1. DESIGN CONDITIONS
Time Dry-bulb, ℉ Wet-bulb, ℉ Specific Humidity, Grain/lb
Outside 11-12 95 80.6 133.5664
Inside 10-11 75.2 66.2 81.1189
Difference 19.8 14.8 52.4475
2. TRANSMISSION LOSS (conductance, Q=U × A × ∆ ℉ ) with respect to exposure
a. Walls
BTU BTU
Overall Heat Transfer Coefficient , U
( 2 )
hr ∙ ft ∙ ℉
× Area ( ft 2) × Temperature Difference( ∆℉ )=
hr
North
BTU
2040.099
hr
East
BTU
1317.938
hr
South
BTU
2169.748
hr
BTU
West 569.296
hr
b. Floor 1042.274
BTU
hr
c. Roof or Ceiling
BTU
2260.551
hr
BTU
d. Others 166.858
hr
BTU
TOTAL 9566.764
hr
3. TRANSMISSION LOSS (Conductance, Q=U × A × ∆ ℉ ) with respect to exposure
e. Glass
BTU BTU
Overall Heat Transfer Coefficient , U
( 2
hr ∙ ft ∙ ℉ )
× Area ( ft 2) × Temperature Difference( ∆℉ )=
hr
North n/a
BTU
East 346.077
hr
South n/a
BTU
West 2206.03
hr
TOTAL 2552.107
BTU
hr
BTU
1342.702
hr
BTU
h. Door 985.308
hr
BTU
TOTAL 2328.01
hr
5. INDOOR LOADS
BTU
(People) Sensible No .of people× Sensible Heat Factor 2300
hr
BTU
(People) Latent No .of people× Latent Heat Factor 1900
hr
BTU BTU
Lightings/ Total Wattage ( lightings ) ×3.4 255
hr ∙Watts hr
BTU BTU
Appliances Total Wattage ( appliance ) × 3.4 3774
hr ∙ Watts hr
BTU
TOTAL 8229
hr
BTU
hr
TOTAL 4278.623
BTU
hr
BTU 1TR
26954.504 × =2.24 T O R ≈ 3 TR
TOTAL LOAD hr BTU
12000
hr
Computations:
North Wall
Q=
( 2.861 hrBTU
∙ ft ∙ ℉ )
2
2
( 294.681 ft ) (19.8 ℉ )
BTU
Q=2040.099
hr
East Wall
1 BTU
Q=
( 2.148 hr ∙ ft ∙ ℉ )
2
2
( 142.71 ft ) (19.8 ℉)
BTU
Q=1317.938
hr
South Wall
BTU
(
Q= 2.9 2
hr ∙ ft ∙ ℉)( 313.408 ft 2 ) (19.8 ℉)
BTU
Q=2169.748
hr
West Wall
BTU
Q=569.296
hr
Floor
Ceiling area=440.465 ft 2
1 BTU
Q=
( 4.226 hr ∙ ft ∙℉ )
2
2
( 440.465 ft ) (95−85 ℉ )
BTU
Q=1042.274
hr
Ceiling
1 BTU
Q=
( 3.858 hr∙ ft ∙ ℉
2 )
( 440.465 ft 2) ( 19.8℉ )
BTU
Q=2260.551
hr
North Wooden Door
Description U
1 3/8” Hollow core Flush Door 0.45
From Table 7-6a, MHVAC by Clifford
A = 18.727 ft 2
BTU
(
Q= 0.45 2
hr ∙ ft ∙ ℉)( 18.727 ft 2 ) (19.8 ℉ )
BTU
Q=166.858
hr
Description U Multiplier
¼” Flat Glass, Single Glass; No Shade, Summer 1.04
Metal Frame, Single Glass 1.1-1.0 (1.05 ave.)
From Table 7-5, MHVAC by Clifford
BTU
U = 1.04 x 1.05 = 1.092
hr ∙ ft 2 ∙ ℉
A = 102.029 ft 2
BTU
(
Q= 1.092 2
hr ∙ ft ∙℉ )
( 102.029 ft 2) (19.8℉ )
BTU
Q=2206.03
hr
Description U Multiplier
0.8
¼” Flat Glass, Single Glass; Indoor Shade, Summer
1
Metal Frame, Single Glass 1.1-1.0 (1.05 ave.)
From Table 7-5, MHVAC by Clifford
BTU
U = 0.81 x 1.05 = 0.8505
hr ∙ ft 2 ∙ ℉
A = 20.964 ft 2
BTU
(
Q= 0.8505 2
hr ∙ ft ∙ ℉ )
( 20.964 ft 2 ) (19.8 ℉ )
BTU
Q=346.077
hr
BTU
SHGFE =50
hr ∙ ft 2
BTU
SHGFW = 14
hr ∙ ft 2
Description SC
¼” Clear 0.94
From Table 9-10, MHVAC by Clifford
BTU
Q=1342.702
hr
Description SC
¼” Clear 0.94
From Table 9-10, MHVAC by Clifford
BTU
(
Q= 50
hr ∙ ft )
2
( 20.964 ft 2 ) (0.94)
BTU
Q=985.308
hr
INDOOR LOADS
People
Let:
BTU
Sensible heat of a person = 230
hr
BTU
Sensible heat of a person = 190
hr
BTU
Q sensible =10 ×230
hr
BTU
Q sensible =2300
hr
BTU
Q latent =10 ×190
hr
BTU
Qlatent =1900
hr
Lightings
BTU
Q=Total Wattage× 3.4
hr ∙ Watts
BTU
Q=75 Watts ×3.4
hr ∙ Watts
BTU
Q=255
hr
Appliances
BTU
Q=Total Wattage× 3.4
hr ∙ Watts
BTU
Q=1110 Watts ×3.4
hr ∙Watts
BTU
Q=3774
hr
VENTILATION/ FILTRATION/ AIR CHANGE
CFM
Q sensible =No. of people × 7.5 ×∆ T × 1.08
person
CFM
Q sensible =10 people ×7.5 × 19.8℉ ×1.08
person
BTU
Q sensible =1603.8
hr
CFM
Q latent =No. of people× 7.5 × Specific Humidity Difference ×0.68
person
CFM grain
Q latent =10 ×7.5 ×52.4475 × 0.68
person lb
BTU
Q latent =2674.823
hr