2002 IS Catalog: Pepperl+Fuchs Inc. - Telephone (330) 486-0002 - FAX (330) 425-4607
2002 IS Catalog: Pepperl+Fuchs Inc. - Telephone (330) 486-0002 - FAX (330) 425-4607
Page
Introduction .............................................................................................................................. 47
Transmitter Power Supply (28 V entity parameter)
KFD2-CR-Ex1.30.200 (2-wire transmitter) .......................................................................................... 48
KFD2-CR-Ex1.30.300 (2- or 3-wire transmitter) .................................................................................. 49
KFD2-CR-Ex1.30.300 90C (2- or 3-wire, sink mode output) .............................................................. 50
KFD2-CR-Ex1.30.340 (2- or 3-wire, 4-20 mA input, 0-20 mA output) ................................................ 51
KFD2-CV-Ex1.30.305 (2- or 3-wire, 0/4-20 mA input, 0/1-5 V output) ............................................... 52
KFD2-CV-Ex1.30.310 (2- or 3-wire, 0/4-20 mA input, 0/2-10 V output) ............................................. 53
Transmitter Power Supply (20 V Entity Parameter)
KFD2-CR-Ex1.20.200 (2-wire, 4-20 mA input and output) ................................................................. 54
KFD2-CR-Ex1.20.300 (2- or 3-wire, 0/4-20 mA input and output) ..................................................... 55
SMART Transmitter Power Supply (0-12 kHz)
KFD2-STC1-Ex1 (SMART, 4-20 mA input and output) ....................................................................... 56
KFD2-STV1-Ex1 (SMART, 4-20 mA input, 1-5 V output) .................................................................... 57
SMART Transmitter Power Supply (0-40 kHz)
KFD2-STC3-Ex1 (4-20 mA input and output) ..................................................................................... 58
KFD2-STV3-Ex1-1 (4-20 mA input, 1-5 V output) ............................................................................... 59
KFD2-STV3-Ex1-2 (4-20 mA input, 2-10 V output) ............................................................................. 60
HART Transmitter Power Supply
KFD2-STC4-Ex1 (dual-channel, 4-20 mA input and output) ................................................................ 61
KFD2-STC4-Ex2 (dual-channel, 4-20 mA input and output) ................................................................ 62
KFD2-STC4-Ex2-Y72195 (dual-channel, sink mode output) ............................................................... 63
KFD2-STC4-Ex1.20 (single-channel, 2 outputs) .................................................................................. 64
KFD2-STC4-Ex1.20-Y72216 (single-channel, sink mode output) ........................................................ 65
Introduction
Transmitter power supplies transfer 4-20 mA signals from transmitters in hazardous areas and
supply them with power. They deliver an electrical signal that is proportional to a measured value
such as temperature, pressure or flow from hazardous areas to safe areas. The power supply and
signal are transferred through the same conductors in 2-wire transmitters allowing only 4-20 mA
signals. The power supply and signal are isolated from one another in 3-wire transmitters allowing
for 0 mA signals. These mA signals can then be repeated on the safe side of the isolator or can be
converted to other usable signals such as voltage. SMART transmitter power supplies repeat the
transmitter current in addition to a digital signal, which is modulated onto the 4-20 mA signal.
SMART transmitters can be calibrated remotely. This allows the transmitter’s span and zero set point
to be modified in the safe area and information on scheduled maintenance or statistical data to be
accessed on-line. SMART transmitters normally operate in a 2-wire mode. This 2-wire connection
is usually interfaced with a hand-held terminal or a PC for data transmission or accumulation.
P+F SMART transmitter power supplies are shipped with terminal blocks to allow easy access to
communication leads. SMART transmitters from ABB, Bailey, Chessel, Edress+Hauser, Fisher-
Rosemount, Foxboro, Honeywell, Smar and Yokogawa have been successfully tested with P+F
isolators. Please note that some higher communication frequencies require use of the KFD2-STC3-
Ex1 or the KFD2-STV3-Ex1. These isolators are rated for frequencies up to 40 kHz.
Transfer Characteristics
Calibrated accuracy ±10 µA nonlinearity, load fluctuations
Model Number Temperature drift ± 0.2 µA/ºC range 0-60ºC
KFD2-CR-Ex1.30.200 Rise time ≈ 50 µs (at 250 Ω load)
Connection Diagram
Class I, Div 1, Group A-G,
Zone 0, IIC
KFD2-CR-Ex1.30 200
Transfer Characteristics
Calibrated accuracy ±10 µA nonlinearity, load fluctuations Model Number
Temperature drift ± 0.2 µA/ºC range 0-60ºC KFD2-CR-Ex1.30.300
Rise time ≈ 50 µs
■ Single-channel
Entity Parameters Terminals 1+, 3 2-, 3
FM control drawing no. 116-0129 ■ 2- or 3-wire transmitter
Voltage VOC 28 V 4.4 V power supply
Current ISC 93 mA 22.2 mA ■ 24 VDC power supply
Explosion group A&B C&E D, F&G ■ 1 kΩ max. output load
Terminals 1+, 3
Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF ■ 3-way isolation
Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH
Terminals 2-, 3 ■ Suitable for Division 2 mounting
1000 µF 3000 µF 8000 µF
(+) 1 (+) 1 8
(+) 1
2 2
2 7
I
3
9
3 3 3
11 +
24VDC
12
Transfer Characteristics
Calibrated accuracy ±10 µA nonlinearity, load fluctuations
Model Number Temperature drift ≤ ± 0.2 µA/ºC range 0-60ºC
KFD2-CR-Ex1.30.300 90C Rise time ≈ 50 µs
11 +
24VDC
12
Transfer Characteristics
Calibrated accuracy ±10 µA nonlinearity, load fluctuations Model Number
Temperature drift ± 0.5 µA / ºC range 0-60ºC KFD2-CR-Ex1.30.340
Rise time ≈ 50 µs
■ Single-channel
Entity Parameters Terminals 1+, 2-, 3
FM control drawing no. 116-0129 ■ 2- or 3-wire transmitter
Voltage Voc 28 V 4.4 V power supply
Current Ioc 93 mA 22.2 mA ■ 24 VDC power supply
Explosion group A&B C&E D, F&G ■ 4-20 mA input
Terminals 1+, 3
Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF ■ 0-20 mA output
Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH
Terminals 2-, 3 ■ Suitable for Division 2 mounting
1000 µF 3000 µF 8000 µF
(+) 1 (+) 1 8
(+) 1
2 2
2 7
I
3
9
3 3 3
11 +
24VDC
12
Transfer Characteristics
Model Number Calibrated accuracy ≤ 5 mV
KFD2-CV-EX1.30.305 Temperature drift ≤ 0.005% of span/ ºC
Rise time 5.2 ms
■ Single-channel
■ 2- or 3-wire transmitter Entity Parameters
power supply BASEEFA no. Ex 97D2085
Voltage Voc 26 V
■ 0/4-20 mA input
Current Isc 93 mA
■ 0/1-5 V output Explosion group II A II B II C
■ Suitable for Division 2 mounting Max. external capacitance (Ca) 0.792 µF 0.297 µF 0.099 µF
Max. external inductance (La) 33.6 mH 12.6 mH 4.2 mH
This single-channel isolator powers and
Analog Input Transmitters
11 +
24VDC
12
Transfer Characteristics
Calibrated accuracy ≤ 10 mV Model Number
Temperature drift ± 0.005% of span/ºC KFD2-CV-Ex1.30.310
Rise time 5.2 ms
■ Single-channel
Entity Parameters ■ 2- or 3-wire transmitter
BASEEFA no. Ex 97D2085 power supply
Voltage Voc 26 V
■ 0/4-4-20 mA input
Current Isc 93 mA
Explosion group IIA IIB IIC ■ 0/2-10 V output
Max. external capacitance 0.792 µF 0.297 µF 0.099 µF
Max. external inductance 33.6 mH 12.6 mH 4.2 mH ■ Suitable for Division 2 mounting
This single-channel isolator powers and
Mechanical repeats a 0/4-20 mA signal from a 2- or 3-
11 +
24VDC
12
Transfer Characteristics
Calibrated accuracy ±10 µA nonlinearity, load fluctuations
Model Number Temperature drift ± 0.2 µA/ºC range 0-60ºC
KFD2-CR-Ex1.20.200 Rise time ≈ 50 µs
KFD2-CR-Ex1.20 200
(+) 1
24VDC
(+) 1 (+) 1
(+) 1
2 2
2 9
I
3
7
3 3 3
11 +
12
Transfer Characteristics
Calibrated accuracy ≤ 10 µA
Temperature drift ≤ 0.002% of span/ºC
Freq. range (250 Ω load) Hazardous area into safe area
Model Number Band width at 1 mAppSignal 0 Hz to 12 kHz (-1 dB)
KFD2-STC1-Ex1 Freq. range (250 Ω load) Safe area into hazardous area
Band width at 1 VppSignal 1 Hz to 12 kHz (-1 dB)
■ Single-channel Rise/fall time 40 µs/40 µs
■ 24 VDC power supply
Entity Parameters Terminals 1+, 3-
■ SMART communication to FM control drawing no. 116-0129
12 kHz (-1dB)
Voltage Voc 28 V
■ 4-20 mA output Current Isc 93 mA
■ Suitable for Division 2 mounting Explosion group A&B C&E D, F&G
Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF
This single-channel isolator powers and Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH
Analog Input Transmitters
KFD2-STC1-Ex1
11
Transfer Characteristics
Calibrated accuracy ≤ 10 µA
Temperature drift ≤ 0.002% of span/ºC
Freq. range (250 Ω load) Hazardous area into safe area
Band width at 1 mAppSignal 0 Hz to 12 kHz (-1 dB) Model Number
Freq. range (250 Ω load) Safe area into hazardous area KFD2-STV1-Ex1
Band width at 1 VppSignal 1 Hz to 12 kHz (-1 dB)
Rise/fall time 40 µs/40 µs ■ Single-channel
■ 24 VDC power supply
Entity Parameters Terminals 1+, 3-
FM control drawing no. 116-0129
■ SMART communication to
12 kHz (-1dB)
Voltage Voc 28 V
Current Isc 93 mA ■ 1-5 V output
Explosion group A&B C&E D, F&G ■ Suitable for Division 2 mounting
Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF
Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH This single-channel isolator powers and
11
Transfer Characteristics
Calibrated accuracy ≤ 0.05% of output signal
Temperature drift ≤ 0.002% of span/ºC
Freq. range (250 Ω load) Hazardous area into safe area
Model Number Band width at 1 mAppSignal 0 Hz to 40 kHz (-1 dB)
KFD2-STC3-Ex1 Freq. range (250 Ω load) Safe area into hazardous area
Band width at 1 VppSignal 0 Hz to 40 kHz (-1 dB)
■ Single-channel Rise/fall time 10 µs/10 µs
■ 24 VDC supply
Entity Parameters Terminals 1+, 3-
■ SMART communication to 40 FM control drawing no. 116-0129
kHz (-1dB)
Voltage Voc 28 V
■ 4-20 mA output Current Isc 93 mA
■ 3-way isolation Explosion group A&B C&E D, F&G
Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF
■ Suitable for Division 2 mounting Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH
Analog Input Transmitters
KFD2-STC3-Ex1
Transfer Characteristics
Calibrated accuracy ≤ 0.03% of output signal
Temperature drift ≤ 0.002% of span/ºC
Freq. range (250 Ω load) Hazardous area into safe area
Band width at 1 mAppSignal 0 Hz to 40 kHz (-1 dB) Model Number
Freq. range (250 Ω load) Safe area into hazardous area KFD2-STV3-Ex1-1
Band width at 1 VppSignal 0 Hz to 40 kHz (-1 dB)
■ Single-channel
Enity Parameters Terminals 1+, 3- ■ 24 VDC supply
FM control drawing no. 116-0129
Voltage Voc 28 V
■ SMART communication to 40
kHz (-1dB)
Current Isc 93 mA
Explosion group A&B C&E D, F&G ■ 1-5 V output
Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF
Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH ■ 3-way isolation
■ Suitable for Division 2 mounting
Mechanical
Transfer Characteristics
Calibrated accuracy ≤ 0.03% of output signal
Temperature drift ≤ 0.002% of span/ºC
This single-channel isolator powers and Max. external capacitance (Ca) 0.14 µF 0.43 µF 1.14 µF
repeats the 4-20 mA signal from a 2-wire Max. external inductance (La) 4.18 mH 16.83 mH 34.21 mH
transmitter inside the hazardous area. This
4-20 mA current is repeated or converted Mechanical
into a or 2-10 V signal Housing Type A4 (see page 387)
Dimensions (mm) 107 x 20 x 115 mm
This isolator can also repeat a maximum 40
kHz digital signal that is modulated on the Weight 150 g (5.3 oz.)
4-20 mA signal. A processing system, field
device or hand-held terminal generates this Ambient Temperature -20ºC to +65ºC (-4ºF to +149ºF)
digital information, which is transferred
bidirectionally by the isolator. This allows the
operator to interrogate and reprogram the
transmitter from a safe area using uncertified
communication equipment. Hand-held
terminals can be connected as shown in the
circuit diagram. These isolators have KF- Connection Diagram
STP-BU and KF-STP-GN terminals with test
Class I, Div 1, Group A-G,
probe access holes for the easy interface of
Zone 0, IIC
hand-held terminals.
Safe Area or Div 2
Note:
KFD2-STV3-Ex1-2
Terminal 12 is placed across an internally
applied capacitance. Active input cards,
such as Foxboro FMB 18, can operate using
this connection.
Transfer Characteristics
Calibrated accuracy ≤ 20 µA
Temperature drift ≤ 0.002% of span/ºC
Freq. range (250 Ω load) Hazardous area into safe area Model Number
Band width at 1 mAppSignal 0 Hz to 7.5 kHz (-3 dB) KFD2-STC4-Ex1
Freq. range (250 Ω load) Safe area into hazardous area
Band width at 1 VppSignal 300 Hz to 7.5 kHz (-3 dB) ■ Single-channel
Rise/fall time 20µs/20µs ■ HART compatible
Entity Parameters Terminals 1+, 3-
■ 24 VDC power supply
UL control drawing no. 116-0173 ■ 3 way isolation
Voltage Voc 25.4 V ■ Suitable for Division 2 mounting
Current Isc 88.2 mA
Explosion group A&B C&E D, F&G The SMART transmitter power supplies
Max. external capacitance (Ca) 0.095µF 0.808 µF 2.88 µF supply a 2-wire SMART transmitter within
(+) 1 (+) 1 8
(+) 1
2 2
2 7
I
3 4-20mA
3 3 3
11 +
12
Transfer Characteristics
Calibrated accuracy ≤ 20 µA
Temperature drift ≤ 0.002% of span/ºC
Model Number Freq. range (250 Ω load) Hazardous area into safe area
KFD2-STC4-Ex2 Band width at 1 mAppSignal 0 Hz to 7.5 kHz (-3 dB)
Freq. range (250 Ω load) Safe area into hazardous area
■ Dual-channel Band width at 1 VppSignal 300 Hz to 7.5 kHz (-3 dB)
■ HART compatible Rise/fall time 20µs/20µs
hazardous area and transfer the analog 4- Max. external inductance (La) 4.2 mH 17 mH 33 mH
20 mA signal from the hazardous area to
the safe area. Mechanical
Digital signals which can be modulated onto Housing Type A4 (see page 387)
the analog signal, can also be transmitted Dimensions (mm) 107 x 20 x 115 mm
bidirectionally on the hazardous or safe side. Weight 100 g (3.5 oz.)
Handheld terminals can be connected as
shown in the block diagram. Ambient Temperature -20ºC to +65ºC (-4ºF to +140ºF)
Connection Diagram
Class I, Div 1, Group A-G,
Zone 0, IIC
If the communicator is connected in Safe Area or Div 2
the safe area, the load resistance
must not be less than 230 Ω. KFD2-STC4-Ex2
Transfer Characteristics
Calibrated accuracy ≤ 20 µA
Temperature drift ≤ 1µA/ºC
Freq. range (250 Ω load) Hazardous area into safe area
Band width at 1 Vpp-Signal 0 Hz to 7.5 kHz (-3 dB) Model Number
Freq. range (250 Ω load) Safe area into hazardous area KFD2-STC4-Ex2-Y72195
Band width at 1 Vpp-Signal 300 Hz to 7.5 kHz (-3 dB)
■ Dual-Channel
Entity Parameters Terminals 1, 3, 4, 6
■ HART compatible
UL control drawing no. 116-0173
Voltage Voc 25.2 V ■ 24 VDC power supply
Current Isc 93.0 mA ■ Sink mode output
Explosion group A&B C&E D, F&G
Max. external capacitance (Ca) 0.093µF 0.798 µF 2.808 µF ■ 3-way isolation
Max. external inductance (La) 4.6 mH 18 mH 36 mH ■ Suitable for Division 2 mounting
Mechanical The SMART transmitter power supplies
20-35VDC
20-35VDC
Transfer Characteristics
Calibrated accuracy ≤ 20 µA
Temperature drift ≤ 1 µA/ºC
Freq. range (250 Ω load) (Hazardous area into safe area)
Model Number Band width at 0.5 VppSignal 0 Hz to 7.5 kHz (-3 dB)
KFD2-STC4-Ex1.20 (Safe area into hazardous area)
Band width at 0.5 VppSignal 300 Hz to 7.5 kHz (-3 dB)
■ Single-channel Interference rejection Unaffected by 260 V, 50 Hz common
■ Dual outputs mode input signal with any safe side
terminal grounded, and 27 MHz
■ HART compatible walkie-talkies
■ 4-20mA current source Entity Parameters Terminals 1+, 3-
outputs UL control drawing no. 116-0173
■ 3-way isolation Voltage Voc 25.4 V
Current Isc 88.2 mA
SMART transmitter power supplies supply a Explosion group A&B C&E D, F&G
Analog Input Transmitters
2-wire SMART transmitter within a hazardous Max. external capacitance (Ca) 0.01 µF 0.081 µF 2.89 µF
area and transfer the analog 4-20 mA signal Max. external inductance (La) 4.2 mH 17 mH 33 mH
from the hazardous area to the safe area as
two current sources. Mechanical
Digital signals which can be modulated onto Housing Type A4 (see page 387)
the analog signal, can also be transmitted Dimensions (mm) 107 x 20 x 115 mm
bidirectionally on the hazardous or safe side. Weight 100 g (3.5 oz.)
Handheld terminals can be connected as
shown in the block diagram. Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF )
Connection Diagram
Class I, Div 1, Group A-G,
Zone 0, IIC
If the communicator is connected in
the safe area, the load resistance Safe Area or Div 2
must not be less than 230 Ω. KFD2-STC4-Ex1.20
2 2 7
2
I 11
3
3 3 3 10
14
24VDC
15
Transfer Characteristics
Calibrated accuracy ≤ 20 µA
Temperature drift ≤ 1 µA/ºC
Freq. range (250 Ω load) (Hazardous area into safe area)
Band width at 0.5 VppSignal 0 Hz to 7.5 kHz (-3 dB)
Model Number
(Safe area into hazardous area) KFD2-STC4-Ex1.20-Y72216
Band width at 0.5 VppSignal 300 Hz to 7.5 kHz (-3 dB)
Interference rejection Unaffected by 260 V, 50 Hz common ■ Single-channel
mode input signal with any safe side
terminal grounded, and 27 MHz
■ Dual outputs
walkie-talkies ■ HART compatible
Entity Parameters Terminals 1+, 3- ■ Sink mode outputs
UL control drawing no. 116-0173 ■ 3-way isolation
Voltage Voc 25.4 V
SMART transmitter power supplies supply
Current Isc 88.2 mA
a 2-wire SMART transmitter within a
Explosion group A&B C&E D, F&G
Connection Diagram
Class I, Div 1, Group A-G,
Zone 0, IIC
Safe Area or Div 2
If the communicator is connected in
KFD2-STC4-Ex1.20-Y72216
the safe area, the load resistance
must not be less than 230 Ω.
14
24VDC
15