1 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
2. THE ELECTRICAL SERVICE POWER SHALL BE 1-PHASE, 3-WIRE,
230V AC, 60Hz.
2 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
3. THE WIRING METHOD SHALL BE AS FOLLOWS:
3 LIGHT OUTLET, 4 -- 100W 400 230 1.40 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC RIGID STEEL CONDUIT (RSC) OR POLYVINYL CHLORIDE CONDUIT (PVC)
SCHEDULE 40 SHALL BE USED AS SPECIFIED IN THE PLAN.
4 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
9 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC TYPE.
1 2
10 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC LIGHT OUTLET 20 AT 20 AT LIGHT OUTLET
11 LIGHT OUTLET, 4 -- 100W 400 230 1.74 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC APPROVED FOR THE PARTICULAR LOCATION AND USAGE. OUTLET
12 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC 7. EQUIPMENT GROUNDING SYSTEM SHALL BE PROVIDED TO THE
ELECTRICAL SYSTEM AS PER PHILIPPINE ELECTRICAL CODE 2 SINGLE LINE DIAGRAM
13 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC REQUIREMENT. E-2 SCALE NTS
14 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS:
15 LIGHT OUTLET, 3 -- 100W 300 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
LIGHT SWITCH 1200mm ABOVE THE FINISH FLOOR OVERHEAD SERVICE ENTRANCE:
230 V, 1Ø, 2W, 60 Hz A.C. W ITH
CONVENIENCE OUTLET 300mm ABOVE FINISH FLOOR 25mm Ø TYPE "F" CONDULET
WEATHERHEAD
16 CONVENIENCE OUTLET, 4 -- 360W 1440 230 6.26 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC PROPOSED REINFORCED CONCRETE PEDESTAL
9. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT POLE: SIZE AS REQUIRED
17 CONVENIENCE OUTLET, 5 -- 360W 1800 230 7.83 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC AND IMMEDIATE SUPERVISION OF A DULY REGISTERED 2 -- 8.00mm2 THWN + 1 -- 5.0mm2 THWN (G)
IN 25mm Ø RSC
ELECTRICAL ENGINEER.
18 CONVENIENCE OUTLET, 3 -- 360W 1080 230 4.70 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
19 CONVENIENCE OUTLET, 3 -- 360W 1080 230 4.70 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
20 CONVENIENCE OUTLET, 5 -- 360W 1800 230 7.83 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC ELECTRICAL LEGEND M
PB
1800
21 CONVENIENCE OUTLET, 2 -- 360W 720 230 3.13 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC IN 25mmØ C-CLAMPED TO
POWER LINE COPPER-CLAD GROUNDING ROD
22 CONVENIENCE OUTLET, 3 -- 360W 1080 230 1.30 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC FINISHED FLOOR LINE
23 CONVENIENCE OUTLET, 3 -- 360W 1080 230 4.70 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC GROUNDING SYSTEM
16mmØ x 2400mm LENGTH
COPPER-CLAD GROUNDING ROD
24 CONVENIENCE OUTLET, 3 -- 360W 1080 230 4.70 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC LIGHTING OUTLET
25 AIR CONDITIONING UNIT, 1-- 1500W 1500 230 6.52 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC 3 RISER DIAGRAM
SCALE NTS
LIGHTING OUTLET E-2
26 AIR CONDITIONING UNIT, 1-- 1500W 1500 230 6.52 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
27 AIR CONDITIONING UNIT, 1-- 1500W 1500 230 6.52 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC CIRCUIT HOMERUN
#
28 AIR CONDITIONING UNIT, 1-- 1500W 1500 230 6.52 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
29 AIR CONDITIONING UNIT, 1-- 1500W 1500 230 6.52 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC PANEL BOARD
30 AIR CONDITIONING UNIT, 1-- 1500W 1500 230 6.52 50 2 20 2 -- 3.50 mm2 THWN 20mm Ø RSC
TOTAL 26920
CONVENIENCE OUTLET
IT = [ 23260/230 ] [ 80% D.F. ] = 80.90 A FOR FEEDER & UNIT SIZE FOR PROTECTION
USE: 2 -- 8.0 mm2 THWN Cu WIRE USE: 40 AT/AF 230 V MAIN DISCONNECT ABBREVIATIONS:
1 -- 5.0 mm2 THWN Cu WIRE
IN 25 mm Ø PVC
S1 SINGLE POLE WALL SWITCH
IN ONE SWITCH PLATE (10 AMP, 230 VOLTS)
REPUBLIC OF THE PHILIPPINES PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
NATHANIEL CHRISTIAN MARCELINO
REGIONAL OFFICE NO. 02 ELECTRICAL NOTES
Basic Infrastructure Program (BIP) - Multi-Purpose AND SCHEDULE
ENGINEERING ASSISTANT