Professional Documents
Culture Documents
Note: If a furnace tube fails, the boiler load must be restricted to 75%
of full power.
There are four locations where plugging of boiler tubes can be relevant.
These locations are shown in Figure 1 and marked as location A, B, C and
D respectively. The plugging locations are divide into two categories:
• Plugging of furnace tubes (section 1.1).
• Plugging of convection tubes (section Error! Reference source not
found.).
Figure 1 plug1.cdr
Furthermore two types of plugs are used for plugging the tubes, an internal
plug and an external plug. Both these types are shown in Figure 2. The
internal plugs are used in the intermediate and upper drum at location B, C
and D in Figure 1, and the external plugs are used in the furnace circular
header at location A.
Nut M20
30
Bolt M12
Tube stub
Figure 2 plug4.cdr
Plugging of the furnace tubes can be performed where the tubes are
connected to the furnace circular header (location A in Figure 1) and where
the furnace tubes are connected to the intermediate drum (location B in
Figure 1).
Plugging of the furnace tubes are described in section 1.1.1 and 1.1.2
respectively. The instructions for applying the refractory where tubes have
been cut away and plugged are described in section 1.1.3.
1.1.1 Plugging of furnace tubes at circular header
The procedure for cutting out a damaged tube piece and plugging the tube
at the circular header (location A in Figure 1), is shown in Figure 3 and
described in the following.
At this location an external plug is used.
Plugging of furnace tubes at circular header
Y-anchors
ø14 mm hole
Min 75 mm
Figure 3 plug2.cdr
At the top of the furnace the tube is to be cut as described in the following
section 1.1.2.
If the damaged tube is one of the tubes forming the burner opening, only
the visible part of the tube is to be removed.
Step C: Clean out any swarf, etc. from the circular header with a vacuum
cleaner.
Step D: The tube end is to be cleaned inside with emery cloth at a depth of
approx. 125 mm, before the external plug is fastened.
Step E: Drill a 14 mm hole in tube wall facing the furnace for fastening
the M12 bolt (see Figure 8). The hole is drilled 30 mm from the
end of the tube as shown in Figure 9.
Step F: Arrange the plug as shown in Figure 2.
Step G: Fasten the M12 bolt by your fingers only.
Step H: Fasten the M20 nut tight with a spanner.
Step I: Secure the M12 bolt by using a spanner.
1.1.2 Plugging of furnace tubes at intermediate drum
The procedure for cutting out a damage tube piece and plugging the
furnace tube at location B in Figure 1, is shown in Figure 4 and described
in the following.
Here the internal plug is used.
Fig 1.
B C
Fig 2.
A
VIEW A-A
CUT LINE
INSULATION
A
CASING
INTERNAL PLUG
FURNACE TUBE
DETAIL B
Figure 4 plug5.cdr
Step A: The tube is cut approx. 15 mm below the lining, without damaging
this. If the tube is going direct into the tube plate (one of the outer
tubes) then cut the tube approx. 25 mm below the tube plate
without damaging this.
When one of these outer tubes is removed, the insulation between furnace
and casing will be unprotected. This insulation is to be removed, and a
refractory lining is to be made to protect the casing (see section 1.1.3).
When the damaged tube has been removed then:
Step B: Clean the inside surface of the tube as mentioned in section 1.1.1.
Step C: The internal plug, (Figure 2), is to be secured by hammer strokes.
1.1.3 Applying refractory
When a furnace tube has been removed, the casing and the remaining piece
of the tube are to be protected with refractory. The refractory should be
Plicast 31.
Figure 5 shows how to apply refractory where the damaged tube piece has
been removed.
PLICAST 31
INSULATING PLICAST 31
C C CASTING
CASING
Fig 4.
VIEW B-B
PLICAST 31
A Fig 5.
Step A: Before applying the refractory wall ties have to be welded onto the
remaining tube piece, as shown in Figure 5 fig. 2 and fig. 3.
Step B: Refractory, Plicast 31, is attached to the furnace wall, see Figure 5.
Step C: Refractory lining at one of the bent furnace tubes is to be
performed as shown in Figure 5, fig. 2. The lining should reach
somewhat above the fins of the straight tubes.
Step D: Refractory lining at one of the straight furnace tubes is to be
performed as shown in Figure 5, fig. 3. The part of the insulation
which is not protected by fins and furnace tubes is to be removed
as shown on fig. 4.
Step E: At the furnace circular header, the remaining piece of tube and
tube plug are to be protected, and the lining is carried out as
shown in Figure 5, fig. 1 and 2.