Professional Documents
Culture Documents
Fig. 1 Typical end device with open phase demonstrates there are only two
The authors acknowledge Tennessee Valley Authority (TVA) for
paths for the current to flow effectively single phasing the equipment.
supporting this research.
The authors are with TVA, Chattanooga TN 37402, USA.
A more noteworthy case occurs when the OPF is above an instantaneous pickup for non-motor loads are between three
OSP transformer as shown in the following diagram. and five times rated current. Assuming positive and negative
sequence voltages create the maximum single phase current
(200% rated) phase overcurrent tripping is not a concern in the
transient timeframe for non-motor loads.
When considering motor loads typical overcurrent devices
used to protect end devices work on single phase values.
Negative sequence currents when combined with positive
sequence currents will elevate one or more phase currents.
Upon inspection it was determined that the worst case single
Fig. 2 Open phase ahead of a transformer similar to the Byron Event. phase currents exist when the positive and negative sequence
currents are in phase (i.e., ±120° out of phase) with each other.
In this configuration (Fig. 2), the magnetic circuits of a
three phase transformer will attempt to reconstruct the missing 1 1 1
phase. This is especially true in the case of three leg core type 1 (1)
transformers. With a three limb core type transformer, the flux 1
is forced into the limb with the OPF. This will rebuild the
missing phase voltage. For example a positive sequence current of 100A and a
negative sequence current of 10A would yield a worst case
phasor current of up to 110A.
1 1 1 0 110 0
1 100 0 95.4 125.2 (2)
1 10 0 95.4 125.2
catastrophic failure. Due to thermal mass of the machines, it review, a bounding technique was developed where the motor
can take anywhere from minutes to hours to reach equilibrium with the smallest X2 on each bus that is running in any
temperatures [6]. Therefore, the heating is not a concern in the applicable case had its diversity set to 0.1% for the remaining
transient (less than 30 cycle) timeframe. cases where it was not “running”. This allows the calculation
By combining Eq. 1 and 3, it can be determined that at of negative sequence currents on these worst-case motors
some point, unbalance would cause there to be more thermal without changing loading on the upstream transformers.
heating of the load than what would be detected by the Elements were added to the model supporting the insertion
overcurrent devices, potentially damaging the loads. of a grounded OPF. A single OPF with ground is modeled in
ETAP using an infinite single-phase load to ground via a
IV. STUDY METHOD single-phase impedance, which can be varied from zero to
With the understanding that the true impact (heating) on the high values to simulate solid grounds or high impedance
faults.
motors can be determined from the positive and negative
sequence results of an OPF, a process was developed to
VI. ASSUMPTIONS
analyze the system response to various OPFs and collect the
necessary data to draw conclusions. The overall method is a The grid unbalance was set to 1.41% based on the
steady-state load flow technique using the Unbalanced Load maximum statistically expected grid unbalance in the
Flow module in ETAP. While this cannot determine the Tennessee Valley [8].
dynamic response of the power system to an OPF, it does The Emergency Diesel Generators (EDG) are assumed as
provide steady-state voltages and currents throughout the not operating during the OPF. This is because EDG protective
devices for the cases studied would either allow the EDGs to
system (phase and sequence quantities). These results are
mask the voltages or trip immediately resulting in the analyzed
indicative of the system’s response to the OPF with all loads
condition. Validating with a few iterations it was confirmed
remaining in their initial state (i.e., running or starting).
that runs in which the OPF was ungrounded the voltage and
Initially, because it would take an almost unlimited number of current were less unbalanced and cases in which the OPF was
simulations to produce accurate results for every eventuality, grounded the unbalance voltage and current would exceed the
(various transformer loadings, temperature variations, capabilities of the diesel generator engine.
impedance tolerances, grid voltages, grid balances, etc.) Because automatic voltage correction actions such as
bounding techniques and modeling conventions were transformer LTCs or yard capacitor actuations may obscure
developed to account for the competing conservatisms needed the results in terms of detectability, existing protection will
to address these variations and tolerances. only be considered if it can detect the OPF before automatic
actions occur. Therefore the LTCs will be assumed as “fixed”
V. ETAP INSTRUCTIONS/CONVENTIONS in the pre-fault position during the OPFA.
Additional data was entered into the transformers to support To make the appropriate determinations for the amount of
the OPFA (i.e., S-C impedance and loss data including zero- unbalance and its effect, the following information was
sequence values). In the case of OSP transformer specific data recorded:
must be used and each transformer model validated against Phase voltage and angles for the medium voltage nuclear
actual tests (see below). If sufficient model data is not safety buses.
available for an OSP transformer, meaningful OPFA is not Phase current for the open-phase bus.
possible since it cannot be assumed. Negative sequence current for the worst-case (lowest
However, delta-delta transformers typical data can be negative sequence impedance) motor per affected bus.
assumed where actual data is not available. The mathematical With the bus information, voltage unbalance can be
model of a delta-delta transformer is provided below, which calculated using the following formula:
from inspection one can determine that any value of ZT will
produce the same results. 100 (4)
100 (5)
Fig. 5 Delta- Delta zero sequence model [3]
This was confirmed in ETAP by performing a sensitivity VII. EXAMPLE BASED RESULTS
study where the typical zero sequence impedance is evaluated After a few initial iterations where many individual
ranging from 1% to 10,000% of the typical values and variables were changed, it was determined that transformer
comparing the downstream voltages. loading and fault impedance were the two critical parameters
All existing motor models had their negative-sequence that affect the results. Two types of faults were considered for
reactance (X2) adjusted such that [4]. To limit the each OSP transformer, truly open (no path to ground) and
The six point analysis determined that the amount of The comparison between Fig. 6 & 7 illustrates the impact of
voltage unbalance increases as the fault impedance decreases the stabilizing winding. The voltage unbalance increases in
(solidly grounded) and that the amount of voltage unbalance the high impedance range of the surface without the presence
increases slightly as the loading on the transformer increases. of a stabilizing winding. Additionally, the rise in unbalance
These six points determined the boundaries of the plant voltage for the range of 10% to 100% loading is increased for
OSP transformers, however did not explore the full that same range of impedance. For a given downstream power
capabilities of the transformers nor various amounts of fault system there is a “saturation point” for which the unbalance
impedance. The second stage of comparison occurred using a will not further increase. The maximum unbalance on both
range of transformer loading (in increments of 10%) and a surfaces is approximately equal.
logarithmic scale of impedance values between true open and A generator connected between the open phase and the
solid ground. loads will produce large negative sequence currents. These
Using this larger progression of data values, a graphical currents will eventually trip the generator in a few seconds.
visual aid was developed that allows for better perception of Fig. 8 shows that the generator will work to balance the
the results. A three dimensional surface of voltage unbalance downstream voltages. It is only when the excitation system
was developed around various transformers and plant becomes maxed out that the unbalances begin to increase.
configurations feeding the same system. These include
transformer with and without a stabilizing winding (i.e., buried
delta) and system configurations such as generator connected Surface for Generator Connected
and disconnected.
40
Voltage Unbalance (%)
35
Surface with Stabilizing Winding 30
25
20
15
Voltage Unbalance (%)
40
35
10
30 5 90
0 70
25 50
20 30
15 10
10
5 90
70 Fault Impedance (Ω)
0 50
30
10 Fig. 8 Voltage unbalance vs. transformer loading and fault impedance
with a generator connected downstream
Fault Impedance (Ω)
These results were compared to a given criteria for either
Fig. 6 Voltage unbalance vs. transformer loading and fault “acceptability” (is the fault acceptable for continued safe
impedance for a Y-D-Y transformer operation), or “detectability” (can the fault be detected with
existing protective devices). The acceptability was originally
This information clearly visualizes the significant unbalance developed based on the unbalanced factors previously
potential, especially as the fault impedance decreases. established such as the 1% and 5% voltage unbalance [7].
To see the effect of stabilizing windings on the results, a These are conservative but acceptable values. Detectability is
transformer with no stabilizing winding was substituted for the discussed in the following section.
previous transformer.
VIII. PROTECTIVE DEVICE CONSIDERATIONS similar maximum unbalances. Having a stabilizing winding
For any protective device scheme to detect an OPF, it must will allow for lower overall unbalances, but with increasing
be sensitive enough to see the fault, and fast enough to loading and ground fault current, it will eventually saturate
preclude damage to the end devices. The results from the and produce similar results to a transformer without a
collective group of simulations can be used to define a set of stabilizing winding.
significant OPFs which have detrimental effects on the end The ETAP unbalanced load flow module can accurately and
devices. These significant cases are defined by two criteria: effectively calculate steady state voltage and current
unbalances resulting from OPFs [9]. Multiple fault simulations
1) The equivalent current (Eq. 3) is greater than the motor can be performed in order to create a three dimensional
“safe” current (i.e., current at motor service factor). surface in order to visualize the effect of open-phase faults on
2) The equivalent current is greater than the worst phase the system voltage unbalance. By using these values, the
current. detrimental effects on end devices can be determined. The
With phase current less than the equivalent current, there can results can then be used to determine applicability of existing
be “unmeasured” heating of the motor by standard overcurrent protection schemes, or to develop new ones.
protection. The timing of an OPF protective scheme must be
fast enough that the equivalent current will not damage the REFERENCES
motor. [1] NRC Bulletin 2012-01 "Design Vulnerability in Electric Power
Existing protective devices that may detect an OPF include Systems," http://pbadupws.nrc.gov/docs/ML1207/ML12074A115.pdf
[2] NRC BTP 8-9 “Open Phase Conditions in Electrical Power System,”
Transformer Phase Overcurrent (50/51), Transformer Neutral http://pbadupws.nrc.gov/docs/ML1505/ML15057A085.pdf
Overcurrent (51N), Transmission line negative-sequence (46), [3] J. D. Glover, M. S. Sarma and T. J. Overbye, “Symmetrical
& loss of voltage (27) relays. Degraded Voltage (27) and Components” in Power System Analysis and Design, 5th ed., Stamford,
Transformer Differential (87) relays have been discounted CT: Cengage Learning, 2012, pp 419-470
[4] J. L. Blackburn and T. J. Domin, “Motor Protection” in Protective
from consideration due to the time delay found in most Relaying Principles and Applications, 3rd ed., Boca Raton, FL: CRC
degraded voltage schemes and the potential that the fault could Press, 2007, pp.385-410
occur outside the zone of protection respectively. [5] M. Bowman et al. “Open-Phase Fault Analysis” presented at 2014
Regardless of technology selected to detect the OPF or ETAP Nuclear Utility User Group (NUUG) Conference and
Symposium. ETAP Learning Center. Irvine, CA, June 18 -20, 2013.
protect the nuclear safety system from the event, it should [6] P. Pillay and M Manyage, “Loss of Life in Induction Machines
coordinate with installed devices to prevent a reduction in Operating With Unbalanced Supplies,” IEEE Trakns on Energy
plant operational margin. For example, an OPF protective Conversion, vol. 21, no. 4, pp. 813-822, Dec 2006.
scheme should be slower than the clearing time for yard faults [7] Motors and Generators, ANSI/NEMA MG 1, 2011
[8] J. Rossman et al. “Transmission Voltage Unbalance Evaluation.” Future
so that an open phase event can be differentiated from a of Instrumentation International Workshop. Park Vista. Gatlinburg, TN.
system fault. This should include the first zone of distance Oct. 9, 2012.
relays as well as the backup overcurrent. If the offsite power [9] A. Eltom, A. A. Karrar, M. M. Kamel and H. A. Saeed, “Investigation of
transformer has a neutral connection, an OPF protective Open Phase Conditions in Three-Leg Core-Type Transformers” Internal
Report prepared for TVA, Sept. 2014
scheme should coordinate with the neutral overcurrent and
overvoltage for unbalanced faults.
Many nuclear power stations have voltage correcting
devices such as capacitor banks or auto-tap transformers. An
OPF protective scheme should coordinate with attempts of the
system to correct the voltage. An OPF protective scheme
should trip fast enough so the end device protective devices
will not preclude nuclear safety related loads from performing
their function [2]. The OPF protection scheme should protect
motors from damage caused by the additional heating that can
occur with elevated negative sequence currents [6].
This methodology was applied to several typical nuclear
power plant protection designs and none of the studied
schemes would completely protect the loads from the
damaging effects of an OPF in all significant cases. Industry
response to the OPF events has revealed a number of new
potential solutions which could be used.
IX. CONCLUSIONS
The following generalities can be observed for a single open
phase with variable ground impedance. Greater transformer
loading results in greater unbalances. Less impedance to
ground results in greater unbalances. When placed into the
same electrical system, different transformers will have a