The document provides calculations to determine lightning protection requirements for a building in Egypt. It summarizes that the collective area of the building is 39236 square meters with a environmental coefficient of 0.25. The expected lightning strike frequency is 0.007 events/year. Based on the structure, contents, occupancy, and consequence coefficients, the tolerable lightning strike frequency is calculated to be 0.0022 events/year. As this is less than the expected strike frequency, lightning protection is required at the Class IV level with a mesh grid of 20x20 meters and 9 down conductors.
The document provides calculations to determine lightning protection requirements for a building in Egypt. It summarizes that the collective area of the building is 39236 square meters with a environmental coefficient of 0.25. The expected lightning strike frequency is 0.007 events/year. Based on the structure, contents, occupancy, and consequence coefficients, the tolerable lightning strike frequency is calculated to be 0.0022 events/year. As this is less than the expected strike frequency, lightning protection is required at the Class IV level with a mesh grid of 20x20 meters and 9 down conductors.
The document provides calculations to determine lightning protection requirements for a building in Egypt. It summarizes that the collective area of the building is 39236 square meters with a environmental coefficient of 0.25. The expected lightning strike frequency is 0.007 events/year. Based on the structure, contents, occupancy, and consequence coefficients, the tolerable lightning strike frequency is calculated to be 0.0022 events/year. As this is less than the expected strike frequency, lightning protection is required at the Class IV level with a mesh grid of 20x20 meters and 9 down conductors.
Width: 99 meters H=17.4 meters So, the collective area will be 39236 meters square.
Environmental Coefficient (C1):
Because the building will be surrounded by other structures with the same height or higher so this coefficient will be 0.25.
Average Flash Density (Ng) & Expected Strike Frequency (Nd):
As the location of the building is in Egypt, so the expected number of times of a lightning strike will occur is Td=10 flashes/year. So the probability of lightning strike to occur is Ng=0.7113 event/year. Then we will get Nd=0.007 event/year.
Structural Coefficient (C2):
The structure of the building and the roof materials will be common so C2=1 according to the table
Structure Contents Coefficient (C3):
The structure of the building is non flammable due to the building material so the coefficient will be C3=0.5
Structure Occupancy Coefficient (C4):
The building will be probably occupied according to its application but it will not be a difficult evacuation building.
Lightning Consequence Coefficient (C5):
For an important building like a university, we need to ensure service continuity during lightning strikes. So, C5=5. Then we will calculate the tolerable lightning strike frequency (Nc) using the above constants according to the relation
So, Nc=0.0022 event/year. As Nd < Nc so the protection is
required in this case.
Efficiency “E” = 1-(Nc/Nd) = 0.6857 which is less than 0.8 so the
protection level is Class IV with maximum area of mesh grid equal to 20*20 meters.
Due to building height being lower than 23m, so the number of
down conductors will be the perimeter over 30 so it will be 9.