QuickCMC controls an OMICRON CMC test set in the way a front panel control
would do.
You can output voltages, currents and frequencies statically or as ramped output
signals, work with binary (digital) outputs and inputs and take simple
measurements at the anlog inputs. Applications such as the manual testing of
an inrush blocking or a synchronizer function can be done with QuickCMC. It is
not necessary to start other modules like Ramping or State Sequencer to
perform quick manual checks.
There is no upper limit regarding the number of outputs (generators) that can be
controlled. In order to test a busbar protection, for example, a CMC 256 test set
and two CMA 156 amplifiers are connected. QuickCMC allows the simultaneous
control of all 16 generators.
QuickCMC represents a good starting point for new users.
3
OMICRON Test Universe
1. For information on the "multifunctional input gid" and the fault calculator check the Test Universe
online help. Go to the index and enter "multifunctional...".
4
QuickCMC
Task
Test of the pick-up, drop-off and trip times for a generic overcurrent relay.
A report should be generated.
Given settings:
Pick-up: 1.2 A
Pick-up / drop-off ratio: 0.9
Trip time: 300 ms.
Solution
With QuickCMC, OMICRON Test Universe offers a dedicated test module to
easily and quickly perform manual tests. It is typically used in stand-alone mode,
although it can also be used as part of the OMICRON Control Center.
The difference between the operational modes "stand-alone" and "embedded"
is explained in chapter 2 ”The Test Universe Start Screen” in the "Concept"
manual.
5
OMICRON Test Universe
6
QuickCMC
7
OMICRON Test Universe
8
QuickCMC
9
OMICRON Test Universe
Binary Outputs
This test example does not require any binary outputs. Nevertheless a brief
explanation for the sake of completeness:
Each one of the 8 Binary Outputs available on your CMC test set can be set to
OFF or ON. An OFF output (check box clear) provides a binary "0" signal to the
connected test object, and an ON output (check box selected) provides a binary
"1" signal.
A binary output may be set to ON at any time, however, its actual output
depends on the status of the analog outputs: only if any of the analog outputs
becomes active (by activating F5 "Outputs ON/OFF" or F8 "Set Prefault" ), the
selected binary outputs provide an ON signal. If the analog signal output stops,
also the binary outputs shut off.
The number of available binary outputs and their routing are defined in the
Hardware Configuration.
If you use a CM ASB2 switching box, binary outputs 5 - 8 run CM ASB2.
10
QuickCMC
11
OMICRON Test Universe
12
QuickCMC
13
OMICRON Test Universe
14
Support
Support
When you are working with our products we want to provide you with the
greatest possible benefits. If you need any support, we are here to assist you!
OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495
15
Support
16