Professional Documents
Culture Documents
Chapter 3 SCR Unit PDF
Chapter 3 SCR Unit PDF
REVISION HISTORY
Rev. Description ERO/ECN #
A Initial Release - ----
B Formatting and content revisions. Added Revision History page and drawing number C23357
in footer.
C Corrected text, table explanation letter, and procedure step numbering. C24068
D Remove references to Ansaldo Ross Hill on pages 3-15 and 3-28. C24670
E Correct figure placement on pages 49 through 51. C25640
F Update figures. C25719
G Add photo numbers, improve appearance of Figure 3-21, and correct errors in text. C25990
H Convert to Word 97 format. C28670
J Add Table of Contents codes. Correct Level 5 and Level 6 styles and errors. C29222
K Correct Figure 3-13 and accompanying text on page 3-19. C29718
L Correct Figure 3-1, and note on page 3-7 (change “50 Hz” to “60 Hz”). C29857
M Edit two images in SCR Removal and Reassembly Procedure for Front and Rear C31629
Access, Horizontal Bridge.
SCR UNIT
OPERATION SPECIFICATIONS
ELECTRICAL
The SCR Unit rectifies the three-phase AC
supply to provide continuously variable DC Three Phase AC Input
power to the traction motors. The SCR
bridge, which performs the rectification, is Voltage: 600 VAC
isolated by a circuit breaker from the Main Frequency: 60 Hz
AC Bus. The bridge output is assigned to
one of the motors via contactors. The DC Output Per SCR Unit
contactors are closed in pairs (DC+ and
DC-)(refer to Figure 3-1). Current
The contactor logic and the DC voltage
Zero to current-limit-value Amps continuous
level are controlled from the DRILLER'S
at stall throughout maximum voltage.
CONSOLE (refer to Section 4 of this
manual). Electronic circuits in the DC
Current Limits
Control Module regulate the voltage and
current within preset limits.
Different limits are selected to allow
All SCR Units are identical. If one unit is not maximum horsepower and torque to be
working, another is usually available to obtained from the Rig Equipment without
maintain power to the motor. Similarly, the exceeding the Manufacturers ratings. Refer
electronic DC Control Modules and SCR to the label on top of each DC Control
cells of the bridge are interchangeable. Module to verify current limit settings.
SCR 1 SCR 2
AC BUS AC BUS
MOTOR
20601-34 Rev. B
bolt clamp is tightened to press the The SCR bridge can be phased up for
heatsinks into the SCR. Pressure exerted testing by setting the MANUAL VOLTAGE
on the SCR is indicated by a gauge located SWITCH (Item 5 on Figure 3-2) to ON and
on the top side of the enclosure. rotating the MANUAL VOLTAGE KNOB
(Item 4 on Figure 3-2) clockwise. In the ON
position, the MANUAL VOLTAGE SWITCH
MAINTENANCE opens all of the assignment contactors so
that power is not applied to the DC traction
This Section contains specific functional
motor.
tests to assure proper operation of the SCR
unit.
Bridge voltage can be monitored at the
SCR VOLTS TEST PINS (Item 7 on Figure
• There are two separate tests: one for 3-2). The voltage ratio is 16:1, such that the
SCRs and one for SCR Bridges. SCR VOLTS TEST PINS (Item 7 on Figure
3-2) will represent a bridge voltage of 750
• Perform the appropriate test(s) after VDC when the SCR VOLTS TEST PINS
repairing or replacing any of the unit register 46.8 VDC.
assemblies.
ACTION RESULT
PRELIMINARY
A. Ensure that SCR Unit to be tested will not be A. This step is performed for safety purposes.
assigned from the Driller's Console.
B. Remove the wire from Terminal 134 of the DC B. This opens the contactors.
Control Module.
C. Energize the AC bus, if required. C. On DC Control Module, POWER ON and ZERO
THROTTLE INTERLOCK lights will illuminate (the
ZERO THROTTLE light will extinguish if a DC motor
is assigned AND the REFERENCE SIGNAL was
zero at that time).
D. Close the SCR circuit breaker. D. SCR ON light will illuminate and blowers will switch
ON.
SCR BRIDGE CHECK
A. Set the DC Control Module MANUAL VOLTS A. There are no measurable results from this step.
SWITCH to ON.
Rotate the DC Control Module MANUAL Observe the reading on the DC Voltmeter mounted
VOLTS KNOB slowly clockwise to MAXIMUM on the DC Control Module. The unloaded bridge will
and counter-clockwise to MINIMUM. This initially read a negative voltage and then go positive
should cause the bridge voltage to go from zero to ≈800 VDC.
to ≈800 VDC. When the SCR bridge is not Voltage Feedback from the Voltage Feedback
loaded, the capacitors in the bridge circuitry Board can be monitored at the DC VOLTS terminals
tend to raise the maximum bridge voltage. located on the front of the DC Control Module.
The bridge voltage will initially go Voltage Feedback should be 46.8 VDC @ 750 VAC.
negative.
ACTION RESULT
MODULE POWER SUPPLY CHECK
A. Power the Main AC Bus (if necessary). A. There are no measurable results from this step.
B. Check the voltage present at the following B. The voltage at each pins should be as follows:
DC Control Module pins:
Pin(s) Voltage
103 through 108 12 VAC
153 +14 VDC
154 -14 VDC
FIRING PULSE CHECK
20601-35 Rev. B
MAINTENANCE (CONTINUED)
Table 3-2. SCR Bridge Test (Concluded)
ACTION RESULT
C. Rotate the MANUAL VOLTAGE KNOB C. The observed SCR Firing Pulse should be similar to
(Item 4 on Figure 3-2) and check the firing that shown in Figure 3-3. This procedure allows all
pulses to each of the six SCRs with an points in the firing circuit to be monitored without
Oscilloscope. having high voltage present.
When making the checks on the SCR
firing pulses: the chassis of the
Oscilloscope must be floated, the
Oscilloscope ground is connected to
the SCR’s Cathode, and the
Oscilloscope probe to the SCR’s Gate.
FEEDBACK CHECK
A. Check the ripple of the Voltage Feedback A. The waveform should be similar to that shown in
signal waveform across the SCR VOLTS Figure 3-4.
TEST pins on front of the DC Control
Module.
The Voltage Feedback waveform
provides an indication of firing of the
SCR's. Note that there are six peaks.
Each SCR contributes a peak.
GOOD
BAD
BAD
20601-36 Rev. B
ACTION RESULT
ISOLATE FAULTY SCR This is accomplished by comparing the
Current Feedback ripple and SCR firing
pulses on a dual-trace Oscilloscope while
the SCR Unit is driving a load. During each
60 Hz cycle, there are six peaks in the ripple.
Each of the six SCRs in the bridge
contributes a peak. If one of the SCRs does
not fire, a peak will be missing. If the SCR
misfires, one of the peaks will be distorted.
A. To check the six SCRs, connect Channel 2 of the A. The waveform will look like the one shown in
Oscilloscope to the DC Control Module SCR Figure 3-5. The firing pulse that is in sync with the
AMPS TEST PINS and connect Channel 1 of the missing or distorted peak is the one going to the
Oscilloscope to the DC Control Module Test faulty SCR (refer to Figure 3-6). In Figure 3-6, the
Points listed below: B+ firing pulse lines up with the distorted peak,
indicating that the B+ SCR is misfiring.
DC Control Module SCR
Test Point
TP1 A+
Ch. 1 on
TP2 A- Test Point
TP3 B+ 4 (B-)
TP4 B-
TP5 C+
TP6 C-
Ch. 2 on
SCR Amps
Test Pins
10223-18 Rev. A
20601-37 Rev. A
MAINTENANCE (CONCLUDED)
ACTION RESULT
SCR RESISTANCE TEST
A. Trip the SCR Circuit Breaker. A. There are no measurable results from this step.
B. Switch Multimeter polarity to + and the scale to R B. There are no measurable results from this step.
x 10,000.
C. Test the Multimeter by connecting the + (red) and C. The meter needle will swing to indicate Zero
– (black) leads. Ohms.
D. Measure resistance across the SCR by touching D. The resistance measured should be in the >10 KΩ
one Multimeter lead to the AC bus bar and the range. The SCR is leaking if the measured
other Multimeter lead to the DC bus bar. resistance is less. The charging action of snubber
capacitor that is across SCR will be observed (the
resistance will not instantaneously be in the >10
KΩ range, but will instead rise over a period of
seconds). Let the Multimeter needle stabilize
before taking final reading.
E. Measure resistance across the SCR in the E. Again, the resistance should be >10 KΩ.
reverse direction by swapping the Multimeter
leads.
AC LEAKAGE TEST
A. Reactivate an SCR bridge, but do not assign it. A. There are no measurable results from this step.
B. Use a Multimeter to check for AC from each leg B. A reading of >50 VAC indicates excess AC
of the DC Bus to ground. leakage. Most likely a snubber network has
opened.
C. If excess AC leakage was detected in either Step C. Repair/replace any defective components.
B or C, remove power to the SCR Bridge and
check all components in the snubber networks.
6281-021-00 Rev. B
6281-028-20 Rev. A
6281-021-00 Rev. B
VOLTAGE FEEDBACK
This is an RC circuit which filters transient There are a number of operating conditions
spikes on the AC bus. Circuit loss does not and problems that may lead to the
disable the drive system but does increase generation of voltage transients. The
the likelihood of damage to the SCR cells energization of a transformer primary, a
(refer to Figure 3-10). fuse that blows during a power fault, and
switch arcing will all cause voltage
The line input is fused and then rectified transients. These voltage transients can be
through a diode bridge. DC output from the responsible for damage to circuit
bridge charges a capacitor bank to 1,000 components. Most semiconductor devices
VDC. A 25Ω, 225 W resistor limits the are not able to withstand voltage transients
charging current to 35 Amps. About 30 mS in excess of their voltage ratings.
after power is turned on, relay K1 closes to
short out the resistor. Transient protection has been provided by
three-phase delta-connected Metal Oxide
The excess charge caused by a spike is Varistors (MOVs). An MOV device exhibits
discharged through the resistor bank. When high resistance until the terminal voltage
power is turned OFF, the capacitors are exceeds its rated clamping voltage. The
also discharged through the resistor bank. resistance of the device then substantially
reduces, causing it to pass the voltage
THE CAPACITOR DISCHARGE transient-induced current to one of the other
TAKES 10 SECONDS. DO NOT phases, thus protecting the devices in the
TOUCH ANY PART OF THE circuit (refer to Figure 3-11).
CIRCUIT DURING THIS
PERIOD. The MOV-Type Surge Suppression Panel
has been made possible due to the
The front panel SURGE SUPPRESSION improved devices in the varistor family. The
LIGHT is normally illuminated. It will varistor combines the desired
extinguish if any of the lines fuses are characteristics of the ideal voltage clamp
blown. The line indicator-type fuses are provided by solid-state diode devices with
linked via indicator fuse switches (F4, F5, the superior energy-absorbing ability of a
and F6) to a microswitch (S1) whose metal oxide element. This MOV-Type Surge
normally closed contacts are in series with Suppression Panel is made of MOV
the SURGE SUPPRESSION LIGHT circuit. devices connected line-to-line on the 600
When a line fuse blows, it’s indicator button VAC bus in each SCR bridge.
opens the indicator switch, thus turning off
the SURGE SUPPRESSION LIGHT. The varistors are fused with 60 Amp
indicating fuses. A blown fuse is indicated
when the green SURGE SUPPRESSION
LAMP is extinguished.
20601-39 Rev. A
6281-028-20 Rev. A
The SURGE SUPPRESSION LAMP The lights will dimly illuminate during
extinguishing may be an indication of a normal operation. If there is a DC ground
failed MOV device. It is possible that these fault, it will complete the circuit through all
devices may completely rupture upon the phases of the Main AC Bus, so all the
failure. They are therefore covered with a three lights will brightly illuminate. A
safety shield to prevent equipment damage deflection reading on the %DC GROUND
or personnel injury. METER indicates a ground on one of the
DC buses.
DO NOT OPERATE THIS
PANEL WITHOUT THE SAFETY THE DC GROUND DETECTION
SHIELD INSTALLED. TO CIRCUIT ONLY PROVIDES AN
INSPECT THE MOVS, OPEN INDICATION OF A DC
THE FUSES BEFORE REMOVING THE GROUND. IT DOES NOT
SAFETY SHIELD. BE SURE TO INSTALL CORRECT THE PROBLEM. THE
THE SHIELD BEFORE CLOSING THE GROUND FAULT MUST BE QUICKLY
FUSES TO REAPPLY POWER TO THE LOCATED AND CORRECTED TO
MOVS. PREVENT FURTHER DAMAGE TO THE
EQUIPMENT.
PERIODIC MAINTENANCE
CONTACTOR CONTROL LOGIC
It is unlikely that the MOVs protection will
be downgraded. The bridge output is assigned to one of
several traction motors by closing the
It is recommended that the MOVs appropriate contactors. The contactor logic
be inspected on a periodic basis is set through the DRILLER'S CONSOLE
(every three months) for loose leads and ASSIGNMENT SWITCH.
evidence of overheating. Ensure that
you observe the precaution shown just Single-pole contactors are used to assign
above this subsection (PERIODIC motors which turn in only one direction. For
MAINTENANCE) before performing the reversing motors, the outputs of the single-
inspections. pole contactors are applied to the motor
armature via a double-pole contactor. The
DC GROUND FAULT DETECTION double-pole contactor reverses the
CIRCUIT armature leads to reverse the motor
direction.
This circuit (refer to Figure 3-12) consists of
three lights. Each light is connected on one The power contactor coils require 74 VDC
side to a phase of the AC bus and to energize. The positive terminal of all coils
grounded on the other. A series-connected is connected to +60 VDC. -14 VDC is
meter indicates the percentage of the fault. connected to the negative terminals of the
coils by a number of wired-in-series
contacts. These monitor and ensure that all
conditions are satisfactory to power the
assigned motor. If any of the contacts in
this control logic open, the power
contactors trip and the SCR bridge is
phased down.
0601-40 Rev. A
During the following discussion, refer to The coil connections for K1, K5 and K6 are
Figure 3-13 (a typical Rotary Table Control shown in the middle of the circuit. The
circuit). positive terminals of all the coils are
connected to +60 VDC.
1. The Rotary Table is assigned to SCR 3
at the DRILLER'S CONSOLE Trace the -14 VDC control signal. The -14
ASSIGNMENT SWITCH. VDC power supply in the DC Control
2. The Rotary Table Module is first passed through the normally-
FORWARD/REVERSE SWITCH is set closed MANUAL VOLTAGE SWITCH. This
to REVERSE. switch is placed in the TEST position to
phase up the SCR bridge without applying
Refer to the assignment switch
power to the traction motors.
configuration at the top-right
corner of the schematic. The rotary table The signal emerges from Pin 134 of the DC
can be run on either SCR 2, 3, or 4. Control Module as CONT PS. It is routed
through a normally-open auxiliary contact of
The Rotary Table motor connections are at the SCR 3 circuit breaker. This normally-
the bottom-left corner of the schematic. open auxiliary contact closes when the
SCR 3 bridge is connected to the Rotary circuit breaker is closed, thereby assuring
Table motor through single-pole contactors that the SCR Unit is turned on.
K1 and K6 and reversing contactor K5.
The control signal is then sent to the The control signal is then routed through all
DRILLER'S CONSOLE where it turns on the normally-closed auxiliary contacts of the
the SCR 3 ON light. The control signal is power contactors in the SCR 3 Unit
also connected to one side of the other than K1, K5 and K6. This assures
DRILLER'S CONSOLE ASSIGNMENT that the bridge output is not connected to
SWITCH. The control signal emerges on two motors at one time.
the other side at the 3 o'clock contact since
the DRILLER'S CONSOLE ASSIGNMENT At this point in time, the coils of K1 and K6
SWITCH is set to the 3 o'clock position. are energized. To ensure that their contacts
have closed, the control signal is passed
The contactor signal now passes through through the normally-open auxiliary
the contacts of the RT vane switch relay contacts of K1 and K6.
RL2. A vane switch was not installed in the
Rotary Table equipment; therefore, a The control signal is then returned to the
jumper was installed so that RL2 will DC Control Module as RT CONT (Pin 129).
always be energized. If a vane switch is In the DC Control Module, the reference for
installed in the Rotary Table sometime in the SCR firing circuits is disabled as long as
the future, the jumper can be removed. all the CONT signals (RT CONT, MP1
CONT, etc.) are not -14 VDC.
The signal next passes through REV
contact of the ROTARY TABLE LOCKOUT The Rotary Table reference and Current
SWITCH energizing the coil of contactor Limit signals which originate in the
K5. DRILLER'S CONSOLE are also shown in
Figure 3-13.
6222-012-01 Rev. C
10197-22 Rev. A
• It’s Gate terminal is FIRED with a The most basic is a single-phase half-wave
current pulse. This pulse is just that, a rectifier (refer to Figure 3-15). This consists
pulse - it is not a constant voltage which of a diode mounted in-line with a one phase
remains applied to the Gate terminal. AC input. The output is a pulsating DC
voltage that varies between zero and
If the Gate terminal is fired as soon as the maximum voltage. The diode conducts for
SCR is forward biased, the SCR is working 180°. For 180° (when the diode is not
just like an ordinary diode. conducting), the output will be zero. During
the other 180°, the output will rise from zero
The SCR Gate terminal firing is delayed to to maximum and then back to zero.
vary the DC output. In this SCR firing
circuit: A single-phase diode full-wave rectifier
bridge (refer to Figure 3-15) has four
• The six-phase Reference will indicate diodes. Each of the AC input lines has two
when the SCR is forward biased. diodes connected to it. Each of these
diodes is connected to a different DC output
• The Firing Reference will indicate when line. The diodes turn on and off
the SCR should be fired to achieve the automatically as the bias changes. This
desired DC output level. process is called commutation.
The left-most part of Figure 3-16 shows a The six-diode bridge waveform shows the
three-phase diode bridge rectifier and commutation process through a single 60
several input waveforms. Hz three-phase cycle. The 360° cycle is
divided into vertically-divided 30° sections
Compare the circuit of the single- (refer to waveform A in Figure 3-16).
phase full-wave bridge rectifier to Observe that between 30° to 150°, the A+
the three-phase bridge rectifier. The only diode is more positively biased than either
major difference is the addition of the B+ or C+ and is therefore conducting.
two diodes for the C phase and the C Similarly, the C- diode is more negatively
phase winding. If these are disregarded biased than either A- or B- during 90° to
and the A and B phase voltages are 210° and is therefore conducting. Each
summed, the two rectifier bridges are diode conducts for 120° and is turned off for
(for all intents and purposes) the same. 240°. Table 3-4 gives the commutation
sequence.
In a three-phase diode bridge rectifier,
things get a little more interesting. Even
Table 3-4. Diode Commutation
though the diode is capable of conducting
for 180°, it will only do so for 120°. This is
because the diode connected to a second DEGREES TURNS ON TURNS OFF
AC phase becomes more positively biased 30 A+ C+
than the diode connected to the first phase. 90 C- B-
At this time, the diode connected to the first
phase stops conducting and the diode 150 B+ A+
connected to second phase starts 210 A- C-
conducting. This process happens on both
output voltage legs of the rectifier. The only 270 C+ B+
difference is that the events on the two 330 B- A-
output voltage legs occur 60° apart.
DIODE BRIDGE
A. DIODE BRIDGE
SCR BRIDGE
If α is 60° (waveform C in Figure 3-16), the The OVERSPEED CIRCUIT works for all
SCRs are not fired until 60° after they are configurations of series motors except
forward biased. In this case, the average where two motors are driven in parallel from
VDC is 0.5. a single SCR bridge (refer to Figure 3-17).
If α is 90° (waveform D in Figure 3-16), the Suppose MP1A breaks its chain drive. The
SCRs are not fired until 90° after they are unloaded motor will overspeed. It will draw
forward biased. In this case, the average full voltage, but little current. Most of the
VDC is Zero. current will flow into MP1B. The
OVERSPEED CIRCUIT will not detect the
SPROCKET SLIP CIRCUIT overspeed because the Current Feedback
signal indicates the total current drawn by
This circuit provides overspeed protection the two motors.
for two series motors that are driven in
parallel from a single SCR bridge. Such an The SPROCKET SLIP circuit measures the
arrangement is normally used for Mud DC current drawn by each motor through
Pumps. Hall Effect Devices (HED) and compares
them to the voltage to detect overspeed.
If either one of the motors exceeds a preset
speed limit, due to a malfunction in the Figure 3-18 is the installation diagram of the
chain or belt drive, the circuit cuts off power HEDs. HED1, mounted on the -DC cable,
to both motors by tripping the measures current to the MP1A motor.
ASSIGNMENT CONTACTORS and turning HED2, mounted on the +DC cable,
on the front panel SPROCKET SLIP measures current to the MP1B motor.
LIGHT.
Refer to Figure 3-18, the Sprocket Slip
In the system, overspeed protection for circuit. Differential voltage signals from
shunt motors is achieved through a FIELD HED1 and HED2 are compared on Op
LOSS RELAY. Amps Z1 and Z2 to obtain I1A, and I1B
respectively. The currents are auctioneered
A shunt motor cannot overspeed via D1 and D10 to select the current with
unless the motor field is low. the lower value. Since the motors have
equal armature voltage, the motor with the
The FIELD LOSS RELAY monitors the field lower current has the higher speed.
current. It opens to trip the assignment
contactors of the motor if the current is The motor with the lower current is slipping
<50% of the motor rated value. (not doing work). The motor with the higher
current is actually driving the sprocket.
20601-43 Rev. A
20601-38 Rev. A
DYNAMIC BRAKE
A. Dynamic Brake Logic Signal DB A. Monitor the voltage at Pin 127 (DB FIELD) of the DC Control
FIELD missing. Module. The voltage should be Zero VAC with the SCR Circuit
Breaker open, 120 VAC during the braking cycle with the SCR
Circuit Breaker closed.
The DB FIELD signal is only present on SCR Units
which are driving the Drawworks.
B. Dynamic Brake Logic Signal DC B. Monitor the voltage at Pin 135 (DB CONT) of the DC Control
CONT missing. Module. When braking, the voltage should be 120 VAC in SCR
units assigned to Drawworks.
C. Dynamic Brake Logic Signal DBØ C. Monitor the voltage at Pin 138 (DBØ) of the DC Control Module.
missing. The voltage should be 120 VAC in SCR units assigned to
Drawworks.
ROTARY TABLE
A. Rotary Table CURRENT LIMIT A. Monitor the voltage at Pin 128 (RT I LIM) of the DC Control
SIGNAL missing. Module while varying the Driller’s Console CURRENT LIMIT
rheostat. It should be between Zero VDC (50 AMPS) to -8 VDC
(MAXIMUM CURRENT LIMIT). If the voltage is absent, trace the
signal to the CURRENT LIMIT rheostat.
B. Rotary Table CONTACTOR B. Monitor the voltage at Pin 129 (RT CONT) of the DC Control
SIGNAL missing. module. It should be +14 VDC with the SCR Circuit Breaker
open OR the SCR Circuit Breaker closed and the DC Contactors
open. In normal operation, the voltage will be -14 VDC when the
Rotary Table Contactors open.
RT CONT will only be present in SCR Units which are
driving the Rotary Table.
C. Rotary Table HAND THROTTLE D. Monitor the voltage at Pin 130 (RT REF) and Pin 132 (RT REF
reference from Driller’s Console 2) of the DC Control Module while varying the Driller’s Console
missing. Hand Throttle. It should be between Zero VDC (MINIMUM) to -8
VDC (MAXIMUM). If either/both voltages are absent, trace the
signal to the ROTARY TABLE rheostat.
MP1 REF DC
MP2 REF DC
PROP CONT
P REF WHC
MP1 CONT
MP2 CONT
SCR AMPS
DB FIELD
DB CONT
RT CONT
RT REF 2
RT REF 1
CNT -14
RT CL
SLV 2
SLV 1
DB
138
137
136
135
134
133
132
131
130
129
128
127
126
125
124
123
122
121
120
119
20601-44 Rev. B
FS-066-12
Figure 3-20. Typical Model 1200 or 1500 Generator/SCR Cubicle - Double Access
(CONCLUDED)
3
SCR CELL 4
2
While performing this procedure, refer to
Figures 3-20 and 3-21. 5
SCR REPLACEMENT
FS-008-21
FS-021-30 FS-021-25
2. Tools needed: screwdriver, 7/16" box 5. Disconnect wires leading into the
end wrench, socket wrench handle and enclosure at the terminal board.
extension, 3/8" socket, and ½" socket.
FS-021-19 FS-021-35
FS-021-17 FS-022-05
4. Replace the trigger fuse if its plunger 7. Remove the fuse assembly, if
has tripped the microswitch. necessary, using a hex wrench.
FS-022-36
FS-022-17
FS-023-19
FS-022-35
FS-025-14
FS-023-22 FS-022-05
13. Tighten both clamp bolts equally until 16. Replace the fuse assembly using a hex
the gauge reads recommended value. wrench.
FS-022-35 FS-021-35
14. Reinstall the Glastic box and connect 17. Replace the SCR enclosure and tighten
the capacitor and trigger fuse leads. the attaching bolts.
FS-022-17 FS-021-25
15. Insert the leads through the Glastic box 18. Connect the wires leading into the
hole and reinstall the 1/4" bolts. enclosure at the terminal board.
SCR REPLACEMENT
FS-059-05
Item Description
1 AC Bus Bar
2 Fuse
3 Fuse Trip Indicator
4 Pressure Gauge
5 SCR
6 25 Ω , 55 W Resistor
7 DC Bus Bar
8 Overtemperature Switch
9 1 µ f Capacitor
10 Pulse Transformer
11 Heatsink
10197-32 Rev. A
Figure 3-23. Layout of Front Access Vertical Bridge Model 1400 SCR Cubicle
FS-044-08
FS-025-22
FS-024-30
FS-025-14
FS-024-28
FS-044-10
FS-024-33
FS-024-36 FS-025-09
9. Carefully slide out the front heatsink and 12. Tighten the SCR clamping bolts until the
SCR assembly. pressure gauge reads 2,500 lb.
FS-025-06 FS-024-28
10. Lift out the defective SCR and put in 13. Using the 7/16" box-end wrench,
new one. Braid the SCR leads. reconnect the bus to the heatsink.
FS-024-36 FS-024-30
11. Carefully slide reinstall the front heatsink 14. Reconnect the clip lead which connects
and SCR assembly. the resistor to the heatsink.
FS-044-08
FS-044-10
FS-025-22
FS-025-14