LC Series - Axial Flow Fans

Technical Description
LC 500 4 10B 20O

Pitch Angle

Number of Blades
and Blade Type
Motor Poles

Diameter Impeller

LC: Axial Flow Fan


LCS: Smoke Extract Fan
LCF: ATEX Fan

LC Series Description
Breeze “LC” Series offer you a complete range of fan system and wide options of accessories such as impellers
and hubs to meet all kinds of applications and demands. With “Breezax” impellers and London Fan Company
Group, “LC” Series offer high efficiency up to 80% or even higher.

Advanced Design of Straightening Stator Vanes and Ogive for Axial impellers:
With world's leading Computational Fluid Design (CFD), London Fan has developed advanced straightening
stator vanes and ogives for axial impellers. As the figur shows, with straightening stator vanes and ogive, turbu-
lence in front of impeller has been greatly reduced, airflow becomes more stable and the efficacy can be
improved up to 8%.

Notes:
1. For detail, please see the fan performance curve or contact with Breeze Industrial Ventilation Fan.
2. Special or other size of air outlet direction, please negotiate with Breeze Industrial Ventilation Fan.

04 www.breeze.com.vn
LC Series - Axial Flow Fan
Casing
Range sizes are from 315mm to 1600mm diameter. Hub Type Number of Blades
The casing are roller formed and double- 110 5
flanged. Are flanged to BS6339 & ISO6580
and manufactured from by mild steel with 160 5,10
epoxy coated to EN ISO1461:1999 and
230 3,6,12
thickness ranges from 2.0mm to 5.0mm. Our
standard casing surface is made in epoxy 250 3,6,12
coated or hot dip galvanized or requested.
330 4,8,12,16
Impellers 400 4,8,12,16
High efficiency aluminium aerofoil type. All units are
fitted with Breezax impellers with AL, GRP or Blade Design/Type
GRN aerofoil blades. Aluminium blades can be We have several options Blades
fitted in standard. Hubs are die cast aluminium Design as following
alloy.

AL Aluminium Blades: Design Type Material Hub Series


Breezax blades are made of air cast aluminum
(LM6). It has been tested that both blades can Breezax,B ALU 110,160,230
be used in fire fighting exhaust when the Breezamax,T ALU 250,330
temperature ranges from -40oc to + 200oc.
The recommended maximum blade tip linear Breezamax,C GRP/ALU 400
velocity is 100m/s.
Motors
GRP Glass Reinforced Polypropylene Blades (Red):
Motor used comply with electrical standard
Our standard red GRP blades, made from glass
reinforced polypropylene, can operate safely in BS5000 and mechanical standard BS4999. Foot or
the range from -40oc to +70oc. The recommend- Pad mounted type. TEFC with protection IP55,
ed maximum blade tip linear velocity is 105 m/s. Class F insulation.
The Breeze be able to provide high temperature
rated 250oC/2 hours or 300oC/2 hours with IP55,
GRN Glass Reinforced Nylon Blades (Black):
class H insulation as requested and conforming to
Glass Reinforced nylon blades 66 (black) are high IEC60034-1 with flying lead. They are fitted with
strength and high temperature resistance sealed for life ball bearings and wired to an exter-
(nonthermal radiation resisting range from -40oc nal junction box on the fan case. Available on all
to +150oc). The recommended maximum blade
sizes, pole changeable, voltage controllable,
tip linear velocity is 105 m/s
inverter control or two speed fans available on a
slightly longer lead time or high temperature motor
Balance:
are available upon request. Single phase
The Axial Fan are tested to the latest interna-
220/240V, Three-phase 380/415/460V and 50/60
tionally recognized standard ISO 1940 with grade
Hz, other frequencies and voltages on demand.
G 2.5 mm/s.

Working Temperature: Explosion Proof Motor: Comply with ATEX Directive


-40oc + 70oc GRP 2014/34/EU, EN50014, EN50018 & EN50281-1-1.
-40oc + 150oc GRN Enclosure IP55, 56 or 65, Class F, Fitted with sealed
-40oc + 200oc ALU for life ball bearings.

Gas and Dust Groups: The range covers Gases


Hub System:
Groups IIA, IIB & IIC and most Dust hazards. The Gas
Our range of axial fans has fully adjustable or Dust type must be specified.
blades and there are 6 hub systems, as
shown below: The motor bearings have a L 10 life of at least
35.000 hours i. e. an average life of 140.000 hours
when calculated in accordance with ISO 281.

05 www.breeze.com.vn
LC Series - Axial Flow Fan
Operating Temperatures:
For Class ‘F’ Motor, working temperature from The sound pressure level at the inlet at 1m distance
-20oC to +50oC as standard, fans for operation in low reflexion installation can be obtained by
beyond these limits are also available. deducting 11dB from the sound power level at the
inlet side. The sound pressure difference from 1m
Performance to distance a is obtained as follows:
Full details are available on our selection software: LpiA= 10 * log (1/a ).
Breeze Fan or London Fan. The selection software Please note that reflections and room character-
committed to quality assurance and certified istics as well as natural frequencies influence the
accordance with ISO 9001:2008. All products are size of the sound pressure level differently.
tested in up to date test facilites in conformity with
BS 848 and ISO 5801.
Certification
The type selection software is convenient, simple, Fully to certified to BSI EN12101-3:2002 for smoke
intelligent. It is easy to choose suitable fans, provide and non-smoke reservoir.
and print out all data to confirm the result of Certificate number 0086-CPD-493412.
choice. You can transfer these data to consultants Manufacturing FLC EN12101-3/ISO9001:2008.
and designers. Please contact Breeze Fan sales
department or login
Mounting & Guards
http://www.breeze.com.vn for type selection
software. All units are suitable for internal or external opera-
tion at any installed angle.
Inlet or outlet wire guards can be supplied for all
Sound Level Power
sizes.
Noise ratings are calculated starting from sound
power level measurements made in accordance
with BS 848-part 2: 1985. The test results keep into
onsideration the presence of the motor inside the
fan.

The sound power levels shown on the fan curves


are for inlet LWiA scale for installation type D:
ducted inlet, ducted outlet. Ratings include the
effects of ducted end correction.

If the sound power frequency spectrum is


needed, for example, the design of sound attenu-
ators, the A- rated sound power levels at particu-
lar octave band frequency LWiA can be calculat-
ed by subtracting the relative sound level Lwrel.
LWiA = LWi - LWrel

The acoustic values of the inlet side can be used for


the outlet side of the fans as well.

PRODUCT RANGE APPLICATIONS


ͻ Long Cased Axial fan ͻ Shopping mall ͻ Universities
ͻ Bifurcated Axial fan ͻ Car parks ͻ Sport Arenas
ͻ Smoke Extract fan ͻ Office Developments ͻ Duct mounted
ͻ Roof Mounted fan ͻ Factory Developments ͻ Wall mounted
ͻ Propeller fan ͻ Schools
ͻ Potable

We also manufacture an extensive range of fans for smoke pressurization.

06 www.breeze.com.vn
LC Series - Axial Flow Fan
Dimensions
J
C

A
B
G/H

Fan size A B C Motor Frame G-nos H-Dia J Wt(kg)


315 315 395 400 D71-90 8 10 355 35
355 355 435 400 D71-90 8 10 395 40
400 400 485 400 D71-90 8 12 450 45
450 450 530 400 D71-90 8 12 500 50
450 D100-112 70
500 500 585 400 D71-90 12 12 560 60
450 D100-112 80
570 D132 110
560 560 660 400 D71-90 12 12 620 70
450 D100-112 80
570 D132 120
630 630 730 400 D71-90 12 12 690 75
450 D100-112 95
570 D132 150
710 D160 240
710 710 810 450 D100-112 16 12 770 104
570 D132 160
710 D160 310
790 D180 360
800 800 900 450 D100-112 16 12 860 110
570 D132 170
710 D160 320
790 D180 370
900 900 1000 450 D100-112 16 16 970 150
570 D132 180
710 D160 280
790 D180 403
840 D200 520

07 www.breeze.com.vn
LC Series - Axial Flow Fan
Dimensions

Fan size A B C Motor Frame G-nos H-Dia J Wt(kg)


1000 1000 1100 570 D132 16 16 1070 200
710 D160 300
790 D180 420
840 D200 550
1000 D225-250 660
1120 1120 1220 570 D132 16 16 1190 250
710 D160 320
790 D180 450
840 D200 580
1000 D225-250 650-780
1200 D280-315 950-1350
1250 1250 1350 570 D132 20 16 1320 300
710 D160 380
790 D180 470
840 D200 600
1000 D225-250 700-800
1200 D280-315 900-1400
1400 1400 1500 570 D132 20 16 1470 400
710 D160 520
790 D180 620
840 D200 710
1000 D225-250 750-950
1200 D280-315 1100-1500
1600 1600 1700 710 D160 24 18 1680 600
790 D180 700
840 D200 800
1000 D225-250 850-1150
1200 D280-315 1350-1950
1800 1800 1900 710 D160 24 18 1880 750
790 D180 890
840 D200 1050
1000 D225-250 1250-1550
1200 D280-315 1750-2250
2000 2000 2100 710 D160 24 20 2080 850
790 D180 1050
840 D200 1250
1000 D225-250 1450-1850
1200 D280-315 2050-2550

08 www.breeze.com.vn
LC Series - Axial Flow Fan

PERFORMANCE CURVES
MORE DETAILED CURVES AVAILABLE ON REQUEST

09 www.breeze.com.vn
LC Series - Axial Flow Fans

Accessories
Suitable Weight (kg)
Silencer - B Type for fan B C
OA B type C type
C
315 415 315 10 13
355 455 355 12 15
400 500 400 15 18
450 600 450 20 24
500 650 500 25 29
PCD
B
A

POD - TYPE C ONLY


560 710 560 30 35
630 780 630 35 42
710 960 710 44 53
800 1000 800 55 66
Tapped hole to 900 1100 900 70 84
match fan flange 1000 1200 1000 82 100
1120 1320 1120 100 118
The above silencers give the approximate dB(A) reductions:-
B Type diameter Length - 7 to 10 dB(A) 1250 1450 1219 127 147
C Type 1 Diameter length - 12 to 15 dB(A) 1400 1600 1400 193 220
For full acoustic details contact with: Breeze Fans. 1600 1800 1600 311 362

Size A B C D Į Wt (kg)
315 365 25 220 50 12 0.5
355 405 25 240 50 12 0.8
CENTRE OF FAN
400 450 25 260 50 12 1.0
450 500 25 280 50 12 1.2
500 550 25 315 60 12 1.5
C
560 610 25 345 60 14 2.0
630 680 30 400 75 14 2.5
2 NOS. O
710 785 30 450 75 14 3.0
B B
A D 800 875 30 500 75 14 5.0
900 975 30 580 75 18 8.0
1000 1075 30 630 75 18 10.0
1120 1220 30 690 75 18 12.0
1250 1350 50 737 95 20 14.0

Size A B C D E Wt (kg)
315 315 395 65 420 2.0 3.0
355 355 435 65 470 2.0 3.5
400 400 485 65 520 2.0 4.0
450 450 530 90 570 2.0 4.5
500 500 585 90 630 2.0 5.0
560 560 660 90 710 2.0 6.0
PLAN 630 630 730 90 780 3.0 8.0
B
710 710 810 90 860 3.0 10.0
A
E
800 800 900 115 980 3.0 12.0
C 900 900 1000 115 1080 3.0 18.0
D 1000 1000 1100 115 1200 3.0 25.0
ELEVATION CONE INLET 1120 1120 1220 115 1320 3.0 30.0
1250 1250 1350 115 1450 3.0 35.0

10 www.breeze.com.vn
LC Series - Axial Flow Fans

Accessories

F Size G. H. J F K L Wt (kg)
L nos Dia
315 8 10 355 395 315 50 2.0
355 8 10 395 435 355 50 2.5
400 8 12 450 485 400 50 3.0
450 8 12 500 530 450 50 3.5
500 12 12 560 585 500 50 4.0
K DIA.

560 12 12 620 660 560 50 4.5


630 12 12 690 730 630 50 5.0
710 16 12 770 810 710 50 6.0
800 16 12 860 900 800 50 7.0
900 16 16 970 1000 900 50 8.0
1000 16 16 1070 1100 1000 50 9.0
1120 16 16 1190 1220 1120 50 10.0
1250 20 16 1320 1350 1250 50 12.0

E Size E Wt (kg)
315 310 1.0
355 350 1.5
400 395 2.0
450 445 2.5
500 495 3.0
560 555 3.5
630 625 4.0
710 705 5.0
800 795 7.0
900 895 8.0
1000 995 10.0
1120 1115 11.0
1250 1245 12.0

* Dimensions shown are approximate only. The details please contact local sales office
for more information.

11 www.breeze.com.vn
LC Series - Axial Flow Fans

INFORMATION
FAN LAWS
SPEED CHANGE – CONSTANT SIZE – CONSTANT DENSITY
Volume Flow ZŽƚĂƟŽŶĂů Speed
Pressure ;^ƚĂƟĐ͕ LJŶĂŵŝĐ ĂŶĚ Total) ;ZŽƚĂƟŽŶĂů Speed)2
Power Absorbed ;ZŽƚĂƟŽŶĂů Speed)3

SIZE CHANGE - CONSTANT SPEED - CONSTANT DENSITY


(For ŐĞŽŵĞƚƌŝĐĂůůLJ ƐŝŵŝůĂƌ ĨĂŶƐ ŽŶůLJͿ
Volume Flow (Impeller ŝĂŵĞƚĞƌͿ 3
Pressure ;^ƚĂƟĐ͕ LJŶĂŵŝĐ ĂŶĚ Total) (Impeller ŝĂŵĞƚĞƌͿ 2
Power Absorbed (Impeller ŝĂŵĞƚĞƌͿ 5

DENSITY CHANGE - CONSTANT SPEED - CONSTANT SIZE


Volume F low = No ĐhaŶg e
Pressure ;^ƚĂƟĐ͕ LJŶĂŵŝĐ ĂŶĚ Total) ĞŶƐŝƚLJ
Power Absorbed

AIR DENSITY
^ƚĂŶĚĂƌĚ ŝƌ ĚĞŶƐŝƚLJ ŝƐ 1.2kg/m 3
KŶĞ ĐŽŶĚŝƟŽŶ that ŐŝǀĞƐ ^ƚĂŶĚĂƌĚ ŝƌ ŝƐ͗
16°͕ 100 kPa ďĂƌŽŵĞƚƌŝĐ ƉƌĞƐƐƵƌĞ͕ 65% ƌĞůĂƟǀĞ ŚƵŵŝĚŝƚy.

{
CHANGE DUE TO TEMPERATURE {
273 + Old Temperature °C
New D eŶs ŝty = O ld D eŶs ŝty x kg/m3
273 + New Temperature°C

ŚĂŶŐĞ due to ĂůƟƚƵĚĞ

{
New D eŶs ŝty = O ld D eŶs ŝty x 288 Ͳ 0.00649 H { 4.256
kg/m3
288
Where H = ,ĞŝŐŚƚ ĂďŽǀĞ sea ůĞǀĞů ŝŶ metres

PRESSURE
It ŝƐ ƉŽƐƐŝďůĞ to ĐŽŶǀĞƌƚ from Total Pressure (PF ) to ^ƚĂƟĐ Pressure (P sF ) ƵƐŝŶŐ the ĨŽůůŽǁŝŶŐ ĞƋƵĂƟŽŶ;ƐͿ͗Ͳ
Total Pressure (P F ) = ^ƚĂƟĐ Pressure (PsF ) + LJŶĂŵŝĐ Pressure (PdF )
ĂŶĚ ^ƚĂƟĐ Pressure (P sF ) = Total Pressure (P F ) Ͳ LJŶĂŵŝĐ Pressure (PdF )

LJŶĂŵŝĐ Pressure (P dF ) ŝƐ also ŬŶŽǁŶ as VĞůŽĐŝƚLJ Pressure (P ǀ) ĂŶĚ ƚŚŝƐ ŝƐ a ĨƵŶĐƟŽŶ of


Volume Flow (q ǀ ) ĂŶĚ ĨĂŶ outlet area (m 2 ). dŚŝƐ ĐĂŶ be ĐĂůĐƵůĂƚĞĚ ƵƐŝŶŐ͗Ͳ

LJŶĂŵŝĐ Pressure (PdF ) = 0.5ʌ V 2 (Pa)


Where ʌ = ŝƌ ĞŶƐŝƚLJ (kg/m 3) Ͳ ^ƚĂŶĚĂƌĚ ŝƐ 1.2 kg/m 3
V = ŝƌ VĞůŽĐŝƚLJ (m/s)
ŝƌ VĞůŽĐŝƚLJ Ͳ V = qǀ x 4 where d ŝƐ the ĚŝĂŵĞƚĞƌ of the ĨĂŶ (m)
ʋ d2 qǀ = Volume Flow (m3/s)

ABSORBED POWER

{
Abs orbed P ower =
Volume ŇŽǁ (m3/s x Total Pressure (Pa) { kW
Total EĸĐŝĞŶĐLJ x10

12 www.breeze.com.vn