RTU500 series

Multimeter 560CVD03
Data sheet

Dis-
Type
Versions play LO HI 1A 5A

560CVD03 R0025 3U3I x x

560CVD03 R0041 3U3I x x

560CVD03 R0045 3U3I x x

Characteristics
The Multimeter is a microprocessor-based Intelligent Electron-
ic Device (IED) intended for current, voltage, power and energy
Figure 1: 560CVD03 without LCD Display
measurement.

Current and voltage inputs are connected via transformer only


(see Wiring). The module supports a configuration with 2 voltage
transformes (3 wire connection) and 2 current transformers. A
second configuration is with 3 voltage transformers (4 wire con-
nection) and 3 current transformers.

Calculated values are scaled by user programmed constants for


current and voltage transformers. All values are updated once
per second.

The current inputs withstand 50 times nominal current for 1 s.

Figure 2: 560CVD03 with LCD Display


Power Measuring Display

Application The display is available for the versions R003x and R005x. It
switches automatically the displayed measurement page screen.
The Multimeter 560CVD03 is used for measuring analog AC in-
put signals from three independent phases. For each phase volt- The scroll mode can configured with RTUtil500:
age and current are measured directly and a number of calcu- – Manual mode: Each screen will be displayed for 4 minutes.
lated values are generated by the module. The module supports The push button can be used for switching the pages man-
configurations with 2 or 3 voltage transformers. ual.
– Scanning mode: Each screen will be displayed for 6 sec-
There are several versions available: onds.

Dis-
Type
Versions play LO HI 1A 5A

560CVD03 R0031 3U3I x x x

560CVD03 R0035 3U3I x x x

560CVD03 R0051 3U3I x x x

560CVD03 R0055 3U3I x x x

560CVD03 R0021 3U3I x x


Wiring

3 Phase 4 Wire

Source Load

RS-232
Figure 4: Power measurement convention

Energy values

Power RS-485 Integrated total (intermediate and end of period readings) are
calculated for:
Figure 3: 3 phase, 4 wire connection (3P4W) – active energy negative
– active energy positive
– reactive energy capacitive
Meter Operation – reactive energy inductive

The following measured or calculated values are available from Voltage / Current Distortion (THD)
the module.
The 560CVD03 provides a measure of the total harmonic distor-
Instantaneous Meter Values tion (THD), in each phase voltage and current waveform, as a
percentage deviation from pure 50Hz or 60Hz sine waves.
Following values are measured by true RMS conversion
THD is calculated by Fast Fourier Transform algorithm (FFT) for:
Measurement Measuring Path – U1, U2, U3
– I1, I2, I3
Neutral voltage Phase 1-N, 2-N, 3-N

Phase voltage Phase 1-2, 2-3, 1-3

Current Phase 1, 2, 3

Active power (Watt) Phase 1, 2, 3, total

Reactive power (Var) Phase 1, 2, 3, total

Apparent power (VA) Phase 1, 2, 3, total

Power factor (PF) Phase 1, 2, 3, total


PF = |cos phi| + high bit set for leading
load (high bit 0 for lagging load)

Frequency System

Phase rotation Positive/ negative sequence

The Multimeter supports 4 quadrant power values.

2 | 1KGT 150 788 V007 1 - Multimeter 560CVD03


Technical data Serial Ports

Load Up to 32 units loads


In addition to the RTU500 series general technical data, the fol-
lowing applies:
Mechanical Layout

Input channels Dimensions 100 mm x 70.3 mm x 114.5 (Width x


Height x Depth)
Voltage Measurement range: 85 ... 400 V AC
U1, U2, U3 phase to neutral Housing type Plastic housing

Load : < 0.3 VA per phase Mounting DIN rail mounting EN 50022 TS35: 35
Input impedance: 1 MΩ mm x 15 mm or 35 mm x 7.5 mm

Current Measurement range: or bottom mounting

I1, I2, I3 – 5 A version: 0.010... 6 A


– 1 A version: 0.002... 1.2 A Immunity test

ANSI / IEEE C37.90.1-1989 3 kV SWC


Load: < 0.3 VA per phase
Overload withstand: IEC 61000-4-12 Class III SWC

– 2 x IN continuous Fast Transient / Burst IEC 61000-4-4 Class IV SWC


– 50 x IN 1 sec
Surge Immunity Test IEC 61000-4-5 Class IV Impulse
Frequency 45... 65 Hz

Samples 32 samples per cycle Insulation tests

Harmonics Up to 15th harmonic for 50/60 Hz Dielectric Strength IEC 60255-5 2 kV AC rms, 1 minute

Data update interval 1 sec


Environmental conditions

Nominal operating temperature range: -25°C... 70°C


Accuracy Start up: -40 °C
Max. operating temperature, max. +85 °C
Phase current I 0.2 %
96h:
Neutral current I 0.2 %
EN 60068-2-1, -2-2, -2-14
Phase voltage U 0.2%
Relative humidity 5 ... 95 %
Phase to phase voltage U 0.2% EN 60068-2-30 (non condensing)

Active power (Watt) 0.5 %


Ordering Information
Apparent power (VA) 0.5 %
560 CVD03 R0021 1KGT 028 000 R0021
Reactive power (Var) 0.5 %
In = 1A, Version LO
Power factor (PF) 0.5 %
560 CVD03 R0031 1KGT 028 000 R0031
Frequency 0.2 %
In = 1A, Version LO, Display
AD converting 12 bit + sign
560 CVD03 R0041 1KGT 028 000 R0041
In = 1A, Version HI
Power supply input
560 CVD03 R0051 1KGT 028 000 R0051
Power supply voltage (LO) 24... 48 VDC ±15 % In = 1A, Version HI, Display

Power supply voltage (HI) 85... 265 V AC/ DC


560 CVD03 R0025 1KGT 028 000 R0025
Power consumption 3 VA AC In = 5A, Version LO
2 W DC
560 CVD03 R0035 1KGT 028 000 R0035
In = 5A, Version LO, Display
Serial Ports
560 CVD03 R0045 1KGT 028 000 R0045
Modbus RTU protocol RS485 In = 5A, Version HI
Distance: < 150 m
560 CVD03 R0055 1KGT 028 000 R0055
Diagnostic Port RS232
In = 5A, Version HI, Display
Baud Rate Always configure 19.2 kbps

Multimeter 560CVD03 - 1KGT 150 788 V007 1 | 3


Additional material

Configuration kit for 560CVDxxx (Tool 1KGT030800R0001


CD, cable)
560KCA01 R0001

4 | 1KGT 150 788 V007 1 - Multimeter 560CVD03


ABB AG Note:
Power Systems Division The specifications, data, design or other information contained in this document
P.O. Box 10 03 51 (the “Brochure”) - together: the “Information” - shall only be for information pur-

68128 Mannheim, Germany poses and shall in no respect be binding. The Brochure does not claim to be ex-
haustive. Technical data in the Information are only approximate figures. We re-

www.abb.com/substationautomation serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be ad-
justed or customized.

This product is designed to be connected to and to communicate information


and data via a network interface. It is the users sole responsibility to provide and
continuously ensure a secure connection between the product and users or end
customers network or any other network (as the case may be). The user shall es-
tablish and maintain any appropriate measures (such as but not limited to the in-
stallation of firewalls, application of authentication measures, encryption of da-
ta, installation of anti-virus programs, etc) to protect the product, the network, its
system and the interface against any kind of security breaches, unauthorized ac-
cess, interference, intrusion, leakage and/or theft of data or information. ABB AG
is not liable for any damages and/or losses related to such security breaches, any
unauthorized access, interference, intrusion, leakage and/or theft of data or infor-
mation.

ABB AG shall be under no warranty whatsoever whether express or implied and


assumes no responsibility for the information contained in this document or for
any errors that may appear in this document. ABB AG's liability under or in con-
nection with this Brochure or the files included within the Brochure, irrespective
of the legal ground towards any person or entity, to which the Brochure has been
made available, in view of any damages including costs or losses shall be exclud-
ed. In particular ABB AG shall in no event be liable for any indirect, consequen-
tial or special damages, such as – but not limited to – loss of profit, loss of pro-
duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-
ital or cost connected with an interruption of business or operation, third party
claims. The exclusion of liability shall not apply in the case of intention or gross
negligence. The present declaration shall be governed by and construed in ac-
cordance with the laws of Switzerland under exclusion of its conflict of laws rules
and of the Vienna Convention on the International Sale of Goods (CISG).

ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents -
in whole or in part - is not permitted without the prior written consent of ABB AG.

© Copyright ABB 2017