Professional Documents
Culture Documents
ASHESH PADHY
15 April 2019, Butibori
Myth - 1
Megger value of the motor
is 10 M Ohm. Hence, Motor
Insulation is good.
INSIGHT INTO DEGRADATION MECHANISM
Mechanisms which govern life of insulation are -
• Resin-Rich
• Resin-Poor / VPI
OPERATING STRESSES
• Thermal Stress
• Electrical Stress
• Mechanical Stress
• Chemical Stress
• DOL Starting
• Steep-fronted Switching Over-voltage
REVIEW OF INSULATION SYSTEM
Bitumen / Shellac /
BONDING
Asphalt (class B),
MEDIUM
Epoxy resin (Class
F), Glass tape (Class
H)
Straight portion of the Bar is coated with a Conductive Paint for effective
conduction of Capacitive Currents in insulation to Ground.
flow point of the asphalt. This leaves space occupied by asphalt a void,
When voltage is applied, Total current that flows are 3 separate currents –
1. Capacitive Current
2. Absorption Current
3. Leakage Current
DIELECTRIC ABSORPTION CHARACTERISTICS
DRY, CLEAN
BFP - B MOTOR
INSULATION
12
10
IR value in Giga Ohm
0
0 1 2 3 4 5 6 7 8 9 10
IR 0 2.96 4.6 5.8 6.76 7.65 8.3 9.05 9.65 10.2 10.7
2.5
IR value in Giga Ohm
1.5
0.5
0
0 1 2 3 4 5 6 7 8 9 10
DAMP / DIRTY IR 0 1.84 1.95 1.98 2.02 2.04 2.05 2.06 2.06 2.08 2.08
IR values for clean and dry insulation will be, in general, slightly less for the
higher test voltages due to Dielectric Absorption effect. But a large decrease in
IR with higher Test Voltage is usually indicative that the insulation is in a less
satisfctory condition – perhaps due to Dirt or Moisture
The step voltage test is the best way to test the insulation on high capacitance
equipment. This is not suitable for low capacitance equipment.
The tip-up is normally the difference between 25% and 100% of rated line-to-
ground voltage.
It acquires current and voltage signals. Uses a FFT analyser to convert the
signals from time domain to frequency domain. Then it analyses various
harmonics signal conditioning to detect the faults.
PROOF TEST
It provides no diagnostic information or data which can be recorded for future
use – it tells what is going on at the moment of test.
Actual service conditions are not simulated during DC test, as stress distribution
is governed by resistivity and the insulation hence is unevenly stressed.
DC is far less damaging to insulation than AC, because of the virtual absence of
partial discharge.
The DC Hipot test is not a diagnostic test, but a go – no go test, since the
outcome is simply pass or fail.
A successful Hi-pot test indicates that no serious cracks have yet appeared in the
ground-wall. Gives some assurance that the ground-wall may be safely stressed
to normal operating voltage.
x multiplier
The electric stress distribution within the stator ground-wall insulation and in
the end winding is more realistic with AC than DC.
The typical RMS test voltage is 1.25 VL-L to 1.5 VL-L for stator winding tests,
although this voltage may be reduced for older windings.
Since severe partial discharge can occur during the AC test, test duration should
be as short as possible
SURGE COMPARISON TEST
Controlled electrical surges from discharging of capacitors are fed into the motor
windings. Instability in the damped return wave is evaluated by means of an
oscilloscope to indicate change in inductive reactance, which is result of of failure
of turn insulation.
CABLE TESTING
• Cable insulation is less prone to Cracking, ionisation, erosion than rotating machine.
Higher Voltage will be needed to show up defects.
D I E L E C T R I C S T R E N G T H I S A P H Y S I C A L T E S T,
AND NOT A ELECTRICAL TEST
• Cellulosic fibers
• Rust or other metallic cuttings
• Filter dust / Dirt
• Free water
B : Normally_refined oil
A : Highly_refined oil
Well over 99% of the Moisture is locked up in its Cellulose Insulation, while
Moisture in the oil is less than 1 %. Di-electric Test of the Oil reveals nothing
about the condition of the Solid Insulation where stress is maximum.
OXYGEN – THE SOURCE OF ALL DETERIORATIONS
Unstable hydrocarbons
(in oil)
+
Oxygen
(from dissolved air in oil and degraded cellulose)
+
Catalysts
(moisture, copper, and dissolved metallic compounds)
+
Accelerators
(heat, vibration, shock-loading, surge voltages, high electrical stress)
=
Oxidation by-product
(peroxide gases, acids, alcohols, aldehydes, ketones, metallic soaps, moisture)
1. The Peroxides so formed react with Cellulose to produce ‘Oxy-Cellulose’.
Acids react with Cellulose to produces ‘Hydro-Cellulose’.
Oxy-Cellulose lacks in mechanical strength & makes insulation embrittled.
2. Sludge occurs after the Oxidation products held in solution finally saturate the
oil and any additional products settle down in solid form.
Sludge may choke the oil ducts in the Transformer, preventing circulation of
the oil and thereby interfering with the removal of Heat.
MOISTURE - THE ENEMY NUMBER ONE !
• Due to this strong affinity, cellulose does not share the moisture equally with oil.
In equilibrium state, the moisture content of cellulose is about 800 times of oil !
• While pure Water is a polar liquid with high dielectric constant (permittivity)
between 79.5 and 81, most commercial insulating materials have dielectric
constant between 2 to 7. So, water gets attracted to areas of strong electric field
• At high temp, Residual Moisture in Insulation can trigger release of Gas bubbles.
PRESSURIZED BREATHING
TRANSFORMER
FREE BREATHING
TRANSFORMER
FREE BREATHING
CONSERVATOR
Many substances like Dust & Cotton Fibres that are non-conducting when dry,
can absorb moisture from oil and become conducting.
From dissolved air in oil, Moisture, copper, & Heat, electrical stress,
degraded cellulose dissolved metallic surge voltage,
compounds shock loading, etc
OXIDATION BY-PRODUCTS
MOISTURE HEAT
OIL-IMPREGNATED CELLULOSE
(O2 present)
CHEMICAL DEGRADATION
(acids, peroxides, more O2 , more H2O)
IN SUSPENSION
BOUND
FREE
COOLING THE TRANSFORMER GIVES OIL THE OPPORTUNITY TO UNLOAD ITS WATER
TO CELLULOSE.
MAX MOISTURE IN OIL AS A FUNCTION OF TEMP
AGED OIL HOLDS MORE WATER IN SOLUTION THAN THE NEW OIL (AS WATER GETS
ABSORBED INTO THE OIL DECAY PRODUCTS).
KARL FISHER IS THE ONLY WAY TO MEASURE THE TOTAL MOISTURE IN THE OIL -
WATER IN SOLUTION, WATER IN THE EMULSIVE STATE AND FREE WATER.
MEASURES DIRECTLY THE FREE & INORGANIC ACID PRESENT TOGETHER, HENCE
PROGRESS OF OXIDATION.
A USED OIL HAVING A HIGH ‘NN’ INDICATES THAT THE OIL IS EITHER OXIDIZED OR
CONTAMINATED WITH MATERIALS SUCH AS VARNISH, PAINT, OR OTHER MATTER.
MOISTURE IN PPM
Reveals total water content. Tells at
what temp water dissolved in oil will
condense.
• EVEN FOR OLD TRANSFORMERS, TAN DELTA SHOULD NOT EXCEED 4%.
SOME GENERAL CONDITIONS SUCH AS CONTAMINATED OIL ALSO CAN RESULT IN
INCREASED TAN-DELTA. AN INCREASE IN TAN-DELTA AS WELL AS CAPACITANCE
INDICATES THAT CONTAMINATION IS MOST LIKELY BY WATER.
IF TIP-UP TEST READING DOES NOT VARY WITH INCREASE IN VOLTAGE, THEN
MOISTURE IS PROBABLE CAUSE.
FURAN TEST
DP TEST
ARCING ACETYLENE
CORONA HYDROGEN
LOW-TEMP OVERHEATING METHANE
HIGH TEMP OVERHEATING ETHYLENE
IF THE RATE OF INCREASE IN GAS GENERATION IS HIGH OR IF THE GAS RATIOS ARE
DIFFERENT FROM THOSE FOR THE PREVIOUS ANALYSIS, A NEW FAULT MAY BE
THOUGHT TO SUPERIMPOSE OVER AN EXISTING ONE OR AGEING
Forms the basis for deciding on the period of testing or loading on the
transformer, etc.
ROGER’S AND IEC RATIO METHOD
RATIO METHODS ARE NOT “SURE THINGS”, BUT ONLY ADDITIONAL TOOLS TO
ANALYSE THE PROBLEMS. RATIO METHODS ARE FOR “FAULT ANALYZING” AND NOT
FOR “FAULT DETECTION”. IT MAY NOT TELL IF YOU HAVE A PROBLEM.
Careless sampling technique has been the source of 99% of “bad” dielectric readings.
Dry, clean apparatus and hands, a normal day ( < 50% humidity ).
Sample must be protected from contact with light, air, & moisture.
The sample should be drawn quickly, kept in a sealed container, and tested within few
hours.
EXPECTED PATTERN IS TWO SIMILAR HIGH CURRENTS ON OUTER PHASES AND ONE
LOWER READING ON THE CENTRE PHASE.
RVM :
TO GET GENERAL INDICATION OF MOISTURE IN CELLULOSE
TO GET IDEA ABOUT AGEING OF PAPER & OIL CONDITION
Wrong !
Transformer has no functional moving parts,
yet is moving continuously while energized.
The magnitude of the movement under
stress can be as high as three inches ( 76
mm ) for “stationary windings” !
No !
Dielectric strength does not speak about the dissolved moisture. A good
BDV often masks a grave moisture problem in the oil and cellulose. Oil
which is significantly oxidized but does not contain free moisture shall
show a good dielectric strength.
“Moisture in my oil is less than 20 ppm; and my transformer is safe.”
Grossly mistaken !
It is not absolute moisture in oil of concern; question is 20 ppm at what
temperature ppm at 60 0C can certainly be a reasonably good value, but
20 ppm at 30 0C is a very bad value.
“Look, I checked DGA readings thoroughly by Roger’s ratio. The ratio does not
detect a fault . “
Roger’s Ratio is a fault-analysing tool, not a fault detection tool. Even if gas
ratios donot fall into Fault Codes, Faults could still be there which can go
unnoticed.
“I am filtering my transformer as frequent as every year; what better could be
done ? “
Unnecessary filtration does more harms to the transformer than any good.
Filtration decision should be based on many test readings ( such as
moisture, cellulose tan-delta and IR, oil tan-delta, etc ) which confirm
presence of moisture.
“You can see the color of silica gel in my transformer; It’s always blue. So how
moisture can go in?”
Hold on ! There are many other entry passes for moisture. The suction side
of your oil pump for instance. Are they perfectly sealed ? What about the
oil – are they not sufficiently oxidized ? Deterioration of oil and cellulose
can produce a lot more moisture inside the transformer !
THANK YOU
1. Name 5 diagnostic tests in order of usefulness (from most useful to least
useful) in evaluating a HT motor insulation.
5. Give at least 3 means by which moisture can get into Transformer Oil?
6. Out of DC HV Test and AC HV Test, which one is more revealing and why?