You are on page 1of 20

General Calculations

Excerpt
from
PRYSMIAN’S
WIRE AND CABLE
ENGINEERING GUIDE

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 1 of 20
www.na.prysmian.com/energy
Voltage Rating Voltage Regulation
The selection of the cable insulation level to Voltage regulation is often the limiting factor
be used in a particular installation shall be in the choice of either conductor or type of
made on the basis of the applicable phase- insulation. While the heat loss in the cable
to-phase voltage and the general system determines the maximum current it can
category as outlined below: safely carry without excessive deterioration,
many circuits will be limited to currents lower
100 Percent Level - Cables in this than this in order to keep the voltage drop
category may be applied where the within permissible values. In this connection
system is provided with relay protection it should be remembered that the high
such that ground faults will be cleared as voltage circuit should be carried as far as
rapidly as possible, but in any case possible so that the secondary runs, where
within one minute. While these cables most of the voltage drop occurs, will be
are applicable to the great majority of small.
cable installations that are on grounded
systems, they may also be used on other The voltage drop of a feeder circuit may be
systems for which the application of calculated by the following formulae:
cables is acceptable, provided the above
clearing requirements are met in 100(V S − V L )
completely de-energizing the faulted V =
VL
section.
Where:
133 Percent Level - This insulation level
corresponds to that formerly designated V = Voltage regulation in percent
for ungrounded systems. Cables in this VL = Voltage across load
category may be applied in situations VS = Voltage at source
where the clearing time requirements of
the 100 percent level category cannot be And VS is defined by the formula:
met, and yet there is adequate
assurance that the faulted section will be VS = (V L ⋅ cos θ + R ⋅ I )2 + (V L ⋅ sin θ + X ⋅ I )2
de-energized in a time not exceeding
one hour. Also, they may be used when Where:
additional insulation strength over the
100 percent level category is desirable. θ = Angle by which the load current
lags the voltage across the load
173 Percent Level - Cables in this cos θ = Power factor of load
category should be applied on systems R = Total AC resistance of feeder
where the time required to de-energize a X = Total reactance of feeder
grounded section is indefinite. Their use I = Load current
is recommended also for resonant
grounded systems. Consult the cable
manufacturer for insulation thicknesses.
When the power factor angle is nearly the
In common with other electrical equipment, same as the impedance angle, that is:
the use of cable is not recommended on
systems where the ratio of the zero to
X
positive sequence reactance of the system tan θ ≅
at the point of cable application lies between R
-1 and -40 since excessively high voltages
may be encountered in the case of ground The voltage regulation equation above will
faults. reduce to the following formula:

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 2 of 20
www.na.prysmian.com/energy
(VS − V L ) = RI ⋅ cosθ + XI ⋅ sin θ Voltage Drop = 5000 - 4904 = 96 volts

5000 − 4904
The above formulas apply directly for single- V = ⋅ (100) = 1.96%
phase lines when resistance and reactance 4904
are loop values and voltage is voltage
between lines. Approximate Formula:

For three-phase circuits, use voltage to Voltage Drop = line to neutral


neutral and resistance and reactance of = R • I • cosθ + X • I • sinθ
each conductor to neutral. This method will = 0.096 • 460 • 0.8 + 0.072
give the voltage drop to neutral. To obtain • 460 • 0.6
the voltage drop line-to-line, multiply the = 35.3 + 19.8 = 55.1
voltage drop by 3 .
Line-to-line drop = 55.1 ⋅ 3 = 95.4 V
Note: The percent voltage drop is the same
between conductors as from conductor to Conductor Reactance
ground and should not be multiplied by 3 .
The reactance of any stranded or solid
Example: conductor can be calculated for a specific
frequency, conductor size, and spacing. The
3 single copper conductors, 5 kV cables in following equation can be utilized to find the
non-metallic conduit. reactance of a given configuration by using
the concept of geometric mean radius.
Size conductor = 350 kcmil copper, 90
Insulation = 90 mils ⎛ g ⎞
Jacket = 70 mils X = 2 ⋅ π ⋅ f ⋅ ⎜ 0.1404 ⋅ log 10 + 0.0153 ⎟ ⋅ 10 −3
⎝ r ⎠
Overall diameter = 1.13”
Voltage (VS) = 5,000 volts (3 phase)
Where:
Current (I) = 460 amperes
Power Factor = 0.8 (cos θ) X = Reactance in ohms/1000 ft
Length = 2550 ft f = Frequency in Hertz
Resistance = 0.0308 ohms/1000 ft r = Radius of conductor
at 25°C 0.096 ohms g = geometric mean radius between
or 2500 ft at 90°C conductors and is given by the
Reactance (X) = 0.024 ohms/1000 ft following formula:
(See section on
conductor reactance)
0.072 ohms for 2500 g = n a ⋅ b⋅... zn
ft including 20%
random lay Where:
n = number of conductors
VS = (V L ⋅ cos θ + R ⋅ I )2 + (V L ⋅ sin θ + X ⋅ I )2 a = distance from conductor a to b
b = distance from conductor b to c
5000
zn = distance from conductor n-1 to n
= [.8V L + (.096 ⋅ 460 )] 2 + [.6V L + (.072 ⋅ 460 )] 2
3 Using the equations above, a nomogram (a
graphic representation that consists of
Solving for VL: VL = 2,831.6 volts several lines marked off to scale and
arranged in such a way that by using a
Line-to-line voltage = 2831.6 3 = 4904 V straightedge to connect known values on
two lines an unknown value can be read at

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 3 of 20
www.na.prysmian.com/energy
the point of intersection with another line) Single conductors should not be installed in
was constructed (the Nomogram is located individual magnetic conduit because of the
at later in this document). This diagram can excessive reactance.
be used to determine the reactance of any
solid or concentric stranded conductor. It Three conductors in magnetic conduit will
covers spacing encountered for conduit have a somewhat higher reactance than
wiring as well as for open wire circuits. cables in non-magnetic conduit.
Various modifications are necessary for use
under special conditions is covered in notes The following table lists equations
on the nomogram. The reactances shown commonly used for determining various
are for 60-Hertz operation. parameters of an electrical system where:
Where regulation is an important
consideration several factors should be kept E = Phase-to-phase voltage
in mind in order to obtain the best operating I = Current, in amperes
conditions. % Eff = Percent efficiency in decimals
Open wire lines have a high reactance. This pf = Power factor in decimals
may be improved by using parallel circuits kVA = Kilovolt-ampere
but is much further reduced by using hp = Horsepower
insulated cable. Three conductors in the kW = Kilowatts
same conduit have a lower reactance than
conductors in separate conduits.

Electrical Formulas for Determining Amperes,


Horsepower, Kilowatts, and Kilovolt-Amperes

ALTERNATING CURRENT
Desired Two-Phase* Three-Phase
Single-Phase
Data Four-Wire (per phase)
Amperes when kVA ⋅1000 kVA ⋅ 1000 kVA ⋅ 1000
kVA is known E 2⋅E 3 ⋅E
Amperes when kW ⋅1000 kW ⋅ 1000 kW ⋅ 1000
kilowatts is known E ⋅ pf 2 ⋅ E ⋅ pf 3 ⋅E ⋅ pf
Amperes when hp ⋅ 746 hp ⋅ 746 hp ⋅ 746
horsepower is known E ⋅ % Eff ⋅ pf 2 ⋅ E ⋅ % Eff ⋅ pf 3 ⋅E ⋅ % Eff ⋅ pf
I⋅E I ⋅ E ⋅2 I⋅E⋅ 3
Kilovolt-Amperes 1000 1000 1000
I ⋅ E ⋅ pf I ⋅ E ⋅ 2 pf I ⋅ E ⋅ 3 ⋅ pf
Kilowatts
1000 1000 1000
I ⋅ E ⋅ % Eff ⋅ pf I ⋅ E ⋅ 2 ⋅ % Eff ⋅ pf I ⋅ E ⋅ 3 ⋅ % Eff ⋅ pf
Horsepower
746 746 746
• In three-wire, two-phase balanced circuits, the current in the common conductor is 2 times
that in either of the other conductors.

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 4 of 20
www.na.prysmian.com/energy
Shielding of Insulated Cables 4. To limit radio interference.
5. To reduce the hazard of shock. This
Shielding should be considered for non- advantage is obtained only if the shield
metallic covered cables operating at a circuit is grounded. If not grounded, the hazard
voltage above 2000 volts for single of shock may be increased.
conductor cables and 5000 volts for
assembled conductors with a common Use of Insulation Shielding
overall jacket.
The use of shielding involves consideration
Definition of shielding of installation and operating conditions.
Definite rules cannot be established on a
Shielding of an electric power cable is the practical basis for all cases. However,
practice of confining the dielectric field of the shielding should be considered for
cable to the insulation of the conductor or nonmetallic covered cables operating at a
conductors. It is accomplished by means of circuit voltage over 2000 where any of the
strand and insulation shields. following conditions exist:

1. Connection to aerial lines.


Functions of Shielding 2. Transition from conducting to non-
conducting environment.
A strand shield is employed to preclude 3. Transition from moist to dry earth.
excessive voltage stress on voids between 4. Dry soil, such as in the desert.
conductor and insulation. To be effective, it 5. Damp conduits.
must adhere to or remain in intimate contact 6. Where the surface of cable collects
with the insulation under all conditions. conducting materials.
7. Where electrostatic discharges are of
An insulation shield has a number of low enough intensity not to damage
functions: cable but are sufficient in magnitude to
interfere with radio or television
1. To confine the dielectric field within the reception.
cable. 8. Where safety to personnel is involved.
2. To obtain symmetrical radial distribution
of voltage stress within the dielectric, More specific information on requirements
thereby minimizing the possibility of for shielding by cable type is provided in the
surface discharges by precluding following table.
excessive tangential and longitudinal
stresses.
3. To protect cable connected to overhead
lines or otherwise subject to induced
potentials.

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 5 of 20
www.na.prysmian.com/energy
Operating Voltage Limits (kV) Above Which Insulation Shielding
is Required
Power Cable - 100 and 133 Percent Insulation Level
1. Single conductor (including assemblies of single conductors)
a. With metallic sheath or armor ................................................ 5kV
b. All others ................................................................................ 2kV

2. Multiple conductors with common covering


a. With discharge-resisting jacket .............................................. 5kV
b. With non-discharge-resisting jacket ....................................... 2kV
c. With metallic sheath or armor ................................................ 5kV

Multiplying Factors for Equivalent Three-Phase Voltages for


Single- or Two-Phase AC Systems or for DC Systems
Single- and Two-Phase AC Systems*
Single- and Two-Phase AC Over 5000 Volts
Systems*
and DC Systems 5000 Volts or Less Ungrounded and Midpoint
One Side Grounded
Grounded

1 1.73 0.866

* Where it is not definitely specified that a line operates as an isolated single- or two-phase system, it will
be considered as a branch of a 100% insulation level three-phase circuit, and the rating will be the line-
to-line voltage of this 100% insulation level three-phase circuit.

Importance of Shielding loose metallic sheath, etc. Likewise,


damage to non-shielded cable may result
Where there is no metallic covering or shield when the surface of the cable is moist, or
over the insulation, the electric field will be covered with soot, soapy grease or other
partly in the insulation and partly in whatever conducting film and the external field is
lies between the insulation and ground. The partly confined by such conducting film so
external field, if sufficiently intense in air, will that the charging current is carried by the
generate surface discharge and convert film to some spot where it can discharge to
atmospheric oxygen into ozone, which may ground. The resultant intensity of discharge
be destructive to rubber insulations and to may be sufficient to cause burning of the
protective jackets. If the surface of the cable insulation or jacket.
is separated from ground by a thin layer of
air and the air gap is subjected to a voltage Where non-shielded non-metallic jacketed
stress, which exceeds the dielectric strength cables are used in underground ducts
of air, a discharge will occur, causing ozone containing several circuits, which must be
formation. worked on independently, the external field
The ground may be a metallic conduit, a if sufficiently intense can cause shock to
damp non-metallic conduit or a metallic those who handle or contact energized
binding tape or rings on an aerial cable, a cable. In cases of this kind, it may be

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 6 of 20
www.na.prysmian.com/energy
advisable to use shielded cable. Shielding solder the connection. The area of contact
used to reduce hazards of shock should should be ample to prevent the current from
have a resistance low enough to operate heating the connection and melting the
protective equipment in case of fault. In solder. For additional security, a mechanical
some cases, the efficiency of protective device, such as a clamp, may be used to
equipment may require proper size ground fasten the ends of the connection together.
wires as a supplement to shielding. The This combination will ensure a permanent
same considerations apply to exposed low resistance, which will maintain contact
installations where personnel who may not even if the solder melts.
be acquainted with the hazards involved
handle cables. The wire or strap used to connect the cable
shield ground connection to the permanent
Grounding of the Insulation Shield ground must be of adequate size to carry
the fault current. Shielding which does not
The insulation shield must be grounded at have adequate ground connection due to
least at one end and preferably at two or discontinuity of the shield or to improper
more locations. This decreases the termination may be more dangerous than
reactance to fault currents and increases non-shielded non-metallic cable and
human safety factor. It is recommended that hazardous to life.
the shield be grounded at cable terminations
and at splices and taps. Stress cones Shield Materials
should be made at all shield terminations.
Two distinct types of materials are employed
The shield should operate at or near ground in constructing cable shields:
potential at all times. Frequent grounding of
shields reduces the possibility of open Nonmetallic shields - consist of either a
sections on nonmetallic covered cable. conducting tape or a layer of conducting
Multiple grounding of shields is desirable in compound. The tape may be conducting
order to improve the reliability and safety of compound, fibrous tape faced or filled with
the circuit. All grounding connections should conducting compound, or conducting fibrous
be made to the shield in such a way as to tape.
provide a permanent low resistance bond.
Metallic shield - should be nonmagnetic
Using a mechanical clamp (such as a and may consist of tape, braid, concentric
constant tension spring or a hose clamp) is serving of wires, or a sheath.
usually adequate to secure the connection.
In some instances, it may be preferable to

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 7 of 20
www.na.prysmian.com/energy
Induced Sheath Metallic Shield Loss
Cable Geometry
Voltage Formulae Formulae for Solidly Where:
Configuration
(µV to Neutral per ft) Grounded Shields
Phase A:
2
⎡⎢
I R ⋅⎢
( X )
M
2 ⎤⎥

⎢ ( RS) + ( XM ) ⎥
S 2 2
Single Phase
⎣ ⎦
S Phase A: IXM

A
Total Loss:
A

⎢ ( XM )
2 ⎤
2 ⎥ P = RS / Y
2I R ⋅ ⎢ ⎥
⎢ ( RS) + ( XM ) ⎥
S 2 2
⎣ ⎦ Q = RS / Z
Equilateral Phase A, B & C:
C 2
I R ⋅⎢
⎡⎢
( XM )2 ⎤⎥

S

⎢ ( RS) + ( XM ) ⎥
S 2 2
⎣ ⎦
Phase A, B & C: IXM
A B
Total Loss:

⎢ ( XM )
S 2 ⎤
2 ⎥
3I R ⋅ ⎢ ⎥
⎢ ( RS) + ( XM ) ⎥
S 2 2
⎣ ⎦
Rectangular Phase A & C: Phase A & C:
2 ⎡ ( P2 + 3Q2) ±2 3⋅ ( P − Q) + 4⎤⎥
I⋅ 3⋅ Y + ⎡⎢X − ⎛⎜ I ⋅R ⋅⎢
C 2 A ⎞⎤ 2

4⋅ ( P + 1) ⋅ ( Q + 1)
S⎢ ⎥
⎣ M ⎝ 2 ⎠⎦ ⎣
2 2

S
2
Y = xM + A/2
A B Phase B:
Phase B: IXM 2 I Z = xM - A/6
I ⋅R ⋅
S S 2
Q +1

Total Loss:
⎡ 2 2
P +Q +2⎤
3 I ⋅R ⋅⎢ ⎥
2
S⎢ 2 ( 2 )( ⎥
⎣ 2⋅ P + 1 ⋅ Q + 1 ⎦ )
Formulae continued on Next Page.

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 8 of 20
www.na.prysmian.com/energy
Induced Sheath Loss Formulae for
Cable Geometry
Voltage Formulae Solidly Grounded Where:
Configuration
(µV to Neutral per ft) Metallic Sheaths
Phase A & C:

S
Flat
S
2
(
I⋅ 3⋅ Y + X
M
−A )2 Y = xM + A
2
A B C Z = xM - A/3
Phase B: IXM
Phase A & C:
2-Circuit, No Phase Phase A & C:
I ⋅R ⋅⎢
2 ( )
⎡ P2 + 3Q2 ±2 3⋅ ( P − Q) + 4⎤

Rotation 2 S⎢

2 ( 2
4⋅ P + 1 ⋅ Q + 1 )( ⎥
⎦ )
I⋅ 3⋅ Y + ⎡⎢X ⎛ B ⎞⎤
2
− ⎜ ⎥
A B C ⎣ M
⎝ 2 ⎠⎦ Y = xM + A + B/2
2
Phase B:
S S 2 I
I ⋅R ⋅ Z = xM + A/3 - B/6
S 2
I⋅ ⎛⎜ X + ⎞ Q +1
A
A B C
Phase B: ⎝ M 2⎠
Total Loss:
2-Circuit, Phase Phase A & C: ⎡ 2 ⎤
P +Q +2
2
3 I ⋅R ⋅⎢ ⎥
2
Rotation
I⋅ 3⋅ Y + ⎡⎢X
2
− ⎛⎜
B ⎞⎤

2 S⎢ 2 ( 2 ⎥
⎣ 2⋅ P + 1 ⋅ Q + 1 ⎦ )( )
A B C ⎣ M
⎝ 2 ⎠⎦
Y = xM + A - B/2
2
S S Z = xM + A/3 - B/6
I⋅ ⎛⎜ X
A⎞
+
C B A Phase B: ⎝ M 2 ⎠

xM = 2Πf (0.1404 log10(S/rm)) µΩ/ft ρ Values (Ωcmil/ft)


A = 2Πf (0.1404 log10(2)) µΩ/ft Overlapped Copper Tape 30

B = 2Πf (0.1404 log10(5)) µΩ/ft Overlapped Brass Tape 70


Overlapped Monet Tape 2500
RS = ρ/(8rmt) µΩ/ft
Overlapped Ambrac Tape 350
RS = Metallic Shield Resistance (µΩ/ft) Lead Sheath 150
t = Metallic Tape Thickness (inches) Aluminum Sheath 20
f = Frequency (Hz) Aluminum Interlocked Armor 28
S = Center to Center Spacing of Cables (inches) Galvanized Steel Interlocked Armor 70
rm = Metallic Shield Mean Radius (inches) Galvanized Steel Armor Wire 102

I = Conductor Current (amperes) Aluminum (5052 Alloy) 30

ρ = Metallic Shield Resistivity at 50°C (Ωcmil/ft)

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 9 of 20
www.na.prysmian.com/energy
Splices and Terminations have been established for the various
insulations as follows (based on ICEA P-32-
382):
The insulation shields must be removed
completely at splices and terminations,
otherwise excessive leakage current and
flashover will result. Auxiliary nonmetallic Thermoplastic Compound 150°C
conducting shields may adhere to the Rubber and Varnished Cloth 200°C
insulation, so that the use of a 100 grit
aluminum oxide cloth (or similar material) Impregnated Paper 200°C
may be required to assure removal of the
Thermoset Compound 250°C
conducting material from the insulation
surface (See pages 28 - 30 for generalized
discussion of cable preparation for splicing The charts on the following pages show the
and terminating). currents, which, after flowing for the times
indicated, will produce these maximum
temperatures for the given conductor sizes.
Short-Circuit Currents for
Insulated Cable Conductors These charts are for copper or aluminum
conductors operating at 90°C or 105°C with
Steady increases in kVA capacity of power thermoset insulations. For other, less
distribution systems have resulted in common charts, reference ICEA P-32-382.
possible short circuit currents of such The system short circuit capacity, the
magnitude that the resulting high conductor conductor cross-sectional area and the
temperature may seriously damage the circuit breaker opening time should be such
conductor insulation. As a guide in that these maximum allowable short circuit
preventing such serious damage, maximum currents are not exceeded.
allowable short circuit temperatures that
damage the insulation to a slight extent only,

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 10 of 20
www.na.prysmian.com/energy
Short Circuit Current (thousands of amperes)

700 Industrial Drive

Fax: 1.803.951.1142
0.1 0.2 0.5 1 2 5 10 20 50 100

Phone: 1.800.845.8507
10 AWG 10 AWG

www.na.prysmian.com/energy
Lexington, South Carolina 29072
8 AWG 8 AWG

6 AWG 10 60 30 16 8 4 2 1 6 AWG
0 cy cy cy cy cy cy
cy cyc cle cle cle cle cle cle
cle les s s s - s s
s - - - 0 - 0 - 0
-0
.0
-1 1. 0. 0. .1 .0 .0 16
4 AWG .6 00 50 26 33 66 33 7 4 AWG
66 00 00 67 3 7 3
7 se se sec sec sec
se
co
se sec
co o c on con ond ond o nd nd
nd nds ds ds s s s s
s
2 AWG 2 AWG
1 AWG 1 AWG
1/0 AWG 1/0 AWG
2/0 AWG 2/0 AWG
Conductor - Aluminum
3/0 AWG Thermoset Insulations
3/0 AWG
4/0 AWG Rated for 90°C 4/0 AWG
250 kcm Maximum Continuous Operation 250 kcm
Curves Based on Formula:

350 kcm I2 (T2 + 228.1) 350 kcm


t = 0.0125 log
A2 (T1 + 228.1)
Where:
I = Short Circuit, Amperes
500 kcm A = Conductor Area, Circular Mils 500 kcm
t = Time of Short Circuit, Seconds
T1 = Maximum Operating Temperature (90°C)
T2 = Maximum Short Circuit Temperature (250°C)
750 kcm 750 kcm
1000 kcm 1000 kcm

06/21/2006
Revision 4

Page 11 of 20
General Calculations
Short Circuit Current (thousands of amperes)

700 Industrial Drive

Fax: 1.803.951.1142
0.1 0.2 0.5 1 2 5 10 20 50 100

Phone: 1.800.845.8507
10 AWG 10 AWG

www.na.prysmian.com/energy
Lexington, South Carolina 29072
8 AWG 8 AWG

6 AWG 10 60 30 16 8 4 2 1 6 AWG
0 cy cy cy cy cy cy
cy cyc
cle le cle cle
cle
s
cle
s
cle
s
cle
s s s s -0 -0 -0 -0
- 1 - 1. -0 -0 . . . .0
4 AWG .6 0 .5 .2 13 06 03 16
4 AWG
66 000 00 66 33 67 33 7
7 0 7 se se se se
se s ec sec s ec co co co co
co on on on nd nd nd nd
nd ds ds ds s s s s
2 AWG s
2 AWG
1 AWG 1 AWG
1/0 AWG 1/0 AWG
2/0 AWG 2/0 AWG
3/0 AWG Conductor - Copper
Thermoset Insulations
3/0 AWG
4/0 AWG Rated for 90°C 4/0 AWG
250 kcm Maximum Continuous Operation 250 kcm
Curves Based on Formula:
350 kcm I2 (T2 + 234.5) 350 kcm
t = 0.0297 log
A2 (T1 + 234.5)
Where:
I = Short Circuit, Amperes
500 kcm A = Conductor Area, Circular Mils 500 kcm
t = Time of Short Circuit, Seconds
T 1 = Maximum Operating Temperature (90°C)
T 2 = Maximum Short Circuit Temperature (250°C)
750 kcm 750 kcm
1000 kcm 1000 kcm

06/21/2006
Revision 4

Page 12 of 20
General Calculations
Short Circuit Current (thousands of amperes)

700 Industrial Drive

Fax: 1.803.951.1142
0.1 0.2 0.5 1 2 5 10 20 50 100

Phone: 1.800.845.8507
10 AWG 10 AWG

www.na.prysmian.com/energy
Lexington, South Carolina 29072
8 AWG 8 AWG

6 AWG 10 60 30 16 8 4 2 1 6 AWG
0 cy cy cy cy cy cy
cy cyc cle cle cle cle
cle le cle cle s s s
s s s s - - - -0
-1 - 1. - 0. - 0. 0.1 0.0 0.0 .0
16
4 AWG .6
66
00
00
50
00
26
67
33
3
66
7
33
3 7 4 AWG
7 se se se se se
se
se sec co co c on c on con
co
nd
co on nd nd ds ds ds s
nd ds s s
s
2 AWG 2 AWG
1 AWG 1 AWG
1/0 AWG 1/0 AWG
2/0 AWG 2/0 AWG
3/0 AWG Conductor - Aluminum
Thermoset Insulations
3/0 AWG
4/0 AWG Rated for 105°C 4/0 AWG
250 kcm Maximum Continuous Operation 250 kcm
Curves Based on Formula:
350 kcm I2 (T2 + 228.1) 350 kcm
t = 0.0125 log
A2 (T1 + 228.1)
Where:
I = Short Circuit, Amperes
500 kcm A = Conductor Area, Circular Mils 500 kcm
t = Time of Short Circuit, Seconds
T1 = Maximum Operating Temperature (105°C)
T2 = Maximum Short Circuit Temperature (250°C)
750 kcm 750 kcm
1000 kcm 1000 kcm

06/21/2006
Revision 4

Page 13 of 20
General Calculations
Short Circuit Current (thousands of amperes)

700 Industrial Drive

Fax: 1.803.951.1142
0.1 0.2 0.5 1 2 5 10 20 50 100

Phone: 1.800.845.8507
10 AWG 10 AWG

www.na.prysmian.com/energy
Lexington, South Carolina 29072
8 AWG 8 AWG

6 AWG 10 60 30 16 8 4 2 1 6 AWG
0 cy cy cy cy cy cy
cy cyc cle cle cle cle
cle le cle cle s s s
s s s s - - - -0
-1 - 1. - 0. - 0. 0 .1 0 .0 0 .0 .0
4 AWG 16
.6
66
00
00
50
00
26
67
33
3
66
7
33
3 7 4 AWG
7 se se sec s ec sec
se
co
se sec
co on c on con ond ond o nd nd
nd ds ds ds s s s s
2 AWG s
2 AWG
1 AWG 1 AWG
1/0 AWG 1/0 AWG
2/0 AWG 2/0 AWG
3/0 AWG Conductor - Copper
Thermoset Insulations
3/0 AWG
4/0 AWG Rated for 105°C 4/0 AWG
250 kcm Maximum Continuous Operation 250 kcm
Curves Based on Formula:
350 kcm I2 (T2 + 234.5) 350 kcm
t = 0.0297 log
A2 (T1 + 234.5)
Where:
I = Short Circuit, Amperes
500 kcm A = Conductor Area, Circular Mils 500 kcm
t = Time of Short Circuit, Seconds
T 1 = Maximum Operating Temperature (105°C)
T 2 = Maximum Short Circuit Temperature (250°C)
750 kcm 750 kcm
1000 kcm 1000 kcm

06/21/2006
Revision 4

Page 14 of 20
General Calculations
Shield Short Circuit Current MA
I=
Formula N
60
The following simplified formula may be
used to calculate allowable sheath currents Where:
(based on ICEA P-45-482):
I = Short circuit current, amperes
1. The maximum time that a given short- A = Shield Area in cmils
circuit current can flow in a given shield N = Number of cycles
or sheath, or M = See Tables on next page

2. The maximum short-circuit current that The final temperature the shield or sheath
can flow in a given shield or sheath for a can reach without damaging the adjacent
given time, or materials limits allowable shield or sheath
currents. This limiting temperature is defined
3. The effective cross-sectional area of a in ICEA P-45-482 as the variable “T2”.
shield or sheath needed to withstand a Various values of “T2” are listed below. For
given short-circuit current for a given greater detail in regards to the calculation
time. please refer to ICEA P-45-482.

Values of T2, Maximum Allowable Shield or Sheath Transient


Temperature

Cable Material in T2
Contact with Shield or (°C)
Sheath

Crosslinked (thermoset) 350*


Thermoplastic 200
Impregnated Paper 200
Varnished Cloth 200

* For lead (Pb) sheaths this temperature is limited to 200°C.

NOTE: The material in contact with the shield or sheath shall limit the temperature of the
shield or sheath. For example, a cable having a crosslinked semi-conducting shield under
the metallic shield and a crosslinked jacket over the metallic shield would have a
maximum allowable temperature of 350°C. With a thermoplastic jacket, it would be 200°C.

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 15 of 20
www.na.prysmian.com/energy
Values of “M” Based on Shield Temperature (T2) Above

T2 Rated Values of “M” Values of “M”


Max Voltage (90°C) (105°C)
(°C) (kV) Cu Al Pb Cu Al Pb

200 5 0.063 0.042 0.012 0.058 0.039 0.01


350 5 0.089 0.059 ---- 0.085 0.056 1
----
200 15 0.063 0.042 0.012 0.058 0.039
350 15 0.089 0.059 ---- 0.085 0.056 0.01
1
200 25 0.063 0.042 0.012 0.060 0.040 ----
350 25 0.089 0.059 ---- 0.086 0.057
0.01
200 35 0.065 0.043 0.012 0.060 0.040 1
350 35 0.090 0.060 ---- 0.086 0.057 ----

200 46 0.065 0.043 0.012 0.060 0.040 0.01


350 46 0.090 0.060 ---- 0.086 0.057 1
----

0.01
1
----

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 16 of 20
www.na.prysmian.com/energy
To calculate the circular mil area of a shield design, use the following
formulas:

Formulas For
Type of Shield or Sheath Calculating “A”
(See notes 1 & 2)
1. Wires applied either helically, as a braid or serving; or 2
longitudinally with corrugations. nd S

2. Helically applied tape not overlapped. 127


. nwb
100
4bd m ⋅
2(100 − L )
3. Helically applied flat tape, overlapped (See note 3).

4. Corrugated tape, longitudinally applied. [


. π ⋅ (d is + 50) + B ⋅ b
127 ]
5. Tubular Sheath. 4bd m

NOTE 1:
Where:
A = Effective cross-sectional area, shield or sheath
B = Tape overlap, mils (usually 375)
b = Thickness of tape, mils
dis = Diameter over semiconducting insulation shield, mils
dm = Mean diameter of shield or sheath, mils
ds = Diameter of wires, mils
w = Width of tape, mils
n = Number of serving or braid wires, or tapes
L = Overlap of tape, percent

NOTE 2:
The effective area of composite shields is the sum of the effective areas of the
components. For example, the effective area of a composite shield consisting of a
helically applied tape and a wire serving would be the sum of the areas calculated from
Formula 2 (or 3) and Formula 1.

NOTE 3:
The effective area of thin, helically applied overlapped tapes depends, also, upon the
degree of electrical contact resistance of the overlaps. Formula 3 may be used to calculate
the effective cross-sectional area of the shield for new cable. An increase in contact
resistance may occur after cable installation, during service exposed to moisture and
heat. Under these conditions the contact resistance may approach infinity, where Formula
2 could apply.

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 17 of 20
www.na.prysmian.com/energy
OTHER CALCULATIONS
Charging Current

The charging current I of a single


conductor insulated power cable can be Dielectric Loss of Cable
obtained from the following formula:
Insulation
I = 2 ⋅π ⋅ f ⋅ C ⋅ E The dielectric loss of a single conductor
cable can be calculated by the following
Where: formula:
I = microamperes per 1000 ft.
0.00276 ⋅ E 2 ⋅ ( SIC ) ⋅ tan δ
f = Frequency, Hz Wd =
C = Capacitance, picofarads per ft ⎛ D⎞
log⎜ ⎟
E = Voltage, phase-to-ground, kV ⎝d⎠
Capacitance of Cables Where:
The capacitance of a one conductor Wd = Dielectric loss, watts per ft.
shielded cable is given by the following E = Phase-to-neutral voltage, kV
formula: SIC = Dielectric constant of the
insulation material
7.354 ⋅ ( SIC ) tan δ = dissipation factor
C=
D
log
d
Where: Maximum Voltage Stress Across
Insulation
C = Capacitance, picofarads per ft 2 ⋅ Eg
SIC = Dielectric constant of the V =
insulation material ⎛ Di ⎞
D = Diameter over insulation
D cs ⋅ ln ⎜⎜ ⎟⎟
d = Diameter under insulation ⎝ D cs ⎠
Where:

Typical Values of SIC V = Maximum voltage stress, kV


Eg = Phase-to-neutral voltage, kV
DCS = Diameter over conductor shield
Polyvinyl Chloride ......................... 3.5 - 8.0
Di = Diameter over insulation
EPR Insulation .............................. 2.5 - 4.0
Polyethylene ................................. 3.0 - 6.0
Crosslinked Polyethylene ............. 2.1 - 2.3 Dissipation Factors for Insulation
Impregnated Paper ....................... 3.3 - 3.7 Materials (tan δ)

Impregnated Paper………..…0.002 - 0.0025


EPR Insulation………………. 0.002 - 0.0800
Crosslinked Polyethylene…..0.0001 - 0.0003

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 18 of 20
www.na.prysmian.com/energy
“balanced” support for the cable (i.e. a
“Double Eye” grip vs. a “Single Eye” type).

NOTE: Grips are not suitable for all


vertical riser installation and the above
Support Grip Length or is offered as a general guide only. If
Maximum Riser Length for Given you have any questions of the
suitability of a grip and/or cable
Support Grip
construction for a vertical application,
please consult the cable manufacturer.
The following formula may be used to
determine either:
1) Minimum support grip lengths for
a given riser section length, or
Inductive Reactance to Neutral
2) Maximum riser section length for
The following is a nomogram used to
a given support grip working
determine the inductive reactance of solid
length.
or stranded (concentric) conductors at 60
Hz. It accommodates various spacing of
1.8 ⋅ (π ⋅ D ⋅ GL )
the conductors and other unique
SL = parameters as indicated within the
WC nomogram itself.

Where: Special consideration should be given to


cables when installed in magnetic ducts.
SL = Riser Section Length, in feet Installing a single cable in a magnetic duct
D = Diameter over cable jacket, in. results in HIGH reactance and a de-rated
GL = Working length of grip, in. ampacity. If magnetic ducts must be used,
WC = Cable weight, pounds per ft it is recommended that all three cables be
placed in a single duct. While resulting in
Prysmian recommends that a recognized slightly higher reactances than three
manufacturer supply the correct grip(s) on cables in a non-magnetic duct, it is optimal
an individual application basis, utilizing the relative to the alternative of a single cable
formula shown above. Prysmian does in a magnetic duct.
suggest using grips, which will provide

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 4
Phone: 1.800.845.8507 06/21/2006
Fax: 1.803.951.1142 Page 19 of 20
www.na.prysmian.com/energy
Nomogram for Determining Conductor Reactance at 60 Hz
(Series Inductive Reactance to Neutral)

700 Industrial Drive General Calculations


Lexington, South Carolina 29072 Revision 2
Phone: 1.800.845.8507 01/18/2005
Fax: 1.803.951.1142 Page 20 of 20
www.na.prysmian.com/energy

You might also like