MUD PUMP/CEMENT PUMP

CONSOLE
REVISION HISTORY
Rev. Description ERO/ECN #
A Initial Release -----
B Formatting and content revisions. 041252
C Added Revision History page and drawing number in footer. C23257
D Made corrections in text. C24068
E Update figures. C25780
F Add photo numbers. C26023
G Make corrections in text. C26160
H Convert to Word 97 format. C28670
J Minor formatting change. C28926
K Add Table of Contents codes. Correct Level 5 and Level 6 styles and errors. C29222

REVISION HISTORY PAGE SCR DRIVE SYSTEM TECHNICAL MANUAL


20605-51 Rev. K 24 HOUR SERVICE (713) 467-2523
5-1

MUD PUMP/CEMENT PUMP CONSOLE


During normal operation of the pumps from
OPERATION the Driller's Console, the OFF/ON switches
should remain switched on. Padlock
DESCRIPTION attachments are available at the
SPROCKET SLIP RESET buttons to
The Mud Pump Console enables control of prevent unwanted operation. The POWER
the pumps for maintenance operations such ON light illuminates when the Mud Pump is:
as changing liners. The following
• assigned.
description is referenced to the Mud
Pumps. The same description applies to • not locked out.
Cement Pumps. • turned on.

The Mud Pump Console is not intended for Table 5-1. Mud Pump Console
routine operation of the mud pumps. The Specifications
throttle range from the Mud Pump Console
is restricted to half the range available from
ELECTRICAL
the Driller's Console. In addition, the Rod
Oiler, chain Oiler, and Charging Pump are The Mud Pump Console has dual- and sometimes
not automatically switched on. triple-control circuits, one for Mud Pump 1 and
another for Mud Pump 2. If there is a third circuit, it
would be for Mud Pump 3. Each circuit receives the
The Cement Pump Console can run the following voltages from the SCR units assignable to
cement pumps from zero to full speed (as Mud Pumps:
needed). Assignment power however is
derived from the Driller's Console so the 1. +14 VDC to turn on a POWER ON light.
Driller can maintain control over when the
2. -14 VDC contactor control logic.
cement pumps can be operated.
Each circuit outputs the following voltages to the
SPECIFICATIONS same SCR units.

1. -14 VDC contactor control logic.


Refer to Table 5-1.
2. Zero to -8 VDC throttle reference.
OPERATING INSTRUCTIONS
The MCC provides single-phase 115 VAC to power
Figure 5-1 identifies the controls and a strip heater and a convenience outlet.

indicators of the Mud Pump. The Mud


MECHANICAL
Pump Console has a dual set of controls,
one for Mud Pump 1 and another for Mud The Mud Pump Console is fabricated from 12
Pump 2. gauge stainless steel. The assembly is watertight.

Size: 18" Long x 10" High x 10" Deep (46 cM


Long x 26 cM High x 26 cM Deep)

Weight: 30 Pounds (14 KG)

SCR DRIVE SYSTEM TECHNICAL MANUAL MUD PUMP/CEMENT PUMP CONSOLE


24 HOUR SERVICE (713) 467-2523 20605-51 Rev. K
5-2

OPERATING INSTRUCTIONS
(CONCLUDED)

POWER ON
OFF/ON LIGHT
SWITCH

THROTTLE HANDWHEEL

FS-067-04

Figure 5-1. Mud Pump Console Controls and Indicators

To operate a pump from the Mud Pump the ON/OFF switch OFF at either of the
Console for maintenance activity, perform consoles prevents operation of the
the following steps: pump from either the Mud Pump
Console or the Driller's Console.
1. Set the MP1 (MP2) OFF/ON switch and
the corresponding throttle to OFF.
MAINTENANCE
2. At the Driller's Console, set the MP1
(MP2) THROTTLE to OFF. Set the Refer to the Section 3 (SCR Unit)
ASSIGNMENT switch to MP1 (MP2) for general instructions regarding
and turn On the corresponding OFF/ON shipping, storage and servicing.
switch.
3. At the Mud Pump Console, the MP 1 INSTALLATION
(MP 2) POWER ON light will illuminate.
4. Set the MP 1 (MP 2) OFF/ON switch to Four stabs are welded to the back panel of
ON and rotate the Mud Pump Console the console to facilitate bulkhead mounting.
THROTTLE HANDWHEEL to achieve
the desired speed. TESTING
5. To resume normal operation from the
Test the affected console after repairing or
Driller's Console, turn the Mud Pump
replacing any of its active components. A
Console THROTTLE HANDWHEEL to
functional test consists of operating the
OFF. Do not turn the Mud Pump
console according to the instructions listed
Console OFF/ON switch OFF. Turning
in the Driller's Console section.

MUD PUMP/CEMENT PUMP CONSOLE SCR DRIVE SYSTEM TECHNICAL MANUAL


20605-51 Rev. K 24 HOUR SERVICE (713) 467-2523
5-3

The Zero to -8 VDC MP 1 REFERENCE (or


TROUBLESHOOTING MP 2 REFERENCE) is applied to DC
Control Module pin 126 (pin 123 for MP 2
THEORY OF OPERATION REFERENCE) of all the SCR units
assignable to MP 1 (or MP 2). A speed
Figure 5-2 shows the Mud Pump Console command is created from this reference by
assembly, Figure 5-3 is the Mud Pump passing it through a 47 KΩ resistor. This
Console circuit, and Figure 5-4 is the Mud contrasts with a 22 KΩ resistor used for
Pump Control Logic circuit. Figure 5-4 reference from the Driller's Console. As a
shows the circuitry that is activated when result, throttle range from the Mud Pump
MP1 is driven from the Mud Pump Console Console is approximately one half the
on SCR 2. Table 5-2 lists several possible range from the Driller's Console.
Mud Pump console problems and the
troubleshooting to determine the problem.

LOCKOUT SWITCH

RHEOSTAT POWER ON
LIGHT
A. DOOR

PC CARD
B. CABINET

FS-017-33, FS-017-36

Figure 5-2. Console Assembly

SCR DRIVE SYSTEM TECHNICAL MANUAL MUD PUMP/CEMENT PUMP CONSOLE


24 HOUR SERVICE (713) 467-2523 20605-51 Rev. K
5-4

THEORY OF OPERATION (CONTINUED)

6265-023-02 Rev. A

Figure 5-3. Mud Pump Console Schematic Diagram

MUD PUMP/CEMENT PUMP CONSOLE SCR DRIVE SYSTEM TECHNICAL MANUAL


20605-51 Rev. K 24 HOUR SERVICE (713) 467-2523
5-5

6281-010-01 Rev. D

Figure 5-4. Mud Pump Control Logic

SCR DRIVE SYSTEM TECHNICAL MANUAL MUD PUMP/CEMENT PUMP CONSOLE


24 HOUR SERVICE (713) 467-2523 20605-51 Rev. K
5-6

THEORY OF OPERATION (CONCLUDED)

6281-010-01 Rev. D

Figure 5-4. Mud Pump Control Logic (Concluded)

MUD PUMP/CEMENT PUMP CONSOLE SCR DRIVE SYSTEM TECHNICAL MANUAL


20605-51 Rev. K 24 HOUR SERVICE (713) 467-2523
5-7

Table 5-2. Mud Pump Console Troubleshooting

PROBLEM/PROBABLE CAUSE ACTION


MUD PUMP DOES NOT RUN
A. -14 VDC contactor logic not reaching A. Make sure the Driller's Console ASSIGNMENT switch is
the assignment contactors. appropriately set and the MP 1 (MP 2) OFF/ON switch is ON.

Check for the presence of the -14 VAC signal at the DC


Control Module and troubleshoot to the point in circuit in which
-14 VAC is absent (refer to Figure 5-4).

B. Zero to - 8 VDC throttle reference B. Check for the presence of the signal at the Mud Pump Console
not reaching the DC Control Module. terminal board. If absent, the Mud Pump Throttle Handwheel
rheostat may be faulty.

CONTROLS AND INDICATIONS


MUD PUMP CONSOLE
Typically an OFF/ON switch, a HAND
The Mud Pump Console (see Figure 5-1)
THROTTLE, a POWER ON indicator lamp
provides local control of the mud pump
and a PURGE LOSS lamp are provided for
during maintenance operations. It is not
each pump, but extra equipment may be
intended for normal running of the pumps,
fitted according to system requirements.
speed range is usually restricted to half of
The OFF/ON switch will prevent the mud
the speed available from the Driller's
pump running from either the Mud Pump or
Console.
the Driller's Console. Set it to the ON
position if operation is required from either
SPECIFICATIONS console.
The enclosure is fabricated from 14 gauge ELECTRICAL INSTALLATION
stainless steel and affords a degree of
protection meeting NEMA Standard 4X. The power supplies for the Console are fed
from the SCR system. A grounding cable
The Mud Pump Console is enclosed in a MUST be run from the Mud Pump Console
stainless steel enclosure that has ground stud to the SCR system ground bus.
connections for externally supplied air The connection must be <1Ω resistance.
purging. The Mud Pump Console can be
made to be suitable for Class I Division II ENCLOSURE
operation by providing proper purging air.
The integrity of the Console and its seals
must be maintained and should not be
modified in any manner. All components
mounted through the enclosure should be
gasketed with RTV sealant. All screws
should be fixed in place with LOCKTITE or
similar.

SCR DRIVE SYSTEM TECHNICAL MANUAL MUD PUMP/CEMENT PUMP CONSOLE


24 HOUR SERVICE (713) 467-2523 20605-51 Rev. K
5-8

SPECIFICATIONS (CONTINUED) It is a stainless steel enclosure having


connections for externally-supplied air
The Mud Pump Console door is held closed purging and is suitable for Class I Division II
by spring catches. These door latches act operation by providing proper purging air.
to discourage entry by unauthorized
personnel. Because of this use, the spring CONTROLS AND INDICATIONS
latches should not be replaced by any other
type of securing device. Typically an OFF/ON switch, a HAND
THROTTLE, a POWER ON indicator lamp
PURGING SYSTEM and a PURGE LOSS lamp are provided for
each cement pump, but extra equipment
The mud pump console has an air regulator may be fitted according to system
system the will maintain positive pressure requirements. A LOCKOUT switch will
inside the console as long as there is air prevent running of the Cement Pump
supplied by the rig's air supply. The Console.
purging system is built to comply with the
National Fire Protection Association's ELECTRICAL INSTALLATION
guideline NFPA 496, Purged and
Pressurized Enclosures for Electrical The power supplies for the Console are fed
Equipment (1989), for type Z purging. Upon from the SCR system. A ground cable
customer request, the equipment can be MUST be run from the console grounding
built to comply with type X purging. stud to the SCR system ground bus with
<1Ω resistance.
BEFORE REMOVING ANY
PLUG CONNECTIONS, ALL ENCLOSURE
POWER MUST BE REMOVED
FROM THE CONSOLE. The integrity of the Cement Pump Console
COMPONENTS MAY ONLY BE and its seals must be maintained. It should
REPLACED WITH APPROVED SPARE not be modified in any manner. All
PARTS. components mounted through the Cement
Pump Console enclosure should be
CEMENT PUMP CONSOLE gasketed with RTV sealant. All screws
should be fixed with LOCKTITE or similar
solution.
It provides local control of the cement pump
during normal or maintenance operations
The Console door is held closed by spring-
and is intended for normal running of the
loaded latches. These deter accidental
cement pumps with control over the full
speed range. Assignment power is only entry. Do not replace with any other type.
available from the Driller's Console.

SPECIFICATIONS

The enclosure is fabricated from 14 gauge


stainless steel and affords a degree of
protection to NEMA Standard 4X.

MUD PUMP/CEMENT PUMP CONSOLE SCR DRIVE SYSTEM TECHNICAL MANUAL


20605-51 Rev. K 24 HOUR SERVICE (713) 467-2523
5-9

CEMENT PUMP CONSOLE


(CONCLUDED)
BEFORE REMOVING ANY
PURGING SYSTEM PLUG CONNECTIONS, ALL
POWER MUST BE REMOVED
The Cement Pump Console has an air FROM THE CONSOLE.
regulator system that maintains a positive COMPONENTS MAY ONLY BE
pressure inside the Cement Pump Console REPLACED WITH APPROVED SPARE
as long as there is air supplied by the rig's PARTS.
air supply. The purging system complies
with the National Fire Protection
Association's guideline NFPA 496 - Purged
and Pressurized Enclosures for Electrical
Equipment (1989), for type Z purging. Upon
customer request, the equipment can be
built to comply with type X purging.

SCR DRIVE SYSTEM TECHNICAL MANUAL MUD PUMP/CEMENT PUMP CONSOLE


24 HOUR SERVICE (713) 467-2523 20605-51 Rev. K
5-10

THIS PAGE INTENTIONALLY LEFT BLANK

MUD PUMP/CEMENT PUMP CONSOLE SCR DRIVE SYSTEM TECHNICAL MANUAL


20605-51 Rev. K 24 HOUR SERVICE (713) 467-2523