SITE TEST REPORT SIEMENS

PRE-COMMISSIONING FORMATS FOR CURRENT TRANSFORMER

I. GENERAL DETAILS DATE OF TESTING – 04/06/2018

DETAILS

Project: 400/220 kV GSS AT JAISALMER (II) Sub-Station: 400/220 kV GSS, RRVPNL, JAISALMER (RJ.)

LOA No. : RVPN/SE(P&P)/XEN/kfw/ICB-1 D.1771 Dated:


Feeder name: 201-M CT
16-10-2015

Make: MEHRU Type: MEHRU

Sr. No.: Year of Manufacture:


R Ø:- OC 6724/3/3/17 RØ:- 2017
Y Ø:- OC 6724/3/2/17 YØ:- 2017
BØ:- OC 6724/3/1/17 BØ:- 2017
Rating: 245/220 kV

II. RATED DATA AND DUTY

PROTECTION /
CORE RATIO CLASS BURDEN
METERING

Winding I 2000-1000-500/1 0.2S 20VA METERING

Winding II 2000-1000-500/1 0.2S 20VA METERING

III. INSULATION RESISTANCE MEASUREMENT (Applied Voltage- 5 kV)

a) Insulation Resistance Measurement Primary to Secondary & Earth


(Using 5 kV Digital Megger)

Make of testing kit --: AGAM (AT501)


Date of calibration --: 13/09/2017 to 12/09/2018
Ambient temperature --: 44 deg. C

Remove the connected earthing to system involving CT under test and disconnect the connected
terminals of CT marshalling box

PHASE
UNIT
CORE RØ YØ BØ
PRIMARY - CORE I GΩ 86.8 138 45.4
PRIMARY - CORE II GΩ 90.5 108 59.6
PRIMARY – EARTH GΩ 588 221 92.7

Format : 220 kV Current Transformer


Page 1 of 2
SITE TEST REPORT SIEMENS
b)Insulation Resistance Measurement between cores:-
(Applied Voltage- 500 Volt)
PHASE
BETWEEN
UNIT RØ YØ BØ
 
SECONDARY CORE I - EARTH GΩ 13.6 13.8 14.4
SECONDARY CORE II - EARTH GΩ 12.2 13.6 14.8
CORE I - CORE II GΩ 17.2 18.3 20.7

c) Check IR value between tan delta point and earth at 500V in secondary box

RØ YØ BØ

>1GΩ >1GΩ >1GΩ

IV. POLARITY
PHASE
CORE BETWEEN
R -PHASE Y -PHASE B –PHASE

1S1 1S2 OK OK OK
CORE I 1S1 1S3 OK OK OK
1S1 1S4 OK OK OK
2S1 2S2 OK OK OK
CORE II 2S1 2S3 OK OK OK
2S1 2S4 OK OK OK
V. TAN DELTA AND CAPACITANCE MEASUREMENT
Make of testing kit : MEGGER (13850213)
Date of calibration : 07/04/2018 to 06/04/2019
Ambient temperature: 45°C
 
CAPACITANCE

PRE COMMISSIONING VALUES (in pF)


ACROSS STACK
R Ø YØ B Ø

2 kV 475.6 482.2 471.8


10 kV 475.6 482.2 471.9

TAN DELTA

ACROSS PRE COMMISSIONING VALUES


STACK
R Ø YØ B Ø
2 kV 0.189 0.189 0.191
10 kV 0.191 0.190 0.194

Format : 220 kV Current Transformer


Page 2 of 2
SITE TEST REPORT SIEMENS

Signature: Signature: Signature: Signature:


OTEPL (Testing ) SIEMENS LTD. T & C , RRVPNL JAISALMER MPT & S , RRVPNL JAISALMER

Format : 220 kV Current Transformer


Page 3 of 2