Professional Documents
Culture Documents
Protection against shock outside the equipotential bonding The provision of residual current protetion throughout a system or in
zone vulnerable parts of a system will greatly reduce the hazard of fire
caused by such faults.
Bonding condutors are used in an installation to maintain metallic
parts, as near as possible, to the same potential as earth. PEN conductors
Working with portable equipment outside this equipotential bonding The use of RCCBs is PEN conductors is prohibited. A PEN conduc-
zone, e.g. in the car park of a factory, introduces tor is a single conductor combining the functions of neutral conduc-
additional shock hazards. Socket outlets rated 32A or less w‘ hich ay tor and protective conductor. This being so, when the PEN conduc-
be reasonably expected to supply portable tor is taken through the torroid of an RCCB, earth faults will go
equipment for use outdoors’should have at least one socket nomi- undetected because the return path for the earth fault current is
nated for outdoor use. This socket should be equipped with RCC included in the resiual sum.
protection unless fed from an isolating transformer or similar device,
or fed from a reduced voltage. Use of Hager RCCBs on 3 phase 3 wire systems
The Hager range of 4 pole RCCBs can be used to provide residual
Protection in special situations (IEE wiring regulation) current protection of 3 phase, 3 wire circuits (no neutral).
The use of RCCBs is obligatory or recommended in the following L1 N L1 L2 L3
situations :
1 3 5 7 N 1 3 5 7 N
T T
- caravans : 30mA RCCBs should be used
- TT systems
2 4 6 8 N 2 4 6 8 N
- swimming pools : 30mA RCCB for socket outlets in zone B obliga-
L1 N L1 L2 L3
tory; recommended in zone C.
Supply entry
- Agricultural and horticultural : 30mA RCCB for socket outlets and Top or bottom feed.
for the purpose of protection against fire, RCCB ≤ 0.5A sensitivity.
OFF ON
green red
or
OFF
grey yellow
T.22