2011.
[2] Sun, B., Sun, T., Xu, B.Y., el al, ‘A zero-mode voltage
measurement method for single phase to ground fault of non-
solidly-earthed overhead lines’, Automation of Electric Power
Systems, Vol. 33, No.6, March 2009. (In Chinese)
Figure 13 Record from the third unit on a compensated test [3] Xu, B.Y., Ma, S.C., Xue Y.D. et al, ‘Transient current
feeder for solid fault based earth fault location for distribution automation in non-
effectively earthed networks’, Proc. of CIRED 2009, Prague,
June 2009.