Professional Documents
Culture Documents
'Departlnent of Building Technology and Structural Engineering, Aalborg University, Sohngaardsholmsvej 57, DK-9000 Aalborg, Denmark.
'Fax: +45 98 1 4 82 43. E.mail: iGhbkcivil.nuc.dk.
Brohus and Nielsen
158
Personal Exposure in Displacement Ventilated Rooms
Two kinds of contaminant source are examined, a pas- The local ventilation index, E ~ is
, defined as
sive source and a non-passive source. The non-passive
source is simulated by nitrous oxide injected through an
upward pointing tube, 0 0.01 m. The tube is located
above a heat source at an elevation of 2 m (see Figure 4). where cp is the concentration at a point in the room.
The passive contaminant source is simulated by a neu- A new ventilation effectiveness is defined, the per-
tral density mixture of nitrous oxide and helium injected sonal exposure index, designated E,
through a porous foam rubber ball, 0 0.1 m.
The tracer gas concentration is measured by photo- & = - cR
ce
acoustic spectroscopy (uncertainty f2%). The tempera-
tures are measured by thermocouples, type k (uncer- where c, is the concentration of inhaled contaminant.
tainty +0.2"C). The velocities are measured by tempera- The personal exposure index expresses the effectiveness
ture-compensated hot sphere anemometers (uncer- actually experienced by a person in the ventilated room.
tainty f0.02 m/s). The new quantity and its use is discussed in more detail
below.
Equations (1)to (3) assume that the supply air is un-
Definitions contaminated.
Ventilation Effectiveness
To describe the efficiency of an air distribution system, Concentration, Exposure and Dose
different quantities are commonly used. The ventilation Before the topic "personal exposure" is further dis-
effectiveness in the occupied zone, E,, is given by cussed, it may be convenient to clarify the differences
between the concepts of concentration, exposure and
dose.
Exposure requires, strictly speaking, the simultane-
where cR is the concentration in the return opening and ous occurrence of two events: a pollutant concentration
c,, is the mean concentration in the occupied zone. In at a particular place and time, and the presence of a per-
this paper the occupied zone is defined as the area up to son at that place and time (Sexton and Ryan, 1988).Ex-
1.8 m above floor level. pressed in another way, exposure is defined as the event
::
m
41 +-
1
m
.-
1.5 - w
r
. A
.B
.- A'
00.0 II
0.2 0.4
Temperature Velocity
Fig. 3 Temperature and velocity profiles. The measurements correspond to the concentration measurements in Figure 4. The velocity profiles are
measured 4 m from the inlet device at the same location as the thermal manikin. q is the airflow rate, @ is the heat load, To is the inlet temperature
and T, the return temperature. ybtis the stratification height.
Please note the different ordinate axis heights.
Case A: ys,=l.OOm, q=145 m3/h (0.8 h-'), @= 771 W, To = 14.7"C, TR=24.4"C
Case B: yS,=1.35m,q=290 m3/h (1.5 h-'), @=376W, To= 17.6"C, TR=22.6"C
Case C: y,,=2.25 m, q=395 m3/h (2.1 h-'), @= 781 W, To= 15.8"C, TR=23.4"C.
159
Brohus and Nielsen
‘I
c, = 0.47 4 c, = 0.57
ured for the three stratification A-Sitting A-Standing
heights 1.00 m (A), 1.35 m (B) and E,, = 1.44 E,, = 1.54
2.25 m (C) for seated (left) and 3
3 E, = 2.13 t, = 1.75
standing (right) manikin. Exposure,
ce, ventilation effectiveness in the
i
+
occupied zone, E,, and personal ex- 1
m rn
B-Sitting 0.50 B-Standing
‘1
31
C, =
eac = 1.65
E,
0.28
= 3.57
C, =
E,, = 1 .84
Concentration Concentration
m m
c. = 0.06 C-Standing
C-Sitting
c,, = 12.41 cOc = 12.08
3- E, = 16.67
1 ic
c/cR
~-1
0
0.0 05 10 1.5
Concentration Co nc ent r a t i o n
during which a person comes into contact with a pollut- varies due to different activity levels (Brohus and
ant. Nielsen, 1994b).
Dose occurs when the pollutant actually crosses The concentration of inhaled contaminant, c , corre-
the physical boundary of a person. Consequently, sponds to the exposure of a person. It represents the
there can be an exposure without a dose but there event during which a person - here, in the shape of a
cannot be a dose without an exposure (Ott, 1985). This thermal manikin - is in contact with a pollutant. Subse-
implies that persons exposed to the same level may quently c, is designated ”exposure” as well as ”concen-
receive different doses if the pulmonary ventilation tration of inhaled contaminant”.
160
Personal Exposure in Displacement Ventilated Rooms
To compare the exposure and the concentration, cp, out by Holmberg et al. (1990) and Stymne et al. (1991),
measured at a "neutral" point at the breathing zone among others. This means that the concentration of in-
height, both quantities should in theory be measured at haled contaminant is smaller than the corresponding
the same location, but in the case of cp without the local concentration at the same height at a "neutral" place in
influence of the person (movements, convective bound- the room. In this case the entrainment provides a better
ary layer flow, etc.). In this way the difference between indoor air quality in the displacement ventilated room
E, and E~ is due solely to the person's presence. The im- than in a room with mixing ventilation.
portance of making this distinction will appear clearly The figure shows also that the effectiveness in the oc-
in the following discussion. cupied zone is higher than in the case of mixing ventila-
In practice, cp is measured at the breathing zone tion, where E, approaches 1 in the ideal case. As ex-
height outside the thermal boundary layer some dis- pected, the effectiveness increases with increasing strat-
tance away from the person. Alternatively, the person in ification height. In all cases the personal exposure in-
question is temporarily moved while measuring cp at dex, E , exceeds E,,, indicating that the quality of the in-
the point of interest. haled air exceeds the mean indoor air quality in the oc-
cupied zone.
Results and Discussion
Exposure in Proportion to Stratification Height Personal Exposure Model for a Displacement Venti-
Exposure measurements are carried out with respira- lated Room
tion through the mouth. In the present measurements The exposure depends among other things on the con-
no significant difference between respiration through centration in the lower zone of the room. At the same
the mouth and respiration through the nose was found. stratification height this concentration may vary from
The present measurements were performed under case to case, depending on the inlet device, the air tem-
steady-state conditions. perature differences, the heat and contaminant source
In Figure 4 the exposure of a seated and a standing configuration, room surface temperatures, etc. To be
manikin is shown. The measurements are performed at able to take the concentration in the lower zone into ac-
three different stratification heights, yst. The corre- count, a new quantity is defined: the effectiveness of en-
sponding temperature and velocity profiles are found in trainment in the human boundary layer, designated q,
Figure 3. Supply flow rates, supply temperatures and cp-c
return temperatures are also shown in Figure 3. q,= cp-ce
f (4)
Figure 4 shows the dimensionless concentration pro-
file and the exposure at the three stratification heights where cf is the concentration at the floor that typically
1.00 m, 1.35 m and 2.25 m. The exposure, ce, the effec- corresponds to the concentration in the lower, cleaner
tiveness in the occupied zone, E, and the personal ex- zone of the displacement ventilated room (see Figure 5).
posure index, E , for the three cases are shown. In all The effectiveness of entrainment in the human
three cases the thermal manikin (approximately 75 W), boundary layer, q, expresses the ability to supply (fresh)
the two person simulators (2x100W) and the point heat air from the floor area to the breathing zone. It expresses
source (100 W or 500 W) constitute the heat load in the the utilized fraction (c,-c,) of the possible concentration
room. difference (cp-cf).
Due to the uninsulated walls there is a slight heat When q,=l, all the inhaled air comes from the lower
transfer between the room and the surrounding labora- zone and c, equals the concentration at the floor, cf
:eF
tory. The difference between the mean room air temper-
ature and the mean surface temperature is less than
t
0.5"C. Nevertheless, due to the temperature gradient,
there will be a heat gain in the lower part of the room
and a heat loss in the upper part. At the walls this
causes a slight upward convective flow on the lower
surfaces and a slight downward convective flow on the Y st cR
161
Brohus and Nielsen
rl. ystz?d+
"le
1 .o
When qe=O the exposure equals the concentration cp at height of the breathing zone, ye, the dimensionless
the breathing zone height, i.e. no particular effect be- height yst/y, may be used. This quantity attains the
cause of the convective transport in the human bound- value from 0 to 1 when the stratification height in-
ary layer (see Figure 6). creases from the floor to the breathing zone height,
In the case of complete mixing, as well as in displace- which is the range of interest in this context. Conse-
ment ventilation with a stratification height located quently, if the effectiveness of entrainment in the hu-
above the breathing zone, q, is not defined. In these man boundary layer is expressed as a function of yst/ye,
cases c, equals the homogeneous concentration in the we may expect that q, ranges from 0 to 1when yst/yein-
room or the concentration in the lower zone, respec- creases from 0 to 1 (see Figure 6). In Figure 7 the effec-
tively. This implies that q,=1 for c,=cf tiveness of entrainment in the human boundary layer
One advantage of using qeis the independence of the versus yst/y, is plotted.
concentration in the lower zone that may vary in differ- The results shown in Figure 7 come from q, calcu-
ent cases. This enables and improves the comparison of lated from the measurements presented in Figure 4 and
results from different test rooms and different experi- corresponding results from different references. Here,
mental set-ups. the effectiveness and the dimensionless height are cal-
From the results in Figure 4, qe is calculated for Case culated on the basis of the various full-scale measure-
A-Seated (0.91), Case A-Standing (0.66) and Case B- ments performed in displacement ventilated rooms.
Standing (0.78), where it is defined. It illustrates the ex- Holmberg et al. (1990) have made measurements with
tent to which the inhaled air is supplied from the lower tracer gas and paraffin oil particles (<2 pm) in a room
and cleaner zone. In Case A-Seated, almost all air comes with heated cylinders as well as persons. The measure-
from the lower zone, while in Case A-Standing, only ments were performed at different stratification heights
somewhat more than half of the air arises from the for persons sitting perfectly still and for seated persons
lower zone. The reason why q, is lower in the Case A- with natural movements. Kruhne and Fitzner (1994)
Standing is that the breathing zone is located at a higher performed measurements at different stratification
level. This implies that more contaminated air is en- heights with a heated cylinder. Mattsson and Sandberg
trained in the boundary layer before it reaches the (1994) performed measurements with a heated cylinder
breathing zone where it is inhaled. continuously moved back-and-forth as well as standing
If c, is expressed by means of the new quantity, we still. Here, the results from the "standing still" situation
get the following equation are used. Mundt (1994) has made measurements in a
ce= Cp-Tlr ( c p - Cf) (5) displacement ventilated room with a person sitting and
a person walking around, respectively. Nickel (1990)
i.e. the concentration of inhaled contaminant is ex- performed measurements with a heated cylinder.
pressed as a function of the concentration at the breath- Although different "models" of a person are used in
ing zone height unaffected by a person present (c,), the different experimental set-ups, the quantity q, and the
concentration at the floor, and the effectiveness of en- relation yst/yeseem to establish a way of expressing the
trainment in the human boundary layer. If q, is known, various results more generally.
equation (5) can be used to estimate the personal expo- If we make a linear equation fit on the plot in Figure 7
sure in a displacement ventilated room. to obtain the coefficients of the equation q,=A+B (yst/
In the expression for q, the stratification height must ye), we find that A=0.22 and B=0.73 with a coefficient of
be considered due to the significant influence of this pa- determination R2=0.58. This reveals that A is close to
rameter. If we furthermore want to incorporate the zero and that B is close to one.
162
Personal Exposure in Displacement Ventilated Rooms
With a power equation fit, the following relation If, for instance, a person is sitting (or standing) very
qe=C(y,,/ye)D is obtained. Here the coefficients C=0.95 close to the edge of a table, the thermal boundary layer
and D=0.75 are found with R2=0.62. is locally interrupted and the convective transport of air
These results suggest an almost linear relationship from below the table is significantly limited. The effect
between q, and yst/yewith a starting point close to origo of this limitation depends to a great extent on the hori-
and with the effectiveness of entrainment in the human zontal distance between the person and the obstacle. If
boundary layer approaching 1when the relative height the distance between the table and the person exceeds
approaches 1. the boundary layer thickness, there will presumably be
For practical engineering purposes and without con- no reduction in the entrainment and transport in the
siderable loss of accuracy, one may use the simple rela- human boundary layer. According to Homma and Yaki-
tion yama (1988), the thickness of the thermal boundary
layer in front of the chest of a standing person is 0.07-
0.15 m. Although the boundary layer thickness in a
seated position is greater, the order of magnitude sug-
By inserting the above expression in equation (5) we gests that even relatively small gaps between the person
obtain a model for the personal exposure in a displace- and the table will enable convective mass transfer to
ment ventilated room. take place. More research on this subject is needed.
This exposure model may also be obtained in another
way by means of a zonal model approach. If it is as- The Effect of Movements on Personal Exposure
sumed that the concentration of inhaled contaminant is The measurements shown in Figure 7 represent mainly
a mixture of the concentration in the lower, cleaner part cases where the model of a person is sedentary or stand-
of the displacement ventilated room and the upper, ing still. This fact raises the question as to the effect of
more contaminated part, we may get the following ex- movement on personal exposure.
pression if the two parts of the room are assumed to One extreme is a sedentary person or a person stand-
contribute with an amount proportional to the height ing still. Here, equation (8) provides a reasonable model
occupied by the person, i.e. for personal exposure in a displacement ventilated
room. The second extreme is the case of a person walk-
(7) ing quickly through a ventilated room. Here, the con-
centration of inhaled contaminant, cc, obviously ap-
Hence, proaches the neutral concentration in the breathing
zone height, cpr due to the considerable horizontal ve-
locity generated around the breathing zone. This case
corresponds to q,=O. The actual case may be found
Comparing equations (5) and (8) reveals that q, is ex- somewhere between the two situations, depending on
pressed as yst/yewhich in fact is the approximate rela- several parameters, for example the type of work, activ-
tion (6) found empirically from Figure 7. ity level, etc.
Further analysis of the human boundary layer may This point is supported by measurements of Holm-
show a nonlinear dependence of qcon y,,/ y, and relations berg et al. (1990) where q, changed from 0.94 to 0.66
where more parameters are considered may be found, when the persons present changed from motionless to
but still the above expression may serve as a reasonable natural motion in a seated position.
approximation for practical engineering use in the case of Measurements of Mattsson and Sandberg (1994)with
an exposed subject in a displacement ventilated room. a moving heated cylinder may serve as another illustra-
One limitation of the model is the effect of persons' tion. From these measurements the effectiveness qe is
movements. Since the basic results arise mainly from calculated and shown in Figure 8 for three different ve-
cases where a "still" model of a person is used, the locities of the heated cylinder continuously moved
equation (8) is not valid when the person is making vio- back-and-forth in a displacement ventilated room. Even
lent movements or when the person is walking fast though Figure 8 is an example involving only one
through the ventilated room. This topic is discussed in heated cylinder in "systematic motions" at one stratifi-
greater detail below. cation height, it clearly illustrates that the effectiveness,
Another limitation may be the influence of an obsta- q, decreases when the movements increase as men-
cle in front of the person. If the boundary layer is dis- tioned above.
turbed or partially destroyed, the effect of entrainment Measurements and smoke tests with a thermal mani-
and transport is obviously reduced. kin in a wind channel confirm that the thermal bound-
163
Brohus and Nielsen
lm, 3m
41
Fig. 8 q, as a function of the velocity relative to a moving cylinder. 3!
Measurements from Mattsson and Sandberg (1994) with a heated cyl-
inder continuously moved back-and-forth in a displacement venti-
lated room.
164
Personal Exposure in Displacement Ventilated Rooms
above, etc. 2o 1
To illustrate the route of the contaminant in the
boundary layer, measurements are performed on the
Chest conc
contaminant concentration at the chest and the contam-
: Back conc.
inant concentration at the back in proportion to the
point source height (see Figure 11).The conditions are
otherwise the same as in Figure 10, Case 2.
The concentration at the two points in Figure 11 are C/CR
7
measured at the same height in the room. If the manikin 15
Concentration
was not present they would be approximately the same,
while in the actual case there is a significant difference. Fig. 11Concentrations measured at the chest (0)and at the back (k) at
a distance of 0.3 m from a virtual point between the ears of the person.
What makes the difference is the presence of a person The concentrations are found as a function of the point contaminant
and the entrainment and transport of the contaminant source height. The conditions are otherwise the same as in Figure 10,
as well as the fresh air in the boundary layer. Case 2.
165
Brohus and Nielsen
Ee
A personal exposure model is proposed. The model
takes the concentration gradient and the influence of
0 the human thermal boundary layer into account.
0
Entrainment of air in the human boundary layer is
'Oi usually an advantage but measurements show also the
0 possible disadvantage when passive contaminant
8 0 sources are present. In this case the convective currents
0
around the person transport contaminated air to the
breathing zone, giving rise to increased exposure.
Two new quantities are defined: the personal expo-
0.5
I
1.o
Ysc/Y. sure index, E, which expresses the concentration of in-
Fig. 12 Personal exposure index, E , as a function of the dimensionless
haled contaminant relative to the return concentration;
height, yst/y,. The results correspond to those shown in Figure 7. The and the effectiveness of entrainment in the human
personal exposure index in the case of complete mixing is indicated boundary layer, q,, which expresses the ability to sup-
by the dotted line, i.e. ~ , = l .
ply (fresh) air from the floor area to the breathing
zone.
sure decreases due to improved indoor air quality, E, ex-
ceeds 1. This is the typical case in displacement venti-
lated rooms (see Figure 12). Acknowledgements
In Figure 12, E, is plotted as a function of yst/yefor the This research was supported financially by the Danish
measurements corresponding to Figure 7. The dotted Technical Research Council (STVF) as part of the re-
line indicates complete mixing. The results show how search programme "Healthy Buildings", 1993-1997.
the displacement principle improves the air quality
compared to dilution ventilation. In practice, the results
will appear less significant due to persons' movements References
and other disturbances in a displacement ventilated Breum, N.O. (1992) "Flow fields of simulated body odor in an
room as discussed previously. office ventilated from the displacement design principle".
In: Proceedings of Roomvent '92, Aalborg, Denmark, Vol. 3,
One of the advantages of using E ~ ,compared to for pp. 181-194.
example the ventilation effectiveness in the occupied Brohus, H. and Nielsen, P.V. (1994a) "Contaminant distribu-
zone, is that the personal exposure index relates to what tion around persons in rooms ventilated by displacement
is actually experienced by a person and not just a kind ventilation". In: Proceedings of Roomvent '94, Cracow, Po-
land, Vol. l, pp. 293-312.
of "mean" air quality. Brohus, H. and Nielsen, P.V. (1994b) "Personal exposure in a
If E, is known, we may, as a first step, treat the venti- ventilated room with concentration gradients". In: Proceed-
lated room as fully mixed. The personal exposure index ings of Healthy Buildings '94, Budapest, Hungary, Vol. 2, pp.
559-564,
is then used to convert the "fully mixed exposure" into Brohus, H. and Nielsen, P.V. (1995) "Personal exposure to con-
"actual exposure" when the mean concentration is di- taminant sources in a uniform velocity field". In: Proceedings
vided by E., ofHealthy Buildings '95, Milan, Italy, Vol. 3, pp. 1555-1560.
Fanger, P. 0.(1972) Thermal Confort -Analyses and Applications
in Environmental Engineering, New York, McGraw-Hill.
Conclusions Holmberg, R.B., Eliasson, L., Folkesson, K. and Strindehag, 0.
Personal exposure in a displacement ventilated room is (1990) "Inhalation-zone air quality provided by displace-
examined. The stratified flow and the considerable con- ment ventilation". In: Proceedinp of Roomven t '90, Oslo, Nor-
way.
centration gradient necessitate an improvement of the Homma, H. and Yakiyama, M. (1988) "Examination of free
widely used fully mixing compartmental approach. convection around occupant's body caused by its metabolic
The exposure of a seated and a standing person as a heat", A S H R A E Transactions, V. 94,Pt. 1.
Hyldgaard, C.E. (1994) "Humans as a source of heat and air
function of the stratification height is examined. It is pollution". In: Proceedings of Roomvent '94, Cracow, Poland,
found that the flow in the boundary layer around a per- Vol. 1, pp. 413433.
son is able, to a great extent, to entrain air from below the Kruhne, H. and Fitzner, K. (1994) "Air quality in the breathing
breathing zone, thus improving the quality of the inhaled zone in rooms with displacement flow". In: Proceedings of
Roomvent '94, Cracow, Poland, Vol. 2, pp. 93-101.
air. Mattsson, M. and Sandberg, M. (1994) "Displacement ventila-
Persons' movements cause the air quality to decrease tion - influence of physical activity". In: Proceedings of Xoom-
due to the disturbance of the human boundary layer vent '94, Cracow, Poland, Vol. 2, pp. 77- 92.
Mundt, E. (1994) "Inhaled air in displacement ventilation". In:
which promotes the high air quality transporting fresh Proceedings of Healthy Buildings, Budapest, Hungary, Vol. 2,
air to the breathing zone. pp. 355-360.
166
Personal Exposure in Displacement Ventilated Rooms
Nickel, J. (1990) "Air quality in a conference room with to- on exposure assessment measurement for indoor contami-
bacco smoking ventilated with mixed or displacement ven- nants", Indoor Air, 1(2), 123-145.
tilation". In: Proceedings of Roomuent '90, Oslo, Norway, Ses- Sexton, K. and Ryan, P.B. (1988) "Assessment of human expo-
sion D24 (64). sure to air pollution: methods, measurements, and models".
Nielsen, P.V. (1993) Displacement Ventilation - Theory and De- In: Watson, A.Y., Bates, R.R., Kennedy, D (eds) Air Pollution,
sign. Department of Building Technology and Structural En- the Automobile, and Public Health, Washington D.C., National
gineering, Aalborg University, Denmark. Academy Press, pp. 207-238.
Ott, W.R. (1985) "Total human exposure", Environmental Sci- Stymne, H., Sandberg, M. and Mattsson, M. (1991) "Disper-
ence and Technology, 19(10),880-886. sion pattern of contaminants in a displacement ventilated
Rodes, C.E., Kamens, R.M. and Wiener, R.W. (1991) "The sig- room - implications for demand control". In: Proceedings of
nificance and characteristics of the personal activity cloud 22th AIVC Conference, Ottawa, Canada.
2 67