Professional Documents
Culture Documents
CSA Tests and Results – All CSA tests witnessed by Ana Adari, P. Eng. of
CSA International (CSA Master File Number: LR19310)
Temperature test produced acceptable results that met the temperature limits specified in
Table 14 of CSA C22.2 No. 14 and Table 39.1 of UL 508C.
1. 50% blocked test: ETU was operated until thermal stabilization occurred. Temperature test
produced acceptable results that met the temperature limits specified in Table 14 of CSA
C22.2 No. 14 and Table 39.1 of UL 508C.
2. 100% blocked test: Test was performed in conjunction with the Inoperative Fan test. ETU
was operated, a protective device activated and “there was no evidence of a risk of fire or
electric shock.”
ETU was operated, a protective device activated and “there was no evidence of a risk of fire
or electric shock.”
Single Phase UL 508C Sec. 41.3
Test requires that three-phase power conversion equipment be operated with one phase
disconnected. The test consists of two parts: 1) one phase is to be disconnected with the ETU
operating and 2) attempt to restart the ETU with one phase disconnected. Tests are to be
conducted until ETU reaches thermal stabilization or until a protective device operates.
1. Phase B was disconnected with the ETU operating. A protective device activated and
“there was no evidence of a risk of fire or electric shock.”
2. A restart of the ETU was attempted with Phase B disconnected. A protective device
activated and “there was no evidence of a risk of fire or electric shock.”
Dielectric Strength CSA C22.2 No. 14 Cl. 6.8 & UL 508C Sec. 44
Test requires that an ETU withstand for one minute, without breakdown, the
application of a 60 Hz sinusoidal potential between the bare live parts of the power circuit
and the grounded enclosure. The applied potential is based on 2.25 times rated voltage plus
2000 for devices rated between 751 V to 1500 V.
A potential of 4250 VAC was applied for one minute. No breakdown occurred.
The capacitor was shorted and AC power was applied to the ETU. A protective device
activated and “there was no evidence of a risk of fire or electric shock.”
A potential of 2300 ADC was passed through the proper points. After the 10 minute period a
potential drop was measured and using the formula above, the calculated potential drop was
less than the limit of 4 V.
Short Circuit CSA C22.2 No. 14 Cl. 6.10 & UL 508C Sec. 45
Test requires that an ETU shall withstand an output short circuit without creating
potentially dangerous conditions.
ETU passed all applicable short circuit tests with no visible damage. A protective device
activated and “there was no evidence of a risk of fire or electric shock.”
All tests produced acceptable results and/or were within the limits specified
by the applicable standard.
Criteria A: Equipment shall operate without malfunction during the whole time of application
of the interference and after its removal at the conclusion of the test.
Criteria B: The equipment may suffer a temporary malfunction during the application of the
transient event. It should recover after the transient event without operator intervention.
Criteria C: The equipment may suffer a malfunction during the test but should fully recover
following a reset or other immediate operation intervention.
Low Voltage Directive (LVD) Test Summary
The following tests were performed in addition to the CSA / UL testing to prove compliance
to the Low Voltage Directive.
ETU completed the vibration test without any visible damage. ETU also passed a post
vibration operation test witnessed by CSA International. Post operation test was an exact
repeat of the pre- vibration operation test.
EX2100 Simplex
Doors Closed, One Meter Doors Open, Adjacent to
from Enclosure Enclosure
Average Maximum Maximum
2 Fans 73.3 dBA 74.9 dBA 79.9 dBA
4 Fans 75.5 dBA 76.1 dBA 81.4 dBA
Other Qualification Tests
See Figure 1 for graph that illustrates the Required Response Spectra for all seismic zones.
Additional Standards
IEEE 421.3 High-Potential Test Requirements For Excitation Systems For Synchronous
Machines
IEEE C37.90.1 Surge Withstand Capability (SWC) Tests For Relays And Relay Systems
Associated With Electric Power Apparatus
EN 60439-1 Low-voltage switchgear and controlgear assemblies Part 1: Specification for type-
tested and partially type-tested assemblies
Enclosure Specifications
Combination of 12 gauge, 0.105” (2.67mm) thick galvanized and painted sheet steel.
Enclosure paint is ANSI-70 Light Gray, with a 2.5 mil (0.0635mm) thickness
Wiring Specifications
All 300 V and 600 V wire is CSA Certified / UL Recognized, 125ºC cross-linked
polyethylene insulation.
Rev 1.
Added revisions page.
Rev 2.
Corrected typographical error to EMC standards numbers
Rev 3.
Corrected reference to UL 508C test clauses to reflect the latest version; and corrected
reference to EN 50178 for vibration test
Rev 4.
Added CSA master file number