S A F E T Y WA R N I N G
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
WA R N I N G
moderate injury. It could also be used to alert Pe r s o n a l P r o t e c t i v e E q u i p m e n t ( P P E )
against unsafe practices.
Required!
Indicates a situation that could result in
NOTICE Fa il u re to w ea r pro pe r PPE f or t he j ob b ei ng
equipment or property-damage only
accidents. u n d e rt a k e n c o u l d r e s u l t i n d e a t h o r s e r i o u s i n j u r y.
Te ch n i c i a n s , i n o r d e r t o p r o t e c t t h e m s e l v e s f r o m
p o t e n t i a l e l e c t r i c a l , m e c h a n i c a l , a n d ch e m i c a l
Important Environmental Concerns h azards, MUST follow pr ecaut io ns in th is man ual
Scientific research has shown that certain man-made a n d o n t h e t a g s , s t i ck e r s , a n d l a b e l s , a s w e l l a s t h e
chemicals can affect the earth’s naturally occurring instructions below:
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified • Before installing/servicing this unit,
chemicals that may affect the ozone layer are t e ch n i c i a n s M U S T p u t o n a l l P P E r e q u i r e d f o r
refrigerants that contain Chlorine, Fluorine and Carbon t h e w o r k b e i n g u n d e rt a k e n ( E x a m p l e s ; c u t
(CFCs) and those containing Hydrogen, Chlorine, r e s i s t a n t g l ov e s / s l e e v e s , b u t y l g l ov e s , s a f e t y
Fluorine and Carbon (HCFCs). Not all refrigerants glasses, hard hat/bump cap, fall protection,
containing these compounds have the same potential electrical PPE and arc flash clothing).
impact to the environment. Trane advocates the A LWAY S r e f e r t o a p p r o p r i a t e M a t e r i a l Sa f e t y
responsible handling of all refrigerants-including Dat a Sheets ( MSDS)/Saf et y Data Sh eets
industry replacements for CFCs such as HCFCs and (SDS) and OSHA guidelines for proper PPE.
HFCs. • Wh en wo rkin g with or arou nd hazardou s
ch e m i c a l s , A LWAY S r e f e r t o t h e a p p r o p r i a t e
Important Responsible Refrigerant MSDS/SDS and OSHA/GHS (Global
Practices H a r m o n i ze d Sy s t e m o f C l a s s i f i c a t i o n a n d
Labelling of Chemicals) guidelines for
Trane believes that responsible refrigerant practices are in for m at io n on a ll owa bl e pe r s ona l e x pos ur e
important to the environment, our customers, and the levels, proper respiratory protection and
air conditioning industry. All technicians who handle handling instructions.
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling, • If there is a risk of energized electrical
reclaiming, recovering and recycling of certain c o n t a c t , a r c , o r f l a s h , t e ch n i c i a n s M U S T p u t
refrigerants and the equipment that is used in these o n a l l P P E i n a c c o r d a n c e w i t h O S H A , N F PA
service procedures. In addition, some states or 7 0 E , o r o t h e r c o u n t r y- s p e c i f i c r e q u i r e m e n t s
municipalities may have additional requirements that for arc flash protection, PRIOR to servicing
must also be adhered to for responsible management the unit. NEVER PERFORM ANY SWITCHING,
of refrigerants. Know the applicable laws and follow D I S C O N N E C T I N G , O R VO LTA G E T E ST I N G
them. WIT HOUT PROP ER ELECT RIC AL PPE AND
A R C F L A S H C LO T H I N G . E N S U R E
E L E C T R I C A L M E T E R S A N D E Q U I P M E NT A R E
P R O P E R LY R AT E D F O R I NT E N D E D VO LTA G E .
SS-SVX12D-EN 3
Table of Contents
Model Number Description . . . . . . . . . . . . . . . . . 6 Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . 6 Control Circuit Features . . . . . . . . . . . . . . . . . . 28
Discharge Temperature Limit
General Information . . . . . . . . . . . . . . . . . . . . . . . . 7 (DTL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Low Outdoor Ambient Cooling . . . . . . . . 28
Evaporator Defrost Control
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 (EDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Low Pressure Cut-Out (LPCO) . . . . . . . . . 28
Inspection Checklist . . . . . . . . . . . . . . . . . . . 8 High Pressure Cut-Out (HPCO) . . . . . . . . 28
Testing for Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . 8 Internal Overload Protector
(IOL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Lifting Recommendations . . . . . . . . . . . . . . . . . 8
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Unit Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Electromechanical Controls. . . . . . . . . . . . . . . 29
Structural Preparation . . . . . . . . . . . . . . . . . 9 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Rooftop Mounting . . . . . . . . . . . . . . . . . . . . 9 Evaporator Fan (Indoor Supply
Ground Level Mounting . . . . . . . . . . . . . . . 9 Air) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . 29
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 10 ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . . . . 29
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Control Cooling Mode . . . . . . . . . . . . . . . . 29
Control Evaporator Fan
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . 14 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Control Heating Operation . . . . . . . . . . . . 30
4 SS-SVX12D-EN
Ta b l e o f C o n t e n t s
SS-SVX12D-EN 5
Model Number Description
Cooling Condenser
TTA 120 A 3 00 * *
123 456 7 8 9 10 11 12
N o t e : When ordering replacement parts or requesting A = Single Compressor, Single Circuit, R-22
service, be sure to refer to the specific model B = Dual Compressor, Dual Circuit, R-22
number, serial number, and DL number (if
DIGIT 8: Electrical Characteristics
applicable) stamped on the unit nameplate.
3 = 208–230/60/3
D I G I T S 1 - 3 : Pr o d u c t Ty p e
4 = 460/60/3
TTA = Split System Cooling
D I G I T S 9 - 10 : F a c t o r y I n s t a l l e d O p t i o n s
DIGITS 4 - 6: No min al Gr oss Co olin g Capacity
00 = Packed Stock
(MBh)
D I G I T S 11 : M i n o r D e s i g n S e q u e n c e
090 = 7.5 Tons (60Hz)
120 = 10 Tons (60Hz) * = Current Design Sequence1
180 = 15 Tons (60Hz) D I GI TS 12 : Serv i c e D ig it
240 = 20 Tons (60Hz) * = Current Design Sequence1
DIGIT 7: Major Develo pment Seq uence
6 SS-SVX12D-EN
General Information
This manual describes proper installation, operation, manual should remain weather-protected with the unit
and maintenance procedures for air-cooled systems. By until all installation procedures are complete.
carefully reviewing the information within this manual N o t e : It is not the intention of this manual to cover all
and following the instructions, the risk of improper possible variations in systems that may occur or
operation and/or component damage will be to provide comprehensive information
minimized. It is important that periodic maintenance be concerning every possible contingency that may
performed to help assure trouble free operation. be encountered during an installation. If
Should equipment failure occur, contact a qualified additional information is required or if specific
service organization with qualified, experienced HVAC problems arise that are not fully discussed in this
technicians to properly diagnose and repair this manual, contact your local sales office.
equipment.
Use the “Installation Checklist,” p. 27 provided In this
I m p o rt a n t : All phases of this installation must comply manual to verify that all necessary installation
with the NATIONAL, STATE & LOCAL procedures have been completed. Do not use the
CODES. In addition to local codes, the checklist as a substitute for reading the information
installation must conform with National contained in the manual. Read the entire manual
Electric Code -ANSI/NFPA NO. 70 LATEST before beginning installation procedures.
REVISION.
Any individual installing, maintaining, or servicing this
equipment must be properly trained, licensed and
Unit Description
qualified. These condensers come with single and dual
I m p o rt a n t : Do not remove the VFD without first compressor options. Single compressor outdoor units
contacting technical support! For feature a single refrigeration circuitry, requiring only
performance-related questions and one set of refrigerant lines. Dual compressor/dual
diagnostic support in North America call 1- circuit models give true stand-by protection; if one
877-872-6363. Any return requires a claim compressor fails, the second will automatically start-
number FIRST. Removal of the VFD prior to up. Also, the first compressor can be serviced without
this step will void the unit’s warranties. shutting down the unit since the refrigerant circuits are
independent. During light load conditions, only one
Installation procedures should be performed in the compressor will operate to save energy.
sequence that they appear in this manual. Do not
destroy or remove the manual from the unit. The
SS-SVX12D-EN 7
Pre-Installation
Unit Inspection Lifting Recommendations
Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made
WA R N I N G
against the transportation company. Compare the I m p r o p e r U n i t L i ft !
information that appears on the unit nameplate with F a i l u r e t o p r o p e r l y l i ft u n i t c o u l d r e s u l t i n u n i t
ordering and submittal data to ensure the proper unit dropping and possibly crushing operator/
was shipped. Available power supply must be t e ch n i c i a n w h i ch c o u l d r e s u l t i n d e a t h o r s e r i o u s
compatible with electrical characteristics specified on i n j u r y, a n d e q u i p m e n t o r p r o p e rt y- o n l y d a m a g e .
component nameplates. Replace damaged parts with Te s t l i ft u n i t a p p r o x i m a t e l y 2 4 i n ch e s t o v e r i f y
authorized parts only. p r o p e r c e n t e r o f g r a v i t y l i ft p o i n t . To a v o i d
d r o p p i n g o f u n i t , r e p o s i t i o n l i ft i n g p o i n t i f u n i t i s
Inspection Checklist not level.
To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of N OT I C E
the unit.
Equipment Damage!
Inspect individual pieces of the shipment before
Use spreader bar s to prevent straps from
accepting the unit. Check for obvious damage to the
d a m a g i n g t h e u n i t . I n s t a l l t h e b a r s b e t w e e n l i ft i n g
unit or packing material.
s t r a p s , b o t h u n d e r n e a t h t h e u n i t a n d a b ov e t h e
Inspect the unit for concealed damage before it is unit to prevent the straps from crushing the unit
stored and as soon as possible after delivery. cabinet or damaging the finish.
Concealed damage must be reported within 15
days. If concealed damage is discovered, stop Before preparing the unit for lifting, estimate the
unpacking the shipment. Do not remove damaged approximate center of gravity for lifting safety. Because
material from the receiving location. Take photos of of placement of internal components, the unit weight
the damage if possible. The owner must provide may be unevenly distributed. See “Weights,” p. 14 for
reasonable evidence that the damage did not occur approximate unit weights.
after delivery. The crated unit can be moved using a forklift of suitable
Notify the carrier’s terminal of damage immediately capacity. For lifting the unit, attach lifting straps or
by phone and by mail. Request an immediate joint slings securely to the lifting holes at each corner (see
inspection of the damage by the carrier and the unit drawings in “Weights,” p. 14). Use spreader bars
consignee. to protect the unit casing from damage. Test lift the unit
to determine proper balance and stability.
Notify the sales representative and arrange for
repair. Do not repair the unit until the damage is
inspected by the carrier’s representative. Clearances
Provide enough space around the unit to allow
Testing for Leaks unrestricted access to all service points. Refer to the
“Dimensional Data,” p. 10 for unit dimensions and
All units are shipped with a holding charge of nitrogen
minimum required service and free air clearances.
in each circuit and should be leak tested before
Observe the following points to ensure proper unit
installation.
operation.
1. Remove the access panel.
1. Do not install the unit under a low overhang.
2. Locate the liquid line or suction line access valve for Condenser discharge must not be restricted—refer
each circuit. to notes in “Dimensional Data drawings,” p. 10.
3. Install gauges to determine if the circuits are still I m p o rt a n t : Do not obstruct condenser discharge
pressurized. If not, the charge has escaped and air. This can result in warm air
should be repaired as required to obtain a leak-free recirculation through the coil.
circuit.
2. Do not locate the unit in a position where runoff
water can fall into the fan discharge openings.
3. Condenser intake air is supplied from three or four
sides of the unit. Adhere to the minimum required
clearances given in unit dimensional drawings (see
“Dimensional Data,” p. 10).
8 SS-SVX12D-EN
Pre-Installation
WA R N I N G Ou td o o r Un it
Ga s (S u ctio n )
Mounting Integrity! Lin e - In s u la te d
Fai l ure t o fol l ow i ns tr uc ti on be l ow c ou ld r es ul t i n Liq u id Lin e
death or serious injury or possible equipment or In s u la te d
p r o p e rt y- o n l y d a m a g e . 6”
E n s u r e t h e r o o f s t r u c t u r e s u p p o rt s a r e s t r o n g Un it Mo u n tin g Ra d iu s
Ch a n n e ls
e n o u g h t o s u p p o rt t h e w e i g h t o f t h e u n i t a n d a n y
accessories. Ele va tio n
(Mo u n tin g Fra m e )
Structural Preparation
N OT I C E
Ro o f D a m a g e ! Ro o f
Co n s tru ctio n
Sy s t e m c o n t a i n s o i l a n d r e f r i g e r a n t u n d e r h i g h
pressu re. Roof s shou ld b e pr otected fro m Ro o f Tru s s in g
exposure to oils and refrigerant in the system. If
r o o ft o p i s n o t p r o t e c t e d , d a m a g e t o t h e r o o f m a y
o c c u r. Ce ilin g
SS-SVX12D-EN 9
Dimensional Data
Figure 2. Height, width and depth measurements
H
W
D
D W
10 SS-SVX12D-EN
Dimensional Data
Figure 3. 7.5 ton condensing unit, single compressor, tube and fin
SEE NOTE 3
NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
W ALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219. 2)
SERVICE PANEL 3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)
SEE NOTE 4
HAIL GUARD
(OP TIONAL)
S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE) S EE NOTE 1
35 15/1 6"
HAIL GUARD (912 .8) REFRIGERANT ACCES S
(OP TIONAL) LINE VOLTAGE WITH HAIL GUARD
33 7/8"
(86 0.4)
CONT ROL WIRING
1/16"
7 15/16" (1.59) 6" (152.4) 2 7/8"
(201.6) 6" (152.4) (73)
SUCTION LINE
21 11 /16" 1 7/8"
(55 0.9) (47.6) 40 15/16"
LIQUID LINE (1039.8)
33 13/1 6" 41 15/16"
(858 .8) (1065. 2)
WITH HAIL GUARD
SERVIC E P ANEL S IDE
40 3/4" BOTTOM
(1035) 34 3/4"
(882.6) OF UNIT
4 3/16"
(106.36)
1 13/16" 27 11/ 16" 2 5/16"
(46) (703.3 ) (58.7)
SS-SVX12D-EN 11
Dimensional Data
NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
SERVICE PANEL WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)
HAIL GUARD
SEE NOTE 4 (OP TIONAL)
S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE
S EE NOTE 1
39 15 /16"
(1014 .4) REFRIGERANT ACCES S
HAIL GUARD 4 1/4" WITH HAIL GUARD
(OP TIONAL) (108)
1 1/4" 37 15/1 6"
(31.7) LINE VOLTAGE
(963 .6)
CONTROL WIRING
39 1/8"
SER VICE P ANEL (993.8)
34 1/16" (865.2)
29 3/4" 26 7/8"
(755.6) (682.6)
14 5/16"
7 1/2" 8 1/4" (363.5)
(190.5) (209.5)
1/16"
SUCTION LINE (1.6) 1 7/8"
1 15/16" (49.2) 6" 25 11/1 6" 6" (47.6)
LIQUID LINE (152. 4) (652 .5) (152. 4) 2 7/8" (73)
4 15/16" 50 15/16"
(125.4) 37 11/1 6" (1294)
(957 .3)
51 15/16"
(1319.2)
WITH HAIL GUARD
50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)
3 13/16"
(96.8)
12 SS-SVX12D-EN
Dimensional Data
Figure 5. 15-20 ton condensing unit, dual compressor, tube and fin
HAIL GUARD
(OP TIONAL)
SEE NOTE 3
S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 1
FOR CLEARANCE)
SERVICE PANEL
DETAIL A 46"
95 7/16" (1168.4)
(2424) WITH HAIL GUARD
WITH HAIL GUARD
41 7/16" 44"
(1052.5) (1117. 6)
HAIL GUARD
(OP TIONAL) HAIL GUARD
(OP TIONAL)
45 1/8"
(1146.2)
3 3/8" 1/16"
(85.7) 3/16"
SER VICE (1.6)
6 5/8" (4.8)
P ANEL
(168.3) 41 3/8"
(1051) 9" 25 11/16" 9"
(228.6) (652.5) (228. 6)
93 5/16"
(2370.1)
9 1/4" (235)
6 13/16" (173)
7/16" (11.1) DIA. ISOLATOR MOUNTING 1 3/16" (30.2)
CONTROL
HOLES (OUTS IDE HOLES - 4 P LACES ) LINE VOLTAGE WIRING
REFRIGERANT ACCES S
41 5/8"
39 7/8" (1057.3)
(1012.8)
18 3/4"
BOTTOM OF UNIT
41 1/ 2" (476.2) 14 5/8"
36 7/8" (105 4) (371.5)
(936.6)
12 9/16"
(319.1) LIQUID LINES
5 9/16"
4 3/8"
(141.3)
(111.1)
3" (76. 2) 2 3/16" 6 13/16" S UCTION LINE 6 5/16" (160.3)
87" (55.6) (173)
(2210) 3 11/16" (93.7)
93" 15/16" (23.8)
(2362.2)
FRO NT DETAIL A
DIMENS IONAL DETAIL
SS-SVX12D-EN 13
Weights
Cooling Condenser
Table 1. TTA unit and corner weights — lbs (60 Hz)
#3 #4
#4 #1
#1
#3
#2
S ER
AC C VIC E
ES S #2
S ER
S ER AC C VIC E
AC C VIC E ES S
ES S
LIFTING HOLES
(BOTH S IDES )
14 SS-SVX12D-EN
Installation
Refrigerant Piping Guidelines
Figure 8. Allowable elevation difference: Above indoor unit
N o t e : Route refrigerant piping for minimum linear length, minimum number of bends and fittings (no reducers) and
minimum amount of line exposed to outdoor ambients.
SS-SVX12D-EN 15
Installation
N OT I C E
Syste m Component Dam age!
Install a regulating valve between the nitrogen
s o u r c e a n d t h e ga u g e m a n i f o l d . U n r e g u l a t e d
pressure can damage system components.
16 SS-SVX12D-EN
Installation
1. Remove both seal caps from the indoor unit System Evacuation
connection stubs.
1. After completion of leak check, evacuate the
N OT I C E system.
Unit Damage! 2. Attach appropriate hoses from manifold gauge to
gas and liquid line pressure taps.
Do n ot re move the se a l cap s fr om r ef ri ge ra nt
connections, or open the service valves until N o t e : Unnecessary switching of hoses can be
prepared to braze refrigerant lines to the avoided and complete evacuation of all lines
connections. leading to sealed system can be
accomplished with manifold center hose and
2. Turn on nitrogen supply. Nitrogen enters through connecting branch hose to a cylinder of R–22
the liquid line gauge port. and vacuum pump.
3. Braze the liquid line connections. 3. Attach center hose of manifold gauges to vacuum
4. Open the gauge port on the suction line and then pump.
braze the suction line to the connection stub.
Nitrogen will bleed out the open gauge port on the N OT I C E
suction line.
O p e r a t i n g U n d e r Va c u u m !
5. Shut off nitrogen supply. Fa il u re to f ol lo w the s e i ns tr uc ti ons wi l l re s ul t in
compressor failure.
Leak Check Do not operate or apply power to the compressor
while under a vacuum.
WA R N I N G
4. Evacuate the system to hold a 500 micron vacuum.
Hazard of Explosion!
5. Close off valve to vacuum pump and observe the
Fai l ure t o fol l ow t he se rec o m m en da ti ons c oul d
micron gauge. If gauge pressure rises above 500
result in death or serious injury or equipment or
microns in one minute, then evacuation is
p r o p e rt y- o n l y d a m a g e .
incomplete or the system has a leak.
Use only dry nitrogen with a pressure regulator for
pre ssu ri zin g uni t. Do n ot use a ce ty le ne , ox yg en or 6. If vacuum gauge does not rise above 500 microns in
compressed air or mixtures containing them for 10 minutes, the evacuation should be complete.
pressure testing. Do not use mixtures of a
hy d r o g e n c o n t a i n i n g r e f r i g e r a n t a n d a i r a b ov e N OT I C E
atmospheric pressure for pressure testing as they Equipment Damage!
may become flammable and could result in an
C h a r g e w i t h a c c e s s p o rt o n t h e l i q u i d l i n e s e r v i c e
e x p l o s i o n . Re f r i g e r a n t , w h e n u s e d a s a t r a c e ga s
v a l v e o n l y.
should only be mixed with dry nitrogen for
pressurizing units. 7. With vacuum pump and micron gauge blanked off,
open valve on R–22 cylinder and allow refrigerant
pressure to build up to about 80 psig.
8. Close valve on the R–22 supply cylinder. Close
valves on manifold gauge set and remove
SS-SVX12D-EN 17
Installation
refrigerant charging hoses from liquid and gas Refrigerant Charging Procedure
gauge ports.
If charging by weight, refer to for starting change. If
9. Leak test the entire system. Using proper refrigerant adjustments are needed because of length
procedures and caution, as described in the of line, refer to “Charging Charts and Superheat,” p. 26.
previous section, repair any leaks found and repeat
the leak test. Charge by weight through the gauge port on the liquid
line. Once the charge enters the system, backseat
(open) the liquid line service valve and disconnect the
Insulating and Isolating charging line and replace the cap on the gauge port.
Refrigerant Lines Notes:
Insulate the entire suction line with refrigerant piping • R-22 should only be charged in the liquid
insulation. Also insulate any portion of the liquid line state.
exposed to temperature extremes. Insulate and isolate • When possible, always charge the
liquid and suction lines from each other. Isolate refrigerant into the liquid line of the unit.
refrigerant lines from the structure and any duct work.
• If the entire charge can’t be charged into the
I m p o rt a n t : liquid line, the balance of the unit charge can
1. To prevent possible noise or vibration be metered through a charging manifold set
problems, be certain to isolate as liquid — preferably through a schrader
refrigerant lines from the building. valve into the suction line to the compressor
— only while the compressor is running.
2. All suction and hot gas bypass piping (if
installed) should be insulated from the • Check and adjust superheat using Table 6, p.
termination in the air handler to the 26, then re-check charging charts to
condensing unit cabinet entry. Failure to determine if charge corrections are
do so can cause condensate drip off and necessary.
performance degradation.
3. Prior to starting a unit, it is advisable to
N OT I C E
have the approved oils available in the Equipment Damage!
event oil needs to be added to the N e v e r ch a r g e l i q u i d r e f r i g e r a n t i n t o t h e s u c t i o n
system. l i n e o f t h e u n i t w i t h t h e c o m p r e s s o r o ff.
18 SS-SVX12D-EN
Installation
Charging Levels
Table 3. Estimated charge levels at ARI rated line lengths (25 feet)
Liquid Charging WA R N I N G
This procedure is accomplished with the unit H a z a r d o u s Vo l t a g e w / C a p a c i t o r s !
operating. Electrical connections must be complete. Do F a i l u r e t o d i s c o n n e c t p o w e r a n d d i s ch a r g e
not proceed until the system is ready to operate. capacitor s before servicing could result in death or
N o t e : The compressor access panel must be installed s e r i o u s i n j u r y.
when the unit is running and being charged. D i s c o n n e c t a l l e l e c t r i c p o w e r, i n c l u d i n g r e m o t e
Manifold hoses must be routed through d i s c o n n e c t s a n d d i s ch a r g e a l l m o t o r s t a rt / r u n
refrigerant gauge access hole(s). See c a p a c i t o r s b e f o r e s e r v i c i n g . F o l l o w p r o p e r l o ck o u t /
“Dimensional Data,” p. 10 for specific locations. tagout procedures to ensure the power cannot be
i n a d v e rt e n t l y e n e r g i z e d . F o r v a r i a b l e f r e q u e n c y
WA R N I N G dri ves or other energy storing components
p r ov i d e d b y Tr a n e o r o t h e r s , r e f e r t o t h e
Li ve Electrical Components! a p p r o p r i a t e m a n u f a c t u r e r ’s l i t e r a t u r e f o r
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s a l l o w a b l e w a i t i n g p e r i o d s f o r d i s ch a r g e o f
when exposed to li ve electrical components could c a p a c i t o r s . Ve r i f y w i t h a n a p p r o p r i a t e v o l t m e t e r
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. t h a t a l l c a p a c i t o r s h a v e d i s ch a r g e d .
When it is necessary to work with li ve electrical Fo r a dd it io na l i nfo rm a ti on re gar di ng th e s af e
components, have a qualified licensed electrician d i s ch a r g e o f c a p a c i t o r s , s e e P R O D - S V B 0 6 A - E N .
or other indi vidual who has been properly trained
in handling li ve electrical components perform 5. Remove the charging system from the unit.
these tasks.
6. Replace all panels.
1. Turn on power to the unit. Allow the system to run
for 15 minutes to stabilize operating conditions. Electrical Wiring
2. Measure airflow across the indoor coil. Compare
the measurements with the fan performance data in WA R N I N G
the Data/Submittal or Service Facts. Once proper
airflow is established, compare discharge pressure
Prope r Field Wiring a nd Grounding
and liquid temperature to the “Charging Charts,” p. Required!
26. Add or remove refrigerant (liquid only) as Fa il u re to f ol lo w c ode c o ul d r es u lt i n de at h or
required to obtain correct discharge pressure and s e r i o u s i n j u r y.
liquid temperature. All field w ir in g MUST be p er for med b y qualif ied
3. Check suction line superheat and condenser sub- per sonnel. Improperly installed and grounded
cooling to ensure the unit is operating properly. field wiring poses FIRE and ELECTROCUTION
h a z a r d s . To a v o i d t h e s e h a z a r d s , y o u M U S T f o l l o w
4. Disconnect all power to the unit. requirements for field wiring installation and
I m p o rt a n t : If the unit is charged and left without grounding as described in NEC and your local/
power until a later date, the crankcase state electrical codes.
heater should be energized for a
minimum of 8 hours prior to powering Field wiring consists of providing power supply to the
the compressor(s). unit, installing the system indoor thermostat and
providing low voltage system interconnecting wiring.
Access to electrical connection locations is shown in
“Dimensional Data,” p. 10. Determine proper wire sizes
and unit protective fusing requirements by referring to
SS-SVX12D-EN 19
Installation
the unit nameplate and/or the unit Service Facts. Field I m p o rt a n t : For the EDC switch to be functional and
wiring diagrams for accessories are shipped with the thereby facilitate reliable unit operation,
accessory. make the EDC connections from the indoor
to the outdoor control boxes.
Unit Power Supply
Figure 12. Electromechanical jobsite connections
The installer must provide line voltage circuit(s) to the Disconnect S witch
unit main power terminals as shown by the unit wiring (By Others)
diagrams (available through e-Library or by contacting
a local sales office) or field wiring. Power supply must
include a disconnect switch in a location convenient to B Air Handler
the unit. Ground the unit according to local codes and
Electric
provide flexible conduit if codes require and/or if Heat Accessory
T’s t a t
vibration transmission may cause noise problems.
C
I m p o rt a n t : All wiring must comply with applicable
local and national (NEC) codes. Type and B
D Disconnect S witch
location of disconnect switches must (By Others) Note 2
comply with all applicable codes.
A Disconnect S witch
(By Others)
WA R N I N G A. 3 power wires, line voltage for 3 phase, (2 power wires for
Pr o p e r F i e l d W i r i n g a n d G r o u n d i n g single phase)
B. 3 power wires, line voltage for 3 phase, (2 power wires for
Re q u i r e d! single phase)
C. Cooling only thermostat: 3 to 7 wires depending on stages of
Fai l ure t o fol l ow c od e c oul d re s ul t in d ea th o r
electric heat
s e r i o u s i n j u r y. D. 3 to 7 wires depending on type of outdoor unit(s)
A l l f i e l d w i r i n g M U ST b e p e r f o r m e d b y q u a l i f i e d
per sonnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION ReliaTel Controls
h a z a r d s . To a v o i d t h e s e h a z a r d s , y o u M U ST f o l l o w
Wiring shown with dashed lines is to be furnished and
requirements for field wiring installation and
installed by the customer. All customer supplied wiring
grounding as described in NEC and your local/
must be copper only and must conform to NEC and
state electrical codes.
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
N OT I C E Notes:
Use Copper Conductor s Only! 1. When electric heater accessory is used,
Fai l ure t o us e c op pe r c o ndu ct or s c o ul d r es ul t i n single point power entry or dual point power
equipment damage as unit terminals are not entry is field optional. Single point power
designed to accept other types of conductors. entry option is through electric heater only.
2. ***Choose only one of the following;
Low Voltage Wiring Thermostat, Zone Sensor, or NSB Panel.
Mount the indoor thermostat, zone sensor, or Night I m p o rt a n t : For the EDC switch to be functional and
Setback Panel (NSB) in accordance with the thereby facilitate reliable unit operation,
corresponding thermostat installation instructions. make the EDC connections from the indoor
Install color-coded, weather-proof, multi-wire cable to the outdoor control boxes.
according to the field wiring schematics (see “Field
Wiring,” p. 21).
Electromechanical Controls
Wiring shown with dashed lines is to be furnished and
installed by the customer. All customer supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
N o t e : When electric heater accessory is used, single
point power entry or dual point power entry is
field optional. Single point power entry option is
through electric heater only.
20 SS-SVX12D-EN
Installation
A Disconnect S witch
(By Others)
C E F
Field Wiring
Figure 14. Night setback panel field wiring
SS-SVX12D-EN 21
Installation
22 SS-SVX12D-EN
Installation
SS-SVX12D-EN 23
Installation
Refrigerant Circuit
Figure 18. Typical split system cooling refrigerant circuit
COOLING ONLY CIRCUIT DIAGRAM
DISCHARGE
TEMPERATURE
LIMIT (DTL)
GAUGE HIGH PRESSURE
CONNECTION SWITCH (HPCO)
NOTE A
D
NOTE A
FIELD SUPPLIED
S INTER-CONNECTING
TUBING
COMPRESSOR
EQUALIZER
EXPANSION TUBE
VALVE BULB
OUTDOOR COIL
AIR
GAUGE
CONNECTION SERVICE
VALVE
NOTE A
AIR
V
TXV
LOW PRESSURE
INDOOR COIL
SWITCH (LPCO)
SERVICE
VALVE
24 SS-SVX12D-EN
Electrical Data
Table 4. Electrical characteristics — compressor and condenser fan motors — 60 Hz
Compressor Motor Condenser Fan Motor
SS-SVX12D-EN 25
Charging Charts and Superheat
Figure 19. TTA090A charging curve Figure 21. TTA180B charging curve
425 425
400 400
375 375
350 350
Re m o ve Re m o ve
c h a rg e c h a rg e
Dis c h a rg e P re s s u re , p s ig
Dis c h a rg e P re s s u re , p s ig
325 325
300 300
275 275
250 250
225 Ad d c h a rg e 225 Ad d c h a rg e
200 200
175 175
150 150
125 125
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te m p e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F
Figure 20. TTA120A charging curve Figure 22. TTA240B charging curve
425 425
400 400
375 375
350 350
Re m o ve Re m o ve
c h a rg e c h a rg e
Dis c h a rg e P re s s u re , p s ig
Dis c h a rg e P re s s u re , p s ig
325 325
300 300
275 275
250 250
225 Ad d c h a rg e 225 Ad d c h a rg e
200 200
175 175
150 150
125 125
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te m p e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F
Cooling Superheat
Notes:
1. An adjustable TXV is provided for each circuit in the TWE and TWA models. If the application causes the superheat to deviate from the values shown
above by more than 1 degree - after the system has achieved steady state - the TXV should be adjusted to provide the values shown as measured at
the compressor.
2. The values given above have been tested and are approved for the matched sets shown. If an alternate combination is used, an expansion device
should be used that provides 16-20°F degrees of superheat measured at the compressor.
3. Check and adjust superheat using this table, then compare with charging chart to determine if charge corrections are necessary.
26 SS-SVX12D-EN
Installation Checklist
Complete this checklist once the unit is installed to Insulated portions of liquid line exposed to
verify that all recommended procedures have been extremes in temperature?
accomplished before starting the system. Do not Performed initial leak test?
operate the system until all items covered by this
checklist are complete. Evacuated each refrigerant circuit to 500 microns?
Inspect unit location for proper required service Charged each circuit with proper amount of R-22?
clearances.
Inspect unit location for proper free air clearances. Electrical Wiring
Inspect unit location for secure, level mounting Provided unit power wiring (with disconnect) to
position. proper terminals in the unit control section?
Installed system indoor thermostat?
Refrigerant Piping Installed system low voltage interconnecting wiring
Properly sized/constructed liquid and suction lines to proper terminals of outdoor unit, indoor unit and
connected to stubs at both the indoor and outdoor system thermostat?
units?
Insulated the entire suction line?
SS-SVX12D-EN 27
Pre-Start
Control Circuit Features drops below the Low Pressure Cut-Out setting. Once
the suction pressure has returned to normal, the
N o t e : Not all of these features may be required for your compressor and outdoor fans will cycle back on.
unit, check electrical schematic.
High Pressure Cut-Out (HPCO)
Discharge Temperature Limit (DTL)
This control’s sensor is located in the discharge line.
The control’s sensor is located on the discharge line. This device will shut off the compressor and the
This device will shut off the compressor and the outdoor fan(s) if the discharge pressure exceeds the
outdoor fan(s) if the discharge temperature exceeds the High Pressure Cut-Out’s setting. Once the discharge
DTL setting. Once the discharge temperature has pressure has returned to normal, the compressor will
returned to normal, the compressor will cycle back on. cycle back on.
Low Outdoor Ambient Cooling
WA R N I N G
The Evaporator Defrost Control is standard equipment
Prevent Injury!
on Air Handlers and will permit low ambient cooling
down to 50°F. For cooling operation down to 0°F, use an D u e t o a g e n c y s a f e t y r e q u i r e m e n t s , n o s ch r a d e r
Accessory Head Pressure Control on the outdoor unit. c o r e i s t o b e i n s t a l l e d b e n e a t h t h e H P C O. R e m o v a l
o f t h e H P C O w i t h o u t e v a c u a t i n g t h e s y s t e m ch a r g e
Evaporator Defrost Control (EDC) could cause injury and release of refrigerant.
28 SS-SVX12D-EN
Start-Up
Electromechanical Controls evaporator fan contactor also energizes on a call for
cooling and initiates evaporator fan operation.
The 24–volt, electromechanical controls feature a
control transformer and contactor pressure lugs for On units with dual circuits, the second stage of cooling
power wiring. Once the unit is properly installed and is initiated as a result of the 2-stage thermostat calling
pre-start procedures are complete, start the unit by for additional cooling.
turning the System Switch on the indoor thermostat to
either H E AT, C O O L or A U TO. The system should ReliaTel Controls
operate normally.
The ReliaTel™ Control is a microelectronic control
N OT I C E feature, which provides operating functions that are
significantly different than conventional
Equipment Damage! Electromechanical units. The ReliaTel™ Refrigeration
Ensure the disconnect for the indoor air handler is Module (RTRM) uses Proportional/Integral control
closed before operating the system. Operating the algorithms to perform specific unit functions that
o u t d o o r u n i t w i t h o u t t h e i n d o o r f a n e n e r g i ze d ca n govern the unit operation in response to application
cause unit trip-out on high pressure control and/or conditions.
l i q u i d f l o o d b a ck t o t h e c o m p r e s s o r. The RTRM provides compressor anti-short cycle timing
functions through minimum “O ff” and “O n ” timing to
General increase reliability, performance and to maximize unit
efficiency. Upon power initialization, the RTRM
Operation of the system cooling (and optional heating)
performs self-diagnostic checks to ensure that all
cycles is controlled by the position of the system switch
internal controls are functioning. It checks the
on the room thermostat. Once the system switch is
configuration parameters against the components
placed in either the H E AT or C O O L position, unit
connected to the system. The system LED located on
operation is automatic. The optional automatic
the RTRM module is turned “O n” within one second
changeover thermostat, when in the A U TO position,
after power-up if all internal operations are okay.
automatically changes to heat or cool with sufficient
room temperature change. Once the unit is properly installed and pre-start
procedures are complete, start the unit by turning the
Evaporator Fan (Indoor Supply Air) System Switch on the indoor thermostat to either
H E AT, C O O L or AU TO. The system should operate
The evaporator fan is controlled by an O N / A U TO normally.
switch on the room thermostat. With the switch
positioned at A U TO and the system operating in the
cooling mode, fan operation coincides with the cooling
N OT I C E
run cycles. If the system is equipped with heat and is Equipment Damage!
operating in the heating mode while the fan switch is at Ensure the disconnect for the indoor air handler is
A U TO, fan operation coincides with the heating run closed before operating the system. Operating the
cycles. When the fan switch is positioned at O N , fan outdoor unit without the indoor fan energized can
operation is continuous. cause unit trip-out on high pressure control and/or
l i q u i d f l o o d b a ck t o t h e c o m p r e s s o r.
Cooling Mode
With the disconnect switch in the O N position, current Control Cooling Mode
is supplied to the compressor sump heater(s), phase
monitor and control transformer. The sump heater(s) For Zone Sensor Control
supplies heat to the compressor(s) during the “O ff” When the system switch is set to the C O O L position
cycle. The phase monitor looks at the incoming power and the zone temperature rises above the cooling
to verify that there is no reversed phase, no phase setpoint, the RTRM energizes the compressor
imbalance, and no loss of phase. If the phase monitor contactor, provided the high and low pressure and the
detects any of these three conditions, it will shut off discharge temperature limit controls are closed. When
control voltage. The transformer steps down the line the compressor contacts close, the compressor and the
voltage to 24V for the low voltage control circuit. When outdoor fan motor start to maintain the zone
the room thermostat system switch is positioned at temperature to within ± 2°F of the sensor setpoint at
C O O L and the fan switch is at A U TO, the compressor the sensed location. On units with dual circuits, the
contactor energizes on a call for cooling. When the second stage of cooling is initiated as a result of the
contacts of the compressor contactor close, operation Proportional/Integral control algorithms calling for
of the compressor and condenser fan begins. The additional cooling.
SS-SVX12D-EN 29
S t a rt - U p
For Thermostat Control cooling requirement has been satisfied to enhance unit
When the room thermostat system switch is positioned efficiency. When the heating cycle is terminated, the
at C O O L and the fan switch is at A U TO, the RTRM evaporator fan relay coil is de-energized at the same
energizes the compressor contactor, provided the high time as the heater contactors. When the fan selection
and low pressure and the discharge temperature limit switch is set to the O N position, the RTRM keeps the
controls are closed. When the contacts of the evaporator fan relay coil energized for continuous fan
compressor contactor close, operation of the motor operation.
compressor and condenser fan begins. The evaporator
fan contactor also energizes on a call for cooling and
Control Heating Operation
initiates evaporator fan operation. On units with dual Electric heat is factory disabled on all split system units
circuits, the second stage of cooling is initiated as a with ReliaTel control (jumper placed between J2-1 and
result of the 2-stage thermostat calling for additional J2-2 RTRM inputs). To configure the unit for electric
cooling. heat, cut or remove the jumper wire between J2-1 and
N o t e : Irregular unit operation may occur when the unit J2-2 on the RTRM. All split system units with ReliaTel
is controlled with a triac-switching thermostat. control are also configured from the factory for only 1-
Please review the approved thermostat vendor stage of electric heat (jumper placed between J1-3 and
list for all recommended relay-switching J1-6 RTRM inputs). To configure the unit for 2-stages of
thermostats. electric heat, cut or remove the jumper placed between
J1-3 and J1-6 RTRM inputs.
Control Evaporator Fan Operation When the system switch is set to the H E AT position
When the fan selection switch is set to the A U TO and heating is required, the RTRM energizes the Heat 1
position, the RTRM energizes the evaporator fan relay relay coil on the RTRM. When the Heat 1 relay contacts
coil approximately 1 second after energizing the close, the first stage electric heat contactor is
compressor contactor coil in the cooling mode. In the energized. If the first stage of electric heat cannot
heating mode, the RTRM energizes the evaporator fan satisfy the heating requirement, the RTRM energizes
relay coil approximately 1 second before energizing the the Heat 2 relay coil on the RTRM. When the Heat 2
electric heat contactors. relay contacts close, the second stage electric heat
contactor is energized. The first and second stages of
The RTRM de-energizes the evaporator fan relay coil heat are cycled “O n” and “O ff” as required to maintain
approximately 60 seconds on dual compressor units the zone.
and 80 seconds on single compressor units after the
30 SS-SVX12D-EN
Service Test Modes for ReliaTel™
™ Controls
Test Modes Step Test Mode
Upon power initialization, the RTRM performs self- This method initiates the different components of the
diagnostic checks to ensure that all internal controls are unit, one at a time, by temporarily shorting across the
functional. It also checks the configuration parameters two test terminals for 2 to 3 seconds.
against the components connected to the system. The For the initial start-up of the unit, this method allows
system LED located on the RTRM module is turned the technician to cycle a component “O n” and have up
“O n ” within one second of power-up if internal to one hour to complete the check. Service Test Mode
operation is okay. will be ignored if a short is present across Test 1 and
Use one of the following “ Te s t ” procedures to bypass Test 2 at start-up.
some time delays and to start the unit at the control
panel. Each step of unit operation can be activated Resistance Test Mode
individually by temporarily shorting across the “ Te s t ”
This method can be used for start-up when a decade
terminals for 2 to 3 seconds. The system LED located
box for variable resistance outputs is available. This
on the RTRM module will blink when the test mode has
method initiates the different components of the unit,
been initiated. The unit can be left in any “ Te s t ” step
one at a time, when a specific resistance value is placed
for up to one hour before it will automatically
across the two test terminals. The unit will remain in
terminate, or it can be terminated by opening the main
the specific test mode for approximately one hour even
power disconnect switch. Once the test mode has been
though the resistance is left on the test terminals.
terminated, the system LED will glow continuously and
the unit will revert to the “ S y s t e m ” control.
There are three methods in which the “ Se r v i c e Te s t ”
can be cycled at LTB-Test 1(T1) and LTB-Test 2 (T2).
Auto Test Mode The unit will start the first test step and change to the
next step every 30 seconds. At the end of the test
This method is not recommended for start-up due to
mode, control of the unit will automatically revert to the
the short timing between individual component steps.
applied “ Sy s t e m ” control method. For unit test steps,
This method initiates the different components of the
test modes, and step resistance values to cycle the
unit, one at a time, when a fixed jumper is installed
various components, refer to Table 7, p. 31.
across the test terminals.
SS-SVX12D-EN 31
Troubleshooting
Troubleshooting ReliaTel™ outputs, and all of the external controls (relays,
contactors, etc.) that the RTRM outputs energize, for
Controls each respective mode. Proceed to Step 6.
WA R N I N G 6. Step the system through all of the available modes,
and verify operation of all outputs, controls, and
Li ve Electrical Components! modes. If a problem in operation is noted in any
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s mode, you may leave the system in that mode for
when exposed to li ve electrical components could up to one hour while troubleshooting. Refer to the
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. sequence of operations for each mode, to assist in
When it is necessary to work with li ve electrical verifying proper operation. Make the necessary
components, have a qualified licensed electrician repairs and proceed to Step 7 and Step 8.
or other indi vidual who has been properly trained
7. If no abnormal operating conditions appear in the
in handling li ve electrical components perform
test mode, exit the test mode by turning the power
these tasks.
“O ff” at the main power disconnect switch.
The RTRM has the ability to provide the service 8. Refer to the individual component test procedures if
personnel with some unit diagnostics and system other microelectronic components are suspect.
status information.
Before turning the main power disconnect switch “O ff,” System Status Checkout
follow the steps below to check the ReliaTel™
Refrigeration Module (RTRM). All diagnostics & system Procedure
status information stored in the RTRM will be lost when “ Sy s t e m S t a t u s ” is checked by using one of the
the main power is turned “O ff”. following two methods:
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard Method 1
and use extreme care when performing service
If the Zone Sensor Module (ZSM) is equipped with a
procedures with the electrical power energized.
remote panel with LED status indication, you can check
N o t e : The J6 & J7 screw terminals must be tightened the unit within the space. If the ZSM does not have
in order to accurately measure voltage in the LED’s, use “Method 2,” p. 33. BAYSENS010B,
required steps. BAYSENS011B, BAYSENS119A, BAYSENS020A,
1. Verify that the system LED on the RTRM is burning BAYSENS021A, BAYSENS023A, BAYSENS109 and
continuously. If the LED is lit, go to Step 3. BAYSENS110 all have the remote panel indication
feature. The LED descriptions are listed below.
2. If the LED is not lit, verify that 24 VAC is present
between J1-1 and J1-2. If 24 VAC is present, • L E D 1 ( Sy s t e m )
proceed to Step 3. If 24 VAC is not present, check – “O n ” during normal operation.
the unit main power supply, check transformer
– “O ff” if a system failure occurs or the LED fails.
(TNS1). Proceed to Step 3 if necessary.
– “ F l a s h i n g ” indicates test mode
3. Utilizing “Method 1,” p. 32 or “Method 2,” p. 33 in
the System Status Checkout Procedure section, • LED 2 (Heat)
check the following: – “O n ” when the heat cycle is operating.
• System status – “O ff” when the heat cycle terminates or the LED
• Heating status fails.
• Cooling status – “ F l a s h i n g ” indicates a heating failure.
N o t e : If a System failure is indicated, proceed to • LED 3 (Cool)
Step 4. If no failures are indicated, proceed to
Step 5. – “O n ” when the cooling cycle is operating.
4. If a System failure is indicated, recheck Step 1 and – “O ff” when the cooling cycle terminates or the
Step 2. If the LED is not lit in Step 1, and 24 VAC is LED fails.
present in Step 2, then the RTRM has failed. – “ F l a s h i n g ” indicates a cooling failure.
Replace the RTRM.
The following information describes the complete
5. If no failures are indicated, use one of the TEST listing of failure indication causes.
mode procedures described in the “Service Test
Modes chapter,” p. 31 to start the unit. This
procedure will allow you to check all of the RTRM
32 SS-SVX12D-EN
Tr o u b l e s h o o t i n g
SS-SVX12D-EN 33
Tr o u b l e s h o o t i n g
Range = 100 to 900 Ohms approximate Test 3 - System Mode and Fan Selection
H e a t S P = Terminals 2 and 5 The combined resistance of the M O D E selection switch
Range = 100 to 900 Ohms approximate and the FA N selection switch can be measured
between terminals 2 and 4 on the Zone Sensor. The
possible switch combinations are listed in Table 9, p. 34
with their corresponding resistance values.
Test 4 - LED Indicator Test (SYS ON, high resistance in both directions, LED is open. If low in
HEAT, & COOL) both directions, LED is shorted.
WA R N I N G Method 3
To test LED’s with ZSM connected to unit, test voltages
Li ve Electrical Components! at LED terminals on ZSM. A measurement of 32 VDC,
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s across an unlit LED, means the LED has failed.
when exposed to li ve electrical components could
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. I m p o rt a n t : Measurements should be made from LED
common (ZSM terminal 6 to respective LED
When it is necessary to work with li ve electrical
terminal).
components, have a qualified licensed electrician
or other indi vidual who has been properly trained
in handling li ve electrical components perform Programmable & Digital Zone
these tasks.
Sensor Test
Method 1 Testing Serial Communication Voltage
Testing the LED using a meter with diode test function.
1. Verify 24 VAC is present between terminals J6-14 &
Test both forward and reverse bias. Forward bias
J6-11.
should measure a voltage drop of 1.5 to 2.5 volts,
depending on your meter. Reverse bias will show an
Over Load, or open circuit indication if LED is
functional.
Method 2
Testing the LED with an analog Ohmmeter. Connect
Ohmmeter across LED in one direction, then reverse
the leads for the opposite direction. The LED should
have at least 100 times more resistance in reverse
direction, as compared with the forward direction. If
34 SS-SVX12D-EN
Tr o u b l e s h o o t i n g
SS-SVX12D-EN 35
Maintenance
WA R N I N G Remove any accumulation of dust and/or dirt from
the unit casing.
H a z a r d o u s Vo l t a g e w / C a p a c i t o r s !
Remove corrosion from any surface and repaint.
F a i l u r e t o d i s c o n n e c t p o w e r a n d d i s ch a r g e
Check the gasket around the control panel door to
capacitor s before servicing could result in death or
ensure it fits correctly and is in good condition to
s e r i o u s i n j u r y. prevent water leakage.
D i s c o n n e c t a l l e l e c t r i c p o w e r, i n c l u d i n g r e m o t e
d i s c o n n e c t s a n d d i s ch a r g e a l l m o t o r s t a rt / r u n Inspect the control panel wiring to ensure that all
c a p a c i t o r s b e f o r e s e r v i c i n g . F o l l o w p r o p e r l o ck o u t / connections are tight and that the insulation is
tagout procedures to ensure the power cannot be intact.
i n a d v e rt e n t l y e n e r g i z e d . F o r v a r i a b l e f r e q u e n c y N o t e : Condenser fan motors are permanently
dri ves or other energy storing components lubricated.
p r o v i d e d b y Tr a n e o r o t h e r s , r e f e r t o t h e
Check refrigerant piping and fittings for leaks
a p p r o p r i a t e m a n u f a c t u r e r ’s l i t e r a t u r e f o r
a l l o w a b l e w a i t i n g p e r i o d s f o r d i s ch a r g e o f Inspect the condenser coils for dirt and debris. If the
c a p a c i t o r s . Ve r i f y w i t h a n a p p r o p r i a t e v o l t m e t e r coils appear dirty, clean them.
t h a t a l l c a p a c i t o r s h a v e d i s ch a r g e d .
For ad di ti on al i n for m at io n rega rdi ng t he s a fe Coil Cleaning
d i s ch a r g e o f c a p a c i t o r s , s e e P R O D - S V B 0 6 A - E N .
Regular coil maintenance, including annual cleaning-
enhances the unit's operating efficiency by minimizing:
N OT I C E • compressor head pressure and amperage draw
O p e r a t i n g U n d e r Va c u u m ! • water carryover
Fai l ure t o fol l ow t he se in st ruc t io ns w il l r es ul t i n • fan brake horsepower
compressor failure. • static pressure losses
Do not operate or apply power to the compressor At least once each year — or more often if the unit is
while under a vacuum. located in a “dirty” environment — clean the coil using
Perform all of the indicated maintenance procedures at the instructions outlined below. Be sure to follow these
the intervals scheduled. This will prolong the life of the instructions as closely as possible to avoid damaging
unit and reduce the possibility of costly equipment the coils.
failure.
Tube and Fin
Monthly N o t e : To clean refrigerant coils, use a soft brush and a
sprayer. Contact your local Parts Center for
Conduct the following maintenance inspections once appropriate detergents.
per month.
1. Remove enough panels from the unit to gain safe
Check unit wiring to ensure all connections are tight access to coil.
and that the wiring insulation is intact.
2. Straighten any bent coil fins with a fin comb.
Inspect the condenser coils for dirt and debris. If the
3. Remove loose dirt and debris from both sides of the
coils appear dirty, clean them.
coil with a soft brush.
With the unit operating in the cooling mode, check
4. Mix the detergent with water according to the
the suction and discharge pressures and compare
manufacturer's instructions. If desired, heat the
them with Pressure Curve values in unit Service
solution to 150° F maximum to improve its
Facts. Record these readings on the “Maintenance
cleansing capability.
Log,” p. 38.
5. Pour the cleaning solution into the sprayer.
Annually (Cooling Season) 6. Spray the leaving-airflow side of the coil first; then
spray the opposite side of the coil. Allow the
The following maintenance procedures must be cleaning solution to stand on the coil for five
performed at the beginning of each cooling season to minutes.
ensure efficient unit operation.
7. Rinse both sides of the coil with cool, clean water.
Perform all of the monthly maintenance
8. Inspect both sides of the coil; if it still appears to be
inspections.
dirty, repeat Step 7 and 8.
With the unit operating, check unit superheat and
9. Reinstall all of the components and panels removed
record the reading in the “Maintenance Log,” p. 38.
36 SS-SVX12D-EN
Maintenance
in Step 1; then restore power to the unit. inadvertently bent during the cleaning process.
10. Using a fin comb, straighten any coil fins that were
SS-SVX12D-EN 37
38
Superheat (°F) Subcooling (°F)
Evaporator Entering Air Compressor (at compressor) (at service valve)
Maintenance Log
Note: Perform each inspection once per month (during cooling season) while unit is operating
SS-SVX12D-EN
Wiring Diagram Matrix
Table 10. Wiring schematics R-22 cooling
Note: Wiring diagrams are available through e-Library or by contacting your local sales office.
SS-SVX12D-EN 39
Notes
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2015 Trane All rights reserved
SS-SVX12D-EN 14 Aug 2015 We are committed to using environmentally
Supersedes SS-SVX12C-EN (January 2014) conscious print practices that reduce waste.