You are on page 1of 2

Relay.

rdb SEL-551C 001


New Settings 1 0551C0AX1X1X

SEL-551C Settings Report

Setting Range Value


Group : 1
RID FEEDER 1
TID STATION A
CTR 1-6000 600
CTRN 1-6000 600
TDURD 0-8000.000 cyc 9.000
50P1P OFF,0.1-16.0A 3.0
50P2P OFF,0.1-16.0A 4.0
50P3P OFF,0.1-16.0A OFF
50P4P OFF,0.1-16.0A OFF
50P5P OFF,0.1-16.0A OFF
50P6P OFF,0.1-16.0A OFF
50ABCP OFF,0.1-16.0A OFF
51P1P OFF,0.1-3.2A 1.2

51P1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51P1TD 0.50-15.00 3.00


51P1RS Select: N, Y N
51P2P OFF,0.1-3.2A OFF

51P2C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51P2TD 0.50-15.00 15.00


51P2RS Select: N, Y N
50N1P OFF,0.1-16.0A OFF

<Filter is Empty>
1 Of 4 4/05/2020 3:18 PM
Relay.rdb SEL-551C 001
New Settings 1 0551C0AX1X1X

Setting Range Value


50N2P OFF,0.1-16.0A OFF
51N1P OFF,0.1-3.2A OFF

51N1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51N1TD 0.50-15.00 15.00


51N1RS Select: N, Y N
50G1P OFF,0.1-16.0A OFF
50G2P OFF,0.1-16.0A OFF
51G1P OFF,0.1-3.2A 0.3

51G1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51G1TD 0.50-15.00 1.50


51G1RS Select: N, Y N
50Q1P OFF,0.1-16.0A OFF
50Q2P OFF,0.1-16.0A OFF
51Q1P OFF,0.1-3.2A OFF

51Q1C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51Q1TD 0.50-15.00 15.00


51Q1RS Select: N, Y N
51Q2P OFF,0.1-3.2A OFF

51Q2C Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3

51Q2TD 0.50-15.00 15.00


51Q2RS Select: N, Y N

<Filter is Empty>

2 Of 4 4/05/2020 3:18 PM

You might also like