Mark* VIe I/O Modules Index fact sheet


Mark VIe I/O modules contain a local processor and a data I/O TYPES
acquisition board inside a plug-in assembly that is known as In this index, the I/O modules are categorized into general-
an I/O pack. One, two, or three I/O packs provide redundancy purpose and turbine-application types. Discrete I/O, analog
and communicate on 100 MB Ethernet on the I/O network. I/O, and I/O communications are used for turbine and non-
Two Ethernet drivers are contained in each pack. The I/O turbine applications, such as balance of plant (BOP)
module also contains either a barrier-type terminal block or a equipment. Turbine-application types consist of analog I/O
box-type (Euro style) terminal block, which can be provided as (such as acoustic monitoring), communications (such as
a removable or non-removable block. Signal flow between electric fuel valve drivers), and primary / backup hydraulic trip
the terminal blocks and the I/O packs occurs on the module's protection for different types of turbines. For additional
printed circuit board, which contains passive noise information reference GEI-100727 Mark VIe General-Purpose
suppression. Plug-in maintenance capability is provided on I/O Modules or GEH-6721 Volume II Mark VIe System Guide.
the terminal blocks and I/O packs where it is most needed.

Discrete I/O Types Terminal Removable Terminal I/O Pack Qty. per
Board Type Terminal Board Board Terminal Board
Six "A" mechanical relays for solenoids, solenoid impedance Barrier Yes TRLYH1D PDOAH1A / 1, 3
diagnostics (24/125 V dc)
12 "C" mechanical relays with six solenoids, coil diagnostics Barrier Yes TRLYH1B PDOAH1A / 1, 3
(115/230 V ac, 24/48/125 V dc)
12 "C" mechanical relays with six solenoids, voltage diagnostics Barrier Yes TRLYH1C PDOAH1A / 1, 3
(115/230 V ac, 125 V dc)
12 "C" mechanical relays with six solenoids, voltage diagnostics Barrier Yes TRLYH2C PDOAH1A / 1, 3
(24 V dc)
12 "C" mechanical relays (115/230 V ac, 24/48/125 V dc) Box No SRLYH1A PDOAH1A / 1
12 "C" mechanical relays (115/230 V ac, 24/48/125 V dc) 1, 2 Box Yes SRLYH2A PDOAH1A / 1
24 DI and 12 "C" mechanical relays (24 V dc group-isolated) SOE 1, 2 Box Yes TBSH2A PDIOH1A / 1
24 DI and 12 "C" mechanical relays (48 V dc group-isolated) SOE 1, 2 Box Yes TBSH4A PDIOH1A / 1
24 DI and 12 "C" mechanical relays (125 V dc group-isolated) SOE 1, 2 Box Yes TBSH6A PDIOH1A / 1
24 DI and 12 "C" mechanical relays (24 V dc group-isolated) SOE 1 Box Yes TBTH2A PDIOH1A / 3
24 DI and 12 "C" mechanical relays (48 V dc group-isolated) SOE 1 Box Yes TBTH4A PDIOH1A / 3
24 DI and 12 "C" mechanical relays (125 V dc group-isolated) SOE 1 Box Yes TBTH6A PDIOH1A / 3
36 mechanical relays, 12 voted form "B" (NC) outputs Barrier Yes TRLYH1F PDIOH1A / 3
(115 V ac, 24/125 V dc)
36 mechanical relays, 12 voted form "A" (NO) outputs Barrier Yes TRLYH1F PDIOH1A / 3
(115 V ac, 24/125 V dc) 3
1 Add solenoid interface to first 6 circuits WROBH1A
2 Add fuse in COM leg of all 12 circuits WROFH1A
2 Add fuse power distribution in COM leg of all 12 circuits WROGH1A
3 Fuses for field solenoid power in positive and negative legs WPDFH1A
3 Fuses for field solenoid power in supply side only for common WPDFH2A
neutral AC solenoids
table is continued on next page

g GEA-S1212
fact sheet
Discrete I/O Types Terminal Removable Terminal I/O Pack Qty. per
Board Type Terminal Board Board Terminal Board
24 DI (125 V dc, group-isolated) SOE Barrier Yes TBCIH1C PDIAH1A / 1, 2, 3
24 DI (24 V dc, group-isolated) SOE Barrier Yes TBCIH2C PDIAH1A / 1, 2, 3
24 DI (48 V dc, group-isolated) SOE Barrier Yes TBCIH3C PDIAH1A / 1, 2, 3
24 DI (115/230 V ac, 125/250 V dc point-isolated) SOE Box Yes TICIH1A PDIAH1A / 1, 2, 3
24 DI (24 V dc, point-isolated) SOE Box Yes TICIH2A PDIAH1A / 1, 2, 3
24 DI (24 V dc, group-isolated) SOE Box No STCIH1A PDIAH1A / 1
Yes STCIH2A
24 DI (48 V dc, group-isolated) SOE Box Yes STCIH4B PDIAH1A / 1
24 DI (125 V dc, group-isolated) SOE Box Yes STCIH6B PDIAH1A / 1
16 DI (24, 48, 125, 250 V dc, 115, 230 V ac point-isolated, line-break Box Yes SDIIH1 PDIIH1A / 1
detection) SOE
- Add 24 V dc, 115/230 V ac wetting voltage Box Yes WDIIH1 PDIIH1A / 1
- Add 48 V dc wetting voltage Box Yes WDIIH2 PDIIH1A / 1
- Add 125 V dc wetting voltage (group-isolation) Box Yes WDIIH3 PDIIH1A / 1
12 "A" solid-state relays (115/230 V ac) Barrier Yes TRLYH1E PDOAH1A / 1, 3
12 "A" solid-state relays (125 V dc) Barrier Yes TRLYH2E PDOAH1A / 1, 3
12 "A" solid-state relays (24 V dc) Barrier Yes TRLYH3E PDOAH1A / 1, 3

Turbine Application - Analog I/O and Communications Types Terminal Removable Terminal I/O Pack Qty. per
Board Type Terminal Board Board Terminal Board
18 inputs and buffered outputs for acoustic monitoring of frame 6, 7, Box Yes SAMBH1A PAMB / 2
9 turbines, Dual 323A4747WCP1
18 inputs and buffered outputs for acoustic monitoring of frame 6, 7, Box Yes SAMBH1A PAMB / 1
9 turbines, Simplex 323A4747WCP2
18 inputs and buffered outputs for acoustic monitoring of frame 6, 7, Box Yes SAMBH1A PAMC / 2
9 turbines, Dual 323A4747WCP3
18 inputs and buffered outputs for acoustic monitoring of frame 6, 7, Box Yes SAMBH1A PAMC / 2
9 turbines, Simplex 323A4747WCP4
Eight Seismic/Proximitor/Accelerometer/Velometer inputs, Barrier Yes TVBAH1A PVIBH1A / 1, 3
three position, one reference probe, buffered outputs
Core analog I/O for heavy-duty gas turbines, Simplex or TMR Box Yes TCASH2A PCAAH2A / 1
- Additional I/O with TCAT, required for TMR applications Box Yes TCATH2A
Electric fuel valve gateway with for IONet communication to NA NA TEFVH1A PEFVH1A / 1, 2, 3
Woodward DVP
Three single-phase CT inputs and three V/I inputs normally used for * * TGNAH1A PGENH1A / 1, 3
power load unbalance
Two servo channels: two three-coil outputs, eight LVDTs and Barrier Yes TSVCH1A PSVOCH1A / 1, 3
excitation, two PR (gas/steam)
Two servo channels: two three-coil outputs, eight LVDTs and Barrier Yes TSVCH2A PSVOCH1A / 1, 3
excitation, two PR (Aero) Class 1, Division 2
* AIs are Box type and removable; CT inputs are Barrier type and not removable

2
GEA-S1212
fact sheet
Analog I/O and Communications Types Terminal Removable Terminal I/O Pack Qty. per
Board Type Terminal Board Board Terminal Board
10 AI (V/I inputs, group isolated) and two AO Barrier Yes TBAIH1C PAICH1A / 1, 3
(4-20 mA outputs, group-isolated) Box No STAIH1A PAICH1A / 1
10 AI (V/I inputs, group) and two AO Box Yes STAIH2A PAICH1A / 1
(4-20 mA outputs, group-isolated)
10 AI (V/I inputs, point) and two AO Box No SAIIH1ABC PAICH1A / 1
(4-20 mA outputs, group-isolated) Yes SAIIH2ABC
10 AI (V/I inputs, group-isolated) and two AO Barrier Yes TBAIH1C PAICH2A / 1, 3
(4-20/0-200 mA outputs, group-isolated) 4 Box No STAIH1A PAICH2A / 1

10 AI (V/I inputs, group) and two AO Box Yes STAIH2A PAICH2A / 1
(4-20/0-200 mA outputs, group-isolated) 4
10 AI (V/I inputs, point) and two AO Box No SAIIH1ABC PAICH2A / 1
(4-20/0-200 mA outputs, group-isolated) 4 Yes SAIIH2ABC
10 AI (V/I inputs) and two AO (4-20 mA outputs) with HART® Box No SHRAH1A PHRAH1A / 1
communications Yes SHRAH2A

16 AO (4-20 mA outputs) eight per I/O Pack Barrier Yes TBAOH1C PAOCH1A / 1, 2
Eight AO (4-20 mA outputs) Box No STAOH1A PAOCH1A / 1
Yes STAOH2A
12 Thermocouples Box Yes STTCH2AZZ PTCCH1A / 1
No STTCH1AZZ
Barrier Yes TBTCH1BZZ PTCCH1A / 1, 2, 3
12 Thermocouples with extended range for EPRI compliance Barrier Yes TBTCH1BZZ PTCCH2A / 1, 2, 3
Box No STTCH1AZZ PTCCH2A / 1
Yes STTCH2AZZ
24 Thermocouples (12 per I/O Pack) Barrier Yes TBTCH1CZZ PTCCH1A / 1, 2
24 Thermocouples (12 per I/O Pack) with extended range for EPRI PTCCH2A / 1, 2
compliance
16 RTDs three wires /RTD (eight per I/O Pack) Barrier Yes TRTDH1D PRTDH1A / 1, 2
16 RTDs three wires /RTD (eight per I/O Pack) supports fast scan Barrier Yes TRTDH2D PRTDH1A / 1, 2
rate
Eight RTDs three wires /RTD Box No SRTDH1A PRTDH1A / 1
Yes SRTDH2A
Six Modbus® Master serial or one Modbus Ethernet Box No SSCAH1A PSCAH1A / 1
Yes SSCAH2A
PROFIBUS™-DPV0, Class 1 Master Communications NA NA SPIDG1A PPRFH1A / 1
4 Adds 200 mA outputs KPAIH1A

3
GEA-S1212
Turbine Application - Primary Trip Protection Types Terminal Removable Terminal I/O Pack Qty. per
Board Type Terminal Board Board Terminal Board
Mixed I/O: four pulse rate inputs / pack, synch, shaft V/I monitor, Barrier Yes TTURH1CZZ PTURH1A / 3
eight flame through TRPG
Mixed I/O: four pulse rate inputs / pack, synch, shaft V/I monitor, Barrier Yes TTURH2CZZ PTURH1A / 3
nuclear applications
Heavy duty gas turbine and medium steam turbine applications
- Primary trip for solenoids TMR (24/125 V dc) G-M flame Barrier Yes TRPGH1BZZ
Channels
- Primary trip for solenoids Simplex (24/125 V dc) eight G-M Barrier Yes TRPGH2BZZ
flame channels
- Primary trip for solenoids TMR (24/125 V dc), nuclear Barrier Yes TRPGH3BZZ
applications
Large steam turbine applications - Primary trip for solenoids TMR Barrier Yes TRPLH1A
(24/125 V dc) energize and de-energize, two E-Stop
Industrial steam turbine applications - Primary trip for solenoids Barrier Yes TRPSH1A
Simplex/TMR (24/125 V dc) energize and de-energize, two E-Stop
Aero derivative gas turbine applications
Mixed I/O: four PR inputs/pack, one E-Stop, four trip string monitors, Barrier Yes TRPAH1AZZ PTURH1A / 3
two 24 V dc voted outputs
Mixed I/O: 4 PR inputs/pack, one E-Stop, four trip string monitors, Barrier Yes TRPAH2AZZ PTURH1A / 3
two 125 V dc voted outputs
Simplex turbine applications
- Four PR inputs, two trip outputs to trip solenoids Box STURH1A PTURH1A / 1
- Four PR inputs, synchronizing, two trip outputs to trip solenoids Box STURH2A PTURH1A / 1
- Four PR inputs, cable to TRPG, TRPL, TRPS, TRPA trip boards Box STURH3A PTURH1A / 1
- Four PR inputs, synchronizing, cable to TRPG, TRPL, TRPS, TRPA Box STURH4A PTURH1A / 1
trip boards
Turbine Application – Emergency Trip Protection Types Terminal Terminal Board Terminal I/O Pack Qty. per
Board Type Removal Board Terminal Board
Mixed I/O: three PR inputs, synch check protection, watchdog for Barrier Yes SPROH1A PPROH1A / 1
primary controller
Mixed I/O: three PR inputs, synch check protection, watchdog for Box Yes SPROH2A PPROH1A / 1
primary controller
Mixed I/O: nine PR inputs, synch check protection, watchdogs for Barrier Yes TPROH1C PPROH1A / 3
primary controllers
HDGT, TMR, DI = 125 V dc, DO = three 24/125 V dc, E-Stop Barrier Yes TREGH1B
HDGT, TMR, DI = 24 V dc, DO = three 24/125 V dc, E-Stop Barrier Yes TREGH2B
Versions of TREGH1B used in nuclear emergency trip systems Barrier Yes TREGH3B
Three independent terminal boards for independent redundancy TREGH4B
TREGH5B
Large steam, TMR, DI = 125 V dc, DO = three 24/125 V dc Barrier Yes TRELH1A
Large steam, TMR, DI = 24 V dc, DO = three 24/125 V dc Barrier Yes TRELH2A
Industrial steam, Simplex/TMR, DI = 125 V dc, Barrier Yes TRESH1A
DO = three 24/125 V dc
industrial steam, Simplex/TMR, DI = 24 V dc, DO = three 24/125 V dc Barrier Yes TRESH2A
Aero, TMR, nine pulse rate, DI = none, DO = two 24 V dc Barrier Yes TREAH1A PPROH1A / 3
Box TREAH3A
Aero, TMR, nine pulse rate, DI = none, DO = two 125 V dc Barrier Yes TREAH2A PPROH1A / 3
Box TREAH4A

For further assistance or technical information, contact the


nearest GE Sales or Service Office, or an authorized GE Sales
Representative.

g
© 2008, General Electric Company, All rights reserved.
* Trademark of General Electric Company.
HART is a registered trademark of HART Communication Foundation.
Modbus is a registered trademark of Schneider Automation.
PROFIBUS is a trademark of PROFIBUS International.

GEA-S1212 081017

You might also like