Machine Monitoring Systems

Speed and Keypulse


Transmitter MMS 3311

• Integrated signal converters


for each channel

• For measurement of speed


and key pulses

• Signal inputs for eddy cur-


rent transducers

• Two redundant 24 V DC sup-


ply inputs

• Comprehensive self test


facilities for electronic cir-
cuits and sensors

• Integrated Microcontroler

• One 0/4...20 mA (life zero)


output for speed, one pulse
output for the key

• To be mounted directly at
the machine

• Two limit values for speed


measurement

• Limit values adjustable


within the speed range
1...65535 rpm

Application:
The MMS 3311 speed / key pulse machines where speeds resp. decentral data processing.
Transmitter serves the measure- key pulses shall be measured e.g. The inputs of the MMS 3311
ment of shaft speeds and the gen- at turbines, fans, compressors, gear transmitter may be operated with
eration of key pulses. Generation of boxes, pumps, coal mills and similar standard epro eddy-current sen-
key pulses is realised by using a machines. sors PR 6422/.., PR 6423/.., PR
toothed wheel or a trigger mark on MMS 3000 transmitters are used as 6424/.., PR 6425/..
the machine-shaft. well in big systems with PLCs and The transmitter must not be used
Both channels may be operated in- host computers as used in power for applications in hazardous areas.
dependently from each other. plants, refineries and chemical
Application areas for the MMS 3311 plants as also in smaller systems
transmitter are all kinds of rotating with only few measuring points and

MMS
Machine Monitoring Systems

Module and sensor supervision:


The internal module supervision • the cable between sensor and The state of the module supervision is
continuously checks the following transmitter must be ok (no short- indicated with a potential-free opto-
functions: circuit, no broken cable) coupler output at the terminal strip.
• the supply voltage must be within
• the input signal must be with-in a permissible limits
predefined range

Technical data:
Sensor inputs: Power consumption: Mounting direction:
two independent inputs for signal approx. 2,5 W Preferably with cable glands
pulses from sensors PR 6422/.. to Environmental conditions: showing to the bottom.
PR 6425/.. (according to IEC 359, DIN 43745) Dimensions:
Frequency range: Housing: refer to drawing
0...20 kHz aluminium, non-corroding Net weight:
manual triggerlevel adjustment Protection class: approx. 1300 g
Measuring range: IP 65 according to DIN 40050, Gross weight:
programmable, up to 65535 rpm, IEC 144 approx. 1500 g
limited by the max. input frequency CE certificated Accessories:
Measuring signal outputs: EMV tested according to: Operating manual
one key pulse output EN 55011 and EN 50082-2
one current output, proportional to Operating temperature range:
the measured speed -20...+80 °C
0...20 mA or 4...20 mA (life zero) Temperature range for storage
burden: < 500 Ohm and transport:
open-circuit and short-circuit proof -30...+90 °C
cable connection with cage-clamp Relative humidity:
terminals 0...95 % non-condensing
Power supply: Shock and vibration:
18...24...31,2 Vdc galvanically Shock: 20 g for 2 ms
isolated with dc/dc converter Vibration: 5 g at 60 Hz
current consumption:
approx. 100 mA

Programmable measuring parameters:


- Measuring range - Warning- and alarm limits Depending on number and type of the
- Number of teeth - Limit watching modes selected additional functions, the
- Transducer sensitivity - Hysteresis values of limits number of programmable parameters
- Offset tracking - Measuring function will increase.
- Trigger thresholds - Slope of input signal
- Gap limits - Key-pulse form

Limit watching:
One alert alarm and one danger alarm In case of errors, the alarm outputs can Outputs:
are available for channel 1. be blocked by the channel supervision The alarm outputs are at disposal
Both alarms may be used in the function. via potential-free opto-coupler out-
following different modes: puts at the internal terminal strip.
Up- or downscale characteristic Adjustable range:
without latching function. 1...65535 rpm Maximum electric load of the opto-
coupler:
U: 48 V DC
I: 100 mA
Machine Monitoring Systems

Operating elements:
The transmitter can be operated and 2 Key ROW/STORE: If this key is kept pressed for
configured via three keys. This key moves the cursor for the approx. 3 seconds, the LED
value to be set by one position from indication starts flashing and the
1 MODE key: right to left. Having reached the adjusted parameter value will be
This key serves the selection of the leftmost position, the cursor moves stored in the EEProm.
parameters to be modified. By to the invisible zero position. After
actuating this key, the program another actuation of the key, the 3 Key COL:
jumps to the next parameter. At the cursor returns to the rightmost With each key actuation the value of
end of the parameter list, the display position. the relevant digit position will be
program returns to position 00. increased by one. Having reached 9,
the next key actuation shows again
digit 0.

Additional functions (optional): Internal view of the transmitter:

Additionally to the basic version, the


MMS 3311 transmitter may be supple-
mented with several options. These
options have to be ordered additionally.
The following options are presently at
disposal:

Detection of standstill and rotational


direction:
If the transmitter does not receive
pulses within a certain time period,
the transmitter recognises this as
machine-standstill and indicates it
via an open collector transistor
output.
When using two speed sensors, it is
possible to detect the rotational
direction of the machine. The
detected direction is indicated via an
open collector output.

Latch – function of alarm outputs:


Alarm outputs after speed limit
exceedings can be programmed
with a latch function. If this function
has been activated, the alarm output
will remain active until the
measuring value has fallen below
the limit and an external reset pulse
has been given (ground potential to
the reset input).
Dual current mode: Speed zoom:
Redundant mode (speed): This function splits the output By means of this function, a certain
This mode requires two speed current into two ranges. speed range may be expanded. For
sensors. Both sensors provide their Example: this, start and end value of the
signal to the transmitter inputs. In Measuring range 0...3000 rpm. speed range must be programmed.
case of an error, the program One part of this range, e.g. 0...300 The resulting speed range is then
switches automatically to the rpm, is scaled to 0/4...20mA. scaled to 0/4...20mA and passed to
second, redundant sensor. Having exceeded the limit of the analogue output.
300rpm, the total measuring range
of the transmitter will be scaled to
0/4...20mA. Switching into the
higher range will be indicated via an
open collector transistor output.
Machine Monitoring Systems

Dimensions:

Connections:

MMS 3311
SPEED / KEY
TRANSMITTER

Transducer
Input
Sensor 2
channel 1 speed
Eingang
PR 642./.. Kanal 1 Drehzahl

Current outp. Ch1


Stromausg. K1

Printed in Germany. Due to continued research and product development


Current outp. Ch2

epro reserves the right to change these specifications without notice.


Transducer Input Stromausg. K2
Sensor 2 channel 2 key
Eingang GAP outp. Ch1
PR 642./.. Kanal 2 Key GAP-Ausg. K1
GAP outp. Ch2
GAP-Ausg. K2

Order numbers:
MMS 3311 Speed / Key Transmitter............................................................................ 9100 – 00034
Additional software functions:
MMS 3910/311-01 Detection of standstill and rotational direction........................................... 9400 – 00007
MMS 3910/311-02 Latch – function of limit values................................................................... 9400 – 00008
MMS 3910/311-04 Redundant mode (speed).......................................................................... 9400 – 00009
6010 – 00025 0201 E

MMS 3910/311-08 Dual current mode..................................................................................... 9400 – 00010


MMS 3910/311-16 Speed zoom function................................................................................. 9400 – 00011

© epro ELEKTRONIK & SYSTEMTECHNIK GmbH


Jöbkesweg 3 D-48599 Gronau MMS Further information:
Tel. +49 (0) 2562/709-245 Internet: http://www.epro.de
Fax +49 (0) 2562/709-255 E-Mail: info@epro.de