Professional Documents
Culture Documents
Managing Editor
Kristen Dietrich
Contributing Authors
Muneef Ahmad, Thomas E. Barnard,
Peder Hjorth, and Robert Pitt
Editors
David Klotz, Adam Strafaci, and Colleen Totz
HAESTAD PRESS
Waterbury, CT USA
10
Gutter Flow and Inlet Design
Storm sewer systems, which are most commonly designed and constructed for service
in urbanized areas, are an integral part of the infrastructure. They are typically
designed as conveyance systems for smaller, more-frequent storms in order to prevent
the nuisances and flood damages that would otherwise accompany them. Runoff from
larger, less-frequent events is generally not conveyed entirely by storm sewers; rather,
it flows over the land surface in roadways and in natural and constructed open chan-
nels.
Stormwater enters the subsurface sewer conveyance system through inlets in roadway
gutters, parking lots, depressions, ditches, and other locations. These surface compo-
nents are critical, and they must be properly designed to ensure that the overall system
functions as intended. For example, an engineer may design a pipe system capable of
handling the 10-year storm event, but the level of protection provided will be lower
(often much lower) if the system’s inlet capacities are not sufficient to intercept the
10-year flows. Inadequate attention to roadway drainage and inlets can cause undue
hazards to the traveling public and can compromise the degree of protection afforded
to private and public properties located along the sides of a roadway.
This chapter is the first of two chapters on the design and hydraulic analysis of storm
sewer systems. It focuses on surface drainage—specifically, the physical and hydrau-
lic characteristics of roadway gutters and grate, curb, combination, and slotted-drain
inlets. The various types of gutter sections, including detailed information on the
hydraulic analysis of uniform and composite gutters, are presented in Section 10.1.
Section 10.2 covers the various inlet types and methods for evaluating the hydraulic
performance of grate, curb, combination, and slotted-drain inlets. Determination of
inlet design flows and proper placement of inlets are discussed in Section 10.3.
Chapter 11 continues the presentation on storm sewer systems with information on
the analysis and design of the subsurface portion of the system.
370 Gutter Flow and Inlet Design Chapter 10
Figure 10.1
Typical gutter cross
sections
Section 10.1 Roadway Gutters 371
To maintain proper drainage, roadway longitudinal slopes (slopes along the length of
the road) are usually specified to be no smaller than about 0.4 percent. It is difficult to
maintain positive drainage with smaller slopes, resulting in localized puddling. Pave-
ment cross slopes (measured perpendicular to the road direction) necessary to induce
flow off of the pavement surface and into the gutter range from 1.5 percent to as high
as about 4 percent, but are typically specified at around 2 percent (ASCE, 1992).
The allowable spread of open-channel flow in a gutter section is generally a function
of the roadway classification, the design traffic speed, and whether that portion of the
gutter is in a sag location (that is, at the low point of a roadway vertical curve). Design
criteria suggested by the FHWA (Brown, Stein, and Warner, 2001) are presented in
Table 10.1; other criteria may be specified by local jurisdictions.
d = TSx (10.1)
Figure 10.2
Uniform gutter cross
section
372 Gutter Flow and Inlet Design Chapter 10
Cf
Q S x5 / 3T 8 / 3 So1/ 2 (10.4)
n
Table 10.2 Manning’s n for streets and gutters (Brown, Stein, and Warner, 2001)
Equation 10.4 is a modified form of the Manning equation presented in Section 6.2
(page 198) and Section 7.2 (page 226). The modification is necessary because the
hydraulic radius does not adequately describe the gutter section, particularly when the
spread may be more that 40 times the depth at the curb face (ASCE, 1992).
Example 10.1 – Computing Gutter Capacity. An asphalt-paved street has a cross slope
Sx = 0.02 and a longitudinal slope So = 0.03. As shown in Figure E10.1.1, the gutter cross section is
uniform with a 6-in.-high concrete curb. The street is in a residential area, and the distance from the
street centerline to the face of the curb is 18 ft. Assuming that the street width allows for a 10-ft-wide
driving lane and 8 ft of parking space on either side of the centerline, estimate the conveyance capac-
ity of each side of the street such that maximum spread criteria are not violated.
0.56
Q 0.025 / 3138 / 30.030.5 8.9 cfs
0.015
Thus, the total capacity of the street (both gutters) is 2(8.9) = 17.8 cfs.
Q = Qw + Qs (10.5)
Figure 10.3
Composite gutter
cross section
T = W + Ts (10.6)
y = d + a = TSx + a (10.7)
Sw = Sx + a/W (10.8)
Cf
Qs S x5 / 3Ts8 / 3 So1/ 2 (10.9)
n
Section 10.1 Roadway Gutters 375
Q w = E oQ (10.10)
where Eo = fraction of the total discharge that flows in the depressed gutter section
(0 d Eo d 1)
then, substituting for Qw from Equation 10.5 and solving for Q gives
Qs
Q (10.11)
1 Eo
The fraction Eo of the total discharge that flows in the depressed gutter section is
given by Brown, Stein, and Warner (2001).
1
½
° °
° Sw / S x °
Eo ®1 ¾ (10.12)
8/3
° § Sw / S x · °
° ¨1 (T / W ) 1 ¸ 1 °
¯ © ¹ ¿
Equations 10.5 through 10.12 permit an easy determination of the discharge in a com-
posite gutter section when the spread is specified. Unfortunately, a trial-and-error
solution of these equations is necessary to determine the spread when the discharge is
known. This solution is accomplished by assuming different spread values until the
computed discharge agrees with the given value. A computer program can also be
used to perform this calculation.
It should be noted that when a roadway is rehabilitated and existing pavement is over-
laid with new asphalt, the existing concrete gutter may be paved over as well. In this
way, a composite gutter section may be transformed into a uniform section.
Example 10.2 – Composite Gutter Capacity. Repeat Example 10.1 to find the capacity of
the gutter if the gutter has a composite cross section with a gutter depression width of W = 2 ft. As
shown in Figure E10.2.1, the curb is again 6 in. in height, and the vertical distance from the lowest
point in the cross section to the top of the gutter depression is 1.5 in. (0.125 ft).
Solution: With the substitutions T = 13 ft and W = 2 ft, Equation 10.6 yields Ts = 11 ft.
The gutter cross slope is
Sw = 0.125/2 = 0.0625
The gutter depression, from Equation 10.8, is
a = W(Sw – Sx) = 2(0.0625 – 0.02) = 0.085 ft
The depth of flow at the curb face is
y = TSx + a = 13(0.02) + 0.085 = 0.345 ft
Again, the spread, rather than curb overtopping, is the limiting criterion. Substituting these values into
Equation 10.9 yields the discharge Qs as
0.56 5/3 8/3 1/ 2
Qs 0.02 11 0.03 5.7 cfs
0.015
The fraction Eo of the total discharge that flows in the depressed gutter section is found from Equation
10.12 as
1
ª º
« »
« 0.0625 / 0.02 »
«
Eo 1 » 0.43
« § 8/3 »
0.0625 / 0.02 ·
« ¨1 ¸ 1 »
« ¨ 13 / 2 1 ¸¹ »
¬ © ¼
The total conveyance capacity from Equation 10.11 is
Q = 5.7/(1 – 0.43) = 10 cfs
Considering both sides of the street, the conveyance capacity is 20 cfs.
Section 10.2 Inlets 377
10.2 INLETS
A stormwater inlet is a structure for intercepting stormwater on the ground surface or
in a roadway gutter and conveying it into the storm sewer piping system. It consists of
an inlet opening at the surface and an inlet box, which is a subsurface box, manhole,
or other structure that supports the inlet opening and connects to the subsurface piping
system. Additional information on inlet boxes and manholes is provided in
Section 10.1.
All basic inlet types can be classified further as either continuous-grade inlets (also
referred to as inlets on grade) or sag inlets. A sag inlet is constructed in the low point
of a road or other surface where water drains to the inlet from all directions. With a
continuous-grade inlet, surface water can flow away from the inlet opening in one or
more directions. The cutaway storm sewer system profile in Figure 10.4 shows inlets
in a roadway gutter for both continuous-grade and sag installations.
Figure 10.4
Cutaway view of a
storm sewer system
profile (vertical scale
exaggerated)
Inlet opening geometries vary considerably from one locale to another, but all can be
classified as one of four general types, as illustrated in Figure 10.5. Grate inlets con-
sist of an opening in a gutter or swale, with the opening covered by a grate. Curb-
opening inlets consist of an opening in the face of a curb. Combination inlets have
both grate and curb openings and combine the advantages of each of the individual
inlet types. Finally, slotted drain inlets consist of a grate opening oriented along the
longitudinal axis of a pipe and manufactured integrally with the pipe.
In most cases, the tops of stormwater inlets and inlet openings are constructed of cast-
in-place reinforced concrete, and grates, if present, are cast or fabricated metal. In
many locales, precast concrete inlet structures are also available.
378 Gutter Flow and Inlet Design Chapter 10
Figure 10.5
Common inlet types
public-safety reasons, the height of the opening should be no greater than about 6 in.
(15 cm).
Combination inlets, which have both grate and curb openings, offer the advantages of
both inlet types. The curb opening is usually the same length as the grate, but it may
extend beyond the grate in either or both directions. When the curb opening is longer
than the grate, it becomes effective for intercepting trash and debris before it has a
chance to clog the grate opening. For this reason, so-called sweeper inlets with this
configuration are often recommended for use in sags where excessive ponding due to
debris accumulation could pose a safety hazard.
Slotted-drain inlets, because of their longer lengths, can be very effective in intercept-
ing sheet flows at locations such as loading docks and garage entrances. They are also
effective for use in locations, such as parking lot entrances, where they can intercept
flow before it enters the roadway. Slotted drains are very susceptible to clogging and
are therefore not recommended for use in sags or other locations where trash and
debris loadings may be considerable. Slotted drains are also susceptible to crushing
loads because of their shallow burial depths, and thus require great care in pipe bed-
ding and backfilling operations.
Given a specific set of inlet dimensions, the performance of a particular type of inlet
depends on a number of factors. Among them are the depth and velocity of the flow in
the approach gutter(s), the longitudinal and cross slopes of the roadway, and the Man-
ning roughness coefficient for the gutter. The performance also depends significantly
on whether the inlet is installed in a depression, such as the sag point of a vertical
curve, or on a continuous grade. Inlets installed in sag points should be sized to cap-
ture the entire design discharge approaching them. Inlets on continuous grades may
be designed to intercept either all or part of the design flow in the approach gutter.
The efficiency of an inlet is defined as the ratio of the discharge intercepted by the
inlet to the total discharge approaching the inlet:
E = Qint/Q (10.13)
Qb = Q – Qint (10.14)
Grate Inlets
The methods for evaluating the capacity of a grate inlet (see Figure 10.6) differ
depending on whether the inlet is located on a continuous grade or in a sag. The sub-
sections that follow present information on determining grate capacity for both condi-
tions.
Capacity of a Grate Inlet on a Continuous Grade. A grate inlet’s
interception capacity on a continuous grade depends on the depth of flow, the size and
configuration of the grate, and the velocity of the approaching flow. The FHWA has
developed a number of standardized grate designs, which are described in Table 10.3
and illustrated in Figures 10.7 through 10.12 (Brown, Stein, and Warner, 2001;
FHWA, 1977). These grates may be used with uniform or composite gutter sections,
or in the bottom of a channel such as a median swale or roadside ditch.
Figure 10.6
Grate inlet
Table 10.3 FHWA standard grate types (Brown, Stein, and Warner, 2001; FHWA, 1977)
Grate type Description Figure Reference
Reticuline “Honeycomb” pattern of lateral and longitudinal bearing bars 10.7
P-50 Parallel bar grate with bar spacing 48 mm (1.875 in.) on center 10.8
Parallel bar grate with bar spacing 48 mm (1.875 in.) on center,
P-50 u 100 and with 10-mm (0.375-in.) diameter lateral rods spaced at 102 10.8
mm (4 in.) on center
P-30 Parallel bar grate with bar spacing 29 mm (1.125 in.) on center 10.9
Curved-vane grate with longitudinal bar spacing 82 mm (3.25
Curved vane in.) on center and transverse bar spacing 114 mm (4.5 in.) on 10.10
center
45q tilt-bar grate with longitudinal bar spacing 57 mm (2.25 in.)
45q–60 tilt bar 10.11
on center and transverse bar spacing 102 mm (4 in.) on center
45q tilt-bar grate with longitudinal bar spacing 83 mm (3.25 in.)
45q–85 tilt bar 10.11
on center and transverse bar spacing 102 mm (4 in.) on center
30q tilt-bar grate with longitudinal bar spacing 82 mm (3.25 in.)
30q–85 tilt bar 10.12
on center and transverse bar spacing 102 mm (4 in.) on center
Section 10.2 Inlets 381
Figure 10.7
Reticuline grate
Figure 10.8
P-50 and P-50 u 100
grates
382 Gutter Flow and Inlet Design Chapter 10
Figure 10.9
P-30 grate
Section 10.2 Inlets 383
Figure 10.10
Curved-vane grate
384 Gutter Flow and Inlet Design Chapter 10
Figure 10.11
45q–60q tilt bar and
45q–85q tilt-bar grates
Section 10.2 Inlets 385
Figure 10.12
30q–85q tilt-bar grate
386 Gutter Flow and Inlet Design Chapter 10
2.67
§ W· (10.15)
Eo 1 ¨1 ¸
© T ¹
With a composite gutter section, the grate width is often equal to the width of the gut-
ter depression. In this instance, the definitions of frontal flow and side flow are the
same as those presented in the discussion of composite gutters in Section 10.1. There-
fore, the ratio Eo for the composite gutter when the spread is greater than the grate
width is determined using Equation 10.16:
1
½
° °
° Sw / S x °
Eo ®1 ¾ (10.16)
8/3
° § Sw / S x · °
° ¨ 1 (T / W ) 1 ¸ 1 °
¯ © ¹ ¿
§ Ac ·
Eoc Eo ¨ w ¸ (10.17)
© Aw ¹
where Eoc = adjusted frontal-flow area ratio for grates in composite cross-sections
Awc = cross-sectional gutter flow area for the grate width (ft2, m2)
Aw = cross-sectional gutter flow area in the depressed gutter width (ft2, m2)
For a grate inlet in the bottom of a trapezoidal channel, as shown in Figure 10.13, the
Manning equation may be used to solve for the flow depth in the channel (see
Section 7.2, page 226). Eo is then given by
Section 10.2 Inlets 387
W
Eo (10.18)
B dz
Figure 10.13
Cross section of a
trapezoidal channel
with a grate inlet
Once Eo (or Eoc ) is known, the gutter flow and side flow approaching the grate are
given by the equations
Q w = E oQ (10.19)
and
Qs = (1 – Eo)Q (10.20)
where
°1 K c V Vo ; V t Vo
Rf ® (10.22)
°̄ 1; V d Vo
Figure 10.14
Graph for determining
Vo and Rf for common
grate types
The side flow intercepted by a grate inlet on a continuous grade, denoted by (Qs)int, is
where
1
§ K sV 1.8 ·
Rs ¨1 ¸ (10.24)
¨ S L2.3 ¸
© x ¹
Ks = 0.15 for U.S. customary units or 0.0828 for SI units
Sx = roadway cross slope (ft/ft, m/m)
L = grate length (ft, m)
Note that Rs as computed by Equation 10.24 will always be less than one, and hence
some of the side flow will always bypass a grate inlet on a continuous grade regard-
less of the flow velocity or inlet length. This is a deficiency of the equation, but it is
not of great concern for practical purposes.
Combining the above equations gives the total discharge intercepted by a grate inlet
on a continuous grade as
The orientation of an inlet grate can have a significant influence on the interception
capacity of the structure. Analyzing the capacity of an inlet grate requires that the
relationships used are appropriate for the intended orientation in which the grate will
be installed.
§ 2(11)(0.02) 0.125 · 2 2
A ¨ ¸ 2 0.5(11) (0.02) 1.27 ft
© 2 ¹
Q = CwPd3/2 (10.27)
Q = 0.67Ag(2gd)1/2 (10.28)
Figure 10.15
Depth d for a grate
inlet in sag
The clear-opening area of a grate used in Equation 10.28 is equal to the total grate
area less the area occupied by the longitudinal and transverse bars when projected
onto a horizontal plane. When the clear opening area is computed in this manner, it
can be increased by about 10 percent for curved-vane and 30q tilt-bar grates (Brown,
Stein, and Warner, 2001). However, curved-vane and tilt-bar grates are not recom-
Section 10.2 Inlets 391
mended for use in sag locations where there is a chance that a grate inlet would oper-
ate as an orifice.
In an analysis of the capacity of a grate inlet in a sag, a conservative practice is to esti-
mate the capacity using both Equations 10.27 and 10.28 and to then adopt the smaller
of the two estimates. For design problems in which the required inlet dimensions are
being determined, the larger of the sizes obtained by solving the two equations should
be used.
Example 10.4 – Capacity of a Grate Inlet in Sag. Determine the required size of a
grate inlet in a sag if the roadway has a uniform cross slope and dimensions as specified in Example
10.1, as shown again in Figure E10.4.1. Assume that the design discharge for the inlet is Q = 3.5 cfs
and that the width of the grate is W = 2 ft.
Because one edge of the grate is adjacent to the curb face and is therefore ineffective, the required
length of the grate is
L = P – 2W = 9.9 – 2(2) = 5.9 ft
If the inlet is assumed to behave hydraulically as an orifice, its required clear-opening area is given by
Equation 10.28:
Q 3.5 2
A g = --------------------------------- = ---------------------------------------------------------- = 1.3 ft
1e2 1e2
0.67 2gd 0.67 > 2 32.2 0.24 @
392 Gutter Flow and Inlet Design Chapter 10
If a P-50 grate has a length of 5.9 ft and a width of 2 ft, then the clear-opening area is well in excess of
1.3 ft2 (shown in Figure 10.8); therefore, weir behavior controls the design.
To provide a factor of safety against clogging of the grate, one might assume (for example) that its
perimeter should be increased by 25 percent. Applying this assumption gives the required perimeter
as
P = 1.25(9.9) = 12.4 ft
Therefore, the inlet length should be
L = 12.4 – 2(2) = 8.4 ft
Curb-Opening Inlets
Like those of grate inlets, the methods used to compute the capacity of a curb-opening
inlet (see Figure 10.16) are different if the inlet is on a continuous grade than if it is in
a sag location. The subsections that follow present methods for evaluating both condi-
tions.
Figure 10.16
Curb-opening inlet
Figure 10.17
Curb-opening inlet
with supports
As noted earlier in Section 10.2, the height of the opening in a curb-opening inlet
should be no more than about 6 in. (150 mm). The length of the opening required for
total interception of the gutter flow when the gutter has a uniform cross-section is
0.6
§ 1 ·
LT C f Q 0.42 So0.3 ¨ ¸ (10.29)
© nS x ¹
where LT = length of curb opening necessary for interception of the total gutter dis-
charge (ft, m)
Q = gutter discharge (cfs, m3/s)
So = longitudinal slope of the gutter (ft/ft, m/m)
n = Manning roughness coefficient for the gutter
Sx = cross slope (ft/ft, m/m)
Cf = 0.6 for U.S. customary units or 0.817 for SI units
The efficiency of a curb-opening inlet of length L less than LT is
1.8
§ L ·
E 1 ¨1 ¸ (10.30)
© LT ¹
Se S x S wp Eo (10.31)
approach is to estimate the capacity assuming both weir and orifice behaviors, and to
then adopt the smaller of the two capacities. Similarly, a conservative approach to
design is to adopt the larger of the two required inlet sizes.
The weir equation for a curb-opening inlet without a gutter depression yields an esti-
mate of the inlet capacity as
Q = CwLd3/2 (10.32)
Q = 0.67hL(2gdo)1/2 (10.34)
Figure 10.19
Curb-opening inlet
throat types
Example 10.6 – Capacity of a Curb Inlet in a Sag. A roadway has a composite gutter
section with a pavement cross slope Sx = 0.02, a normal gutter cross slope Sw = 0.0625, and a curb-
face height of 15 cm. The gutter width is W = 0.61 m. Thus, the top of the curb is normally 11 cm
higher than the elevation of the lip of the gutter. A curb-opening inlet with a horizontal throat is to be
designed at a sag point in the roadway with a design discharge of Q = 0.3 m3/s. The gutter is
depressed at the inlet location so that an opening height of 12 cm and a top slab thickness of 8 cm
yield a total curb height of 20 cm. The allowable spread at the inlet is T = 4 m. Determine the required
curb-opening length.
Solution: Because the gutter is depressed at the inlet, Equation 10.33 can be used to estimate the
required inlet length under the assumption that it behaves as a weir. Setting
d = TSx = 4(0.02) = 0.08 m
gives the required length as
Q 0.3
L 1.8W 1.8(0.61) 6.89 m
Cw d 3/ 2 1.66(0.08)3 / 2
Because this length is greater than 3.6 m, Equation 10.32 should be applied instead. The depth d used
in Equation 10.32 is the depth at the curb face. This value is equal to the depth at the curb face at a
normal gutter cross-section, plus an additional 5 cm for the depressed gutter. [The 5-cm depression is
computed as the difference between the normal curb height (15 cm) and the height at the inlet (20
cm).] At a normal gutter section, the curb-face depth is
y = (T – W)Sx + WSW = (4 – 0.61)(0.02) + 0.61(0.0625) = 0.11 m
and thus the depth for use in Equation 10.32 is
Section 10.2 Inlets 397
Comparing the lengths shows that weir behavior controls the design, and the required length is L =
2.58 m. This length should be increased by an assumed amount in order to account for clogging of the
inlet opening.
Combination Inlets
As previously discussed, a combination inlet is a configuration in which a grate inlet
and curb inlet are used together (see Figure 10.20). Like both calculations for grate
and combination inlets, the method used to compute combination inlet capacity
depends on whether the inlet is on grade or in a sag.
Figure 10.20
Combination inlet
P=L+W (10.35)
Slotted-Drain Inlets
Slotted-drain inlets may be installed either along the length of the gutter, as shown in
Figure 10.21, or perpendicular to the flow direction to intercept sheet flows. The cal-
culation of hydraulic capacity for both installation types is presented in this section.
Capacity of a Slotted-Drain Inlet on a Continuous Grade. The inter-
ception capacity of a slotted-drain inlet on a continuous grade depends significantly
on the orientation of the longitudinal axis of the slotted drain with respect to the sur-
face-flow direction. When slotted drains are installed in the normal fashion (along the
length of the gutter), as illustrated in Figure 10.21, and when the slot width is at least
1.75 in. (45 mm), FHWA tests show that the required length of a slotted drain for total
interception of the gutter flow is given by Equation 10.29. In other words, the slotted
drain performs similarly to a curb-opening inlet in this instance. If the actual length of
the slotted drain is shorter than the length required for total interception, then its effi-
ciency is given by Equation 10.30.
If a slotted drain is installed in a configuration for sheet-flow interception, its capacity
can be approximated by treating it as a grate inlet with a grate length equal to the
width of the slotted opening. Thus, its capacity can be approximated using Equations
10.21 and 10.22, where the frontal flow is the total sheet-flow discharge approaching
the slotted drain opening. Use of this approximation requires some judgment about
the appropriate value of the splash-over velocity. Although no specific recommenda-
tion is made here, intuition suggests that because of the generally shallow nature of
sheet flow, the factor Rf can often be taken as unity.
Section 10.2 Inlets 399
Figure 10.21
Slotted-drain inlet
Credit: McCuen, 1998. Reprinted by permission of Pearson Education, Inc., Upper Saddle River, NJ.
Q = CwLd3/2 (10.36)
Q = 0.8LW(2gd)1/2 (10.37)
Inlet locations based on the above criteria should be plotted on a plan view of the
roadway system. Topographic information and roadway profile drawings can then be
used to delineate the boundaries of the drainage basin contributing runoff to each
inlet. Estimates of design flows to each inlet are then computed for a selected design-
storm (see Table 2.2, page 37). The design flow in the approach gutter to each inlet
can be compared with the allowable gutter conveyance capacity to check that flow
depth and spread criteria are not violated. In all cases, one should strive to place inlets
using projections of land-parcel or lot lines so the inlets will not interfere with poten-
tial driveway locations. In sag vertical curves, such placement often requires adjust-
ment of roadway grades and/or vertical curve lengths.
Provided that the gutter capacity is not exceeded at an inlet, the selection of an inlet
type and the inlet design can proceed as outlined in the previous subsections. Designs
of sag inlets should be such that the entire design flow approaching the inlet is inter-
cepted. Conversely, inlets on continuous grades may be designed to intercept only a
fraction of the approaching flow, leaving the bypass flow to proceed to the next down-
stream inlet.
For any inlet, the total design flow consists of the runoff from its local drainage basin
plus any bypass flow from upstream inlets. However, if the bypass flow is large, or if
the times of concentration are significantly different for the bypass flow and the local
runoff to an inlet, then the total design discharge may be computed using the proce-
dure outlined by Guo (1997).
In the event that the discharge approaching an inlet is in excess of the conveyance
capacity of the gutter section, a trial-and-error approach is required to determine loca-
tions for additional inlets. These inlets are virtually always continuous grade, but are
usually necessary only on extended lengths of roadway where inlets are not already
required on the basis of the geometric criteria previously listed.
The trial-and-error approach entails selection of a trial inlet location. Based on the
trial location, drainage basins are again delineated and design discharges computed. A
comparison of the design discharges with allowable gutter capacities is then made to
check the adequacy of the selected inlet locations. Where possible, inlet positions
determined in this manner should coincide with locations where projections of lot or
parcel lines intersect the gutter. As noted above, this practice avoids potential con-
flicts with driveways or access roads.
In roadway sag locations, especially where there is no outlet for stormwater other than
through the storm sewer system, flanking inlets should be provided on either side of
the sag inlets. These inlets provide relief if the sag inlet becomes clogged. This prac-
tice should not be necessary in newly developed areas if proper attention has been
given to the major storm-drainage system, but it may be required in retrofit or rehabil-
itation projects. Flanking inlets should be designed to intercept all of the design flow
without violating allowable spread criteria if the sag inlets are completely clogged.
402 Gutter Flow and Inlet Design Chapter 10
Computer programs can be useful tools when deter- decides to locate inlet B so that its drainage area is
mining where inlets should be placed to meet design roughly half that of the original area. The flow
constraints such as allowable gutter spread and depth. approaching inlet B is calculated as 2.1 cfs.
A number of programs have been written to perform Because 2.1 cfs is less than 3.0 cfs (the maximum
these types of calculations, including the FlowMaster
allowable gutter capacity), the location of inlet B
software packaged with this book. Like the methods
appears acceptable from the standpoint of upstream
presented in this chapter, FlowMaster’s computational gutter capacity. The computer program or hand calcu-
methods are based on FHWA’s HEC-22 publication
lations can now be used to evaluate the performance
(Brown, Stein, and Warner, 2001).
of inlet B. It is determined that inlet B intercepts
Consider that an engineer is designing a subdivision 1.4 cfs and bypasses 0.7 cfs to inlet A. (The gutter
and plans to use curved-vane grate inlets measuring spread upstream of inlet B is found to be 7.0 ft.)
2 ft long by 2 ft wide as the standard inlet size. He or Summing the bypass flow from inlet B and the flow
she begins by proposing inlets at the minimum num- from inlet A’s additional contributing drainage area,
ber of locations using the guidelines provided in
the engineer determines that the flow approaching
Section 10.3. The next step is to evaluate the perfor-
inlet A will be 0.7 cfs + (4.0 cfs 2.1 cfs) = 2.6 cfs.
mance of the gutters and inlets, given these inlet loca- Because this flow is less than 3.0 cfs, the gutter spread
tions.
constraint is met. Inlet A is computed to intercept 1.6
The first inlet the engineer examines, inlet A, is the cfs and bypass 1.0 cfs. (The gutter spread immedi-
most-upstream inlet on a section of roadway. The ately upstream of the inlet is 7.6 ft.)
engineer delineates the contributing drainage area for
this inlet and calculates that the peak runoff flow rate
to the inlet for the design storm is 4.0 cfs.
This section of roadway has a 3-percent longitudinal
slope and a 2-percent cross slope. A composite gutter
section with a a 2-ft–wide depressed gutter having a
cross slope of 3-percent will be used on this project.
According to local regulations, the maximum amount
of gutter spread permitted for this roadway is 8 ft.
The engineer uses a computer program or hand calcu-
lations to determine whether the gutter can handle a
flow of 4.0 cfs without violating the maximum-spread
constraint. Assuming a spread of 8 ft and solving for
flow, the engineer determines that the maximum
capacity of this gutter is 3.0 cfs. The design of the remaining inlets in the subdivision
proceeds in a similar fashion, working downstream
Based on this calculation, the engineer knows that an
from the most upstream inlets, transferring bypass
additional inlet must intercept, at a minimum, (4.0 cfs
flows downstream, checking gutter spread, and add-
3.0 cfs) = 1.0 cfs.
ing or enlarging inlets as needed. Note that in this
simple example, the peak bypass flow and the peak
additional flow from the drainage area are assumed to
be additive. If the times of concentration for these
flows differed significantly, this would not be the
Anticipating that some of the flow from the additional case.
inlet (inlet B) will be bypassed to inlet A, the engineer
Section 10.4 Chapter Summary 403
intersections. Inlets are then added or resized as necessary to meet gutter-flow con-
straints. A computer program that performs gutter and inlet calculations can be of
great assistance in this trial-and-error process.
REFERENCES
American Society of Civil Engineers (ASCE). 1992. Design and Construction of Urban Storm Water Man-
agement Systems. New York: ASCE.
Brown, S. A., S. M. Stein, and J. C. Warner. 2001. Urban Drainage Design Manual. Hydraulic Engineering
Circular No. 22, Second Edition, FHWA-SA-96-078. Washington, D.C.: U.S. Department of Transpor-
tation.
Federal Highway Administration (FHWA). 1977. Bicycle Safe Grate Inlets Study: Vol. 1 and 2—Hydraulic
and Safety Characteristics of Selected Grate Inlets on Continuous Grade. FHWA-RD-77-44. Washing-
ton, D.C.: U.S. Department of Transportation.
Guo, J. C. Y. 1997. Street Hydraulics and Inlet Sizing Using the Computer Model UDINLET. Highlands
Ranch, Colorado: Water Resources Publications.
McCuen. 1998. Hydrologic Analysis and Design. Upper Saddle River, New Jersey: Pearson Education.
Young, G. K., S. E. Walker, and F. Chang. 1993. Design of Basic Bridge Deck Drainage. Hydraulic Engi-
neering Circular No. 21, GHWA-SA-92-010. Washington, D.C.: U.S. Department of Transportation.
PROBLEMS
10.1 A roadway gutter has a longitudinal slope of 0.01 and a cross slope of 0.02. Using a Manning’s n of
0.016, find:
a) the spread at a flow of 1.8 cfs
b) the gutter flow at a spread of 8.2 ft
10.2 A composite curb and gutter section is located on a roadway with a longitudinal slope of 0.01 and a
cross slope of 0.02. The gutter width is 2 ft, and the depression is 2 in. Assume Manning’s n = 0.016.
a) What is the gutter flow if the spread is 8.2 feet?
b) What is the spread if the flow is 4.2 cfs?
10.3 Find the interception capacity of a 610-mm–wide by 914-mm–long P-50 grate located in a compos-
ite gutter section having a longitudinal slope of 0.01 and a roadway cross-slope of 0.02. The width W
of the depressed portion of the gutter is 0.6 m, the depth of the depression a is 50 mm, and the gutter
cross slope is 0.103. The flow in the gutter is 0.065 m3/s, and Manning’s n is 0.016.
10.4 A uniform roadway gutter has a grated inlet in a depressed sag configuration. The flow is 0.20 m3/s,
and the depth of flow at the curb is 122 mm. Determine the length of 610-mm–wide, P-50-type grate
needed to intercept the flow in a sag configuration.
Problems 405
10.6 A 3.05-m curb-opening inlet is located on a grade with a slope of 0.01 and n = 0.012. The gutter sec-
tion is depressed, and its dimensions are:
• Sx = 0.03
• Swp = 0.05
• a = 51 mm
• W = 0.91 m
Determine the flow intercepted by the inlet if its efficiency if 50 percent. (Hint: use the included
FlowMaster software to graph efficiency versus discharge.)
Workers install a
section of concrete
pipe for a storm
sewer.