Professional Documents
Culture Documents
~,~vllall
AND
BUII..DII IG
ELSEVIER Energy and Buildings 23 (1995) 73-81
Abstract
Local thermal discomfort in offices with displacement ventilation is investigated using computational fluid dynamics. The standard k-e
turbulence model is used for the prediction of indoor air flow patterns, temperature and moisture distributions, taking account of heat transfer
by conduction, convection and radiation. The thermal comfort level and draught risk are predicted by incorporating Fanger' s comfort equations
in the airflow model. It has been found that for sedentary occupants with summer clothing common complaints of discomfort in offices
ventilated with displacement systems result more often from an unsatisfactory thermal sensation level than from draught alone. It is shown
that thermal discomfort in the displacement-ventilated offices can be avoided by optimizing the supply air velocity and temperature. It is also
shown that optimal supply air conditions of a displacement system depend on the distance between the occupant and air diffuser.
ture and mean velocity but also by the turbulence of air flow ble steady-state flow, the time-averaged equations can be
and that an air flow with high turbulence causes more com- written in the following form:
plaints of draught than that with low turbulence for the same
air temperature and mean velocity. However, in displacement
ventilation the velocity and turbulence intensity of supply air -~x~(°U~4J) Ox~t Ox,]
are generally low. It may therefore be inferred that apart from
where ~bdenotes the dependent variable which may represent
draught there are other possible sources such as unacceptable
thermal sensation levels which could contribute to the thermal mean velocity component U~ in x~ direction, mean enthalpy
discomfort in offices ventilated with displacement systems. for an air mixture H, mean concentration of moisture in air
Fountain et al. [ 9 ] carried out laboratory tests on air move- C, turbulent kinetic energy k and dissipation rate of turbulent
kinetic energy e; p is the air density; F,~ is the diffusion
ment for cooling in warm isothermal environments and devel-
coefficient for variable ~b; S~ is the source term for variable
oped a model for predicting the percentage of satisfied people
in an office environment when locally controlled air move- ~. Details of the equations and the method of solution are
described elsewhere [ 16,17].
ment is available. They found that people preferred more air
movement than the draught limit proposed by Fanger et ai.
[ 8 ], especially at operative temperatures higher than 27 °C. 2.2. Thermal sensation
Their results appear to suggest that occupants are tolerant of
higher air velocity than the draught limits even in displace- Thermal sensation is evaluated in terms of the predicted
ment-ventilated offices.
mean vote (PMV) and the predicted percentage of dissatis-
Recently numerical methods have been used to predict the
fied (PPD) proposed by Fanger [ 18]. PMVis a function of
indoor environment of buildings with displacement ventila-
air velocity, air temperature, mean radiant temperature, water
tion. Koschenz [10], for example, used a zonal model to
vapour pressure of air, clothing thermal resistance and occu-
simulate the displacement ventilation and radiative cooling
pant's metabolic rate. PPD (%) is related to PMV by the
of a test room. Chen and van der Kooi [ 11 ], Jiang et al. [ ! 2]
following equation [6]:
and Shankar et al. [ 13] predicted thermal comfort and air
quality in offices with displacement ventilation using com- PPD= 100-95 e x p - (O.03353PMV*+O.2179PMV 2) (2)
putational fluid dynamics. Evaluations of different room air
distribution systems based on the predicted indoor thermal Although the PMV and PPD models are derived for pre-
comfort and air quality [ 14,15] show that a ventilation sys- dicting the thermal comfort for the body as a whole based on
tem resulting in displacement flow generally gives rise to a uniform thermal climate in the occupied zone of a room,
higher thermal efficiency and better air quality in the occupied these indices can be used to analyze the thermal variability
zone than traditional mixing systems. However, local discom- in the room for given environmental variables [ 18]. In this
fort may arise in offices with displacement ventilation investigation, the air velocity, temperature and water vapour
because of the inherently non-uniform distributions of air pressure (humidity) distributions in the room are calculated
temperature and velocity. from the air flow equations. The distribution of mean radiant
These experimental and numerical studies have shown the temperature is attained with the help of a radiation heat
improvement of the indoor environment of offices with dis- exchange model. The procedure to calculate the mean radiant
placement ventilation on the one hand and the potential of temperature at each grid point is as follows (see Ref. [ 17]
local thermal discomfort on the other hand. This study aims for details):
to investigate the causes of local thermal discomfort in such (i) calculate room surface temperature from the heat
offices by means of computational fluid dynamics in con- balance equations for conduction, convection and radiation;
junction with comfort models. (ii) calculate room surface radiosity based on the room
surface temperature and radiation shape factors;
(i ii) calculate six plane radiant temperatures for each rec-
2. Method tangular parallelepiped grid cell;
(iv) calculate the mean radiant temperature for the grid
This section presents the method for the numerical predic- cell; it is taken as a weighted mean of the plane radiant
tion of air flow patterns, thermal sensation and draught risk temperatures.
in rooms. Steps (i) and (ii) are performed within each of the iterations
for flow equations if radiation heat transfer between room
2.1. Airflow model surfaces takes place.
In addition to the calculation of thermal sensation, radiant
Air flow in rooms is generally turbulent. The model for temperature asymmetry for three orthogonal directions can
turbulent air flow is based on the equations for continuity, be obtained from the plane radiant temperatures. Local dis-
momentum, enthalpy and concentration together with the comfort due to an asymmetric radiation field such as cold or
equations for the k-e turbulence model. For an incompressi- hot windows can then be evaluated.
G. Gan / Energy and Buildings 23 (1995) 73--81 75
2.3. Draught risk however, for the purpose of simulation, it is assumed that the
window is closed and the room is ventilated by a displacement
The draught risk is assessed according to the draught model ventilation system in the summer season. This is achieved by
developed by Fanger et al. [8]. In the draught model, the introducing cool air horizontally from a diffuser installed on
sensation of draught is associated with air temperature, mean one of the walls. The effective area of the diffuser, unless
velocity and turbulence intensity as follows: specified otherwise, is taken to be 0.12 m 2. The room air exits
for V> 0.05 m/s through an extract duct installed on the rear wall (opposite
to the curtain wall). No air is recirculated since in normal
P D = ( 3 . 1 4 3 + O . 3 6 9 6 V ~ ; ~ ) ( 3 4 - T ) ( V - O . 0 5 ) °6223 (3)
practice displacement ventilation is applied as a full fresh air
for V<0.05 m/s system [2]. As the incoming air stream for displacement
ventilation is usually characterized by low velocities and tur-
PD = 0 bulence levels, the supply air velocity of 0.2 m/s (air flow
where P D is the percentage of dissatisfied due to draught rate of 24 I/s) is designated as a standard value and the
(%); Tis the air temperature (°C); Vis the mean air velocity turbulence intensity of supply air is taken to be 10%. The
(m/s); Tu is the turbulence intensity (%), defined as the supply air temperature ranges from 18 to 22 °(2 and relative
standard deviation divided by the mean air velocity and cal- humidity varies between 62% and 80% so that the supply air
culated using is at a constant dew point. The outdoor air temperature is
assumed 30 °1:2and the wind speed 3 m/s normal to the south
Tu = ~/2k X 100 (4) facade, which are required for calculating the room surface
V temperature based on the amount of fabric heat
transfer.
where k is the turbulent ki,netic energy (m2/s2).
The office is occupied by one person, seated by a desk and
Hence, the distribution of PD in the space can be obtained
1.2 m away from the window (calculated from the mid-point
from the solution of the air flow equations.
of the occupant) as a standard position for simulation. The
simulated occupant generates metabolic heat of 70 W / ( m 2
skin area) of which 30% is considered to be latent heat. The
3. Simulation moisture production rate by the occupant is estimated from
the amount of latent heat and this is assumed to be a source
Predictions of thermal sensation and draught risk were at a grid point near the head level. The occupant wears
carded out for a standard low energy office room [ 19]. clothes equivalent to a clothing level of 0.5 clo ( 1.0 clo =
0.155 m2K/W).
3.1. Test room
3.3. Results
The room has dimensions of 4.7 m long, 3.65 m wide and
2.5 m ceiling height (see Fig. 1(a)). It consists of one exter- In all 14 simulations were performed for different supply
nal wall and five internal walls including the floor and ceiling. air conditions. The conditions of supply air and locations of
The external wall is insulated to a U value (overall thermal the air diffuser and occupant are given in Table I. Figs. 1 and
transmission coefficient) of 0.22 W / m 2 K. The U value for 2 show the predicted air flow patterns, temperature, thermal
internal walls is 1.70 W / m 2 K. The external wall has a double- sensation and draught risk on a vertical plane in the office for
glazed window of width 2.95 m and height 1.3 m with a U two of the cases, one with air supplied from the rear wall near
value of 2.9 W / m 2 K. In winter the window is locked and the floor at a velocity of 0.2 m/s and a temperature of 18 °C
the room is heated with a recirculating mechanical heating (Case l) and the other for the diffuser under the window
and ventilation system. In warm seasons, large areas of south- with the same supply air velocity and temperature (Case 6).
facing glazing is protected from solar radiation by means of As indicated by the velocity vectors in the figures, the supply
computer controlled roller blinds fitted outside the office. air spreads over the floor and after reaching the occupant air
then moves upwards due to thermal buoyancy. Room air is
3.2. Assumptions nearly stagnant (air velocity <0.05 m/s) in the occupied
zone (from the floor to 1.8 m high) except for the areas in
It is assumed that the room is located in the south facade the supply air stream and in the vicinity of thermal buoyancy
of the office building and surrounded by identical rooms. sources (occupant and window). The vertical temperature
Hence, heat transfer takes place through the external curtain stratification can be observed in Figs. 1 (b) and 2(b) but the
wall to or from the room but there is no heat gain/loss through stratification is not large because the internal heat source
the internal walls. All the room surfaces are assumed to be (only one occupant's metabolic heat) and the heat gain
grey and have an emissivity of 0.9. The building is designed through the window with external shading are small. The
to take maximum advantage of natural lighting and ventila- mean radiant temperature is high near the window. Apart
tion in summer by unlocking the windows. In this study, from this area, the variation in the mean radiant temperature
76 G. Gan / Energy and Buildings 23 (1995) 73--81
Wir'~dow~," , ~ " T ~ , ~ . . . - ~
~ - ~ . ~ , ~ , .~-.~,,~ ~>-~,~,
(a) Air vMoclty on three vertlcld secUonl (b) Isothmma ('C) on • v~UCed plane (c) Melm rIdInt temper•lure (*C) on • vertJcII pllmi
,e
(d) Iso-PMVs on I vertical plane (e) Iso-PPD8 1%) on a vertical plane If) IIO-PD* (%1 on • vertical p~ane
Fig. 1. Predicted air flow pattern, temperature,thermal sensation and draughtrisk in the office with air diffuser on the rearwall.
Sc :h wOI •
E: I~ct ' u ~, a. t, ~.
',
i , J
North woll
(I) /dr vek~ty on three vertical sections (b) IIotherm~ ('C) On -, vertlc~ I~lme (c) Mean radiant temperature ('C) on * vectlc=l i~me
u ~ a,
(d) IIo-PMVI On • vertical plane (I) Iso-PPDI (%) on • vertical plane If) Iso-PDs I%1 on • v•rUcll plane
Fig. 2. Predicted air flow patterns, temperature,thermalsensation and draughtrisk in the office with air diffuser on the curtainwall.
with space is small (Figs. l (c) and 2 ( c ) ) largely due to the between the diffuser and occupant. This is discussed in detail
external shading. The room thermal environment is in general below.
acceptable. However, the area near the window is warm
whereas the area along the supply air stream is cold (seen
from the PMV contours in Figs. 1 (d) and 2(d) ); the potential
draught risk also exists along the air stream (Figs. 1 (f) and 4. Discussion
2(f)).
Between these two cases, Case 1 produces a better thermal According to the ISO comfort standard [6], P P D should
environment for the occupant since there is no thermal dis- be lower than 10% for thermal comfort. The comfort limit
comfort close to the occupant with regard to thermal sensation for draught ( P D ) is 15% [5]. In order to analyze the causes
or draught. In Case 6 some discomfort due to either cold of thermal discomfort in the room, two levels of comfort
thermal sensation or draught or both around the lower part of requirements ( 10% and 15%) for P P D and P D are adopted
the occupant is predicted because of the reduced distance for defining the following terms:
G. Gan / Energy and Buildings 23 (1995) 73--81 77
For a given supply air temperature, e.g. 18 °C, the likelihood 120
of local discomfort due to either cold thermal sensation or -----o---- Nppdl0
100
draught increases with the increase of air velocity. However,
the proportion of the discomfort due to draught decreases as
the supply air velocity increases (see also Table 2 for Cases
4-8). For P P D = P D = 10%, the risk of draught is generally
much smaller than that of cold thermal sensation except for
a supply air velocity of 0.1 m/s, i.e. Np--b--~to>> Nh--Blo. For 40 ."'
PPD = P D = 15%, the draught risk is almost negligible com-
20 ~ _ . . . . . a - - "
pared to the cold thermal discomfort, i.e. N-f-B~s/N-F~15 = O.
Moreover, the mean value for the discomfort due to draught 0 I I I
exceeding the requirement is generally smaller than the cor- O. 10 0.15 0.20 0.25 0.30
responding value for the cold thermal sensation, i.e. Air velocity 0n/s)
PPDto > PDto and PPD~5 > PD~5. In other words, when there Fig. 3. Effect of supply air velocity on the variation of discomfort grid points.
is a risk of draught, the risk of the local discomfort associated
with cold thermal sensation will be greater. Therefore, cold air velocity than is draught at such low supply air tempera-
thermal sensation is the principal cause of local thermal dis- tures. The effect of air velocity and temperature on P P D and
comfort in offices with displacement ventilation at low supply PD is illustrated in Fig. 4. This is produced using the com-
air temperatures. In order to lessen the risk of draught, empha- bination of the following predicted environmental data for
sis should be placed on securing thermal comfort for all parts the area surrounding the legs and feet:
of a human body.
The reason for the above phenomena can be explained by turbulence intensity = 2 0 % ;
the fact that thermal sensation is in theory more sensitive to vapour pressure = 1700 Pa;
Table 2
Predicted thermal discomfort around the occupant's legs and feet
Note: total number of grid points around the legs and feet= 144.
G. Gan / Energy and Buildings 23 (1995) 73-81 79
ity 0.2 m/s thermal discomfort is largely due to cold feeling rate is increased appropriately by using a diffuser with a larger
of thermal sensation at supply air temperatures below 20 °C opening for example.
whereas the cold (not warm) discomfort is predominantly
caused by draught above this temperature level.
5. Conclusions
4.4. Implications
A method for predicting the thermal comfort and draught
According to the above analysis, the frequently reported risk in offices is described. The numerical predictions have
complaints of draught at low temperatures could be the result shown that common complaints of local thermal discomfort
of confusion of thermal perception in real life between ther- in offices with low turbulent air flow such as displacement
mal sensation and draught. Besides, the draught risk model ventilation often result from unsatisfactory thermal sensation
is considered to overestimate the draught at foot level [8] rather than draught itself or alone. This is in theory true
because the feet and legs are relatively insensitive to draught especially at the lower end of commonly quoted supply air
[20]. Furthermore, the draught risk limit is too restrictive on temperatures between 18 and 20 °C.
the air movement preference [9]. The implications are that It is shown that decreasing supply air velocity or increasing
the draught risk would be smaller and the cold discomfort supply air temperature reduces the potential cold thermal
associated with thermal sensation could even be more signif- discomfort. It is also shown that optimal supply air conditions
icant than predicted. of a displacement system vary with the distance between the
In the cases investigated, at supply air velocity 0.2 m/s occupant and air diffuser besides cooling load and load dis-
and forPD = 15%, out of 144 points the number of grid points tribution. The numerical method can be used for optimizing
for thermal discomfort due to draught is from 17 at supply the supply air conditions.
air temperature 18 °C to 4 at 22 °C. If the cold discomfort This study has highlighted the importance of accurate cal-
associated with thermal sensation can be eliminated by culation of mean radiant temperature for predicting thermal
increasing the local radiant temperature for example, the comfort levels and for identifying the principal cause of local
draught feeling could be reduced considerably, say at the thermal discomfort between cold thermal sensation and
standard supply air temperature (18 °C) and velocity (0.2 draught so that appropriate preventative measures can be
m/s), from 59 grid points (the cold thermal sensation which taken.
would have been misinterpreted as draught) to 17 (the pre- It will be very useful to conduct laboratory or field tests in
dicted draught risk) or even less (because of overestimation displacement-ventilated buildings on the reduction of draught
of the draught risk at foot level). Fanger [ 18 ] considered the complaints by avoiding the local discomfort due to cold ther-
sensation of draught to be a function of the general thermal mal sensation using a radiant temperature control system for
state of the human body. Therefore, if certain measures are instance.
taken so that the thermal sensation at foot level is at or above
the thermal neutrality, the local cooling due to air movement
could be felt as a pleasant stimulus rather than the unpleasant
References
draught.
One of such measures is the optimization of supply air
[ 1] P. Haddlesey, An upward trend, HAC (July) (1993) 14-17.
conditions. Even at the distance between the diffuser and
[2] P. Jackman, Displacement ventilation, Proc. CIBSE National Conf.,
occupant of 1.2 m, the cold discomfort can be avoided by Canterbury, UK, 7-9Apr. 1991, pp. 364-380.
decreasing the supply air velocity and/or increasing the sup- [3] M.E.A. Holmgren, Displacement ventilation in a Swedish foundry, in
ply air temperature. For example, at supply air velocity 0.1 R.T. Hughes, H.D. Goodfellow and G.S. Rajhans (eds.), Ventilation
m / s and air temperature 20 °C ( Case 14), the discomfort due "91: Proc. 3rd Int. Symp. Ventilation for Contaminant Control,
to cold thermal sensation is eliminated and the draught risk Cincinnati, OH, USA, 16-20 Sept. 1991, ACGIH, Cincinnati, OH,
1993, pp. 405-412.
is reduced to 5 grid points. The draught level at all these five [4] D.P. Wyon and M. Sandberg, Thermal manikin prediction of
grid points is only slightly above 10% with a maximum of discomfort due to displacement ventilation, ASHRAE Trans., 96 ( 1)
12.6%. If one takes 15% as the comfort limit for draught, (1990) 67-75.
then the local thermal discomfort for cold thermal sensation [5] A.K. Melikov, G. Langkilde and B. Derbiszewski, Airflow
characteristics in the occupied zone of rooms with displacement
and draught can be ignored. In fact, at these supply air tem-
ventiinfion, ASHRAE Trans., 96 (1) (1990) 555-563.
perature, mean velocity and turbulence, the predicted draught [6] Moderate thermal environments - - determination of PMV and PPD
risk in front of the diffuser is 7.3%. The draught near the indices and specification of the conditions for thermal comfort, ISO
occupant is mainly due to buoyancy-induced air movement 7730, International Standards Organisation, Geneva, Switzerland,
which causes velocity to exceed that of supply air 0.1 m/s. 1984.
[7l P.O. Fnnger and N.K. Christenscn, Perception of draught in ventilated
Although further increasing the supply air temperature can spaces, Ergonomics, 29 (2) (1986) 215-235.
reduce the draught to within the 10% limit, it may incur warm [8l P.O. Fanger, A.K. Melikov, H. Hanzawa and J. Ring, Air turbulence
discomfort for thermal sensation unless the supply air flow and sensation of&aught, Energy Build, 12 (1988) 21-39.
G. Gan / Energy and Buildings 23 (1995) 73-81 81
[9] M. Fountain, E. Arens, R. de Dear, F. Bauman and K. Miura, Locally [ 14] Q. Chen, T.G. Hoornstra and J. van der Kooi, Energy analysis of
controlled air movement pnfferred in warm isothermal environemnts, buildings with different air supply and exhaust systems, ASHRAE
ASHRAE Trans., 100 (2) (1994). Trans., 96(1) (1990) 344-356.
[ 10] M. Koschenz, Simulation of displacement ventilation and radiative [15]G. Gan, Evaluation of room air distribution systems using
cooling, Energy Impact of Ventilation and Air Infiltration: Proc. 14th computational fluid dynamics, Energy and Buildings, 23 (1995) 83-
AIVC Conference, Copenhagen, Denmark, 21-23 Sept. 1993, pp. 131- 93.
139. [ 16] H.B. Awbi and G. Gan, Predicting air flow and thermal comfort in
[ 11] Q. Chen and J. van der Kooi, A methodology for indoor airflow offices, ASHRAEJ., 36 (2) (1994) 17-21.
computations and energy analysis for a displacement ventilation [17] G. Gan, Numerical method for a full assessment of indoor thermal
system, Energy Build., 14 (4) (1990) 259-271. comfort, lndoor Air, 4 (1994) 154-168.
[12] Z. Jiang, Q. Chen and A. Moser, Comparison of displacement and [18] P.O. Fanger, Thermal C o m f o r t - Analysis and Applications in
mixing diffusers, indoorAi,,, 2 (1992) 168-179. Environmental Engineering, Robert E. Krieger, Florida, 1982.
[ 13] V. Shankar, L. Davidson and E. Olsson, Ventilation by displacement: [ 19] D.J. Leighton and A.A. Pinney, A set of standard office descriptions
calculation of the flow in ~ertical plumes, Roomvent '92: Proc. 3rd for use in modelling studies, BEPAC Teclt Note 90/5, Building
Int. Conf. Air Distribution in Rooms, Aalborg, Denmark, 2-4 Sept. Environmental Performance Analysis Club, UK, 1990.
1992, Vol. 1, pp. 59-73. [20] D.A. Mclntyre, Indoor Climate, Applied Science, London, 1980.