You are on page 1of 8

Journal of the Human-Environmental System

Review Article Vol. 11; No. 2: 77–84, 2008

The Air Distribution Index as an Indicator for Energy Consumption and


Performance of Ventilation Systems

T. KARIMIPANAH1),2), H.B. AWBI2) and B. MOSHFEGH1),3)


1)
Division of Energy and Mechanical Engineering, Department of Technology and Built Environment,
University of Gävle S-801 76 Gävle, Sweden
2)
School of Construction Management and Engineering, University of Reading,
Reading, RG6 6AW, UK
3)
Division of Energy Systems, Department of Management and Engineering, Linköping University,
S-581 83 Linköping, Sweden
E-mail: tkh@.hig.se

(received on June 11, 2007, accepted on August 7, 2007)

Abstract
This paper deals with the energy consumption and the evaluation of the performance of air supply sys-
tems for a ventilated room involving high- and low-level supplies. The energy performance assessment is
based on the airflow rate, which is related to the fan power consumption by achieving the same environmental
quality performance for each case. Four different ventilation systems are considered: wall displacement venti-
lation, confluent jets ventilation, impinging jet ventilation and a high level mixing ventilation system. The venti-
lation performance of these systems will be examined by means of achieving the same Air Distribution Index
(ADI) for different cases.
The widely used high-level supplies require much more fan power than those for low-level supplies for
achieving the same value of ADI. In addition, the supply velocity, hence the supply dynamic pressure, for a
high-level supply is much larger than for low-level supplies. This further increases the power consumption for
high-level supply systems.
The paper considers these factors and attempts to provide some guidelines on the difference in the en-
ergy consumption associated with high and low level air supply systems. This will be useful information for de-
signers and to the authors’ knowledge there is a lack of information available in the literature on this area of
room air distribution.
The energy performance of the above-mentioned ventilation systems has been evaluated on the basis of
the fan power consumed which is related to the airflow rate required to provide equivalent indoor environ-
ment. The Air Distribution Index (ADI) is used to evaluate the indoor environment produced in the room by the
ventilation strategy being used. The results reveal that mixing ventilation requires the highest fan power and
the confluent jets ventilation needs the lowest fan power in order to achieve nearly the same value of ADI.

Key words: ventilation, air distribution index, energy, CFD, modelling, indoor environment

1. Introduction pinging jet ventilation and a high level mixing venti-


The major part of energy consumption in both in- lation system.
dustrial and residential buildings is for HVAC sys- During the past two decades, the world demand for
tems. This paper focuses on the energy consumption primary energy has been doubled while during the
of air supply processes for a ventilated room involv- same time the demand for electrical energy has
ing high and low-level supplies. The energy perform- tripled. In Sweden for example, energy demand for
ance will be based on the fan power consumption, the built environment is growing and the building
which is related to the airflow rate, by achieving the sector accounts for nearly 40% of total energy use
same environmental performance for each case. Four and for 15% of the total CO2 emission. In other coun-
different ventilation systems are considered: wall dis- tries the CO2 emission from buildings is even a
placement ventilation, confluent jets ventilation, im- higher ratio as Sweden relies extensively on hy-
78 T. Karimipanah, H.B. Awbi and B. Moshfegh

dropower generation. usage for mixing, displacement and confluent jets


The EU Commission states in the directive for en- systems was numerically investigated by Vulle.9) He
ergy efficiency in the built environment (EPBD) that used the IDA-Indoor Climate and Energy program10)
the building sector has to decrease its use of energy for simulation of thermal comfort, indoor air quality
to reduce CO2 emissions. In Sweden, the Environ- and energy usage in buildings in his calculations. He
mental Advisory Council have stated, within the presented a potential energy saving of about 10–15%
framework of “Bygga Bo Dialogen”, (Build Housing for confluent jets and displacement systems com-
Dialogue) that the demand for purchased energy in pared with a traditional mixing air supply system. In
the building sector should decrease at least by 30% contrast to this paper, Vulle9) does not discuss the re-
by 2025 compared to 2000 and energy use in 2010 lation between thermal comfort and air quality with
should be lower than in 1995. energy usage.
The link between the increased CO2 emissions and
the use of energy is also a motive to render a more ef- 2. Computational set-up and numerical proce-
ficient energy usage, and lower the total energy de- dure
mand. As a result, the need for energy conservation The room under consideration, which is furnished
and reduction of electrical energy usage in the built like an office for a single occupant, is shown in Fig-
environment is very strong. Ventilation systems, ther- ure 1. The room has the dimensions 2.782.782.3
mal comfort and air quality within the built environ- m. The boundary conditions for inlet velocity profile
ment are important issues as they relate both to en- and turbulent intensity as well as the interior wall
ergy consumption and the health of the occupants. surface temperatures have been derived from the
The aim of this study is to fulfill the above-men- measurements by Cho et al.3) The supply air tempera-
tioned goals and is thus a step towards a sustainable ture is 18°C. The heat load consists of the heat gain
building sector. This paper focuses on the energy at the exterior wall (55 W), the window (120 W) and
usage of air supply processes for a ventilated office the internal heat generation (100 W), corresponding
space involving high- and low-level supplies. The en- to a cooling load of 35 W/m2.
ergy performance will be based on the fan power The VORTEX CFD code11) is used for both grid
consumption, which is related to the airflow rate, by generation and the numerical solution of the pro-
achieving the same indoor environmental perform- posed problem. The generated mesh is a 3-D struc-
ance in each case. Four different ventilation systems tured grid with 615863 points (in x, y, z) for mix-
are considered: wall displacement ventilation, conflu- ing, 584451 for confluent jets, 606065 for
ent jets ventilation, impinging jet ventilation and a displacement and 676069 for impinging jet, giv-
high-level mixing ventilation system. The ventilation ing a total of about 222 894, 130 152, 234 000 and
performances of these systems are examined else- 277 380 cells respectively. Clustering the mesh to-
where1–8). wards the walls has been controlled in such a way
The influence of temperature gradient on energy that the employed wall-function treatment is properly

Fig. 1 A sketch of the office room.


The Air Distribution Index as an Indicator for Energy Consumption and Performance of Ventilation Systems 79

applied. The Renormalization Group (RNG) k-e Thus, low values for both indices guarantee a good
model has been used to predict the turbulent behav- indoor air quality and thermal comfort.
iour of the flow within the room. The governing To examine the quality of a ventilation system a
equations are solved using a segregated scheme. The thermal comfort number, Nt, and an air quality num-
equations for the momentum, energy, concentration, ber, Nc, may be found by combining relations (1) and
kinetic energy and turbulent dissipation rate are dis- (2) with PPD and PDAQ respectively [12 and 15]:
cretized spatially with a QUICK scheme. The pres-
sure-velocity coupling algorithm SIMPLE is used to εt
Nt  (5)
solve the continuity equation. The local criterion for PPD
numerical convergence, i.e. the maximum relative
difference between two consecutive iterations for any εc
Nc  (6)
local variable, is less than 103. To extend the degree PDAQ
of accuracy in the solution a calculation of the energy
balance is also made. These two numbers can be combined into a single
parameter which determines the effectiveness of an
3. Data reduction air distribution system in providing air quality and
To assess the effectiveness of a ventilation system, thermal comfort in the form of an Air Distribution
the effectiveness for heat removal (e t ) and contami- Index (ADI), defined as [12]:
nant removal (e c) are used together with the predicted
ADI(NtNc)0.5 (7)
percentage of dissatisfied (PPD) for thermal comfort
and percentage of dissatisfied (PDAQ ) for air quality. In addition, the effect of draught in the room is cal-
e t and e c are defined by [12]: culated using the equation below, see [16], which
gives the percentage dissatisfied due to draught
To  Ti (PDD):
εt  (1)
Tm  Ti
PDD(34ta)v0.05)0.6223(3.143
0.3696 v · TI) (8)
Co  Ci
εc  (2)
Cm  Ci where ta is the air temperature (°C), v is the air speed
(m/s), and TI is the turbulence intensity (%).
In Eqs. (1) and (2), T is temperature (°C), C is the In this investigation the above relations are used
contaminant concentration (ppm), subscripts o, i and for comparing the ventilation performance of the
m denote outlet, inlet and mean value for the occu- ventilation systems.
pied zone (to a height of 1.8 m). e t is similar to a heat The following relations between the flow rate, q,
exchanger effectiveness and is a measure of the heat- pressure difference, Dp, and the fan power, E, are
removing ability of the system. e c is a measure of used to evaluate the energy performance of the venti-
how effectively the contaminant is removed. The val- lation systems:
ues for e t and e c are determined by heat and contami-
D pç q2, Eç q3 (9)
nant sources, the method of room air distribution,
room characteristics, etc. However, high values do
not always give a good indication of the thermal 4. Results
comfort and air quality in the occupied zone. 4.1 Comparison between the indoor quality per-
The expressions for the Percentage of Dissatisfied formance of the ventilation systems for
(PDAQ) with the indoor air quality and the Predicted achieving the same value of ADI
Percentage of Dissatisfied (PPD) with the thermal Figure 2 (a and b) shows a perspective view of the
environment are given by Eqs. (3) and (4), see velocity in the occupied zone for the summer case
Fanger.13) with the iso-velocity0.25 m/s represented by the
floods for the mixing and confluent jets ventilation
PDAQ395 · exp (1.83 v̇ 0.25) (3)
systems. The occupied zone here is defined by a
height of 1.8 m and distances of 0.30 m from each
PPD10095 exp[0.033353 (PMV)4
wall and 0.1 m above the floor. Figure 2(a) shows that
0.2179 (PMV)2] (4)
the mixing system has a small area at the floor with a
where v̇ is the ventilation rate (l/s) and PMV is the velocity higher than 0.25 m/s and the confluent jets
Predicted Mean Vote as defined in ISO 773014) and supply shows a small area under the supply device
the recommended PPD limit for ideal thermal envi- also at floor level where the velocity is 0.25 m/s.
ronment is 10%, corresponding to 0.5PMV0.5. The same effect has also been observed for the dis-
80 T. Karimipanah, H.B. Awbi and B. Moshfegh

Fig. 2(a). Iso-velocity for 0.25 m/s in occupied zone (mixing ventilation left and confluent jets ventilation right).

Fig. 2(b). Iso-velocity for 0.25 m/s in occupied zone (impinging jet ventilation left and displacement ventilation right).

placement system which creates a so-called near- some high values of PDD are observed far from the
zone. In the case of the impinging jet system, the air occupant and close to the jet zone which is not of
velocity is lower than 0.25 m/s in the whole occupied much interest in this case. The PDD levels for the
zone. This means that the impinging jet fulfils the ac- confluent jets and the other two systems are lower
cepted criterion for velocities below 0.25 m/s in the than those of the mixing system and are within the
occupied zone very well, see Fig. 2(b). range of recommended values. This could be due to
To relate the physical parameters of the indoor en- the low ventilation effectiveness of the mixing system
vironment to the occupant’s comfort, the PDD (Per- which is usually much less than 100% compared with
centage Dissatisfied due to draught) index has been that for the displacement, confluent jets and imping-
used. The PDD index is illustrated in Fig. 3(a) and (b) ing jet systems which is over 100% in many cases.
for the mixing and the confluent jets. The PDD index Figure 4 shows predicted PDD values at 1.1 m
is plotted at a plane which is 1.1 m over the floor above the floor level for the mixing and confluent jets
level, i.e. at about neck height. systems. One can see that the highest levels of PPD
As shown in Fig. 3(a), draught may cause prob- are observed close to the occupant for the mixing
lems for the mixing system used in the present study system. It is worth mentioning that PPD values over
as PDD10% for large parts of the plane at neck 10% are not considered acceptable. In the case of the
level. However, the confluent jets system shows ac- confluent jets, the highest levels of PPD are observed
ceptable levels of PDD near the occupant although very close to the occupant and under the supply de-
The Air Distribution Index as an Indicator for Energy Consumption and Performance of Ventilation Systems 81

Fig. 3(a). Percentage Dissatisfied due to draught at 1.1 m over the floor level (mixing ventilation left and confluent jets venti-
lation right).

Fig. 3(b). Percentage Dissatisfied due to draught at 1.1 m over the floor level (impinging jet ventilation left and displacement
ventilation right).

Fig. 4. Predicted Percentage of Dissatisfied 1.1 m over the floor level (mixing ventilation left and confluent jets ventilation
right).
82 T. Karimipanah, H.B. Awbi and B. Moshfegh

Fig. 5. Temperature (left) and velocity (right) contours at mid-plane (ca z1.6 m) for the confluent jets ventilation.

Table 1. PPD and PDAQ values in the occupied zone for all ventilation systems with the same ADI index.

Mixing Displacement Impinging jet Confluent jets

Min Max Mean Min Max Mean Min Max Mean Min Max Mean

PPD (%) 8.4 13.9 11.2 5.0 11.4 8.0 5.0 14.6 8.8 5.2 11.1 8.3
PDAQ (%) 2.2 12.9 11.7 1.0 6.8 4.5 1.4 5.0 3.6 1.2 10.0 6.9

vice. It is worth mentioning that in the most parts of Table 2. The average values of e t, PPD, e c, PDAQ and
the room the PPD level is below or equal to 10%. ADI in the whole room for all ventilation systems.
Here one can see the benefits of CFD calculations in
Impinging Confluent
the pre-design stage. With the above observation it Mixing Displacement
jets jets
will be recommended to re-position the occupant into
other more favorable zones in the room. e t (%) 99 121 125 123
PPD (%) 9.0 9.2 8.9 8.5
Finally, by analysing the PPD data, it was found
Nt 11.0 13.2 14.0 14.5
that the three systems—confluent jets, impinging jet e c (%) 118 118 120 121
and displacement systems—behave similarly in the PDAQ (%) 5.4 6.1 7.0 7.2
ventilation of a small office with acceptable ranges of Nc 21.8 19.3 17.1 16.8
ADI [] 15.5 15.9 15.5 15.6
PPD values. But for the market-dominated mixing
system this is not the case and this system should be
avoided when possible due to its high energy con- 4.2 Comparison between the energy consump-
sumption and less favorable aspects of the indoor en- tion of ventilation systems for achieving the
vironmental quality for the occupants. same value of ADI
The temperature and velocity floods of the conflu- The minimum, mean and maximum values of
ent jets ventilation system in the mid-plane of the PDAQ and PPD in the occupied zone are summarized
room are shown in Fig. 5. The highest temperatures in Table 1. The results show that the displacement,
exist at ceiling level and the velocities are within the impinging jet and confluent jets supply systems pro-
recommended values. Therefore the confluent jets vide similar performance in terms of indoor air qual-
system can combine the positive effects of the dis- ity and thermal comfort due to the similar range of
placement system (stratification) and the mixing sys- values of PDAQ and PPD, while the mixing ventila-
tem (rapid entrainment of the surrounding air into the tion system has the highest PDAQ and PPD values in
jet). Another benefit of using a confluent jets system the occupied zone, see also [17].
is that it can be used for both heating and cooling The average values of e t, PPD, Nt , e c, PDAQ, Nc
purposes. and ADI in the whole room are summarized in Table
2. Taking the ventilation space as a whole (including
the jet region), the results reveal that the highest val-
ues of the effectives, e t and e c were produced by the
The Air Distribution Index as an Indicator for Energy Consumption and Performance of Ventilation Systems 83

Table 3. Comparison between the fan power consumption of the ventilation systems for the same ADI.

ADI Total flow rate Energy usage

Mixing ventilation 15.5 0.045 m3/s


Difference compared to confluent jets 180% 580%
Impinging jet ventilation 15.7 0.035 m3/s
Difference compared to confluent jets 140% 270%
Displacement ventilation 15.9 0.0275 m3/s
Difference compared to confluent jets 110% 130%
Confluent jets ventilation 16.1 0.025 m3/s

displacement, impinging and confluent jets systems. purpose of energy saving, new developments in low-
The same also applies to the values of the thermal level air supply systems are needed to reduce the re-
comfort number, Nt. However, the mixing ventilation liance on traditional mixing systems, which have in-
achieved the highest value of the air quality number, ferior performance compared to low-level air supply
Nc, due to the low value of PDAQ, although the value systems.
of e c for the mixing system is one of the lowest
among the four systems. References
Table 3 compares the air flow rates required for 1. Karimipanah T., Sandberg M. and H. B. Awbi, A
Comparative Study of Different Air Distribution Sys-
achieving an Air Distribution Index (ADI) of about
tems in a Classroom. In Proc. of Roomvent 2000,
16. The confluent jets system requires the lowest flow
Reading, England, 1013–1018 (2000).
rate (0.025 m3/s) of the four systems considered. To 2. Karimipanah T. and H. B. Awbi. Theoretical and Ex-
obtain nearly the same ADI value for a mixing sys- perimental Investigation of Impinging Jet Ventilation
tem we need 1.8 times greater flow rate. Using rela- and Comparison with Wall Displacement Ventilation,
tion (9), this gives 5.83 times higher fan power con- Building and Environment 37 (2002) 1329–1342.
sumption. For the impinging jet system the flow rate 3. Cho Y., Awbi H. B and T. Karimipanah. A Compari-
is 1.4 times higher and demands 2.74 times more son between Four Different Ventilation Systems. In
power. The power consumption of the impinging jet Proc. of Roomvent 2002, Copenhagen, June (2002).
system is almost half of the mixing system. The dis- 4. Karimipanah T., Awbi H. B., Sandberg M. and
Blomqvist C. Investigation of air quality, comfort pa-
placement system requires 1.1 times greater flow rate
rameters and effectiveness for two floor-level air sup-
and 1.33 times higher power consumption compared ply systems in classrooms. Building and Environment
to the confluent jets. Although the power consump- 42 (2007) 647–655.
tion is lower than the other two systems, it is still 5. Cehlin M., Moshfegh B. and Sandberg M., Measure-
higher than the confluent jets system. ments of air temperatures close to a low-velocity dif-
fuser in displacement ventilation using infrared cam-
5. Concluding remarks era: parameter and error analysis. Energy and Build-
The choice of air supply system in a room has a ings, 34 (2002) 687–698.
major impact on the energy consumption of the ven- 6. Cho YJ, Awbi H. B. and T. Karimipanah (2004), The
characteristics of wall confluent jets for ventilated en-
tilation system because of the large differences in the
closures. In Proc. of Roomvent 2004, Coimbra, Portu-
thermal and air quality effectiveness between the sys-
gal (2004).
tems as well as in the fan power consumption which 7. Karimipanah T. and H. B. Awbi. Performance evalua-
constitutes a large component of the total HVAC sys- tion of two air distribution systems. Presented in The
tems energy requirement. The overall performance of 5th International Conference on Ventilation for Auto-
the confluent jets air supply system is somewhat bet- motive Industry, 11–12 June 2001, Stratford-Upon-
ter than the displacement and impinging jets systems Avon, United Kingdom (2001).
but superior to the mixing system. The confluent jets 8. Awbi H. B. and T. Karimipanah. A comparison be-
behave like the displacement and the impinging jet tween three methods of low-level air supplies. In
ventilation systems combined. To obtain the same Air Proc. of Internat. Conference on Indoor Air Quality,
Ventilation and Energy Conservation in Buildings
Distribution Index for a mixing system 1.8 times
(IAQVEC 2001), Chagsha, China, Vol. I, 311–316
greater flow rate is required and 5.83 times more fan
(2001).
power is used. The displacement system uses 1.33 9. Vulle M. The impact of air temperature gradient on
times and the impinging jet system uses 2.74 times energy consumption, SIY Sisäilmatito Oy Finland, In
the power used by the confluent jets system, but they Finish, (2006).
still perform better and use less power than the tradi- 10. IDA Indoor Climate and Energy, http://www.equa.se/
tional mixing system. The authors believe that for the eng.ice.html
84 T. Karimipanah, H.B. Awbi and B. Moshfegh

11. Awbi H. B. VORTEX: A computer code for airflow, tion of the conditions for thermal comfort (1994).
heat transfer and concentration in enclosures, Version 15. Awbi H. B. Energy Efficient Room Air Distribution,
3C and 4D-RNG, Reading, UK (2005). Renewable Energy 15 (1998) 293–299.
12. Awbi H. B. Ventilation of Buildings. 2nd Ed., Taylor 16. Fanger, P. O., et al. Air turbulence and sensation of
and Francis (E&FN Spon), (2003). draught, Energy and Buildings, 12, 21–39 (1998).
13. Fanger P. O. Thermal comfort. McGraw-Hill New 17. Karimipanah T., Awbi H. B. and Moshfegh B., On the
York, (1972). energy consumption of high and low-level air suppli-
14. ISO/CEN 7730. Moderate thermal environments: De- ers. In Proc. of World Renewable Energy Congress IX
termination of PMV and PPD indices and specifica- and exhibition, Florence, Italy (2006).

You might also like