Professional Documents
Culture Documents
Reference Manual
OF LARGE SUBSTATIONS
V 1.4
CP CU1 Reference Manual V 1.4
2
Contents
Contents
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operator Qualifications and Safety Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Conventions and Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating the Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Orderly Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1 Hardware Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.2 Circuit Diagram of CP CU1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3 Operating Controls of CP CU1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.4 CP CU1 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.5 CP GB1 Grounding Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.5.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.5.2 Shorting the Phases. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.5.3 Changing the Surge Arrestors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.6 Clamp-on Ammeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
2.1 Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2 Operating Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.3 Configuring CPC 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.4 Setting CP CU1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
3.1 Template Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Safety Instructions for Connecting CP CU1 to Power Lines . . . . . . . . . . . . . . . 26
3.2.1 Before Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2.2 Recommended Current Range Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2.3 Estimating the Open-Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2.4 Connecting the Measurement Setup to Power Lines. . . . . . . . . . . . . . . . . . . 28
3.3 k Factor Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3.1 Why k Factor Measurement? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3
CP CU1 Reference Manual V 1.4
4
Using This Manual
5
CP CU1 Reference Manual V 1.4
Symbol Description
Equipment damage or loss of data
possible.
Related Documents
The following documents complete the information covered in the CP CU1
Reference Manual:
Title Description
CPC 100 User Manual Contains information on how to use
the CPC 100 test system and
relevant safety instructions.
CPC 100 Reference Manual Contains detailed hardware and
software information on CPC 100
including relevant safety instructions.
6
Safety Rules
Safety Rules
Before operating the CP CU1 coupling unit, read the following safety rules
carefully. If you do not understand some safety rules, contact OMICRON
electronics before proceeding. CP CU1 is designated for use with the CPC 100
test system. Therefore observe the safety rules both in this Reference Manual
and in the CPC 100 User/Reference Manual when working with CP CU1.
Depending on the application and the device under test, specific safety
instructions must be observed. Very often the danger coming from the device
under test is even higher that the danger from CP CU1 itself. For application
specific safety instructions, see 3.2 "Safety Instructions for Connecting CP CU1
to Power Lines" on page 26.
General
Always observe the five safety rules:
• Disconnect completely
• Secure against re-connection
• Verify that the installation is dead
• Carry out grounding and short-circuiting
• Provide protection against adjacent live parts
Do not touch any terminals without a visible connection to ground.
Before handling CP CU1 or CPC 100 in any way, connect them with a solid
connection of at least 6 mm2 cross-section to ground. Ground CP CU1 as close
as possible to CPC 100.
Use the CP GB1 grounding box to connect CP CU1 to overhead lines and power
cables. For detailed information, see the application specific 3.2 "Safety
Instructions for Connecting CP CU1 to Power Lines" on page 26.
When using CP GB1, ground it near the place where the connection to the test
object is made. Make sure that the grounding stud is in good condition, clean
and free of oxidation.
Make sure that all studs and cables of CP GB1 are screwed tight.
Make sure that the test object’s terminals to be connected to CP CU1 do not
carry any voltage potential. During a test, the only power source for a test object
may be CP CU1 (powered by CPC 100). The only exception are measurements
on overhead lines as described in 3 "Applications" on page 25.
Do not open the CP CU1’s or CP GB1’s housing.
7
CP CU1 Reference Manual V 1.4
8
Safety Rules
Orderly Measures
The CP CU1 Reference Manual or alternatively the e-book in PDF format has
always to be available on the site where CP CU1 is being used. It must be read
and observed by all users of CP CU1.
CP CU1 may be used only as described in 3 "Applications" on page 25. Any
other use is not in accordance with the regulations. The manufacturer and/or
distributor is not liable for damage resulting from improper usage. The user
alone assumes all responsibility and risk.
Following the instructions provided in this Reference Manual is also considered
part of being in accordance with the regulations.
Disclaimer
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
9
CP CU1 Reference Manual V 1.4
10
Hardware Information
1 Hardware Information
1.1 Overview
CP CU1 is a coupling unit designated for measurements with the CPC 100 test
system mainly on overhead lines and power cables. Typical applications include
line and cable impedance measurements, measurements of k factors, mutual
coupling of power lines, measurements of coupling between power lines and
signal cables, and ground impedance measurements. The CP GB1 grounding
box (see 1.5 "CP GB1 Grounding Box" on page 14) available as an accessory
from OMICRON electronics is a surge arrestor unit protecting the operating staff
and equipment from high-voltage hazards during measurements on overhead
lines and power cables in case of unexpected events on the power line.
Voltmeter
Surge arrestor VT
11
CP CU1 Reference Manual V 1.4
12
Hardware Information
13
CP CU1 Reference Manual V 1.4
14
Hardware Information
1-2: "Grounding Studs and Socket Clamps" below. For ordering information,
contact OMICRON electronics sales office. When ordering CP GB1, choose one
connection set; additional connection sets are available optionally.
Table 1-2:
Grounding Studs and
Socket Clamps
Grounding Stud in the Substation Proper Grounding Socket Clamp
16 mm cylindrical 16…20 mm grounding socket clamp
grounding stud (shipped with the 16 mm cylindrical
and 20 mm ball CP GB1’s studs)
12 mm
20 mm ball
grounding stud
15
CP CU1 Reference Manual V 1.4
For transportation, the CP GB1’s studs are usually removed. If this is the case,
mount them onto CP GB1 using the delivered wrench and screw them tight (see
Figure 1-4: "Screwing the CP GB1’s Studs" on page 16).
16
Hardware Information
To short the phases, connect the line studs of CP GB1 as shown in Figure
1-6: "Shorting the Phases" below.
Figure 1-6:
Shorting the Phases
17
CP CU1 Reference Manual V 1.4
Note: Before changing the surge arrestors, check whether there is a fault
that caused the problem and remove it.
18
Hardware Information
Contact screw
3. Turn CP GB1 upright and move the stud over the surge arrestor chamber
until the surge arrestor falls out.
4. Replace the defective surge arrestor by the spare one.
5. Screw the contact screw very tight (torsional moment of 15…20 Nm).
19
CP CU1 Reference Manual V 1.4
20
Operation
2 Operation
2.1 Measurement Setup
The measurement setup consists of the CPC 100 test system, of the CP CU1
coupling unit and, in case of measurements on overhead lines and power
cables, of the CP GB1 grounding box. Figure 2-1: "Measurement Setup" below
shows the functional block diagram.
Caution: CP CU1 must be connected to the test object through the CP GB1
grounding box for measurements on overhead lines or power cables. For
these applications, connect the measurement setup by following
3.2 "Safety Instructions for Connecting CP CU1 to Power Lines" on
page 26.
Figure 2-1:
Measurement Setup
Dangerous zone
V1 AC I AC I AC V1 AC CP GB1
I OUT (optional)
CPC 100 CP CU1 Device under test
EXT. BOOSTER BOOSTER V SENSE
21
CP CU1 Reference Manual V 1.4
22
Operation
Figure 2-3:
Quick Test Card
Window
Output Range
combo box
Measured
Quantities
combo box
4. Open the item list from the Output Range combo box.
The item list displays the CU1:10A, CU1:20A, CU1:50A and CU1:100A
CP CU1 relevant current ranges.
5. Select VT sel and/or CT sel from the Measured Quantities combo boxes
when measuring with the CP CU1’s built-in voltage and current transformers
to account for their transformation ratio.
6. Select the current range you want to use.
23
CP CU1 Reference Manual V 1.4
24
Applications
3 Applications
3.1 Template Usage
The test procedures running on the measurement setup are controlled by
templates available on the CPC Explorer CD-ROM shipped with your CP CU1
or in the customer area of the OMICRON electronics home page
http://www.omicron.at.
The templates are pairs of XML documents and Microsoft Excel templates
designed by OMICRON electronics for designated applications. The XML
templates are predefined test procedures, often with comments, that run on
CPC 100 and guide the user through the test. Once completed, the XML file is
saved, downloaded to the PC using CPC Explorer and then loaded into the
corresponding Microsoft Excel template. There the results are post processed
and a final test report is generated. The template pairs facilitate and speed
testing with CP CU1 and the evaluation of results.
Note: Some template pairs allow version control. If an error message
appears after loading the XML template, use a template pair of the same
version.
To run a test procedure according a template:
1. Using CPC Explorer, upload the XML template for the intended application
from the PC to CPC 100.
2. Open the template on CPC 100.
3. Run the test procedure according to the template.
4. After completing the test procedure, save the test in a new file.
5. Using CPC Explorer, download the test results from CPC 100 to your
preferred working directory on the PC.
6. Open the corresponding Microsoft Excel template by double-clicking the
*.xlt file in the folder labeled with the test procedure name.
A Microsoft Excel workbook appears.
7. Click the Load XML-File button and open the *.xml file saved in your
preferred working directory before to load the test results.
8. After all worksheets are filled with data, the test results are calculated.
25
CP CU1 Reference Manual V 1.4
26
Applications
27
CP CU1 Reference Manual V 1.4
Caution: During the grounding switch at the near end of the power line is
open, the area around CP GB1 in the range of 5 m/15 ft and around CP CU1
in the range of 2 m/5 ft is a dangerous zone due to high-voltage and
mechanical hazards. Do not enter the dangerous zone. Keep the
grounding switch open for a time as short as possible.
Caution: If you see or hear anything uncommon in the test equipment, e.g.
noise of electrical discharge or lightening of surge arrestors, close the
grounding switch before touching the measurement setup.
28
Applications
Figure 3-1:
Wiring the
Measurement Setup Connection using
grounding sets on site
L3/C L2/B L1/A
8. Ground CPC 100 using a cable of at least 6 mm2 cross-section close to the
position of the operator.
9. Connect CP CU1 with CPC 100 as shown in Figure 3-1: "Wiring the
Measurement Setup" above.
10.Mark the area around CP GB1 in the range of at least 5 m/15 ft and around
CP CU1 in the range of at least 2 m/5 ft as dangerous zone.
11.Open the grounding switch and read the voltmeter on the CP CU1’s front
panel from outside of the dangerous zone.
Caution: If the voltmeter’s reading is
• > 500 V, stop. The measurement is not possible due to high-voltage
hazard.
• 250…500 V, the measurement is possible only in the 10 A range.
• 100…250 V, the measurement is possible in the 10 A or 20 A range.
• 50…100 V, the measurement is possible in the 10 A, 20 A or 50 A range.
• < 50 V, the measurement is possible in all current ranges.
If the open-line voltage allows measurement, proceed as described in the
respective "Performing Measurements" section of the following applications.
Caution: Make sure that the grounding switch is always closed when no
measurement is performed and especially when the wiring is modified or
the current range switch of CP CU1 is set.
29
CP CU1 Reference Manual V 1.4
30
Applications
Figure 3-2:
Zero-Sequence
Impedance Definition
31
CP CU1 Reference Manual V 1.4
In the course of the k factor test procedure, the following measurements are
performed:
• Line-to-line impedance measurements: L1-L2, L1-L3, L2-L3 (Figure
3-3: "Line-to-Line Impedance Measurements" below shows the L1-L2
measurement as example.)
Figure 3-3:
Line-to-Line Impedance Far end Near end
Measurements
Overhead line
V1 AC I AC I AC V1 AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER CP GB1
V SENSE
32
Applications
Overhead line
V1 AC I AC I AC V1 AC I OUT
CP GB1
CPC 100 CP CU1
EXT. BOOSTER BOOSTER
V SENSE
33
CP CU1 Reference Manual V 1.4
Overhead line
V1 AC I AC I AC V1 AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER
V SENSE
CP GB1
34
Applications
After wiring the measurement setup to the line under test proceed as follows:
1. Configure CPC 100 as described in 2.3 "Configuring CPC 100" on page 22
for the CP CU1’s current range set by the current range switch.
Caution: The configured current range must not exceed the limit by the
open-line voltage.
2. Choose the XML template for the mains frequency
(e.g. "Line Imp CU1 60Hz.xmt" for the 60 Hz mains frequency) and open the
template.
Caution: Open the grounding switch at the near end before making the test
and keep it open only during the measurement. Close the grounding
switch after the test and before reconnecting the measurement setup.
3. Run the test procedure.
The following measurements are performed:
• Line-to-line measurements: L1-L2, L1-L3, L2-L3
For each measurement, connect the I OUT and V SENSE inputs of
CP CU1 to the corresponding CP GB1’s line studs.
• Line-to-ground-measurements: L1-E, L2-E, L3-E
For each measurement, connect the I OUT and V SENSE inputs of
CP CU1 to the corresponding CP GB1’s line studs.
• Zero-sequence impedance measurement: L1||L2||L3-E
4. If an overload of CPC 100 occurs, reduce the test current or set a lower
current range and run the test procedure once again.
Lower test currents at the two highest frequencies are recommended.
5. Save the test procedure as a file on CPC 100.
6. Download the test file from CPC 100 to the PC using CPC Explorer.
7. Load the test file into the Microsoft Excel template.
The measurement results are displayed.
The measurement of mutual coupling of two power lines is performed in a similar
way. All three phases of both systems under test are connected together and
grounded at the far end of the line. The current II is fed into all the phases of the
system I and the voltage UII is measured on the near end of the system II which
is not grounded here. The mutual coupling factor for the relay II is then given by
kM0 = (UII/II)/ZLII (Eq. 3-7)
35
CP CU1 Reference Manual V 1.4
36
Applications
Figure 3-6:
Measurement Results
37
CP CU1 Reference Manual V 1.4
Figure 3-7:
Measured Overhead
Line
L2
L1 L3
The L2-E measurement features the lowest X component because the line is
very close to the ground wire. The X component of the L3-E measurement is
decreased by a parallel system taking course close to L3 on the other side of the
tower. Short-circuiting of the parallel system during the measurement would
have increased the effect and would have lead to erroneous results because this
is not the normal operating condition. The interpretation of the result of zero-
sequence impedance measurement is more difficult. Some methods for
verifying it are shown below.
Several intermediate results are hidden in the Microsoft Excel template due to
their minor importance. However, by clicking on the "+" symbol on the left (see
the lines 32 and 51 in Figure 3-6: "Measurement Results" on page 37) you can
view the individual k factor results for each line. If the individual measurements
are very close to each other and close to the overall k factor, the measurement
is most likely correct. Broadly spread results with the average value close to the
overall k factor value indicate a very asymmetrical line under test but the results
are most likely correct. If the individual k factor measurements differ
considerably from each other, the relay should be set to a value smaller than the
average k factor to avoid zone overreaches.
38
Applications
Another interesting effect can be observed when measuring power cables. If the
screen or shield is very close to the conductors but the conductors are relatively
wide from each other, the inductive part of the line-to-line measurements is
higher than the inductive part of the line-to-ground measurements, resulting in a
negative X component of the calculated impedance ZE. This seemingly strange
result is explained as follows. Recalling (see 3.3.1 "Why k Factor
Measurement?" on page 30) that the zero-sequence impedance is given by
Z0 = Z1 + 3ZE (Eq. 3-8)
and hence
ZE = (Z0 –Z1)/3 (Eq. 3-9)
where Z1 is the positive-sequence impedance and ZE is defined as a difference
between the line-to-ground loop measurement and a half of the line-to-line loop
measurement, the X component of ZE can become negative.
39
CP CU1 Reference Manual V 1.4
40
Applications
Figure 3-8:
Ground Impedance and
Step Voltage
Measurement
90º
V1 AC I AC I AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER
CP GB1
41
CP CU1 Reference Manual V 1.4
42
Applications
43
CP CU1 Reference Manual V 1.4
Figure 3-9:
Ground Impedance vs.
Distance for a Terrain
Approaching Optimum
In some cases, measurement results shows peaks and drops until an area free
of buildings and buried conductors or pipes is reached. Until then, erroneous
results can be obtained. Figure 3-10: "Ground Impedance vs. Distance for a
Difficult Terrain" below shows typical measurement results obtained under such
conditions. The graph shows a peak due to a street lamp close to the test probe.
The street lamp was connected to a protective ground wire approaching the
location of the remote grounding system. Voltage drops can be observed when
the measurement points are set close to objects (i.e. towers of power lines
leaving the substation under test) connected to the grounding system under test.
Figure 3-10:
Ground Impedance vs.
Distance for a Difficult
Terrain
In a difficult terrain, the measurement results may show no noticeable trend until
values converging to a constant are obtained. Consequently, the terrain analysis
on site is of highest importance. Setting the measurement points close to the line
injecting the current results in erroneously high measured values. An area within
the angle of at least 60º relative to the line should be avoided.
44
Applications
45
CP CU1 Reference Manual V 1.4
In the course of the test procedure, the following tests are performed:
• Calibration with the loop shaped by two lines with the largest area (Figure
3-11: "Calibration with the Line-to-Line Loop" below shows the L1-L3
calibration as example)
Short-circuit the measurement cable and connect it to the cable under test.
Figure 3-11:
Calibration with the
Line-to-Line Loop
V2 AC I AC I AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER CP GB1
46
Applications
• Measurement with the loop shaped by two lines with the largest area (Figure
3-12: "Measurement with the Line-to-Line Loop" below shows the L1-L3
measurement as example)
Figure 3-12:
Measurement with the
Line-to-Line Loop
Signal cable
V2 AC I AC I AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER CP GB1
47
CP CU1 Reference Manual V 1.4
• Measurement with the loop shaped by three lines in parallel and the ground
(see Figure 3-13: "Measurement with the Loop Between Parallel Lines and
Ground" below)
Short the three phases with the delivered three-lead cable as shown in Figure
1-6: "Shorting the Phases" on page 17.
Figure 3-13:
Measurement with the
Loop Between Parallel
Lines and Ground
Signal cable
V2 AC I AC I AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER
CP GB1
48
Applications
• Calibration with the loop shaped by three lines in parallel and the ground (see
Figure 3-14: "Calibration with the Loop Between Parallel Lines and Ground"
below)
Short the three phases with the delivered three-lead cable as shown in Figure
1-6: "Shorting the Phases" on page 17. Short-circuit the measurement cable
and connect it to the cable under test.
Figure 3-14:
Calibration with the
Loop Between Parallel
Lines and Ground
V2 AC I AC I AC I OUT
CPC 100 CP CU1
EXT. BOOSTER BOOSTER
CP GB1
49
CP CU1 Reference Manual V 1.4
50
Technical Data
4 Technical Data
4.1 CP CU1 Output Ranges
Table 4-1:
Output Ranges of
CP CU1
Range Current Compliance Voltage @ > 45 Hz
10 A 0…10 Arms 500 Vrms
20 A 0…20 Arms 250 Vrms
50 A 0…50 Arms 100 Vrms
100 A 0…100 Arms 50 Vrms
51
CP CU1 Reference Manual V 1.4
52
Technical Data
4.6 Accuracy
Table 4-6:
Accuracy of CPC 100
and CP CU1
Impedance Typ. Typ. V SENSE I OUT Current
Range Accuracy1 Accuracy1 Voltage Current Range
of abs(Z) of Phase
Value Angle
0.05…0.2 Ω 1.0…0.5% 1.5…0.8º 5…20 V 100 A 100 A
0.2…2 Ω 0.5…0.3% 0.8…0.5º 20…50 V 100…25 A 100 A
2…5 Ω 0.3% 0.5º 100 V 50…20 A 50 A
5…25 Ω 0.3% 0.5º 100…250 V 20…10 A 20 A
25…300 Ω 0.3…1.0% 0.5…1.5º 250…500 V 10…1.5 A 10 A
1. Ambient temperature 23ºC ± 5ºC/73ºF ± 10ºF
53
CP CU1 Reference Manual V 1.4
For detailed information on the clamp-on ammeter, see the Digital Clamp Meter
User’s Manual shipped with the clamp-on ammeter.
54
Contact Information / Technical Support
Asia, Pacific
OMICRON electronics Asia Ltd, Hong Kong
Phone: +852 2634 0377
E-Mail: support@asia.omicron.at
Web: www.omicron.at
55
OMICRON Contact Addresses
56
Index
Index
E
EN 50110-1 . . . . . . . . . . . . . . . . . . . . . . . 5, 53
EN 50191 . . . . . . . . . . . . . . . . . . . . . . . . . 5, 53
A EN 61010-1 . . . . . . . . . . . . . . . . . . . . . . . . . 53
address
manufacturer . . . . . . . . . . . . . . . . . . . . . . 55
arc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 F
factor
current reduction . . . . . . . . . . . . . . . . . . . 43
B ground impedance matching . . . . . . . . . . 30
k . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30, 38
BOOSTER input . . . . . . . . . . . . . . . . . . . . . . 12 frequency selective measurements . . . . . . . 22
front panel . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C
cardiac pacemaker . . . . . . . . . . . . . . . . . . . . . 8
G
CENELEC HD637 S :1999 . . . . . . . . . . . . . . 43 ground impedance matching factor . . . . . . . 30
CENELEC HD637S1 . . . . . . . . . . . . . . . . . . 39 grounding cables . . . . . . . . . . . . . . . . . . . . . 27
clamp-on ammeter . . . . . . . . . . . . . . 20, 27, 43 grounding stud . . . . . . . . . . . . . . . . . . . . 14, 28
coupling grounding switch . . . . . . . . . . . . . . . . . . . . . 27
into signal cables . . . . . . . . . . . . . . . . . . . 45
mutual . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
coupling impedance . . . . . . . . . . . . . . . . . . . 45
CPC 100 software . . . . . . . . . . . . . . . . . . 21, 23
CPC Explorer . . . . . . . . . . . . . . . . . . . . . . . . 25
H
CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 hotline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
current range switch . . . . . . . . . . . . . . . . . . . 12
current reduction factor . . . . . . . . . . . . . . . . . 43
I
I AC output . . . . . . . . . . . . . . . . . . . . . . . . . . 12
D I OUT current output . . . . . . . . . . . . . . . . . . 12
dangerous zone . . . . . . . . . . . . . . . . . . . 28, 29 IEEE Std 80-2000 . . . . . . . . . . . . . . . . . . . . 39
dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 54 IEEE Std 81-1983 . . . . . . . . . . . . . . . . . . . . 39
DIN VDE 0101 . . . . . . . . . . . . . . . . . . . . . . . 39 IEEE 510 . . . . . . . . . . . . . . . . . . . . . . . . . 5, 53
impedance
ground . . . . . . . . . . . . . . . 30, 39, 40, 42, 43
line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
57
CP CU1 Reference Manual V 1.4
positive-sequence . . . . . . . . . . . . . . . 30, 39
zero-sequence . . . . . . . . . . . . . . . . . . . . . 30
IP20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
S
safety instructions . . . . . . . . . . . . . . . . . . . . 26
safety regulations . . . . . . . . . . . . . . . . . . . . . . 5
safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
K Service
OMICRON address . . . . . . . . . . . . . . . . . 55
k factor . . . . . . . . . . . . . . . . . . . . . . . . . . 30, 38 short-circuit bar . . . . . . . . . . . . . . . . . . . . . . 12
socket clamp . . . . . . . . . . . . . . . . . . . . . 16, 28
step voltage . . . . . . . . . . . . . . . . . . . 40, 42, 45
support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
L surge arrestor . . . . . . . . . . . . . . . . . . . . . . . . 14
changing . . . . . . . . . . . . . . . . . . . . . . . . . 18
LAPG 1710.6 NASA . . . . . . . . . . . . . . . . . 5, 53
T
M technical support . . . . . . . . . . . . . . . . . . . . . 55
manufacturer address . . . . . . . . . . . . . . . . . . 55 templates . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
measurement setup . . . . . . . . . . . . . . . . . . . 21 thunderstorm . . . . . . . . . . . . . . . . . . . . . . . . 26
mutual coupling . . . . . . . . . . . . . . . . . . . . . . . 35
O V
V SENSE input . . . . . . . . . . . . . . . . . . . . . . . 12
OMICRON address . . . . . . . . . . . . . . . . . . . . 55 V1 AC output . . . . . . . . . . . . . . . . . . . . . . . . 12
open-line voltage VDE 0101 . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
estimated . . . . . . . . . . . . . . . . . . . . . . . . . 27 VDE 0104 . . . . . . . . . . . . . . . . . . . . . . . . . 5, 53
measured . . . . . . . . . . . . . . . . . . . . . . . . . 29 VDE 0105 Part 100 . . . . . . . . . . . . . . . . . 5, 53
operator qualifications . . . . . . . . . . . . . . . . . . . 5 voltmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
orderly measures . . . . . . . . . . . . . . . . . . . . . . 9 VT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12, 31
P W
parallel weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 wiring
system . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 CP GP1 . . . . . . . . . . . . . . . . . . . . . . . . . . 29
working ground . . . . . . . . . . . . . . . . . . . . . . . 27
58