SITE: ***PRELIMINARY*** WORKSHEET, CONTROL SYSTEM © Copyright 2010 GE PACKAGED POWER, L.P.

GE Packaged Power, L.P.


SH 2 LM6000PC 50HZ - MicroNet Plus All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in
strict confidence with th understanding that will not be reproduced nor used for any purpose except that fo
which it is loaned. It shall be immediately returned on demand and is subject to all other terms and
conditions of any written agreement or purchase order that incorporates or relates to this drawing.

R
E ACTION TRIP UNIT ALARM ACTIVE CONTACT BOX-CHASSIS-BOARD- TERMINALS PANEL WIRE WIRE
ITEM V FUNCTION SIGNAL SOURCE POINT R/F SIGNAL USED COMMENTS CHANNEL-CABLE FTM TERMINALS FUNCTION TERMINAL NO. DESTINATION
*** PROPRIETARY INFORMATION ***
LOCAL DISCRETE INPUTS

1--- 1 UTILITY BREAKER OPEN RELAY STATUS 1 N.O. CONTACT CLOSE WHEN BREAKER OPEN TCP-1-12-1-W112.1- FTM112.1-1/25 IN/+24VDC TB52- 73 40
1--- 2 UTILITY BREAKER CLOSED RELAY STATUS 1 N.C. CONTACT CLOSE WHEN BREAKER CLOSED TCP-1-12-2-W112.1- FTM112.1-2/26 IN/+24VDC TB52- 74 41
1--- 3 (SPARE) 0 N.C. TCP-1-12-3-W112.1- FTM112.1-3/27 IN/+24VDC
1--- 4 BUS/UTILITY 86 TRIP 86U ALARM 0 N.C. CONTACT OPEN WHEN 86 UTILITY TRIPPED TCP-1-12-4-W112.1- FTM112.1-4/28 IN/+24VDC TB52- 87 86B
1--- 5 (SPARE) TCP-1-12-5-W112.1- FTM112.1-5/29 IN/+24VDC
1--- 6 (SPARE) TCP-1-12-6-W112.1- FTM112.1-6/30 IN/+24VDC
1--- 7 RAISE NOX SUPPRESION FLOW NOX_RAISE CNTRL 1 N.O. TCP-1-12-7-W112.1- FTM112.1-7/31 IN/+24VDC TB52- 107 2298
1--- 8 LOWER NOX SUPPRESION FLOW NOX_LOSER CNTRL 1 N.O. TCP-1-12-8-W112.1- FTM112.1-8/32 IN/+24VDC TB52- 108 2299
1--- 9 (SPARE) TCP-1-12-9-W112.1- FTM112.1-9/33 IN/+24VDC TB52- 104 2338
1--- 10 (SPARE) TCP-1-12-10-W112.1- FTM112.1-10/34 IN/+24VDC TB52- 105 2339
1--- 11 NOX SYSTEM ENABLE TCP-1-12-11-W112.1- FTM112.1-11/35 IN/+24VDC TB52- 237 2218
1--- 12 (SPARE) TCP-1-12-12-W112.1- FTM112.1-12/36 IN/+24VDC TB52- 199 2402
1--- 13 WATER FUEL METERING VALVE DRIVER FAILURE ZC-6238 FSWM 0 N.O. TCP-1-12-13-W112.1- FTM112.1-13/37 IN/+24VDC
1--- 14 GAS FUEL METERING VALVE DRIVER FAILURE ZC-6201 FSWM 0 N.O. OPT: GAS FUEL (SAC ONLY) TCP-1-12-14-W112.1- FTM112.1-14/38 IN/+24VDC TB52- 212 1002
1--- 15 LIQUID FUEL METERING VALVE DRIVER FAILURE ZC-6202 FSWM 0 N.O. TCP-1-12-15-W112.1- FTM112.1-15/39 IN/+24VDC
1--- 16 CRITICAL PATH SHUTDOWN K2 FSLO 0 N.O. TCP-1-12-16-W112.1- FTM112.1-16/40 IN/+24VDC TB41- 161 2282 K2-10
1--- 17 TURB EXTERNAL OVERSPEED SSW1,2 FSLO 0 N.O. TCP-1-12-17-W112.1- FTM112.1-17/41 IN/+24VDC TB31- 96 507
1--- 18 ISOCH/DROOP CONTROL K67 CNTRL 1/0 N.O. 1 = ISOC, 0 = DROOP TCP-1-12-18-W112.1- FTM112.1-18/42 IN/+24VDC TB41- 164 48
1--- 19 GEN 86 TRIP (LOCAL) SWBD FSWM 0 N.O. OPEN WHEN 86 LOCAL TRIPPED TCP-1-12-19-W112.1- FTM112.1-19/43 IN/+24VDC TB52- 76 86A GPRC
1--- 20 GEN 86 TRIP (REMOTE) 86G FSWM 0 N.C. CONTACT OPEN WHEN 86 TRIPPED TCP-1-12-20-W112.1- FTM112.1-20/44 IN/+24VDC TB52- 77 93
1--- 21 GEN BREAKER OPEN (52b) GTG BKR STATUS 1 N.C. CONTACT CLOSED WHEN BREAKER OPEN TCP-1-12-21-W112.1- FTM112.1-21/45 IN/+24VDC TB52- 71 17
1--- 22 GEN BREAKER CLOSED (52a) GTG BKR STATUS 1 N.O. CONTACT CLOSED WHEN BREAKER CLOSED TCP-1-12-22-W112.1- FTM112.1-22/46 IN/+24VDC TB52- 72 18
1--- 23 SYNCHRONIZER SPEED RAISE DSM_RAISE CNTRL 1 N.O. ACTIVE ONLY DURING AUTO SYNCH TCP-1-12-23-W112.1- FTM112.1-23/47 IN/+24VDC TB41- 145 2208
1--- 24 SYNCHRONIZER SPEED LOWER DSM_LOWER CNTRL 1 N.O. ACTIVE ONLY DURING AUTO SYNCH TCP-1-12-24-W112.1- FTM112.1-24/48 IN/+24VDC TB41- 148 2211
24+21COM-W112.1- FTM112.1-49 +24VDC COM

REVISION LIST DATE

A INITIAL ISSUE 09/20/10 JFS

===== END ====================

DWG NO: XXXXXXX-XXX146


ORIGINATED: 09/20/10 REV: A
PRINTED: 4/6/2011 12:47 PM LOCAL EC: XXXXX
REV DATE: DISCRETE INPUTS Local Ins OF 7 PAGE 1 OF 1