You are on page 1of 6

30th International Conference on Lightning Protection - ICLP 2010

(Cagliari, Italy - September 13th -17th, 2010)

LIGHTNING LEAD-IN CHANNELS AND SPD SELECTION


FOR RADIO BASE STATION
Liu Jike1 Lin Yongshuang2 Meng Qi3 Chen Qiang1 Yuan Qiangong2 Wang Zhigang1 Qi Zheng1
Email: liujike@dimpt.com, linyongshuang@jm.gd.chinamobile.com,mqi@emersonnetwork.com.cn,
chenqiang63@chinaunicom.cn, wangzg200@chinaunicom.cn, qizheng5@chinaunicom.cn

RBSs, type of the building, and power supply mode, etc.


ABSTRACT
This paper discusses four lightning lead-in channels of the 2 LIGHTNING LEAD-IN CHANNELS
RBS(Radio Base Station), analyzes the influence of these
channels on RBS and proposes solutions; quadratic Lightning can affect the normal work of RBS
counterattack-effect is proposed according to the earth through four interfaces of the RBS telecommunications
potential rise on the grounding grid caused by the equipment, as shown in Figure 1:
lightning strike on iron tower and the lightning current’s
flowing to earth; this lightning model is different from
lightning current distribution model in IEC lightning
standard. In addition, according to the theoretical analysis
and abundant experiences of China Mobile RBSs’ large
usage of voltage limiting type SPD(Surge Protective
Devices), it is proved that the voltage limiting type SPD
can protect equipment in the telecom room no matter in
Guangdong(South China) which has 120 thunderstorm
days or in RBSs under the severest environment.
Key Words: RBS Earth Potential Rise Quadratic
Counter Voltage-limiting Type SPD

1 INTRODUCTION
The key to solve RBS’s lightning damage is to clarify
the incoming channels of lightning. China is the
country with the most RBSs in the world and it also has
the most extensive thunderstorm days. In Guangdong
Figure 1: Lightning influence on 4 interfaces of RBS
Province alone, the number of thunderstorm days is
telecommunications equipment
more than 70 and even up to 120. The number of RBS
in Guangdong Province is nearly 100,000, so its
experience of lighting protection is representative. For 2.1 Power port
years, there is a controversy over the usage of voltage
switching type SPD and voltage limiting type SPD in In terms of the lightning damage rate, power type
different countries. Telecommunications Industry equipment accounts for about 90% (including
Standards of PRC YD5098-2005, i.e. Design transformer, distribution box, AVR, rectifier module,
Specifications of Lightning Protection and Earthing for air conditioning board, lighting system, etc.). These
Telecommunications Bureau (Station) stipulates that equipments supplied by power line are more likely to be
RBSs must use voltage limiting type SPD; as the first influenced by lightning surge; in the lightning strike,
level SPD at the power port of RBS, voltage limiting the insulation and internal components of the equipment
type SPD has been used in China for years and has been are broken down as the result of the earth potential rise
applied in tens of thousands of RBSs. The practical or surge between equipment brought by lightning
experience shows that voltage limiting type SPD can magnetic field. Power port is always the key point of
meet the needs of lightning protection of the RBS. lightning protection; statistical data of China[5]
Moreover, the surge rating of voltage limiting type demonstrates that more than 90% of equipment
SPD should be chosen according to the intensity of the lightning damages are related to power port. Well-
lightning, category of RBSs, geographic location of the known power supply manufacturers in the world also
have such experience.

1038-1
2.2 Signal / Control port and microwave equipment;
If the RRU system adopts RF cables for remote
The RBS adopts environmental monitoring devices
transmission, when the RRU system is struck by the
to achieve unattended system and there are signal wires
lightning, the equipment directly connected with the
connected with the transmission equipment and RBS
RRU maybe damaged, including DC RRU system,
transmitter, etc., when signaling equipments, such as
control RRU system, RF RRU system, MF RRU
CPU, user board, E1 port, microwave transmission
system , GPS and microwave equipment ports, etc;
interface, environmental monitoring, transducer, fire
If the RRU system adopts intermediate frequency
control panel, mini microwave and so on, are struck by
cables, when the RRU system is struck by the lightning,
the lightning surge, the surges are conducted to other
the equipment directly connected with the RRU maybe
equipments through the interconnected signal/control
damaged, including DC RRU system, control RRU
wires, which will present safety hazard to other
system, GPS and microwave equipment ports.
equipment.
2.4 Earthing port
2.3 Antenna port / power transmission port
The main influence of the earthing ports is the
2.3.1 Antenna port: instantaneous potential rise to the equipment. When
In the past, people thought antenna was the main lightning surge discharges through the grounding grid,
channel to lead the lightning current to the RBS; the earth potential will rise sharply in a short time and
however, theoretical analysis and calculations[5] show thus the transient potential difference between the
that antenna ports are not the key channel of the positive and the negative electrodes of the DC power
incoming lightning current, the reasons are listed below: supply becomes very high, which may damage the
sensitive components of the equipment (such as rectifier
• Under the protection of air termination system, the
modules and transceivers). As the earth potential rise
antenna feeder is in LPZ0B zone where only the sometimes will damage the equipment from the front
induction effects exist; (DC output port of switching power supply), or from
• It shows from the analysis of the antenna theory the bottom (DC input port powered devices as GSM),
that as the cable conductor and armor of antenna we should install SPDs on both ends of the DC power
are normally conductive in the low frequencies supply to form transient equipotential between the
and they are non-conductive just in high positive and negative electrodes of DC power supply
frequencies; for lightning band, the cable and the earth. Prevent the striking-back potential caused
conductor and armor are relatively earthing; by the rise of the ground potential from damaging the
• The lightning damage examples of antenna system equipment. In the regions with many thunderstorm days
in the RBS are rare; calculation results and or large lightning intensity, especially for the RBSs
practical application show that: lightning surge with iron tower, we should provide lightning protection
from antenna port normally won’t exceed the measures in the DC-ended output side of switching
protection level of RBS ports. power supply.

2.3.2 The differences between various types of 3 SELECTION OF CLASS I SPD OF


distribution RBSs and traditional RBS are POWER PORT
RRU (radio remote unit) systems of the former:
3.1 Adaptability of IEC standards and
RRU systems include DC, controlling, signal, GPS, recommendations in various industries
microwave, optical transmission equipment, etc.; the
transmission mediums it adopts are RF cable, control 3.1.1 The adaptability of standards and
wires, DC feeder, intermediate frequency cable, optical recommendations of IEC are not the same to
fiber cable, etc. These RRU systems expose to the all fields. Therefore, it is inappropriate for the
external environment and their transmission mediums RBS to select SPD directly according to
are in LPZOB zone (These transmission mediums adopt IEC61643-1[1] and IEC61643-12[2].
the form of coaxial cable or combined cable except for
optical fiber cable, actually, they are within the critical IEC61643-1 mainly explains “technical requirements
section between LPZOB and LPZ1), so the possibility of and test methods for low-voltage SPD”. All the other
introducing the incoming lightning current increases. IEC documents and recommendations, including
If the RRU system adopts optical fiber cables for IEC62305, are fundamental standards. The SPD for
remote transmission, when the RRU system is struck by RBS should be selected according to the division of the
the lightning, the equipment directly connected with the lightning active area, category of RBS, geographic
RRU maybe damaged, including DC RRU system, GPS environment of the RBS, type of the building, power

1038-2
supply mode, and the voltage stability on the site, for reactance of the tower components, and when it flows
the environmental factors and conditions of the RBS are into the earth, the waveform of lightning current
usually very special, and can not be fully covered by the changes again.
fundamental standards, it also relates to the matching of As the current flows into the earth, the 10/350μS
different class SPDs, so not all type of SPD can solve lightning current waveform of the original direct
some particular problems of lightning protection. lightning changes due to the inductance reactance of the
Different fields are facing with different lightning tower and the inductance and capacitance of the
protection problems. The IEC lightning protection earthing electrode. The changed lightning current and
standards that primarily take building into consideration the resistance of earthing devices generate earth
are not applicable to electric power, petrochemicals, potential rise to the infinity points, namely, striking-
railway or RBS! IEC recommendations can’t meet the back earth potential, belonging to the quadratic effects
environmental characteristics of every field. These of lightning. Whether the outgoing high potential or the
recommendations can only be adaptable to the ordinary incoming low potential, earth potential rise on the wire
buildings environment. Each type of SPD has its own generated while the lightning current flows through the
adaptable environment and installation mode, and tower create ultimately tens of thousands volts or even
insecurity factors of the RBS may be caused if the millions of volts of common mode voltage. Earth
IEC61643-1 and IEC61643-12 are adapted directly to potential rise of grounding grid impacts on the RBS
them. Therefore, the way of selecting the SPD based on outgoing wires by means of resistive coupling, which
the IEC standards, which is simply proposed in ITU K has nothing to do with the lightning current waveform
56, is inappropriate. that flows into the earth through tower while lightning
strike, namely, irrelevant to the 10/350μS waveform
3.1.2 The distribution mode of the lightning current that has been under endless discussion. Therefore, the
assumed in IEC61312 [3] exists problems. ground voltage or ground-to-line voltage on the
Lightning current distribution mode described in outgoing wire can be described by 1.2/50μS simulated
IEC61312: When the direct lightning striking on the air lightning voltage waves. The 1.2/50μS simulated
termination system of the building, 50% of the lightning lightning voltage waves are corresponding to 8/20μS
current among various facilities of the building flows to simulated lightning current waves. So the class I SPD is
the ground along the down conductor, and the acceptable as long as it can withstand the 8/20μS
remaining 50% flows out along the pipelines between current.
the building and the outside. However, if the power In terms of the lightning current led in along the
distribution cable of the RBS adopts sheathed buried outgoing lines, no matter what form the lightning may
power cable, the lightning current that falls on the air be, for example, whether the direct lightning strikes on
termination system on the roof of the building doesn’t the distribution lines, or the lightning impacts on the
fulfill that assumed condition. In this case, the lightning RBS’s equipment by way of electromagnetic fields, or
current flows to the ground through the external down the lightning current flows in along the incoming power
conductor, and flows into the earth ground through lines and optical fiber cables, the direct lightning can
metal jacket of the buried cable. Actually, traditional not strike on the power distribution lines near the RBS,
lightning current distribution mode is controversial; the which is in the protection area of the tower, especially
lightning current added on the protected equipment is in the case of the shielded and buried cables adopted for
caused by the lightning voltages that created by the the RBS distribution lines; according to the lightning
quadratic counterattack of the earthing resistances. protection zone concept, it is in the LPZ0B~LPZ1 zone,
so the lightning wave should be the 8/20μS waveform
3.1.3 Lightning added on the protected equipment is rather than the 10/350μS. Therefore, at this point, the
caused by the lightning voltages created by the 8/20μS waveform should be used to describe the
quadratic counterattack lightning wave on SPD.
When direct lightning strikes the air termination of 3.2 Voltage switching type SPD does not conform
the tower, the lightning current flows to grounding grid to the conditions of RBS application.
through the tower and is discharged through the smooth
channel provided by the ground grid; the maximum SPD recommended for RBS by the
current can be up to 200 kA, and creates tens of Telecommunications Industry Standards of People’s
thousands or even millions of volts of earth potential Republic of China YD/T5098-2005, i.e. Design
rise in the RBS’s grounding grid. We suppose that the Specifications of Lightning Protection and Earthing for
described direct lightning has a current wave of Telecommunications Bureau (Station) is of voltage
10/350μS, and when it flows through the tower, the limiting type SPD, which has been widely adopted and
10/350μS wave changes because of the inductance verified in China for many years.

1038-3
In Guangdong Province alone, tens of thousands of levels of SPDs is not easily fulfilled). Therefore,
RBSs have used the voltage limiting type SPD since the Class I voltage switching type SPD cannot
2000. Generally, the voltage limiting type SPD of 3+1 match with the Class II SPD effectively.
mode (80~120kA and 8/20μS, Class I ,or type 1 or • Some companies may use serial inductors to form
Class B) is adopted at the RBS distribution box, and the a de-coupler between two levels of protection and
Class II (type 2, or Class C) SPD is already installed therefore solve the problem of protection distance
inside the power supply equipment. After ten years’ between two levels of SPDs. Blind spot or
verification, voltage limiting type SPD of 3+1 mode reflection problem for coordination between the
with the maximum discharge current mentioned above two levels may also exist. It introduces like this:
can solve the lightning damage problems well. Statistics “taking the inductance as a decoupling component
show that: the SPD of the voltage limiting type SPD of is closely related to waveform. For the waveform
3+1 mode nearly has little record of lightning damage. of long semi-value time (e.g., 10/350μS), the
The number of thunderstorm days in Guangdong, which inductance decoupling is not very effective (the
is one of the regions with the strongest thunderstorms in voltage switching type SPD plus an inductance
the world, is up to 70~120 days in a year; but the SPD cannot meet the requirement for protecting
can serve properly in such severe environments. different lightning spectrums when there is
Therefore, voltage limiting type SPD of 3+1 mode with lightning). When taking the inductance as a
the highest current rating ( 60~100kA, 8/20μS), as the decoupling component, it is necessary to take the
Class I SPD of power supply, is enough for applications surge voltage rise time and peak value into
in the region with the severest thunderstorm in China. account.” Even if the inductance is added, the
Moreover, the environment for RBS in Guangdong is issue of the voltage switching type SPD residual
probably the severest, which is incomparable with other voltage which is normally up to 4000V can not be
international or domestic environments or buildings in solved as well. And the on-site operation indicates
cities. It reveals that the relevant IEC recommendation, that: After the voltage switching type SPD is
which explains the Class I lightning test current is connected with an inductor in serial, there are
10/350μs based on the evidence that the voltage many lightning damage records of Class II 40kA
switching type SPD can adapt to the 10/350μS lightning module SPD installed in the power supply
current, is wrong. It is improper to propose to adopt the equipment.
voltage switching type SPD in any circumstance.
• Both the di/dt and the du/dt value are very high
Application cases indicate that IEC analyze SPD by
when the voltage switching type SPD operating,,
adopting lighting current analysis mode isn’t in
which will obviously affects the semiconductor
accordance with actual situation. Field experience
components inside the protected equipment.
shows the following facts:
• The voltage switching type SPD has no function of
• The lightning current may damage the lightning-
indicating deterioration, it can not achieve the
sensitive components in the equipment if the RBS
functions of alarming upon damage or tele-
only has voltage switching type SPD and has no
signaling the fault (available function currently is
other SPDs for Class II (type 2 or Class C)
just to indicate the working status of the auxiliary
protection, for the voltage switching type SPD’s
circuit through the LED, and this doesn’t reflect
respond time to lightning is relatively long.
the deterioration or damage status of the gap
• When the RBS adopts two-stage protections, if electrode). Therefore, in the unattended RBS, the
Class I SPD is voltage switching type, all the voltage switching type SPD can not be used
lightning current may flow through the Class II effectively.
voltage limiting protector, and cause the Class II
In sum, from parameters, indexes and functional
protection devices’ damage, because the voltage
factors of residual voltage, decoupling distance,
switching type SPD is slow to respond to the
response time, lack damage alarming and lack fault
lightning.
tele-signaling, the application of using voltage
• Blind spot may exist in energy coordination switching type SPD in RBS will endanger the safe
between voltage switching type SPD and voltage operation of the telecommunications system.
limiting type SPD, due to the gas discharge
characteristic of voltage switching type SPD. This 3.3 Voltage limiting type SPD is recommended to
may make the voltage switching type SPD out of be used in RBS.
service, and the Class II SPD needs to handle high
lightning current; therefore, the Class II SPD may The di/dt and du/dt value of the voltage limiting type
be damaged by lightning (as been limited by SPD are much less than those of the voltage switching
type SPD, which is helpful for protecting the safety of
RBS’s area, the decoupling distance of the two

1038-4
the protected equipment. Selecting the voltage limiting • Suburban type: Located in equipment room on the
type SPD properly can solve the problem of follow roof of the isolated high-rise building in the city;
current extinguishing. The voltage limiting type SPD RBS in the suburban area, residential house,
can achieve the function of deterioration indicating and beside the pool and the RBS without exclusive
remote signaling for faults, which is helpful for distribution transformer, and the areas with the
implementing unattended RBS. number of thunderstorms days belong to frequent-
The selection of the maximum discharge current lightning area(40~90 days/year):
value of the SPD is always the issue that attracts much The maximum discharge current of power
attention of the lightning protection designers. supply SPD: L-G, L-N and N-G must meet these
According to the introduction of relevant documents: conditions: nominal discharge current ≥
“Under the test condition with the same simulated
35KA/line, maximum discharge current ≥
lightning current of 8/20μS and 10kA, the service life of
80KA/line.
MOV component with the maximum discharge current
of 135kA is 1000-2000 times, and that of MOV • Mountain type: Located in equipment rooms with
component with the maximum discharge current of lead-in overhead power line in medium-thunder
40kA is 50 times, the lives of these MOVs are dozens areas(26~40 days/year); these rooms may located
apart from each other”. Since RBSs are frequently on the hills, by the roads, in the farmer house, or in
struck by lightning; therefore, the service life of the the farm fields, which are easily hit by lightning;
SPD must be considered. If the selected maximum The maximum discharge current of power
discharge current is too low, the SPD will be supply SPD: L-G, L-N and N-G must meet these
deteriorated quickly and need to be replaced frequently; conditions: nominal discharge current ≥
if the selected maximum discharge current is high, it 40KA/line, maximum discharge current ≥
will cause unnecessary waste. Therefore, the selection 100KA/line.
of the SPD must be considered according to the specific
situation from perspective of technology and cost- 3.4 Installation mode of the SPD for TT power
effectiveness. And the redundancy of the maximum system
discharge current of the voltage limiting type SPD
should be considered. Like in many other countries, RBSs in China
The surge rating selection of SPD should be done generally adopt the TT power system. The installation
according to the environmental factors and direct mode of the SPD will not affect the safety problem
related factors (including intensity of the lightning, when the RBS adopting the TN system. The power
classification of telecommunications station, geographic system of the RBS can adopt the voltage limiting type
environment of the telecommunications station, type of SPD which is 4-mode, 7-mode or 9-mode SPD. The
the building, power supply mode, etc.) and to the selection of the SPD needs only to consider the
technical and cost-effective factors. It is recommended maximum discharge current of SPD besides the
to use voltage limiting type SPD (testing waveform of maximum continuous operating voltage. But, for the TT
8/20μs) in Class I (Class B) of the RBS, and categorize system application, the installation mode of SPD will
the SPDs into urban type, suburban type and mountain present safe and fire hazard..
type. The maximum continuous operating voltage of the 3.4.1 Reasons for fire accident of SPD in the TT
SPD should be chosen according to the nominal voltage power system and relevant solutions[4]
and the voltage fluctuation status in each country.
Generally, in the region where the supply voltage is For the TT power system, if the SPD adopts four-
220V the maximum continuous operating voltage of wire to ground mode, as shown in Figure 2 i.e., the
320-385V is recommended. The classification of SPD same SPD is used across A-PE, B-PE, C-PE and N-PE,
in China telecom standard is shown below when the SPD failing for certain reasons, the high
• Urban type: Located in downtown area, public
circuit resistance due to grounding resistance will cause
building, computer equipment room, buildings the short circuit current not high enough to blow the
need no direct lightning protection, areas where fuse or MCB, and the SPD may catch fire, and even
the thunderstorm days belong to medium level burn the frame, cabinet and equipment room.
lightning area (26~40 days/year).
The maximum discharge current of power
supply SPD: L-G, L-N and N-G must meet these
conditions: nominal discharge current ≥
25KA/line, maximum discharge current ≥
60KA/line.

1038-5
installation adopted by SPD

Equipment
Protected
After adopting this circuit, the MOV modules are
installed between line and neutral. Since the loop
resistance is low, so once short-circuit failure occurs,
the over current protection device will operate to avoid
Figure 2: Circuit diagram of protection mode of four-wire to
fire.
ground installation adopted by the SPD in the TT power Although there is a gas discharge component in such
supply mode circuit, there is no problem like distributed actions, arc
elimination and slow response speed; and full-mode
For the power supply loops A, B and C, the SPD of protection can be implemented, because it is located
each phase to ground has the equivalent circuit in between N and PE. Therefore, it is applicable to various
Figure 3: grounding modes.

4 CONCLUSION
We should clarify the main lead-in channels and find
out solutions for lightning protection according to the
incidence on four interfaces of the telecommunications
equipment in RBS caused by lightning; we should also
clarify proper modes of the effect on RBS of lightning
according to effects on RBS of the quadratic counter
voltages, so as to avoid causing wrong selection of SPD
because of adopting wrong lightning modes.

5 REFERENCES
[1] IEC 61643-1 (2005), Low-voltage surge protective devices
- Part 1: Surge protective devices connected to low-
voltage power distribution systems - Requirements and
tests.
[2] IEC 61643-12 (2008), Low-voltage surge protective
devices - Part 12: Surge protective devices connected to
low-voltage power distribution systems - Selection and
Figure 3: Equivalent circuit diagram of each phase-to-ground application principles.
of power supply loops A, B and C [3] IEC 61312-1:1995,Protection against lightning
electromagnetic impulse--Part 1:General principles.
3.4.2 Solution to prevent SPD fire in TT power [4] Liu Jike, Chen QIang, Li Meng, “ The Choice of Power
system SPD of RBS and Recommendation for ITU K56”,
Supplement of Designing Techniques of Posts and
It is recommended that the RBS SPD should adopt Telecommunications, China Lightning Ablum pp.145 –
the protection circuit of the “3+1” installation mode. 148, February 2007.
This protection mode is also recommended by IEC [5] YD/T5098-2005 Specifications of Engineering Design for
standard: For the TT system, adopts “ 3+1” mode Lightning Protection and Earthing Design for
Telecommunication Bureaus(Stations).
means that connects 3 MOV modules among A/N, B/N
and C/N, and connects one gas discharge tube module
between N and PE, as shown in Figure 4:
Equipment
Protected

Note:
1 China Information Technology Designing & Consulting
Institute(China Unicom).
2 China Guangdong Mobile Communication Co., Ltd.
Jiangmen Branch.
3 Emerson Network Power Ltd. (China)

Figure 4: Circuit diagram of protection mode for “3+1”

1038-6

You might also like