Professional Documents
Culture Documents
6.3-Off-Grid Solar System PDF
6.3-Off-Grid Solar System PDF
EN B12
CHINT Off-grid
PV System Solution
June 2019
Contents:
1. Company Introduction 01
1. Equipment supply 06
2. System design 07
2. Working Principle 09
3. Main equipment 10
4. System Solution 18
New Energy Power P&D
s
Instruments & Mete
Automation
NOARK
and integrated supplier, with strength from power generation, storage, power construction in the global market.
transmission, transformation,distribution to terminal consumption.To
01 http://en.chint.com/ http://en.chint.com/ 02
CHINT PV in the world
GANSU NEIMENG
Cases
03 http://en.chint.com/ http://en.chint.com/ 04
Business scope and competitive advantage Equipment Supply
Normally we take granted that electricity can be obtained anywhere, but at present more than 2 billion
people live without electricity in the world: most of them live in poor and remote areas, far away from power
plants and public grid which makes their life inconvenient and lack of modern civil information. CHNIT is
committed to solving the power problems in areas without power or power instability. With the advantage
of easy installations, low maintenance and operating cost, zero carbon emission, automatic running, and
inexhaustible solar, the off-grid PV system is gradually become the first choice.
PV Arrays Controller Off-grid Inverter
05 http://en.chint.com/
System design System solution
PV Modules
Based on the strong industry chain advantages and PV plants development, design and construction advantage, CHINT
provides the world-leading One-stop solution for Off-grid PV system.
Solar
Cables Controller/Inverter
Residential Off-grid system
The residential off-grid PV system can be
installed on the roof or on the ground.
According to the IEA survey, 1.456 billion
people live in a power-poor environment,
83% of whom are born in rural areas,
which is why most off-grid systems are
Professional on-site construction guidance and used in rural areas. It has the characteristics
after-sales service
of low-cost, clean, renewable, reliable and
convenient, easy installation and
maintenance, etc.
The company has a strong and experienced team in product development, system design and
engineering construction. It can provide comprehensive Off-grid PV system solutions, professional
on-site construction technical guidance and stable after-sales service.
07 http://en.chint.com/ http://en.chint.com/ 08
Working principle Main equipment
Off-grid PV system consists of seven parts: PV modules, DC combiner box, controller, off-grid Inverter, batteries, cables
and mounting system. The power of Off-grid PV system can be used for user equipment during the day, the excess
Off-grid Inverter electricity generated during the day can also be stored in batteries and used for equipment at night.
Meters Grid
PV Modules
1 PV module is composed of several solar cells, which absorb the solar radiation of sunlight and convert it into
electricity to provide power for the whole system.
1 AC Switchgear
2 PV Combinerbox Monocrystalline Polycrystalline
3 Controller
4 Battery Cells 60-72 Cells 60-72
Output: 275Wp-385Wp Output: 255Wp-345Wp
Module Efficlency Up to 19.7% Module Efficlency Up to 18.5%
Loads Size 1648x990x35mm Size 1648x990x35mm
1986x992x40mm 1954x990x40mm
1 2 3 4
AC charging Pole
09 http://en.chint.com/ http://en.chint.com/ 10
2
MECHANICAL SPECIFICATIONS PACKING SPECIFICATIONS The controller adopts MPPT technology and maximizes the utilization of solar
1648 x 990 x 35 mm ①
Weight (module only) 18.3 kg / 40.34 lbs
Outer dimensions (L x W x H) panels; System sampling advanced circuit topology design brings ultra-high
64.88 x 38.98 x 1.38 in ②
Packing unit 31 pcs / box
Frame technology Aluminum, silver / black anodized power conversion efficiency of equipment, system efficiency up to 95%,
Weight of packing unit reducing energy loss process. Meanwhile it has intelligent battery management,
Module composition Glass / EVA / Backsheet (white) 606 kg / 1336 lbs
(for 40‘HQ container)
Front glass thickness 3.2 mm / 0.13 in Number of modules per monitoring alarm and DC distribution functions. The device meets the
868 pcs
①
Cable length (IEC/UL) 900 mm / 35.43 in 40‘HQ container maintenance requirement; the control module and monitoring module are all
Cable diameter (IEC/UL) 4 mm² / 12 AWG
①
②
Tolerance +/- 1.0kg modular design.
Subject to sales contract
②
Maximum mechanical test load 6000 Pa
Fire performance (IEC/UL) Class C (IEC) or Type 1 (UL)
Connector type (IEC/UL) MC4 compatible
①
②
Refer to Astronergy Crystalline Silicon PV Module Installation Manual or contact technical department.
Maximum Mechanical Test Load=1.5×Maximum Mechanical Design Load.
MODULE DIMENSION DETAILS Voltage level CPS DI48 CPS DI96 CPS DI192 CPS DI220 CPS DI240 CPS DI360
Rated voltage (VDC) 48 96 192 220 240 360
990 mm/3.248 feet 35 mm/0.115 feet
Over voltage value(VDC) 62 124 248 279 310 465
A-A I
16-3.5 mm x 8.5 mm/
0.011 feet x 0.028 feet 40:1 10:1 Over voltage recovery value(VDC) 60 120 240 270 300 450
Drainage hole Float charge Voltage(VDC) Settable 54 108 216 243 270 405
11 mm/0.036 feet
18.5 mm/0.061 feet 7 mm/0.023 feet Bulk charge Voltage(VDC) Settable 56.8 113.6 227.2 255.6 284 426
200 mm/0.656 feet
11
Charging Mode Three-stage: constant current(MPPT), bulk charge, float charge
35 mm/0.115 feet
0
/0.
626 mm/2.054 feet
mm
3.5
5.7/11.4/ 11.4/22.8/ 12.8/25.6/ 14.2/28.4/
MPPT voltage range (VDC) 50-150 110-280 230-450 260-450 290-450 410-620
6-7 mm x 11.5 mm /
946 mm/3.104 feet
Maximum input voltage (VDC) 170 300 480 760
0.023 feet x 0.038 feet 35 mm/0.115 feet
Mounting hole >98%
>99%
Noise (dB) <55
Degree of protection IP20
Display LCD+LED
Communication RS485(optional)
Working temperature -10~+50℃
Relative humidity 0 to 95% (non-condensing)
Altitude (m) ≤5000m, (1000 meters above derating)
Degree of protection IP20
Dimensions (W H D mm) 400*280*160 400*280*160/440*685*440
PV array reverse polarity protection; reverse battery protection; nighttime anti-charge protection;
Protection
battery overcharge protection, output overload protection, over temperature protection ect.
11 http://en.chint.com/ http://en.chint.com/ 12
3 CPS SI series off-grid inverter is particularly designed for off-grid power system Model Three Phase Inverter
with high efficiency up to 85%. The excellent overload capacity and complete Rated power(W) 10K 20K 30K 40K 50K 80K 100K 120K 150K 200K
protection are suitable for all sorts of electrical appliances. The inverter can DC voltage 220V/240V/360V/384V 360V/384V
be used in harsh environments e.g. wide temperature range, high altitude, Phase Tri-phase+N+G
etc. This series can be applied for solar lighting, remote communication Rated voltage 380VAC±1%(steady-state load),380VAC±3%( )
base, high way monitoring system, custom system of pastoral areas and less Rated frequency 50Hz±0.05%
developed areas, etc.
Frequency stability < ±0.05%
Frequency
stability:when < ±5%
synchronous
Crest factor 3:01
Model Single Phase Inverter Output wave Pure sine wave
THD linear load < 3%, un-linear load < 5%
Rated capacity 6-8KVA 6-10KVA 6-15KVA 6-15KVA 20-30KVA
Battery Dynamic
load voltage < ±5%
Rated Voltage(VDC) 96 110 192 220 240 transient(0-100%
jump)
Shut down voltage(VDC)
86.4 97.2 172.8 194.4 216
(Settable) Recovery time < 20ms
Low voltage recovery Balanced load < ±1%;< ±5%(un-balanced load voltage)
104 117 208 234 260 voltage
value(VDC)
Overload capacity 125% 10min,150% 1min
Over voltage protective
128 144.5 256 288 320 >90%
value(VDC)
Over voltage recovery communication RS232,(485, Network remote, optional)
124 139.5 248 279 310 interface
value(VDC)
Mains bypass(Optional) working 0 ~ 40℃
temperature
Input voltage range(Vac) 110/220/230/240±15%(Special voltage can be customized)
Relative
Input frequency(Hz) 50/60±3% humidity(non 30% ~ 90%
condensation)
AC charging current Optional
AC output Max.altitude <1000mts(decrease 1% when the hight increase every 100mts,max.5000mts)
Output wave L+N, Pure sine wave cooling method forced cooling
Output voltage(Vac) 110/220/230/240±1%(optional) noise dB 45 ~ 55
Output frequency(Hz) 50/60±1% Case color Black(optional)
Output£¨THD) ≤2%(linear load) Input cable bottom/front
(80% easy maintenance front/top/left and right side all can be opened
≥85%
line load)
Weight(kg) 220 300 400 480 750 900 1000 1200 1400 1800
Current peak factor 3:01
Dimension 480*840*1228 765*640*1610 1040*815*1735 1105*900*1810 1490*1100*1910
Over load ability 105-110%,600s;110-125%,60s;>125%,1s W×D×H(mm)
Display LCD+LED
Input inverse polarity protection, input under-voltage protection, input overvoltage protection, output
Protection overload protection, output short circuit protection(need to restart machine because of No automatic
recovery)、overheat protection.
Communication RS485/GPRS(optional)
Ambient environment
Protection degree IP20
Applied altitude(m) ≤5000(1000 meters above derating)
Permissible relative
<95% (No condensation)
humidity
Environment
-10 ~ +50
temperature(℃ )
Noise(1 meter) ≤50dB
Size and weight
W*D*H(mm) 305*645*770(192V-6K:210*580*580) 405*699*978
Weight(Kg) 65-85(192V-6K:45) 105-125
13 http://en.chint.com/ http://en.chint.com/ 14
3 CPS SIC series off-grid inverter adopts integrated design of solar controller, Model Single Phase Solar Controller & Inverter
inverter and isolated transformer. The controller adopts MPPT technology Rated capacity 3-5KVA 5-8KVA 5-8KVA 5-15KVA 5-15KVA 20-30KVA
and intelligent battery management design which is very efficient and smart; Battery
integrated pure sine wave inverter and low frequency isolated transformer Rated Voltage(VDC) 48 96 110 192 220 240
Low voltage protective
make it with excellent overload performance, suitable for a variety of electrical 43.2 86.4 97.2 172.8 194.4 216
value(VDC)
appliances. Low voltage recovery
52 104 117 208 234 260
value(VDC)
Over voltage protective
62 124 139.5 248 279 310
value(VDC)
Over voltage recovery
60 120 135 240 270 300
value(VDC)
PV input
Max input power(kWp) 3.4 5.7 6.4 11.4 12.8 14.2/28.4
Max charge current(A) 60 50 50/100
Start voltage(VDC) 60 120 130 240 270 300
Model Single Phase Solar Controller & Inverter MPPT work range(VDC) 50-150 110-280 120-280 230-450 260-450 290-450
Max input PV
170 300 300 480 480 480
Type CPS SIC-W 1.5/2K CPS SIC-W 3/4/5K voltage£¨VDC)
Rated power 1.2KW/1.6KW 2.4KW/3.2KW/4KW Float charge Voltage(VDC)
54 108 121.5 216 243 270
Settable
Battery Bulk charge Voltage(VDC)
Rated voltage(VDC) 24 48 56.8 113.6 127.8 227.2 255.6 284
Settable
Overvoltage protection point(VDC) 33 66 Mains bypass(Optional)
Overvoltage protection recovery point (VDC) 32 64 Input voltage range(Vac) 110/220/230/240±15%(Special voltage can be customized)
Floating Charge Voltage (VDC) settable 27 54 Input frequency(Hz) 50/60±3%
Bulk charge Voltage(VDC) settable 28.4 56.8 AC charging current Optional
PV input AC output
Max input power(kWp) 0.85/1.7 3.4 Output wave L+N, Pure sine wave
Max charging current(A) 30/60 60 Output voltage(Vac) 110/220/230/240±1%(optional)
Start voltage(VDC) 30 60
Output frequency(Hz) 50/60±1%
MPPT work range(VDC) 25-75 50-150
Output(THD) ≤2%(linear load)
Max input PV voltage(VDC) 85 170 (80% line
Mains bypass ≥85%
load)
Input voltage range(Vac) 220±15%/110±15%(Special voltage can be customized) Current peak factor 3:01
Input frequency(Hz) 50/60±3% Over load ability 105-110%,600s;110-125%,60s;>125%,1s
AC charging current 10A (default) Display LCD+LED
AC output Input inverse polarity protection, input under-voltage protection, input overvoltage protection, output
Output wave Pure sine wave Protection overload protection, output short circuit protection(need to restart machine because of No automatic
Output voltage 220VAC±1%;110VAC±1%(Special voltage can be customized) recovery)、overheat protection.
Output frequency 50/60±1% Communication RS485/GPRS(optional)
Output(THD) ≤2%(linear load) Ambient environment
(80% line load) ≥85% Protection degree IP20
Current peak factor 3:01 Applied altitude(m) ≤5000(1000 meters above derating)
Over load ability 105-110%,600s;110-125%,60s;>125%,1s
Permissible relative humidity <95% (No condensation)
Display LCD+LED
Environment temperature(℃ ) -10 ~ +50
PV reverse protection, input under-voltage protection, input overvoltage protection,
Protection output overload protection, output short circuit protection(need to restart machine Noise(1 meter) ≤50dB
because of no automatic recovery)、overheat protection. Size and weight
Communication RS485/(optional) D*W*H(mm) 560*220*515 600*305*800 750*450*1100
Ambient environment Weight(Kg) 35-45 80-85 80-95 120-140
Protection degree IP20
Applied altitude(m) ≤5000(1000 meters above derating 1% every 100m)
Permissible relative humidity <95% (No condensation)
Environment temperature(℃ ) -20 ~ +50
Noise(1 meter) ≤50dB
Size and weight
W*D*H(mm) 337*214.5*503
Weight(Kg) 20-35
15 http://en.chint.com/ http://en.chint.com/ 16
System Solution
17 http://en.chint.com/ http://en.chint.com/ 18
Type CPS OGS1.6K - 9.6kWh Type CPS OGS6.4K - 38.4kWh
NO. Product Name Technical Parameter Unit QTY Notes NO. Product Name Technical Parameter Unit QTY Notes
1 PV Modules 280Wp Poly pcs 6 2 pics of PV modules connect to one string 1 PV Modules 280Wp Poly pcs 20 5 pics of PV modules connect to one string
2 Mounting System 1.68kWp set 1 Customized 2 Mounting System 5.6kWp set 1 Customized
3 Solar Controller & Inverter CPS SIC24-2KT-W,AC220V/50HZ set 1 3 DC Combiner Box 4-IN-1 set 1
4 Batteries and battery rack 12V200AH set 4 4 Solar Controller & Inverter CPS SIC96-8KT,AC220V/50HZ set 1
5 MC4 Connector 1 positive, 1 negative pair 4 5 Batteries and battery rack 2V400AH set 48
Estimated: from PV modules to the solar 6 MC4 Connector 1 positive, 1 negative pair 5
6 DC Cable PV1-F 1×4 m 50 charger & Inverter
7 DC Cable PV1-F 1×4 m 150 Estimated: from PV modules to the DC
Estimated: from Battery to solar charger & combiner box
7 DC Cable ZC-YJV 0.6/1kV 2*10mm2 m 5 Inverter
8 DC Cable ZC-YJV 0.6/1kV 2*10mm2 m 30 Estimated: from DC combiner box to the solar
charger & Inverter
8 PE Cable BVR 4mm2 m 30
9 DC Cable ZC-YJV 0.6/1kV 2*25mm2 m 5 Estimated: from Battery to solar charger &
Notes: Largest AC load is about 1.6kW, and available battery capacity is about 5.76kWh. Inverter
10 PE Cable BVR 6mm2 m 30
11 AC Cable ZC-YJV 0.6/1kV 2*16mm2 m 20 Estimated: from solar charger & inverter to the
AC box
12 AC Box set 1 Option, Customized
Type CPS OGS2.4K - 14.4kWh
Notes: Largest AC load is about 6.4kW, and available battery capacity is about 23.04kWh.
NO. Product Name Technical Parameter Unit QTY Notes
1 PV Modules 280Wp Poly pcs 8 4 pics of PV modules connect to one string
2 Mounting System 2.24kWp set 1 Customized
3 Solar Controller & Inverter CPS SIC48-3KT-W,AC220V/50HZ set 1
4 Batteries and battery rack 12V150AH set 8 Type CPS OGS8K - 57.6kWh
5 MC4 Connector 1 positive, 1 negative pair 3
NO. Product Name Technical Parameter Unit QTY Notes
Estimated: from PV modules to the solar
6 DC Cable PV1-F 1×4 m 80 charger & Inverter 1 PV Modules 280Wp Poly pcs 27 9 pics of PV modules connect to one string
Estimated: from Battery to solar charger & 2 Mounting System 7.56kWp set 1 Customized
7 DC Cable ZC-YJV 0.6/1kV 2*16mm2 m 5 Inverter
8 PE Cable BVR 4mm2 m 30 3 DC Combiner Box 3-IN-1 set 1
Notes: Largest AC load is about 2.4kW, and available battery capacity is about 8.64kWh. 4 Solar Controller & Inverter CPS SIC192-10KT,AC220V/50HZ set 1
5 MC4 Connector 1 positive, 1 negative pair 4 Notes: Largest AC load is about 8kW, and available battery capacity is about 34.56kWh.
7 DC Cable ZC-YJV 0.6/1kV 2*16mm2 m 5 Estimated: from Battery to solar charger &
Inverter
8 PE Cable BVR 4mm2 m 30
Notes: Largest AC load is about 3.2kW, and available battery capacity is about 11.52kWh.
19 http://en.chint.com/ http://en.chint.com/ 20
Type CPS OGS12K - 88kWh(Three-Phase) Type CPS OGS24K - 180kWh(Three-Phase)
NO. Product Name Technical Parameter Unit QTY Notes NO. Product Name Technical Parameter Unit QTY Notes
1 PV Modules 280Wp Poly pcs 44 11 pics of PV modules connect to one string 1 PV Modules 280Wp Poly pcs 90 15 pics of PV modules connect to one string
2 Mounting System 12.32kWp set 1 Customized 2 Mounting System 25.2kWp set 1 Customized
3 DC Combiner Box 4-IN-1 set 1 3 DC Combiner Box 5-IN-1 set 1
4 Solar Inverter CPS SI220-15KT,AC380V/50HZ set 1 4 Solar Inverter CPS SI360-30KT,AC380V/50HZ set 1
5 Charger controller CPS DI220-100A set 1 5 Charger controller CPS DI360-80A set 1
6 Batteries and battery rack 2V400AH set 110 6 Batteries and battery rack 12V250AH set 60
7 MC4 Connector 1 positive, 1 negative pair 5 7 MC4 Connector 1 positive, 1 negative pair 6
Estimated: from PV modules to the DC Estimated: from PV modules to the DC
8 DC Cable PV1-F 1×4 m 250 combiner box 8 DC Cable PV1-F 1×4 m 250
combiner box
Estimated: from DC combiner box to the solar Estimated: from DC combiner box to the solar
9 DC Cable ZC-YJV 0.6/1kV 2*10mm2 m 30 charger 9 DC Cable ZC-YJV 0.6/1kV 2*16mm2 m 30
charger & Inverter
Estimated: from Battery to solar charger & Estimated: from Battery to solar charger &
10 DC Cable ZC-YJV 0.6/1kV 2*25mm2 m 10 solar charger to inverter 10 DC Cable ZC-YJV 0.6/1kV 2*25mm2 m 10
solar charger to inverter
11 PE Cable BVR 10mm2 m 30 11 PE Cable BVR 10mm2 m 30 Estimated: for Inverter and controller
Estimated: from solar charger & inverter to Estimated: from solar charger & inverter to
12 AC Cable ZC-YJV 3*6+1*4mm m 20 three phase loads(distribution box) 12 AC Cable ZC-YJV 3*10+1*6mm m 20
three phase loads(distribution box)
13 AC Box set 1 Option, Customized 13 AC Box set 1 Option, Customized
Notes: Largest AC load is about 12kW, and available battery capacity is about 52.8kWh. Notes: Largest AC load is about 24kW, and available battery capacity is about 108kWh.
9 DC Cable ZC-YJV 0.6/1kV 2*16mm2 m 30 Estimated: from DC combiner box to the solar
charger & Inverter
10 DC Cable ZC-YJV 0.6/1kV 2*25mm2 m 10 Estimated: from Battery to solar charger &
solar charger to inverter
11 PE Cable BVR 10mm2 m 30 Estimated: for Inverter and controller
21 http://en.chint.com/ http://en.chint.com/ 22