Tag/Item Numbers:
GUK-VKM-732 GUK-VKM-731
• Page: 1
GOR-V-730/731/732
N2 COMPRESSORS
CERTIFIED-
Siemens Energy & Automation, Inc. Norwoo.d, Oh~o FOR
• COf~SIRUCTION
INDOC~ION MO~OR DA~A
S~ARTING DUTY :
Number of starts, coasting to rest between starts:
3 starts with motor initially at ambient temperature (cold) .
2 starts with motor at service factor operating temperature (hot) .
Cool~ng period, after either of above before making an additional start:
30 minutes, motor running at service factor load. --
20 minutes, motor runn~ng, equipment unloaded.
60 mdnutes, motor de-energized, coasted to rest and left idle.
RECO~NDED DETECTOR SET~INGS ..
ALABM Shutdown
Stator RTD'S : 155 deg C. 170 deg c.
Bea~ing RTD'S : 90 deg C. 95 deg C .
B~!~K__N_~.~~~a~.\TE 2. 8 mils 3.3 mils
• PROJI~CT----·--- EQUATE P..'FRASTRUCTt:R.E PIWJECT
Calculated Data 06-01-96 GRH
PL-\.'111'.--..·---·--- 770 !of T·D AIR SEMAAnON Pl.A.'IIT
l'l.A.'II'T LOCAnON.._ _ _ AL SIIIJAIBA. Kl..'WAIT
DESCR!mON.........._ .._ l'IITROOEN COMPR.ESSOit. PACICAGE
TAGN() _ _ _ _ Gl:K·Y·73017Jim2
AIR LIQUIDE P.O.-··--- ~1-1-3:~
FlUOil OA.'liEL P.O.~-- 61r..St-l-010t
1420100406
FLUOil OA.'IIEL CO!'<'TRACT • 6&1291
EQt:l~t~'TTAGl'IO............... _ _ _ _ _ __
1'01 :U>'I.fF'IT OF'U"RIPTION