FIELD WORK
ELECTRICAL SYSTEM INSPECTION OF
EXISTING COMMERCIAL BUILDING(CHURCH)
November 2018
Prepared by:
PANLILIO, ELIJAH JAMES S.
MAGLAQUI, JAMAICA J.
SEMILLA, JOYZA JANE J.
COMIA, EULLA C.
B.S. Electrical Engineering
Submitted to:
Engr. Generoso G. Restubog
Professor
1.0 Objectives
1. To be familiar with the different electrical system protection in
a commercial establishment.
2. To be familiar with the different machines in a commercial
establishment.
3. To be familiar with how the service entrance is connected.
4. To be familiar with the actual lighting outlets, fixtures, and
switches used in a commercial establishment.
5. To be familiar with the panel boards and protective devices
used in a commercial establishment.
2.0 Commercial Establishment Description
MDP
LOCATED AT THE
GROUND FLOOR
ELECTRICAL ROOM
CI LOAD V V AMPERES NUMBER, PROTECTI
RC SERVE A O A B C 3Ø SIZE AND ON
UI D L B C A TYPE OF
T T CONDUCTORS
N
O.
1 DPa 1 2 46 2 Sets (3-250 1200AT,
8 3 3. mm2 THWN) 3P, ACB
4 0 29 in existing 240 Volts
3 conduit
4
4
2 DPb 3 2 97 2 Sets (3-250 1200AT,
8 3 5. mm2 THWN) 3P, ACB
8 0 75 in existing 240 Volts
2 conduit
5
0
3 DPb-a 6 2 16 3-125 mm2 300AT,
5 3 4. THWN in 3P, ACB
3 0 11 existing 240 Volts
0 conduit
0
4 DPc 4 2 11 2 Sets (3-250 1200AT,
4 3 2. mm2 THWN) 3P, ACB
8 0 59 in existing 240 Volts
0 conduit
0
MAIN 9 sets (3- 2000AT,
CIRCU 250 mm2 3P, ACB
IT THHN) 60Hz,
BREAK 240 Volts
ER
TOTAL LOAD = 1, 9 sets (3- 2000AT,
71 250 mm2 3P, ACB
5. THHN) 60Hz,
74 240 Volts
DPa
LOCATED AT THE
GROUND FLOOR
ELECTRICAL ROOM
CI LOAD V V AMPERES NUMBER, PROTECTI
RC SERVED A O A B C 3 SIZE AND ON
UI L B C A Ø TYPE OF
T T CONDUCTOR
N S
O.
1 PP Grnd 4 2 1 3 - 30.0 125A, 3P,
Floor 3 3 0 mm2 THWN ACB 240
LT/CO 3 0 8. in existing Volts
(EE 4 9 conduit
Room) 0 2
2 PP 2nd 1 2 4 3 - 30.0 125A, 3P,
Floor 8 3 5. mm2 THWN ACB 240
LT/CO 0 0 2 in existing Volts
(EE 0 4 conduit
Room) 0
3 ACCU 2nd 1 2 4 3 - 30.0 125A, 3P,
Floor (EE 6 3 1. mm2 THWN ACB 240
Room) 6 0 8 in existing Volts
6 7 conduit
0
4 Spare 125A, 3P,
ACB 240
Volts
5 MP1 4 2 1 3 - 30.0 125A, 3P,
ACCU 01 1 3 0. mm2 THWN ACB 240
0 0 3 in existing Volts
3 1 conduit
6 MP1 8 2 2 3 - 30.0 125A, 3P,
ACCU 02 2 3 0. mm2 THWN ACB 240
& 03 0 0 6 in existing Volts
6 2 conduit
7 Mezzanin 4 2 1 3 - 30.0 125A, 3P,
e ACCU 1 3 0. mm2 THWN ACB 240
5TR 0 0 3 in existing Volts
3 1 conduit
8 PP 4 2 1 3 - 38.0 125A, 3P,
Sanctuary 5 3 1 mm2 THWN ACB 240
LT/CO 0 0 3. in existing Volts
0 0 conduit
0 9
9 PP 2nd 1 2 4 3 - 30.0 125A, 3P,
Floor 8 3 5. mm2 THWN ACB 240
LT/CO 0 0 2 in existing Volts
(EE 0 4 conduit
Cabinet) 0
10 ACCU 2nd 2 2 6 3 - 30.0 125A, 3P,
Floor (EE 6 3 7. mm2 THWN ACB 240
Cabinet) 9 0 6 in existing Volts
3 9 conduit
2
MAIN 2 Sets (3- 1200AT,
CIRCUIT 250 mm2 3P, ACB
BREAKE THWN) 60Hz,
R 240 Volts
TOTAL LOAD = 4 2 Sets (3- 1200AT,
6 250 mm2 3P, ACB
3. THWN) 60Hz,
2 240 Volts
9
PP Sanctuary LT/CO
LOCATED AT THE GROUND FLOOR
ELECTRICAL ROOM
CIRCU LOADS VA VOL AMPERES N
IT NO. T AB BC CA 3Ø O
16 Spare
17 Mezzanine 5000 230 21.74 2- 5.5 mm2
CIRCUIT AMPERES
LOADS VA VOLT NUMBER, SIZE AND TYPE OF CONDUCTORS PROTECTION
NO.
AB BC CA 3Ø
1 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
2 PP Maintenance Office 5000 230 21.74 2- 5.5 mm2 THWN in existing conduit 60A, 1P, ACB 240 Volts, P-In
3 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
4 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 20A, 1P, ACB 240 Volts, P-In
5 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
6 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 20A, 1P, ACB 240 Volts, P-In
7 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
8 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
9 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
10 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 20A, 1P, ACB 240 Volts, P-In
11 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
12 CO Basement 1000 230 4.35 2- 3.5 mm2 THWN in existing conduit 20A, 1P, ACB 240 Volts, P-In
13 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 20A, 1P, ACB 240 Volts, P-In
14 CO Basement 1000 230 4.35 2- 3.5 mm2 THWN in existing conduit 30A, 1P, ACB 240 Volts, P-In
15 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
16 Spare 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
17 CO Basement 1000 230 4.35 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
18 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
19 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
20 Spare 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
21 Spare 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
22 Spare 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
23 LT Basement 360 230 1.57 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
24 CO Basement 1000 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
25 Exhaust Fan 1500 230 6.52 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
26 LT Basement 500 230 2.17 2- 3.5 mm2 THWN in existing conduit 15A, 1P, ACB 240 Volts, P-In
27 Welding Machine 5000 230 21.74 2- 5.5 mm2 THWN in existing conduit 60A, 1P, ACB 240 Volts, P-In
28 Suction Pump 1200 230 5.22 2- 5.5 mm2 THWN in existing conduit 30A, 1P, ACB 240 Volts, P-In
MAIN CIRCUIT BREAKER 3 - 30 mm 2 THWN in existing conduit 125A, 3P, ACB 60Hz, 240 Volts