You are on page 1of 2

Curves

Plant: Customer: GBP- Toledo Power Company


Switchboard: No. 4 Station TR Secondly Designer: R Jay G. Fran, REE
Project: Rehabilitation of TPC1

Time-Current curve LLL-LL @400V

1000s

100s

10s

1s
Main Breaker Incoming No. 4

Circulating Water Pump B


100ms

10ms

100mA 1A 10A 100A 1kA 10kA 100kA 1MA

Main Breaker Incoming No. 4

Rated voltage:400 [V]

Circuit:LLL

Distribution system: TNC

InN: OFF

L: IEC60947-2

I1: 0.94

t1: 5s

S function on t=k

I2: 1.50

t2: 0.80s

I3: 8.00
Curves
I3: 8.00

INST 2 - off

G - off

Circulating Water Pump B

Rated voltage:400 [V]

Circuit:LLL

Distribution system: TNC

InN: OFF

L: IEC60947-2

I1: 0.53

t1: 3s

S function on t=k

I2: 1.50

t2: 0.05s

I3: 5.00

INST 2 - off

G - off

Curves

You might also like