S.No.

Queries
1 Is the structure Welded or Bolted
2 Availability of UKB sections in India.
3 If Pilling is done by external entity who will do the set-out of centreline
4 The size and section of the cleat angle (50x50x6mm) is very slender for resting of beams.
5 Make and specification of welding rods is not mentioned
For columns and shear walls Self Compacting Concrete will be required as there is congestion
6
of steel
7 Plinth beam level and design not mentioned in the drawing.
8 Connection details of shear wall with decking slab no mentioned.
9 Slab thickness is 125mm which doesn't provide 2 hour fire rating.
10 Column to column splice details not mentioned