You are on page 1of 3

 Indoor loads

Sensible and latent heat gain thru people


QS = sensible heat gain thru people
QL = latent heat gain thru people
NP = number of occupants
NP = 10 persons
Solving the sensible heat, QS

230 BTU
hr . = sensible heat of occupants

230 BTU
QS = N P × hr .
230 BTU
= 10 persons × hr .
2300 BTU
QS = hr.
Solving for latent, QL

190 BTU
hr. = latent heat of occupants

190 BTU
= 10 persons × hr.
1900 BTU
QL = hr .
Lightings /
a. 5 bulbs = 15 watts per bulb × 5 = 75 watts

3. 4 BTU
QL = total wattage × hr .W
3. 4 BTU
QL = 75 watts × hr .W
BTU
QL = 255
hr

appliances, QW
a. 2 desktop = 200 watts per desktop × 2= 400 watts
b. 6 laptops = 65 watts per laptop × 6 = 390 watts
c. 2 water dispensers = 80 watts per dispenser × 2= 160 watts
d. 4 electric fans = 40 watts per electric fan × = 160 watts
total wattage = 1110 watts

3. 4 BTU
QW = total wattage × hr .W
3. 4 BTU
QW = 1110 watts × hr .W
BTU
QW = 3774
hr

 Ventilation

Specific humidity (SH),


Dry bulb, °F Wet bulb, °F grains of moisture Relative

( lb . of dry air ) humidity, RH

Outside 95 °F 80.6 °F 133.5664 54 %


Inside 75.2 °F 66.2 °F 81.1189 62.2 %

Solving for total cfm

7. 5cfm
total cfm = NP × occp.
7. 5cfm
total cfm = 10 × occp.
total cfm = 75 cfm

Dry bulb difference = (to - ti)


= 95 °F - 75.2 °F = 19.8 °F

Δ T(dry bulb) = 19.8 °F


Specific humidity difference = (SHo – SHi)

52. 4475 g
= 133.5664 - 81.1189 = lb.
52. 4475 g
Δ SH = lb.
Solving the sensible heat, QS

QS = total cfm × Δ T(dry bulb) × 1.08


= 75 cfm × 19.8 °F × 1.08

1603.8 BTU
QS = hr.
Solving for latent, QL

QL = total cfm × Δ SH × 0.68

52. 4475 g
= 75 cfm × lb. × 0.68

2674 .8225BTU
QL = hr.