Professional Documents
Culture Documents
NEXTseries
Water-Cooled Fixed Speed
TWO STAGE
DSP-132W6N
DSP-145W6N
DSP-160W6N
DSP-200W6N
DSP-240W6N
DSP-160V6WN
DSP-240V6WN
● This INSTRUCTION MANUAL explains in detail
the important items that require attention;
observed as the following:
● Always observe notations of WARNING, CAUTION
and IMPORTANT, as they indicate considerable
risks to safety.
GRAPHIC DESCRIPTIONS:
WARNING
Never remove a protective device from the air compressor or modi-
fy the air compressor.
It is imperative to install an earth leakage (ground) circuit breaker
on the power cable. This prevents a ground fault accident.
DSP air compressors are not designed, intended or approved for
breathing air applications. Hitachi does not approve specialized
equipment for breathing air applications and assumes no responsi-
bility or liability for compressors used for breathing air services.
DS P - 160 V W 6 N
Dry or Oil-Free Rotary
Screw Air Compressor N-Type (NEXT Series)
Frequency (6: 60 Hz)
Packaged
W: Water-Cooled
w/ V: VSD, w/o V: Fixed
Motor Output (kW)
● Hitachi may make improvements and/or changes in the products described in this publication at any time without notice.
Contents
1. SAFETY ………………………………………………………………………………………… 2
10. PRECAUTIONS WHEN THE COMPRESSOR IS TO BE IDLE FOR AN EXTENDED PERIOD OF TIME …………… 84
11. PARTS LIST ………………………………………………………………………………………… 85
1
1. SAFETY
To ensure safe and proper operation of the air compressor, it is indispensable to carefully
read and understand the following warnings and instructions detailed below. These warn-
ings and instructions are attached to the air compressor as shown in the figure below.
WARNING
WARNING Electric Shock Hazard!
●Before servicing or wiring the
Rotating Parts! air compressor, disconnect
●Keep hands and rods, etc. away from the power. This will prevent
the rotating parts (Cooling fans, etc.)
●Use caution at all times, when air com- anyone from turning on the
pressor is powered. The air compres- power and causing an elec-
sor may be capable of restarting with- tric shock that could lead to
out hitting the START button. severe injury or death.
●When the air compressor is operating,
do not remove or open the enclosure ●Do not allow any unlicensed
panels and doors. person to wire the air compres-
●Before servicing the air compressor, sor. Always use a licensed
stop it, disconnect the power, especially electrician.
when accessing any rotating parts.
●Ground the air compressor.
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
WARNING
Discharge Air pipe Electric Shock Hazard!
Heated!! ●Before servicing or wiring the
air compressor, disconnect
the power. This will prevent
anyone from turning on the
power and causing an elec-
tric shock that could lead to
severe injury or death.
Aftercooler Header ●Do not allow any unlicensed
person to wire the air compres-
sor. Always use a licensed
electrician.
Air End ●Ground the air compressor.
2
1. SAFETY
WARNING WARNING
WARNING
WARNING
3
2. GENERAL DESCRIPTION
This section illustrates and describes the major components of the DSP air compressor. Be familiar
with the name, location and function of each component before using the DSP air compressor.
2.1 Appearance
2.1.1 Fixed Speed
[Front View]
Air Exhaust
(Air Compressor Package)
Instrument Panel This panel discharges
See page p. 10, chap- the hot air generated
ter 3, for details. in the air compressor.
Enclosure
Front Left Door Enclosure panels
lower the sound level
Open the front left
of the air compressor
door only when servic-
ing the DSP air com- package.
pressor. Keep it closed
when operating the
DSP air compressor. Compressor Name plate
Model designation,
manufacturing number
and specification are
printed.
Power Supply Port
Check the specifica-
tions, power supply Plate of Operating /
and voltage before Servicing Instructions
connecting the power Read carefully the
supply. plate before operating
and servicing the DSP.
Air Exhaust
Air Exhaust
Air Intake
(Inlet to the Air End) OMR
See page 55 for the
details
Air Intake
4
2. GENERAL DESCRIPTION [Appearance]
[Front View]
Air Exhaust
(Air Compressor Package)
This panel discharges
the hot air generated
in the air compressor.
Instrument Panel
See page p. 10, chap-
ter 3, for details.
Enclosure
Enclosure panels
lower the sound level
Front Left Door
of the air compressor
Open the front left package.
door only when servic-
ing the DSP air com-
pressor. Keep it closed
when operating the
DSP air compressor.
Plate of Operating /
Servicing Instructions
Power Supply Port Read carefully the
plate before operating
Check the specifica- and servicing the DSP.
tions, power supply
and voltage before
connecting the power
supply.
Air Exhaust
[Rear View]
Air Exhaust
Air Exhaust
5
2. GENERAL DESCRIPTION [Components]
2.2 Components
Intercooler
Enclosure
Ventilating Fan
Oil Pump
Instrument Panel
Main Motor
Common Base
6
2. GENERAL DESCRIPTION [Daily Operating Components]
運転管理 運転状況
RUNNING CONTROL RUNNING MODE
自 動
AUTO
モニタ 警 報 遠 方 電 源
REMOTE
MONITOR
POWER
ALARM
メニュー 負 荷
[× 10h] LOAD
MENU
機 能 リセット 起動待ち
FUNC RESET 故 障 AUTO START
+/− SHUTDOWN
UP/
DOWN
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
設 定 STR 1 2
SET
MONITOR
UNLOAD STOP
7
2. GENERAL DESCRIPTION [Daily Operating Components]
Sight Glass
8
2. GENERAL DESCRIPTION [Daily Operating Components]
7 Stopping operation
● Normally use UNLOAD STOP button to stop the
compressor. The compressor then unloads for 5
minutes and stops running.
(In the case of an emergency, press the STOP
button to stop operation.)
運転管理 運転状況
RUNNING CONTROL RUNNING MODE
自 動
AUTO
モニタ 警 報 遠 方 電 源
REMOTE
MONITOR
POWER
ALARM
メニュー 負 荷
[× 10h] LOAD
MENU
機 能 リセット 起動待ち
FUNC RESET 故 障 AUTO START
+/− SHUTDOWN
UP/
DOWN
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
設 定 STR 1 2
SET
MONITOR
UNLOAD STOP
IMPORTANT
9
3. OPERATING THE DSP
3.1 Instrument Panel
Liquid Crystal Display MONITOR Button AUTO light (yellow) RESET Button
(LCD) Enables movement within ON (glowing) when an Reset the system or cancels
Displays the operation data, each of the monitoring automatic operation (an the shutdown/alarm circuit
various setting, shutdowns/ displays (M1, M2) and the AUTO operation, a schedul- ( page 15)
alarms information, etc message display (M3). This ing operation, or lead/lag
button also enables you to operation) is activated.
( page 13)
return to the M1 display from ON (flashing) when external
the FUNCTION MENU calendar or scheduling
display ( page 13). operation is abnormal.
( page 16, 20)
自 動
AUTO
モニタ
MONITOR
メニュー
MENU
+/−
UP/
DOWN
設 定
SET
MONITOR
10
3. OPERATING THE DSP [Instrument Panel]
Y
AUTO START light (green):
ON (glowing) while the air compressor is in a stop due to an
AUTO operation, lead/lag operation, or scheduling operation.
ON (blinking) while the air compressor is in a stop due to a
STOP restartable instantaneous power interruption. ( page 16)
SHUTDOWN light (red):
ON (either glowing or blinking) when a shutdown/alarm
problem has occurred. ( page 15)
運転管理 運転状況
RUNNING CONTROL RUNNING MODE
警 報 遠 方 電 源 STOP Button
REMOTE
ALARM
POWER Used to stop the compressor
負 荷 immediately without first unload-
[× 10h] LOAD
機 能 リセット 起動待ち ing. ( page 12)
FUNC RESET 故 障 AUTO START
SHUTDOWN
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
STR 1 2 UNLOAD STOP Button
Used for normal stop. Stops
after the compressor and air
hoses are dry. ( page 12)
11
3. OPERATING THE DSP [Start/Stop Operation]
COMPRESSOR MONITOR
CONTROLLER
3.2.3 Emergency Stop
Pressing EMERGENCY STOP botton, the DSP com-
pressor immediately.
5 sec
This switch should only be pressed in emergency.
㻞 㻜 㻜 㻥 䠋 㻜 㻠 䠋 㻝 㻟 㻝 㻥 䠖 㻜 㻞 The compressor can not be restarted until the switch is
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻜 㻜 㼜 㼟 㼕 manually reset. Turn the switch knob clockwise and
press the RESET button to reset.
㻾 㼁 㻺 㻌㻴 㻻 㼁 㻾 䠖 㻝 㻞 㻜 䡄
㻸 㻻 㻭 㻰 㻌 㻴 㻻 㼁 㻾 䠖 㻡 㻠 䡄
㻸 㻻 㻭 㻰 㼀 㻵 㻹 㻱 㻿 䠖 㻝 㻞 㻟
㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻝 㻝 䠂
㻸 㻻 㻭 㻰 㼀 㻵 㻹 㻱 䠖 㻞 㻠 䡏
㼁 㻺 㻸 㻻 㻭 㻰 㻌 㼀 㻵 㻹 㻱 䠖 㻝 䡏
㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻡 㻜 䠝
㻲 㻾 㻱 㻽 㼁 㻱 㻺 㻯 㼅 䠖 㻞 㻟 㻚 㻤 䠤 䡖
㻻 㼁 㼀 㻼 㼁 㼀 䠖 㻝 㻜 㻚 㻡 䡇 䠳
12
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
㻿 㻱 㼀 䠖 㻻 㻼 㻱 㻺 㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
モニタ
䠘 㻿 㻴 㼁 㼀 㻰 㻻 㼃 㻺 䠚
㻯 㻻 㻻 㻸 㻭 㻺 㼀 䠖
㻻
㻞
㻵
䠪
㻸
㻰
䠖
㻌 㻿 㼁 㻯 㼀 䠊 㼀 㻱 㼜 㼟 㼕
■ Message Display
モニタ 㻴
㻯
㻵
㻻
㻳
㻺
㻴
㼀
㻌㻰
㻭 㻯
㻵
㼀
㻿
㻻
䠊 㼀 㻱 㼜
㻾 㻌㻱 㻾
㼟 㼕
㻾 䠖
There is only one message display: M3 (the contents,
㻻
㻸
㼂
㻻
㻱
㼃
㻾
㻌
㻸 㻻
㼃 䠊
㻭 㻰 䠖
㻵 㻺 㼀 㻿 㼀 㻳 㻌 㻼 䠊 however, vary from time to time). It is available only
MONITOR
when some event (air compressor alarm or shutdown,
㻰 㻾 㼅 㻱 㻾 㻌㻌㻌㻌 㼃 䠋 㻻 㻌 㻿 㻱 㻼 䠊
㻱 㻸 㻱 㻹 㻱 㻺 㼀
㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㻌 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊
maintenance notice, etc.) has occurred. Once an event
happens, however, the M3 message display appears
immediately and automatically. From the M3 display,
pressing the MONITOR button will switch the LCD
to the M1 or M2 monitoring displays; but after
approximately ten (10) seconds, the M1 or M2 moni-
toring displays will revert back to the M3 display.
13
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
IMPORTANT
(1) Displays current time. Asterisk flashes. (6) Indicates the amperage current of the main motor
(CURRENT).
(2) Indicates a capacity control type.
(7) Displays an operating frequency of main motor.
(3) Displays compressor discharge port pressure.
(V type only. Fixed speed type displays **.*)
(4) Indicates total running hours (RUN HOUR), total
(8) Indicates “***” for this air compressor.
loaded hours (LOAD HOUR), and total number of
loads (LOAD TIMES.). (9) Displays master or slave control status when in lead/
Blink asterisk indicates running time is being mea- lag operation mode.
sured.
(10) Displays various pressures and temperatures.
(5) Indicates a percentage of load to unload of the DSP air (Asterisk indicates not in use.)
compressor (LOAD RATE), For Vtype, the rate is cal-
(11) Displays time remaining till next inspection as main-
culated based on only frequency. Indicates “***”,
tenance period and next maintenance period.
if PQ wide mode is selected.
14
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
䠘 㻿 㻴 㼁 㼀 㻰 㻻 㼃 㻺 䠚 䠘 㻲 㻭 㻵 㻸 㼁 㻾 㻱 䠚
㻯 㻻 㻻 㻸 㻭 㻺 㼀 䠖
㻻 㻵 㻸 䠖
㻞 䠪 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 㻱 㻹 㻼 㻌 㻿 㼅 㻿 㼀 㻱 㻹 㻱 㻾 㻾 䠖 㼙 㼙 㼙 㼙
㻴 㻵 㻳 㻴 㻌㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 䠖 㻿 㼅 㻿 㼀 㻱 㻹 㻌 㻾 㻱 㼀 㻾 㼅
㻯 㻻 㻺 㼀 㻭 㻯 㼀 㻻 㻾 㻌㻱 㻾 㻾 䠖 㻼 㻯 㻮 㻌 㻱 㻾 㻾 䠖 㼚 㼚 㼚 㼚 㼚 㼚
㻻 㼂 㻱 㻾 㻸 㻻 㻭 㻰 䠖 㻼 㻾 㻱 㻿 㻿 䠊 㻿 㻺 㻿 㻾 㻌 㻱 㻾 㻾 䠖 㼛
㻸 㻻 㼃 㻌 㼃 䠊 㻵 㻺 㼀 㻿 㼀 㻳 㻌 㻼 䠊 㼀 㻱 㻹 㻼 䠊 㻿 㻺 㻿 㻾 㻱 㻾 㻾 䠖 㼜
㻰 㻾 㼅 㻱 㻾 㻌㻌㻌㻌 㼃 䠋 㻻 㻌 㻿 㻱 㻼 䠊 㻰 䡅 㼟 㼏 㼛 㼚 㼚 㼑 㼏 㼠 㼜 㼛 㼣 㼑 㼞
㻱 㻸 㻱 㻹 㻱 㻺 㼀 㼟 㼚 㼐 㼏 㼛 㼚 㼠 㼍 㼏 㼠
㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㻌 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊 㼐 㼕 㼟 㼠 㼞 䡅 㼎 㼡 㼠 㼛 㼞
(Example) (Example)
In the case the thermal relay trips and the compressor stops Example of temperature sensor malfunction, sensor 1 discon-
running, SHUTDOWN and OVERLOAD flash and the mal- nection FAILURE and TEMPERATURE SENSOR flash and
function part of the main circuit is indicated. the location of the abnormality is indicated.
② Take the proper corrective action, and press the RESET button.
③ For further information, see pages 33, 34.
NOTE) Malfunction detection of water failure is available for only water cooled single stage compressor. Malfunction
detection of dryer is available for only built-in dryer models. Malfunction detection of oil water separator and
element is not available.
■ Alarm Messages
① In the case an alarm occurs for the compressor, the ALARM light and contents / details displayed on alarm screen on
the LCD monitor flash and operation continues. There are 2 types of alarm screens: ALARM and PROBLEM.
㻞 㻜 㻜 㻥 䠋 㻜 㻤 䠋 㻜 㻝 㻝 㻥 䠖 㻝 㻥 㻖 㻞 㻜 㻜 㻥 䠋 㻜 㻤 䠋 㻜 㻝 㻝 㻥 䠖 㻝 㻥 㻖
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㻌 㻌 㻌 㻌 㻌 㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㻌 㻌 㻌 㻌 㻌
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 䚷 䚷 㻢 㻣 㼜 㼟 㼕 㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 䚷 䚷 㻢 㻣 㼜 㼟 㼕
䠘 㻭 㻸 㻭 㻾 㻹 䠚 䠘 㻼 㻾 㻻 㻮 㻸 㻱 㻹 䠚
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 䠖 䠄 㻌 㻌 㻌 䠅 㻖 㻖 㻖 䉣
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 䠖 㻖 㻖 㻖 䉣 㻯 㻻 㻺 㻺 㻱 㻯 㼀 㻵 㻻 㻺 㻌 㻱 㻾 㻾 䠖 㻌 㻌 㻌
㻸 㻻 㼃 㻌 㻻 䠊 㻼 䠊 䠖 㻖 䠊 㻖 㻖 㼜 㼟 㼕 㻾 㼑 㼏 㼛 㼚 㼚 㼑 㼏 㼠 㻌 㼜 㼛 㼣 㼑 㼞 䠊
㻯 㻸 㼀 䠊 㼀 㻱 㻹 㻼 䠊 䠖 㻖 㻖 㻖 䉣 㻹 㼁 㻸 㼀 䠥 㻙 㼁 㻿 㻱 㼀 㻱 㻾 㻾
㻸 㻻 㼃 㻌 㻯 㻸 㼀 䠊 㻼
㻖 䠊 䠖 㻖 㻖 㼜 㼟 㼕 㻿 㻯 㻴 㻱 㻰 㼁 㻸 㻱 㻌 㻿 㻱 㼀 㻌 㻱 㻾 㻾
㻞 䠪 㻰 㻙 㻿 䠊 㼀 㻱 㻹
㻲 㻵 㻼 㻌 㻺 㻙 㼀 㻯 㻻 㻹 䠊 㻱 㻾 㻾 㻌 㻿 㼀 㻻 㻼 䠖 㻌 㻌 㻌 㻌 㻌
㻸 㻻 㼃 㻌 㼃 䠊 㻸 㻻 㼃 㻌 㻻 㻵 㻸 㻯 㻻 㻹 䠊 㻱 㻾 㻾 㻌 㻭 㻸 㻹 䠖 㻌 㻌 㻌 㻌 㻌
㻰 㻾 㼅 㻱 㻾 㻭 㻵 㻾 㻌㻲 㻵 㻸 㼀 㻱 㻾 㻮 㻭 㼀 㼀 㻱 㻾 㼅 㻌㻻 㼁 㼀
㻸 䠊 㻯 㻻 㼁 㻺 㼀 㻌 㻻 㼂 㻱 㻾 㻌 㼃 䠋 㻻 㻌 㻿 䠊
㻼 㼞 㼑 㼟 䡏 㻾 㻱 㻿 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊 㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㼍 㼒 㼠 㼑 㼞 㻯 㻴 㻷 䠊
(Example) (Example)
In the case ALARM and AIR FILTER flash while the com- Example of battery replacement period.
pressor is running, it indicates the filter is clogged.
② Take the proper corrective action, and press the RESET button.
③ For further information, see pages 33, 34.
NOTE) Malfunction detection of water failure is available for only water cooled single stage compressor. Malfunction
detection of dryer is available for only built-in dryer models. Malfunction detection of oil water separator and
element is not available.
IMPORTANT
ALARM and PROBLEM messages are treated as alarms, but aside from connection abnormalities that make operation impos-
sible such as reverse phase and no phase when power is turned on, they also may indicate shutdown due to malfunction of the
communication status.
15
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
● DRYER PRESTARTED
(Note: Applies only to machines equipped with a
built-in dryer.)
<AUTO START light flashes>
When dryer prestart is set, the dryer starts operating
in advance, and compressor stopped status is indicat-
ed.
RESTART WAIT time is counted down.
● AUTO OPERATION
(Note: Applies only to machines equipped with
AUTO function)
<AUTO START light ON>
Indicates status stopped by low load when set to
AUTO operation. AUTO START light flashes during
restart limit while stopped, and RESTART WAIT time
is counted down.
16
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
㻞 㻜 㻜 㻥 䠋 㻜 㻤 䠋 㻜 㻝 㻝 㻥 䠖 㻜 㻞 㻖
Every these calendar periods: Service the DSP according to the schedules:
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㻌 㻌 㻌 㻌 㻌
0.5 years, 1.5 years, 2.5 years
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻌 㻌 㻢 㻣 㼜 㼟 㼕 Half-Yearly
3.5 years, 4.5 years, 5.5 years
CAUTION
If the inspection/maintenance is displayed, check the display contents, refer to maintenance standards
given in the compressor instruction manual and perform inspection/maintenance as soon as possible.
When inspection is complete, press and hold the SET button for at least 7 seconds.
The LCD monitor display contents then move to “Maintenance initial value completed” of the message
screen, and then return to the monitor screen 1 minute later.
NOTES:
1. MAINTenance can be reset, if the servicing is done earlier than expected and if the remaining operating time to next maintenance
is less than 2,000h in the case of A, 1,000h in the case of B.
2. On the contrary, if the servicing is done after the maintenance notice has appeared, the remaining operating hours to the next main-
tenance has been zero until the maintenance is done. After maintenance and resetting the counter, new counting time starts just
after the maintenance notice message has appeared on the display.
■ Other Messages
(1) SWITCHED TO LOCAL. (3) UNLOAD STOP
If set to local by remote operation following shut- If the UNLOAD STOP button is used, the display
down restoration, operation automatically returns flashes. The compressor unloads for 5 minutes and
to local when shutdown occurs, and the message is then stops.
displayed for 1 minute. For setting details, see
“3.4 How to Use the Digital Monitor.”
( page 25)
17
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
18
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
19
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
20
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
latest data is displayed for item 1. The screen shows ① Operation state is indicated by a symbol next to the
record for 2 times, and the necessary data can be con- shutdown code.
firmed by △ ▽ button operation. If altered before
L: Load, U: Unload, S: Stop
time is up, the data prior to change is maintained, and the
Displays alarm contents and code, date, time, state and
time recorded as soon as the data is altered changes.
how many times alarm occurred. If the same alarm con-
1. and 2. - :Indicates the MONTH / DAY HOUR: MINUTE.
tinues to occur, it is overwritten as update data, and the
P - Represents a pressure (psi) and indicates, from left to
number of times the alarm occurs is updated. The latest
right, the: Discharge air pressure, pressure data.
warning is recorded as item 1. If there is no alarm, aster-
C - Current (A).
isks are displayed. The screen displays data for 3 types,
T - Represents a temperature (℉) and indicates from
and the necessary data can be confirmed by △ ▽
left to right: 1st stage discharge air temperature, 2nd
button operation.
stage discharge air temperature.
L - Represents a load ratio percentage (%). and out put (kW).
If there is no data, an asterisk is displayed. 8 Shutdown History Display
㻝 䠊 㻮 㻭 㻿 㻵 㻯 㻌㻿 㻱 㼀 㼁 㻼
㻞 䠊 㻹 㼁 㻸 㼀 㻵 㻙㼁 㻺 㻵 㼀
㻟 䠊 㻯 㻭 㻼 㻭 㻯 㻵㼀 㼅 㻯 㻻 㻺 㼀 㻾 㻻 㻸
㼇 㻰 㻱 㼀 㻭 㻵 㻸 㻿 㼉
㻠 䠊 㻿 㻯 㻴 㻱 㻰 㼁㻸 㻱
㼇 㻸 㻻 㻭 㻰 㻰 㻭 㼀 㻭 㼉 㻡 䠊 㻻 㻼 㻱 㻾 㻭 㻝㻵
㼀 䠊
㻻 㻺 㻰 㻭 㼍㼀 㻭㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍
㻢 䠊 㻸 㻻 㻭 㻰 㻰㻭 㻰
㼀 㻭㻵 㻿 䠊 㻼 㻾 㻱 㻿 䠖 㻌 㻌 㻠 㻤 㼜 㼟 㼕
㻣 䠊 㻭 㻸 㻭 㻾 㻹 㻴 㻵㻵 㻿㻺 㼀 㼀㻻 㻿㻾 㼀
㼅 㻳 䠊 㻼 䠖 㻖 䠊 㻖 㻖 㼜 㼟 㼕
㻝 䠊 㻜 㻤 䠋 㻜 㻝 㻤 䠊 㻿 㻴 㼁 㼀 㻰 㻻 㼃 㻺
㻻 㻴 㻵 㻿 㼀 㻻 㻾 㼅
㻵 㻸 㻼 㻾 㻱 㻿 䠖 㻖 䠊 㻖 㻖 㼜 㼟 㼕
㻭 㼂 㻳 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻌 㻌 㻣 㻡 㼜 㼟 㼕 㻯 㻸 㼀 䠊 㻼 㻾 㻱 㻿 䠖 㻖 䠊 㻖 㻖 㼜 㼟 㼕
㻭 㼂 㻳 䠊 㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻜 㻠 㻜 䠝 㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 䠊 㻝 䠖 㻝 㻤 㻜 䉣
㻭 㼂 㻳 䠊 㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻜 㻢 㻡 䠂 㻿 㻱 㼀 䠖 㻻 㻼 㻱 㻺 㻰
㻹 㻻㻵 㻺 㻿 䠖 䠊㻮 㼀
㻭 㻯㻱 㻷㻹 㻼 䠊 㻞 䠖 㻝 㻤 㻜 䉣
㻻 㻵 㻸 㼀 㻱 㻹 㻼 䠖 㻖 㻖 㻖 䉣
㻭 㼂 㻳 䠊 㻼 䠫 䠳 䠡 䠮 䠖 㻌 㻝 㻣 㻚 㻤 㼗 㼃
㻯 㻸 㼀 䠊 㼀 㻱 㻹 㻼 䠖 㻖 㻖 㻖 䉣
㻞 䠊 㻜 㻝 䠋 㻜 㻝 㻞 㻺 㻰 㻿 㼁 㻯 㼀 䠊 㼀 䠖 㻖 㻖 㻖 䉣
㻭 㼂 㻳 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻌 㻌 㻣 㻡 㼜 㼟 㼕 㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻝 㻜 㻜 㻭
㻭 㼂 㻳 䠊 㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻜 㻠 㻜 䠝
㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
㻭 㼂 㻳 䠊 㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻜 㻢 㻡 䠂
㻭 㼂 㻳 䠊 㻼 䠫 䠳 䠡 䠮 䠖 㻌 㻝 㻣 㻚 㻤 㼗 㼃
Up to 6 items of alarm history are recorded aside from
㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷 shutdown history. Contents and occurrence state can be
This display shows the averaged load data per day. Data confirmed. Select the number of the shutdown on the
can be recorded for a maximum of six days; the 7th day of SHUTDOWN HISTORY screen, press the SET button
averaged loaded data is automatically deleted and the 1st and the operation state when the shutdown occurred can
or most recent day of averaged data is added. The most furthermore be confirmed on the details screen.
recent data is arranged at the top of the display. ● How to clear shutdown and alarm history.
The screen shows record for 2 times, and the necessary
If you want to clear the entire shutdown history and
data can be confirmed by △ ▽ button operation.
alarm history, set F041 from the F mode of the digital
Data is averaged from operation start to stop. The aver-
age is however fixed at 0.00 minutes in the case of 24 monitor to “1: CLEAR HISTORY” while referring to
hours operation. the instructions manual of the compressor.
21
3. OPERATING THE DSP [How to Use the Liquid Crystal Display (LCD)]
22
3. OPERATING THE DSP [How to Use the Digital Monitor]
Press SWITCH DISPLAY. on the screen of the digital monitor. Use the following proce-
Flashes when operation time is added. dure to switch the digital monitor to other display.
Operation time (×10)
① Press the SWITCH DISPLAY button. Operation time is
then displayed on the screen.
表示切替 1 b : Interstage pressure (psi)
Proceeds by 1 each
② Press the SWITCH DISPLAY button. Interstage pressure
time pressed. is then displayed on the screen together with “b.”
C: Compressor discharge
2
temperature (℉) ③ Press the SWITCH DISPLAY button. Compressor discharge
Returns by 1 each (122℉)
time pressed. temperature is then displayed on the screen together with
23
3. OPERATING THE DSP [How to Use the Digital Monitor]
IMPORTANT
Not used (display only) If the shutdown code “XX ”is “ ” it means there is no
shutdown history. Also, when anything other than shut-
down history is displayed without resetting shutdown,
To display of various settings it returns to the latest shutdown history in 3 minutes.
(3) How to Display Various Settings (Perform operation only when confirmation is
necessary.)
Discharge pressure display Use the following procedure to display capacity control type
SWITCH DISPLAY
1
No.0 : Control status and pressure setting values for confirmation.
A : Capacity control type
Press 16 times.
① Press the SWITCH DISPLAY button 16 times. “0.A**” is
No.1 : Start pressure 1
100 : 100psi
then displayed on the screen. ** changes with specifica-
表示切替 1
tions. “A” may be “L” or “U” depending on capacity control
No.2 : Recover pressure 1
Proceeds by 1 087 : 87psi specifications.
each time pressed.
2
② Consists of items 0 - 9. Pressure setting status and optional
No.3 : Pressure differential 1
Returns by 1 each
007 : 7psi pressure setting 2 can be confirmed each time the SWITCH
time pressed.
No.4 : ECOMODE
[Energy conservation mode]
DISPLAY button is pressed.
Decision time
リセット
③ Press the RESET Button. The screen then returns to the
Returns to No.5 : Start pressure 2
discharge pressure.
100 : 100psi usual discharge pressure display.
24
3. OPERATING THE DSP [How to Use the Digital Monitor]
■ Various settings (instantaneous power interruption (IPI), remote operation, capacity control
setting, pressure setting, etc.)
Switches display from monitor mode to setting mode (F mode).
リセット
Displays 000th item of F mode.
表示切替 1
Back
Settings can be altered or entered into the memory from the digital monitor without opening the start panel.
7 segment Precision/
Function Item Range Initial value
display unit
0:Single operation, 1: Multiple unit
Multiple unit control setting F000 Control setting 0∼1 1 0
control (communication supported)
Instantaneous power inter-
F002 0∼ 1 1 0 0:ON、1:OFF
ruption (IPI) setting
When IPI is available, Instantaneous
Instantaneous power inter-
Instantaneous power inter- power interruption is detected between
ruption (IPI) restart setting
F003 ruption (IPI) detection period 1 ∼5 1 1 20ms and the setting detection period,
setting" then the compressor restarts.
( page 25)
0:Panel setting, 1:Local fixed,
Remote control switch
F005 0 ∼3 1 0 2:Remote fixed,
method
Remote operation set- 3:Remote switch signal
ting F006 Remote operation method 0∼1 1 0 0:Pulse input, 1:Level input
Remote operation shut-
F007 0∼ 1 1 0 0:Disable, 1:Enable
down recovery
AUTO setting (*2) F011 AUTO operation enable 0∼ 1 1 0 0:Enable, 1:Disable
0:Setting 1, 1:Setting 2,
Capacity control F018 Control pressure selection 0∼ 2 1 0
2:External input
Function setting 0:Built-in sensor, 1:External contact,
F021 Pressure control mode 0∼2 1 0
(optional) 2:External input
Note:
※ Setting can be altered at any time other than this.
*1:When set to 1,” history is cleared. After clearing, the value is automatically reset to “0.”
*2:Only the V type is equipped with AUTO function. The AUTO function is available as an option for the Fixed speed type.
*3:Refer to the below chart about the Pressure setting.
Don’t change the setting of digital monitor besides the above parameter F (7 segment display: F***).
25
3. OPERATING THE DSP [How to Use the Digital Monitor]
7 segment Precision/
Function Item Range Initial value
display unit
Control pressure setting 1 0.5 ∼ 0.75【0.86】 0.01MPa 0.75【0.86】
F022
(control pressure) (73 ∼ 110【125】) (1.5psi) (110【125】)
Pressure Start pressure 1 0.5 ∼ 0.77【0.88】 0.01MPa 0.77【0.88】
F023
setting 1 (cut out pressure) (73 ∼ 112【128】) (1.5psi) (112【128】)
※ Recovery pressure 1 0.5 ∼ 0.73【0.84】 0.01MPa 0.72【0.83】
F024
(*3) (cut in pressure) (73 ∼ 106【122】) (1.5psi) (104【120】)
P type recovery pressure 1 0.5 ∼ 0.73【0.84】 0.01MPa 0.72【0.83】
0.75【0.86】MPa (110【125】psi)
F025 (*2)
(restart pressure) (73 ∼ 106【122】) (1.5psi) (104【120】)
V type ※Setting can be altered at any time.
Control pressure setting 2 0.5 ∼ 0.75【0.86】 0.01MPa 0.75【0.86】
F031
(control pressure) (73 ∼ 110【125】) (1.5psi) (110【125】)
Pressure Start pressure 2 0.5 ∼ 0.77【0.88】 0.01MPa 0.77【0.88】
F032
setting 2 (cut out pressure) (73 ∼ 112【128】) (1.5psi) (112【128】)
※ Recovery pressure 2 0.5 ∼ 0.73【0.84】 0.01MPa 0.72【0.83】
F033
(*3) (cut in pressure) (73 ∼ 106【122】) (1.5psi) (104【120】)
P type recovery pressure 2 0.5 ∼ 0.73【0.84】 0.01MPa 0.72【0.83】
F034 (*2)
(restart pressure) (73 ∼ 106【122】) (1.5psi) (104【120】)
Pressure Start pressure 1 0.5 ∼ 0.75【0.86】 0.01MPa 0.75【0.86】
F023
setting 1 (cut out pressure) (73 ∼ 110【125】) (1.5psi) (110【125】)
※ Recovery pressure 1 0.5 ∼ 0.65【0.76】 0.01MPa 0.65【0.76】
F024
Standard (*3) (cut in pressure) (73 ∼ 94【110】) (1.5psi) (94【110】)
※Setting can be altered at any time.
type Pressure Start pressure 2 0.5 ∼ 0.75【0.86】 0.01MPa 0.75【0.86】
F032
setting 2 (cut out pressure) (73 ∼ 110【125】) (1.5psi) (110【125】)
※ Recovery pressure 2 0.5 ∼ 0.65【0.76】 0.01MPa 0.65【0.76】
F033
(*3) (cut in pressure) (73 ∼ 94【110】) (1.5psi) (94【110】)
Control pressure setting 1 0.5 ∼ 1.0 0.01MPa 1.0
F026
(control pressure) (73 ∼ 145) (1.5psi) (145)
Pressure Start pressure 1 0.5 ∼ 1.02 0.01MPa 1.02
F027
setting 1 (cut out pressure) (73 ∼ 148) (1.5psi) (148)
※ Recovery pressure 1 0.5 ∼ 0.98 0.01MPa 0.97
F028
(*3) (cut in pressure) (73 ∼ 142) (1.5psi) (141)
P type recovery pressure 1 0.5 ∼ 0.98 0.01MPa 0.97
F029
(restart pressure) (73 ∼ 142) (1.5psi) (141)
V type ※Setting can be altered at any time.
Control pressure setting 2 0.5 ∼ 1.0 0.01MPa 1.0
F035
1.0 MPa (145 psi)
IMPORTANT
1. Pressure setting
V type: Set pressure differential of start pressure and recovery pressure to a minimum of 7 psi when using a standard receiv-
er. Set Pressure differential of start pressure and control pressure to a minimum of 3 psi.
Fixed speed type: Set pressure differential of start pressure and recovery pressure to a minimum of 15 psi.
2. Function for switching to pressure setting 2 by external pressure alteration input is optional.
26
3. OPERATING THE DSP [How to Use the Digital Monitor]
1
F011 0 : Enable 1 : Disable
Alter
values. Digital monitor display 0.AXX 0.UXX
2
3.4.5 Restart for Instantaneous Power The DSP has restart function for instantaneous power
Interruption interruption (IPI). When the DSP detects IPI, blinking
the AUTO START Light, the DSP restarts automatically.
① This function is abailable for IPI between 20ms and 5
運転状況
RUNNING MODE seconds.
② The DSP stops automatically after detecting IPI and
遠 方
REMOTE
電 源
POWER
the OPERATION Light is turned off.
負 荷
LOAD
③ After recovering the voltage, the AUTO START Light
起動待ち
故 障 AUTO START
③ blinks and the OPERATION Light turns on.
SHUTDOWN
④ The DSP restarts automatically.
運 転 停 止
START STOP
2
IMPORTANT
(1) Instantaneous power interruption (IPI) means that the
power voltage drops to zero (0) instantaneously.
(2) For the IPI time of less than 20 ms, the DSP air com-
pressor will continue to run.
UNLOAD STOP (3) For the IPI time of more than the setting, the DSP judg-
es it as a power failure; the DSP stops but does not
②③ restart automatically. Press the START button to restart
the DSP air compressor.
27
3. OPERATING THE DSP [How to Use the Digital Monitor]
3.4.6 Remote Operation Setting Operation mode is basically switched by panel operation.
The remote operation mode can also be set by methods
(2) and (3).
On (1) Remote setting by instrument panel
遠 方
REMOTE
On (2) Remote setting fixed ① Turn off the main power supply.
Flashing (3) Remote setting by external operation button
Off Local setting ② Remove the front cover and remove the start panel
cover.
③ Connect the wiring of the remote control panel and
IMPORTANT
the compressor control panel.
● In the case of multiple unit control specifications, when ( See the wiring diagrams on pages 51 - 56.)
multiple unit control is set, it automatically changes to
④ Mount the start panel cover and the front cover.
the remote setting. The REMOTE light flashes at this
time. ⑤ Turn on the main power supply.
● Remote operation method alteration in the setting
mode can only be entered when the compressor is not
operating. [1] To “set the operation buttons of the instrument
● The compressor STOP button can also be used to panel to remote operation mode”
stop operation when operating in the remote mode.
① Press the REMOTE button.
② The REMOTE light lights to indicate that operation of
Remote
the instrument panel buttons is set to the remote
operation
switch 機能 Press button. operation mode.
method
③ To return to local operation mode, press the
Press button.
記憶
Set to remote fixed. REMOTE button again. The REMOTE light then
(Initial value 1) goes off to indicate that operation has been switched
1
Alter to the local operation mode.
2
values.
28
3. OPERATING THE DSP [How to Use the Digital Monitor]
Line pressure
Recovery
ing and goes off when unloading. With pressure setting pressure 1
Load Unload
2, however, the light flashes when loading and goes off Recovery
pressure 2
when unloading.
Load light Ordinary (on range) Pressure setting 2 selection (flash range)
For details, refer to page 24. (The ECOMODE however
External pressure setting switch OFF ON
cannot be used with pressure setting 2.)
Time
3.4.8 Capacity Control Flow when ECOMODE (Energy Saving Mode) is Set
(ECOMODE is set to off when shipped from the factory, but may be set according to your needs.)
Execute capacity control in accordance with the following
time charts.
trol, if the cycle time for load → unload exceeds 30 RUNNING CONTROL SELECT/WIDE
29
3. OPERATING THE DSP [Daily Operation]
CAUTION
● When using the DSP air compressor, do not raise the discharge pressure excessively. Operating the
DSP air compressor over the rated pressure can result in main motor overload, shutdown of the
airend and/or damage of parts.
● If the safety relief valve has blown or a protective device has shutdown the DSP air compressor,
investigate the cause of and take corrective action. If there any questions or comments in taking these
actions, please contact the local Hitachi distributor.
3.5.1 Preparing the DSP Air Compressor ① Turn on the main power supply.
– STOP lamp on the add-on reactor starer panel glows for
reactor starting model.
– Power lamp glows for −△ starting model.
② Check the POWER light and LCD monitor display.
– Is the light lit ?
– Is the monitor screen displayed on the LCD monitor?
③ Check the level of lubricating oil.
– Is the oil level near the red line ?
④ Set the water drainage cock valve of the cooling water
②
piping and the water drainage cock on the back of the
運転管理
RUNNING CONTROL
運転状況
RUNNING MODE
compressor to “fully closed.”
警 報
ALARM
遠 方
REMOTE
負 荷
電 源
POWER ⑤ Allow cooling water to pass through.
LOAD
③ IMPORTANT
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
STR 1 2
Make sure the oil level of the lubricating oil is between the
UNLOAD STOP
red lines while the compressor is running. Because lubri-
cating oil is circulated through the cooler and the piping
while the compressor is running, the position when the
compressor is running and when it is off differs, and is
higher when the compressor is not running.
① 運転管理
RUNNING CONTROL
運転状況
RUNNING MODE
④ Make sure the discharge pressure rises gradually.
警 報
ALARM
遠 方
REMOTE 電 源
POWER
– Make sure the maximum pressure does not exceed the spec-
負 荷
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
③④
UNLOAD STOP
30
3. OPERATING THE DSP [Daily Operation]
モニタ 警 報 遠 方 電 源
REMOTE
MONITOR
POWER
ALARM
メニュー 負 荷
UNLOAD STOP drain discharge port and after cooler drain discharge
port is intermittently discharged.
㻞 㻜 㻜 㻥 䠋 㻜 㻠 䠋 㻝 㻟 㻝 㻥 䠖 㻜 㻞
㻼 㻾 㻱 㻿 㻿 㼁 㻾 㻱
㻵 㻺 㼀 㻿 㼀 㻳 䠊 㻼 䠖 㻌 㻌 㻞 㻥 㼜 㼟 㼕
㻻 㻵 㻸 㻌 㻼 㻾 㻱 㻿 䠖 㻌 㻌 㻝 㻡 㼜 㼟 㼕
㻯 㻸 㼀 䠊 㻼 㻾 㻱 㻿 䠖 㻖 䠊 㻖 㻖 㼜 㼟 㼕
㼀 㻱 㻹 㻼 㻱 㻾 㻭 㼀 㼁 㻾 㻱
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻝 䠖 㻟 㻞 㻜 䉣
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻞 䠖 㻟 㻟 㻤 䉣
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 䠖 㻝 㻟 㻢 䉣
㻯 㻸 㼀 䠊 㼀 㻱 㻹 㻼 䠖 㻖 㻖 㻖 䉣
㻞 㻺 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 䠊 䠖 㻝 㻜 㻤 䉣
㻹 㻭 㻵 㻺 㼀 㻱 㻺 㻭 㻺 㻯 㻱
㻴 㻾 䠊 㼀 㻻 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻜 㻜 㻜 㻜 䡄
㻺 㻱 㼄 㼀 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻖 㻖 㻖 㻖
警 報 遠 方
REMOTE 電 源
piping and drain the cooling water.
To avoid damaging the casing and cooler, be careful
POWER
ALARM
負 荷
LOAD
③ 遠 方
REMOTE
表示切替/
ワイドモード
SELECT/WIDE
運 転
START
停 止
STOP
② ① UNLOAD STOP
31
3. OPERATING THE DSP [Oil Mist Remover Daily Operation, Adjusting the DSP]
3.6 Oil Mist Remover Daily Operation ② The first steps to resolve the lower suction vacuum
pressure are as following.
3.6.1 When Starting A) Clean or replace the air intake filter.
B) Clean the suction throttle valve’s valve plate.
φ8 Note; If the unloaded interstage pressure drops as
low as -0.08MPa (-12 psi), discharge air tem-
perature will gradually increased.
③ If the DSP air compressor cannot be shutdown to
Pressure Gauge clean these parts, turn the adjusting bolt (the suction
51 to 58 psi bypass valve) counterclockwise to open. This will
Make sure that the pressure
gauge reads as follows:
allow the air intake and increase the discharge air
pressure to be geater than -0.08 MPa (-12 psi) when
running unloaded.
④ Replace the consumable parts in the air intake filter
and suction throttle valve with new consumable parts
in accordance with the appropriate maintenance
schedule. For the detail refer to the section 9,
Make sure that the
condensate is not
Maintenance the DSP.
Make sure that the vacuum collected in the
indicator does not show a filter bowl.
If the condensate is IMPORTANT
red mark.
collected, push up
the cock to drain If the discharge pressure becomes lower than -0.08 MPa (-12
the condensate. psi) during unload operation, shaft sealing function decrease.
Condensate Drain Cock
Relief Valve
① Use the relief valve to regulate the oil pressure. To
regulate the oil pressure, open the relief valve cap,
loosen the lock nut, and turn the regulating bolt to
keep the oil pressure at the specified 0.12 to 0.16 MPa
(17 to 23 psi).
・0.12 to 0.16 (17 to 23 psi) when the ambient temper-
ature is 20 degree C or higher.
・0.14 to 0.18 (20 to 26 psi) when the ambient temper-
Seal Washer
ature is 20 degree C or lower.
Locknut (for V type, adjust at the maximum operating frequency.)
③
Adjusting Bolt ② Turn the regulating bolt clockwise to increase the oil
(Suction Bypass Valve) pressure and vice versa.
Usually keep the bolt
tightened, but not excessively. ③ Tighten the locknut and replace the cap.
① When dust particles accumulate on the valve plate of
the suction throttle valve, the suction vacuum pres- IMPORTANT
sure may drop and eventually causing the discharge If the oil pressure is reduced to 0.08 MPa (12 psi) or lower, the oil
air temperature to rise. pressure sensor will detect it and shut down the DSP air compressor.
32
4. TROUBLESHOOTING
CAUTION
If an alarming trouble or a shutdown trouble has happened, investigate the cause and take a corrective
remedy before restarting.
If you have anything unclear or any question, please contact the local Hitachi distributor.
■ During Operation
LCD Indication What and SHUTDOWN How to History
Detector Shutdown What Actions to Take
Heading Trouble Description How to Detect MODE Light Reset Code
The temperature detected
Discharge air tem- at 1st stage rises above Blinks Press RESET
the below settings. Thermistor Yes See page 35 55
perature (1) in red button.
Warning seeting+5℃ (+41℉)
The temperature detected
Discharge air tem- at 1st stage rises above Blinks Press RESET
the below settings. Thermistor Yes See page 35 56
perature (2) in red button.
Warning seeting+5℃ (+41℉)
Blinks Press RESET
Interstage pressure 0.27MPa (39psi) or higher Pressure sensor Yes See page 35 52
in red button.
2nd-stage suction air 70℃ (158℉) or higher Blinks Press RESET
Thermistor Yes See page 35 5B
temperature (after the intercooler) in red button.
Blinks Press RESET
Oil temperature 70℃ (158℉) or higher Thermistor Yes See page 35 58
in red button.
Oil pressure Blinks Press RESET
SHUTDOWN [Fixed speed] 0.08MPa (12psi) or lower Pressure sensor Yes See page 35 5C
in red button.
Oil pressure descends
Oil pressure under below settings.
(OIL-LOW PRESS) Freg. 45Hz 0.08MPa Blinks Pressure sensor Yes Press RESET
See page 35 5C
or higher (12psi) in red button.
Freg. less 0.04MPa
than 45Hz (6psi)
Overloading Detected during oper- Blinks Press RESET
Thermal relay Yes See page 35 17
(main motor) ation in red button.
Overloading Detected during oper- Blinks Press RESET
Thermal relay Yes See page 35 53
(ancillary motor) ation in red button.
Detected during Blinks Press RESET
Answer error of 52 CPU Yes See page 35 51
running. in red button.
Detected after shifting Blinks Press RESET
Answer error of 42 CPU Yes See page 35 16
to △ running. in red button.
FAILURE Inverter tripping or main Failure
Failure signal from Blinks stop after Press RESET
motor overloading with CPU repetition
See page 35 44
inverter in red button.
INV STOP automatic retrials. of retrials.
33
4. TROUBLESHOOTING [Protective Devices]
■ Others
LCD Indication What and SHUTDOWN How to History
Detector Shutdown What Actions to Take
Heading Trouble Description How to Detect MODE Light Reset Code
Clogging of air Pressure differential of Blinks Pressure Press RESET
differential No See page 73 21
intake filter −4.98kPa (0.7psi) or more in green sensor button.
The temperature detected
at 1st stage rises above
Discharge air the below settings. Blinks Automatically
Thermistor No See page 35 25
temperature (1) in green reset.
NOTE 5)
34
4. TROUBLESHOOTING [Troubleshooting the Air Compressor]
Shutdown – 1. 2nd-stage AIR END air intake effi- 1. Contact your Hitachi distributor.
1st-stage dis- <A L A R M> ciency - Lowered 2. Clean the air intake filter.
charge air tem- 2. Air intake filter - Dirty 3. Lower the suction air temperature.
DIS. TEMP.1:
perature and/ or 3. Temperature of Suction Air-High
RES
pressure too high Press after CHK.
<S H U T D O W N>
Shutdown – 1. Cooling water pump – Failed, or 1. Check the cooling water system.
2nd-stage suction <S H U T D O W N> Cooling water pressure – Fluctuating 2. Clean the intercooler
air temperature 2. Intercooler – Dirty
2ND SUCT. TEMP:
too high
Press RES after CHK.
Shutdown – 1. Oil strainer and/or oil filter – Dirty 1. Clean the oil strainer
Oil pressure too <S H U T D O W N> 2. Oil level – Low 2. Replace the oil filter.
low 3. Add the oil.
OIL : LOW TEMP
Press RES after CHK.
Shutdown – 1. Power supply voltage – Low 1. Rectify the power supply voltage.
Main motor and/ <S H U T D O W N> 2. Discharge air pressure – Too high 2. Check the suction throttle valve
or ancillary motor 3. Check the capacity control system.
OVERLOAD : MAIN
overloading
Press RES after CHK.
1. Power supply voltage – Low or in unbalance 1. Rectify the power supply voltage.
Shutdown – 2. Discharge air pressure – Too high 2. Check the capacity control system.
<F A I L U R E> 3. Main motor – Overloading
Inverter tripping/ 3. Measure insulation resistance etc. or
NOTE:‘INVERTER RESTART’ means that the DSP
restarting SYSTEM RETRY : check the main motor.
shutdowns when the inverter repeats a
restarting action within 1 minute.
35
4. TROUBLESHOOTING [Troubleshooting the Oil Mist Remover]
② The safety relief valve has opened and oil mists are vented (the gear case internal pressure has risen).
See the NOTE below.
The safety relief valve is dirty or stuck open by a foreign Yes Disassemble and clean the safety relief valve.
object. Replace if necessary.
No
Go to the procedure ①. The vacuum indicator shows a
red mark. (Gear case has a positive internal pressure.)
NOTE:
The safety relief valve opens immediately when starting the DSP (the control air pressure is still low) or when the DSP has
stopped. This is a normal occurrence.
③ Oil is vented through the ejector’s compressed air outlet (the separated oil is not being recovered).
No
Element may be dirty.
Inspect the element and replace if necessary.
36
5. INSTALLING AND PIPING THE DSP
5.1 Unpacking the DSP Air Compressor
■ After unpacking the crate, verify that the inside DSP is what you have ordered, by referring to page 81 through 82
STANDARD SPECIFICATIONS” and also by checking the model nameplate.
■ Verify that the DSP is not damaged or deformed in transportation.
Pad
Use the strong wires.
Use a pad to protect Keep the distance of Adjust the wire length to
the DSP enclosure 1500 mm (60 inches) keep the DSP’s balance
panels. or more. when hoisting it.
37
5. INSTALLING AND PIPING THE DSP [Installing the DSP Air Compressor]
WARNING
1. Keep flammable solvents or any other hazardous chemicals away from the DSP. Such chemicals may be
sucked by the air end, compressed, and exploded.
2. Do not use fire near the DSP; otherwise the sparks may enter the air end and burn it internally.
Ventilating Fan
Air Intake Maintenance Space
Keep a space of 1.5 m (59 inches) or
If you install the DSP in a more. Note that the air intake grill is
small room, provide a located on the rear enclosure panel.
ventilating fan to keep the
room temperature at 40℃ Foundation
(104℉) or lower. Provide a vibration-absorbing mat if
the foundation is vibrative. If it is too
Piping and vibrative, look for another dequate
Maintenance Space location.
Keep a space of 1.0 m (39
inches) or more to connect Maintenance Space
a plant airline pipe and Keep a space of 0.8 m (31 inches) or
ease the maintenance more to connect the discharge
servicing. compressed air piping and for ease of
Plug the fork slots with Maintenance Space maintenance.
the fork slot covers
Keep a space of 1.5 m (59 inches) or
(standard accessory)
more to allow opening the front door.
■ Install the DSP in a dry and dust-free room, and avoid the following.
Raindrops, Basements, Steam Metals, Sand, Other Hard Materials Harmful Gases
Chlorine, hydrogen sulfide, sulfurous acid, highly
( concentrated ozone, and ammonium gases )
These conditions may cause leakage, These conditions may cause deterio- These conditions may cause oil deterio-
condensation, rusting and CPU mal- ration of motor insulation level, dam- ration, corrosion of coolers and peeling
function. age to the air end bearings and CPU of the rotor coatings.
malfunction.
■ Install the DSP on a level floor. ■ Do not install the DSP near a wall. Doing
Installing on a level floor is required to keep an
Do not set the DSP
this may cause the operating sound to
adequate amount of lubrication oil in the DSP Prohibited resonate and increase the sound levels.
and prevent excessive noise and vibration. on the blocks.
CAUTION
● Install the DSP indoors. Installing it outdoors may lead to a damage of the air end due to water vapor,
dust, etc.
● The DSP installation room must have an air intake opening and an air exhaust opening and must be
well ventilated. If the room is poorly ventilated, hot air exhausted by the DSP may cause the room
temperature to rise abnormally and in the worst case lead to damage of the air end.
38
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
5.4 Piping the DSP Air Compressor ⑦ If you connect the DSP’s discharge pipe to a main plant
airline pipe, run the discharge pipe upwards and then
5.4.1 General Instructions downwards before joining to the main plant airline pipe,
① Use the degreased pipe as a plant airline pipe. to prevent the condensate from flowing back.
② If you connect the DSP directly to a gas pipe, use a
union or flange joint to ease disassembling the DSP
enclosure panels.
Flange Joint Main Plant
Airline Pipe
Discharge
Air
Stop Valve
IMPORTANT
Assume that one DSP is operating and another is not. In
case that the discharge stop valve of the non-operating
DSP is opened, a back pressure is applied on that DSP ’s
aftercooler, check valve, etc. As a result the condensate is
produced much more than otherwise; even the Aftercooler
is rusted internally and the check valve is earlier rusted.
39
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
Stop Valve
The V type is equipped with an AUTO operation as a
standard function, and gets its structure from the second-
ary side of the motorized isolation valve.
Mount the pressure detecting pipe (customer supplied) Connect the DSP’s
discharge pipe to the
and motorized isolation valve (standard accessory). secondary part of the
Connect the pressure detecting pipe from the position on air receiver tank.
the upper pipe, which is as close as possible to the sec-
IMPORTANT
ondary side of the motorized isolation valve, to the
receiver pressure detecting port of the compressor. (1)This is to prevent the reciprocating compressor’s air
pulsation from affecting the DSP.
Also, avoid operating the equipment without mounting
(2)Usually, continue to operate the DSP as long as possi-
the pressure detecting pipe. The safety valve actuates ble and start and stop a reciprocating compressor in
because pressure is not detected. parallel as required by the compressed air demand.
IMPORTANT
CAUTION
As shown in the figure above, if the compressor is stopped
by the AUTO function, the motorized isolation valve closes. Do not install a check valve between the DSP
If a motorized isolation valve is not mounted, back pres- and the air receiver tank. Otherwise, the DSP
sure rises in the after cooler, check valve, etc., when the
may hunt, that is, load and unload very fre-
compressor stops running. These conditions promote
drainage, and are contributing factors to rusting inside the quently ; the capacity control system may not
after cooler and early rusting of the check valve, etc. work normally.
40
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
Stop Valve
Discharge
Air
Drain Pit
CAUTION
If you fail to install an air receiver tank, the Drain Pipe
DSP may load and unload frequently; its
mechanical service life may be shortened.
① As the DSP employs a 0%- or 100%-capacity, 2-step ①Leave open the end of any condensate drain pipe.
capacity control system, install an air receiver tank on
②Do not merge the DSP’s condensate drain lines (for
the plan airline pipe. Its capacity is as indicated in the
the aftercooler, for intercooler, for the control line fil-
following table.
ter) into one. Also, do not merge any condensate drain
Dis.Pressure (MPa) Minimum Capacity of Air pipe into an external condensate drain pipe (for exam-
Model
[psi] Receiver Tank (m3) [US gallon]
0.75/0.86/1.0 ple, one for other DSPs or one for an air receiver
DSP-132WN 4.0 [1057]
[110/125/145] tank). Otherwise, a pressure difference may be gener-
0.75/0.86/1.0 ated; as a result, the DSP cannot drain the condensate
DSP-145WN 4.0 [1057]
[110/125/145]
0.75/0.86/1.0 or can drain it only abnormally or you cannot visually
DSP-160WN 4.0 [1057]
[110/125/145] check whether the condensate is regularly drained.
0.75
4.5 [1190]
[110]
DSP-200WN
0.86/1.0
4.0 [1057]
[125/145]
0.75
5.0 [1320]
CAUTION
[110]
DSP-240WN
0.86/1.0 Un-drained condensate can backflow to the
4.5 [1190]
[125/145] DSP air compressor and cause it to fail.
0.75/0.86/1.0
DSP-160VWN 4.5 [1190]
[110/125/145]
0.75/0.86/1.0
DSP-240VWN 5.0 [1320]
[110/125/145]
②Do not install a check valve between the DSP and the
air receiver tank. Otherwise, the DSP may hunt, that
is, load and unload very frequently; the capacity con-
trol system may not work normally.
③However, in case of AUTO operation specification,
quantity control specification and alternate operation
specification, install air chambers of 4.5 m3 (1190 US
gallon) or more for 132kW to 160kW and 5.0 m3 (1320
US gallon) or more for 200kW to 240kW so as to max-
imize the energy saving effect.
④When selecting energy saving operation, install air
chambers of 4.5 m3 (1190 US gallon) or more for
132kW to 160kW and 5.0 m3 (1320 US gallon) or more
for 200kW to 240kW so as to maximize the energy
saving effect in all the areas of load factors .
41
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
5.4.7 Cooling water piping 5.4.8 Connecting with the Control Air
Pipe
Pressure
Gauge
A
Cooling
Water
Outlet Filter
Cooling Regulator
Water
Water Drain Valve Inlet
42
5. INSTALLING AND PIPING THE DSP [Ventilation of Air Compressor Room]
IMPORTANT
CAUTION
1. Stop the ventilating fan when the DSP has stopped.
Provide a ventilating system to the air com- 2. Keep the ventilating fan operating while the DSP is
pressor room in the event of a room tempera- operating. Resistance of the un-operated ventilating fan
ture exceeding the allowable ambient operat- may reduce the performance of the DSP cooler.
ing temperature of 40°C (104℉). Operating the 3. Duct is to be detachable so that you can service the
DSP easily.
DSP under the ambient operating temperature
above 40°C (104℉) may cause a serious prob-
lem to the air end.
intake opening.
air
intake
② Ventilation without Ventilating Fan (Figure B)
For a large air compressor room, install the DSP in
the airy area. Figure B
43
6. STARTUP OPERATION
Follow the instructions in this chapter, also when you restart the DSP after a long-term suspension.
CAUTION
● Before you connect the power, verify that the DSP is correctly installed, piped, and wired.
● Check the power supply, and verify that it is firmly grounded and that the voltage is within an allow-
able range (–5% to +10%).
6.1.1 Preparing the Air Compressor ① Fill the oil through the oil filling port until the oil
reaches the upper red line of the oil level gauge. Use
the Hitachi recommended oils ( p. 7).
② Fully close the water drain valve and start to flow the
cooling water.
③ Make sure that the cooling water flow rate is normal.
④ Connect the power, and verify that the POWER light
is ON.
– STOP lamp on the add-on reactor starter panel glows for
② reactor starting madel.
運転管理 運転状況
⑤ Change 2 of 3 wires of the power cord if the display
shows CABLE CONNECTED: REV ersal PHASE.
RUNNING CONTROL RUNNING MODE
警 報 遠 方
REMOTE 電 源
POWER
ALARM
負 荷
LOAD
WARNING
機 能 リセット 起動待ち
RESET
FUNC 故 障 AUTO START
SHUTDOWN
③
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
STR 1 2
負 荷
LOAD
機 能 リセット
① FUNC
RESET
表示切替/
故 障
SHUTDOWN
起動待ち
AUTO START
75
starting, operate the DSP at 15 psi with the
CAUTION
60 discharge stop valve fully opened. Then raise
the pressure (close the discharge stop valve)
65 by 100 psi every 15 minutes until the pressure
30 reaches the specified 110 psi.
Raise the pressure as illustrated in the 15
For the DSP startup operation, observe the
method without fail.
Pressure Raising Pattern (see illustration to 0
the right). If this pattern is not followed, the 0.5 1.0 1.5 2.0
44
6. STARTUP OPERATION [Air Compressor]
モニタ
MONITOR
警 報 遠 方
REMOTE
電 源
tures, and verify that:
POWER
MONITOR
6.1.4 Stopping the DSP Air Compressor ① Press the UNLOAD STOP button. The compressor
then unloads for 5 minutes and then stops running.
(In the case of an emergency, press the STOP button.)
– STOP lamp on the add-on reactor starter panel glows for
④ reactor model.
警 報 遠 方
REMOTE 電 源
POWER
ALARM
記 憶
STR 1 2
③
NTSTG. P:
OIL PRESS:
000psi
000psi
piping and drain the cooling water.
To avoid damaging the casing and cooler, be careful
CLT PRESS: ***psi
①
② UNLOAD STOP
45
6. STARTUP OPERATION [Oil Mist Remover]
① Set a control air pressure to a maximum level. ④ Make sure that the vacuum indicator does not show a
Example: If a control air pressure varies between red mark.
0.54 MPa (78 psi) and 0.64 MPa (73 psi),
⑤ Make sure that there is no leak of the control air pipe
maintain it at its maximum 0.65 MPa (74
joints.
psi).
⑥ Press down the regulator knob to lock.
② Pull up the regulator knob, and then the regulator is
unlocked or settable. ⑦ The oil mist remover makes the gear case internal
pressure negative during operation reducing the oil
③ Turn the regulator knob so that the pressure gauge
pressure by 0.005 to 0.01 MPa (0.7 to 2 psi). This is
reads as follows:
not abnormal.
Standard Setting of Regulator Air Flow Rate Reset the oil pressure on the relief valve.
MPa (psi) liter/min (cmf) ⑧ Stop the DSP. Make sure that the solenoid valve is de-
energized to close, the pressure gauge reads 0 (zero),
0.35 (51) about 100 (35)
and accordingly the vacuum indicator shows a red
NOTE:
mark.
The pressure gauge readings may increase/decrease by
0.03 MPa (4 psi) as the control air pressure decreases/
increases respectively by 0.10 MPa (15 psi). Remember that,
due to the regulator’s characteristics, the former rather rises
if the latter drops.
CAUTION
1. The oil mist remover can operate when the control air pressure is to 0.39 MPa (57 psi) or more. If the
control air of this pressure is not available (that is, when the DSP is just started or is unloading with
opening the blowoff valve), the ejector can not operate and, as a result, the gear case internal pres-
sure rises. When the gear case internal pressure reaches about 20mmH2O, the relief valve opens to
relieve it to the atmosphere for preventing its abnormal rise, and thereby oil mists are inevitably
vented. Avoid, therefore, a long time unloading operation as possible as you can; and, if it is
unavoidable, take a precaution so that the DSP dos not suck the oil mists.
2. If you use two or more DSPs in parallel, the system forces a specific unit to unload for a long time. Its
oil mist remover ejector seldom operates and thereby its relief valve opens frequently with much oil
mists vented. To solve the problem, connect its control air pipe to where is always pressurized there-
by minimizing the period to open the relief valve.
3. The relief valve shortly opens when you start/stop the DSP even if the control air pressure is high.
After the repeated starting/stopping, the relief valve may be slightly oozed with oil. This is not abnor-
mal.
4. The oil mist remover consumes the compressed air of 100 liters per minute or lower or higher.
Exact air consumption depends on the setting of the regulator.
5. Take a precaution if you use the DSP in an AUTO operation mode with the oil mist remover, because
the DSP may not stop automatically due to an uninterrupted consumption of the compressed air by
the oil mist remover.
46
7. WIRING
WARNING
1. Always use a licensed electrician. Do not allow an unlicensed person to wire the air compressor. An
unlicensed person may wire the air compressor wrongly, and a wrong wiring may cause an electric shock.
2. Do not remove any protective relays on the air compressor. Also, do not make a modification of the
control circuit that may result in impairing the protective relay's function. Remember that the loss of the
protective relay's function may cause serious damage to the air compressor such as a burning of the air
end. In the event that you need to modify the control circuit, consult your distributor.
3. Before opening the starter/control box cover to service or wire the air compressor, disconnect the power;
otherwise you may receivean electric shock. In addition, attach a notice on the power supply stating “Under
the maintenance work. Keep the switch off.” to prevent someone from carelessly turning the switch on.
47
7. WIRING [Connecting a Power Cable]
⑤ Disconnect the power and verify that it is safe before Remove the starter/control box covers and connect a
1.) Overhauling the DSP, 2.) Filling oil the DSP and/or power cable as illustrated below.
3.) Servicing the starter/control box.
⑥ Field wiring connections must be made by UL and
Starter /
CSA certificated ring lug terminal connectors sized
Control Box
for the wire gauge being used. The connector must
be fixed using the crimping tool specified by the con-
nector manufacturer.
⑦ Use the attached rubber bushes (on the power cable
holes) and the protective tube to protect the power
cable (see illustration below).
If the customer utilize bushings by their own, follow
UL requirements. Type 1 device is the minimum level
of replacement for the provided rubber bushings.
⑧ Customer should follow UL requirement; See refer-
ences below: Power Supply
a) The branch circuit protection shall be Wiring
CAUTION
An unprotected power cable can cause direct
contact with the steel plates e. g. the power
cable holes is resonated with a slight vibra-
tion, it could damage the cover over time and
result in a short circuit accident.
CAUTION
● Install an earth leakage circuit breaker between the air compressor and the power supply. Do not use
a mere disconnector such as a knife switch in wiring because it cannot protect the air compressor
and may result in a burning of the air end if a ground fault has occurred.
● Ground the air compressor; otherwise you may receive an electric shock, or the air compressor may
fail. As a ground, do not use a steel skeleton of the building because it may cause an operational fail-
ure. Ground independently and directly into the earth.
48
7. WIRING [Connecting a Power Cable]
49
7. WIRING [Wiring Connection Diagram, Control Panel /LCD monitor Specifications]
50
CLASS 1 CONTROL CIRCUIT TB2
DA1 CN C C REMOTE UNLOAD STOP
USP
DA DA1 DA1
C
500ms OR MORE
TH4 TH5 USP DA ONE-SHOT INPUT
32
R S T LED R2
4 3 2 1
PS4 R4
33 ES
(R) (W) (B) C
S2
1 2 3 4 1 2 3 4 1 2 1 2
CN11 RUNNING CONTROL RUNNING MODE
BT PS3 CN1 PS4 CN2 TH4 CN3 TH5 CN4
1
※SHORT CIRCUIT
2 REMOTE
POWER
AUTO ALARM DURING LEAD-LAG OPERATION,
DC24V(C)
DC GND(DA)
TB0 R S T TAB1 LOAD REMOVE TWO SHORT CIRCUIT WIRES
[×10h] AUTO
MONITOR FROM EITHER OF THE TWO UNITS.
(G) R1 S1 T1 TAB2 FUNC SHUTDOWN START
MENU RESET
LCD SELECT
REMOTE /WIDE START STOP TB3 TB3
CN7 +/− (MASTER) (SLAVE)
POWER UP/
STR 1 2 C C
DOWN
1 DA DA
(K)
2 SET D1 D1
(L) 1 9 1 13
CN10 CN9 CN8 PWB2 D2 D2
CT CN1 CN2
D3 D3
3 2 1 1 2 3 1 5
D4 D4
D5 D5
D6 D6
(+) 24V
to RS+
AVR1 (–) 24E RS485(+)
RS−
RS485(−)
WIRING BETWEEN EACH UNIT
SHALL BE SHIELD CABLE.
(+) C
to
AVR2 (–) DA
CLASS 1 CONTROL CIRCUIT
D1 D2 D3 D4 D5 D6
1 2 3 1 2 3 1 2 3 4 1 9 1 13 1 5 1 2 3 4 5 6 7 8
CN18 CN17 CN25 CN19 CN20 CN23 CN21
485DP 485EX 485FC OPE2 OPE1 DUAL
51
7. WIRING [Wiring Connection Diagram]
52
BOTH MAIN DISCONNECT MEANS AND BRANCH CIRCUIT
PROTECTION SHALL BE PROVIDED BY THE CUSTOMER. C
IN ADDITION,MAIN DISCONNECT MEANS SHALL BE PROVIDED to to to to CN
3φ ON THE LINE SIDE OF THE BRANCH CIRCUIT PROTECTION. LCD CN9 PWB2 CN1 PWB2 CN2 TB3 USP 4 3 2 1
AC460V 60Hz FOR USE ON A SOLIDLY GROUNDED WYE SOURCE ONLY.
RP 460V 115V SP1 5A
1 2
CE CE R2
R S T
RS
CE S2
SP S2
TR (G) 46 42 T2
SUCF 1 2 3 1 2 3 1 2 3 4 1 9 1 13 1 8 1 5
1kVA 32
T2A DS1-1 A CN18 CN17 CN25 CN19 CN20 CN21 CN23 CN21 DUAL DC24V(+) 1
Y52A
46 LF 1
2 CN24
OPE2 OPE1 CN12 2 33 SHORT CIRCUIT
R2 63SV DS1-2 B CHG DC24V INPUT TR OUT 3 A K DURING REMOTE OPERATION,
(R) 1 PS2 4 D1 REMOVE SHORT CIRCUIT WIRES.
RP REMOTE SETTING
R4 (W) PWB1(HC55)
2 CN16 5
DC24V
PS2
R S T TB0 SP S2 R4 R2 C 3 SW2 SW1 EXTERNAL LOAD/UNLOAD 24L 1 REMOTE STOP
(B) 4 500ms OR MORE
STOP 2
(G) T1A ES (R)
REMOTE OPERATION START 3 REMOTE START ONE-SHOT INPUT
(W)
1 PS1
DRYER ANSWER COM1 4
2 CN11 TB2
Y1 5 Y1 OPERATION DRY "a" CONTACT(0.5A)
PS1
T1 CB2 5A (B)
3 C
4 OPERATION ANSWER COM2 6
S1 Y2 7 CAUTION DRY "a" CONTACT(0.5A) DA1 UNLOAD
Y2
R1 30W TH3 1 TH3 OVER LOAD Y3 8 Y3 SHUTDOWN DRY "a" CONTACT(0.5A) DA STOP
60W 90W 2 CN13 UNL 9 S2
CT EXTERNAL LOAD/UNLOAD : "a" CONTACT(0.5A)
(K) TH2 OVER LOAD REM10 REMOTE SETTING : "a" CONTACT(0.5A) R4
CB1
(G) AVR3 (G) 1 TH2 ES
2 CN10 TB1 R2
(L) (+) (–) (G) AVR1 (G) AVR2 C
15A Y52A
(+) (–) (+) (–) R 1 TH1 41 41
S1A C1 DA1 2 CN9 Y52C CN15 CE 42 42 C
Y42 Y42α Y21 S2 CE
20UM
Y52 Y6 Y20 1 S2
R1A T1A REVERSE T2
1 PHASE 3 CE Y52A 43 43
R2
2 24V1 5 C 44 44
DA 3 DSA 7 X
20A
42 C OVLD ANS DA
52
to PWB2 TAB2
to PWB2 TAB1
4 DA
7. WIRING [Wiring Connection Diagram]
C
1.1A CN14 CN2 DA
145kW 460V/152A 49M1 DA DA1
160kW 460V/167A V2 W2 U2 U V W Y52A D
38 R4 17
U V W C C 37 34 8 11 S3 6 S3
to TB3 36 35 S3
IM1 IM2 1 2 39
31 10 18 S3 CE
6 RY21X RY
W1 V1 U1 0.4kW to X 88F 21X
LCD CN7 52 52
460V/1.0A CE CE S
K
S S
132kW 460V/240A K K
145kW 460V/250A CE CE CE
160kW 460V/275A SK
NOTES: S3 6
1. SIZING OF ELECTRICAL COMPONENTS NOT SUPPLIED BY HITACHI IS THE S2
35
RESPONSIBILITY OF THE CUSTOMER. R3
CE 49M1
2. RATED DRY CONTACT IS AC110V 0.5A (MAX) S3 18
CLASS 1 CONTROL CIRCUIT
18
35
S3
S3
S3
S2
R3
4 3 2 1
PS4 R4
33 ES
(R) (W) (B) C
S2
1 2 3 4 1 2 3 4 1 2 1 2
CN11 RUNNING CONTROL RUNNING MODE
BT PS3 CN1 PS4 CN2 TH4 CN3 TH5 CN4
1
2 ※SHORT CIRCUIT
REMOTE
POWER
AUTO ALARM DURING LEAD-LAG OPERATION,
DC24V(C)
DC GND(DA)
TB0 R S T TAB1 LOAD
[×10h] AUTO
REMOVE TWO SHORT CIRCUIT WIRES
MONITOR
(G) R1 S1 T1 TAB2 FUNC SHUTDOWN START FROM EITHER OF THE TWO UNITS.
MENU RESET
LCD SELECT
+/− REMOTE /WIDE START STOP TB3 TB3
CN7 UP/ (MASTER) (SLAVE)
POWER DOWN STR 1 2 C C
1 DA DA
(K)
2 SET D1 D1
(L) 1 9 1 13
CN10 CN9 CN8 PWB2 CN1 CN2 D2 D2
CT
3 2 1 1 2 3 1 5 D3 D3
D4 D4
D5 D5
D6 D6
(+) 24V
to RS+
AVR1 (–) 24E RS485(+)
RS−
RS485(−)
(+) C
WIRING BETWEEN EACH UNIT
SHALL BE SHIELD CABLE.
to
AVR2 (–) DA
CLASS 1 CONTROL CIRCUIT
D1 D2 D3 D4 D5 D6
1 2 3 1 2 3 1 2 3 4 1 9 1 13 1 5 1 2 3 4 5 6 7 8
CN18 CN17 CN25 CN19 CN20 CN23 CN21
485DP 485EX 485FC OPE2 OPE1 DUAL
SYMBOL PARTS NAME
PWB1 CONTROL PC BOARD PWB1 PID OUTPUT(0-5V)
PWB2 DISPLAY PC BOARD OPERATION INPUT (DC24V)
LCD LCD MONITOR LOAD/UNLOAD INPUT (DC24V)
PS4 PRESSURE SENSOR (OIL) OPERATION OUTPUT (TR OUT)
TH4 THERMISTOR (1ST DIS.) LOAD/UNLOAD OUTPUT (TR OUT)
TH5 THERMISTOR (OIL)
TB0 TERMINAL BROCK
7.4.3 Wiring Connection Diagram 2 (200WN, 240WN, 460V Class (1/2))
53
7. WIRING [Wiring Connection Diagram]
54
BOTH MAIN DISCONNECT MEANS AND BRANCH CIRCUIT
PROTECTION SHALL BE PROVIDED BY THE CUSTOMER.
IN ADDITION,MAIN DISCONNECT MEANS SHALL BE PROVIDED C
ON THE LINE SIDE OF THE BRANCH CIRCUIT PROTECTION. to to to to CN
3φ FOR USE ON A SOLIDLY GROUNDED WYE SOURCE ONLY. LCD CN9 PWB2 CN1 PWB2 CN2 TB3 USP 4 3 2 1
AC460V 60Hz
RP 460V 115V SP1 5A 1 2
CE CE R2
R S T
RS
CE S2
SP TR S2 46 42
1kVA (G) T2 1 2 3 1 2 3 1 2 3 4 1 9 1 13 1 8 1 5
SUCF 32
T2A DS1-1 A CN18 CN17 CN25 CN19 CN20 CN21 CN23 CN21 DUAL DC24V(+) 1
Y52A
LF 1
46 OPE2 OPE1 CN12 2 33 SHORT CIRCUIT
B
2 CN24
R2 63SV DS1-2 CHG DC24V INPUT TR OUT 3 A K DURING REMOTE OPERATION,
(R) 4 D1 REMOVE SHORT CIRCUIT WIRES.
RP R4 1 PS2 REMOTE SETTING
(W) PWB1(HC55) 5
2 CN16 DC24V
C
PS2
R S T TB0 SP S2 R4 R2 3 SW2 SW1 EXTERNAL LOAD/UNLOAD 24L 1 REMOTE STOP
(B)
4 STOP 2 500ms OR MORE
(G) T1A ES (R)
REMOTE OPERATION START 3 REMOTE START ONE-SHOT INPUT
TB2 (W)
1 PS1
DRYER ANSWER COM1 4
2 CN11
Y1 5 Y1 OPERATION DRY "a" CONTACT(0.5A) TB2
PS1
(B)
3 C
T1 CB2 5A OPERATION ANSWER COM2 6
4 CAUTION DRY "a" CONTACT(0.5A)
S1 Y2 7 Y2 DA1 UNLOAD
R1 30W TH3 1 TH3 OVER LOAD Y3 8 Y3 SHUTDOWN DRY "a" CONTACT(0.5A) DA STOP
60W 90W 2
CN13
UNL 9 EXTERNAL LOAD/UNLOAD : "a" CONTACT(0.5A) S2
CT TH2 OVER LOAD REM 10
(K) (G) AVR3 (G) 1 TH2 REMOTE SETTING : "a" CONTACT(0.5A) R4
CB1 TB1 ES
(L) (+) (−) (G) AVR1 (G) AVR2 C 2 CN10 R2
15A Y52A
(+) (−) (+) (−) R 1 TH1 41 41
C1 DA1 CN9 CN15 CE 42 42 C
S1A 2 Y42 Y42α Y21 Y52C CE
S2
20UM
Y52 Y6 Y20 1 S2
R1A T1A 1 REVERSE T2
PHASE 3 CE Y52A 43 43
2 24V1 R2
5 C 44 44
3 DSA 7 X
20A
C DA OVLD ANS
52 42 DA
to PWB2 TAB2
to PWB2 TAB1
4 DA
7. WIRING [Wiring Connection Diagram]
C CN1
200kW 460V/213A 49M1 1.1A CN14 CN2 DA1
DA
DA Y52A
240kW 460V/242A V2 W2 U2 U V W D
R4 17
C 38 37 34 8 11 S3 6 S3
U V W C to TB3 36 35 S3
IM1 IM2 1 2 39
31 10 18 S3 CE
6 RY21X RY
W1 V1 U1 0.4kW to X 88F
52 52 21X
460V/1.0A LCD CN7 CE CE S
K
S S
200kW 460V/352A K K
240kW 460V/399A CE
CE CE
NOTES: SK
1. SIZING OF ELECTRICAL COMPONENTS NOT SUPPLIED BY HITACHI IS THE S3 6
35 S2
RESPONSIBILITY OF THE CUSTOMER.
CE R3
2. RATED DRY CONTACT IS AC110V 0.5A (MAX) 49M1 S3 18
3. SIGNAL INPUT FOR REMOTE OPERATION IS DC24V
CLASS 1 CONTROL CIRCUIT
S3
S3
S3
S2
R3
4 3 2 1
PS4 R4
33 ES
(R) (W) (B) C
S2
1 2 3 4 1 2 3 4 1 2 1 2
CN11 RUNNING CONTROL RUNNING MODE
BT PS3 CN1 PS4 CN2 TH4 CN3 TH5 CN4
1
2 ※SHORT CIRCUIT
REMOTE
POWER
AUTO ALARM DURING LEAD-LAG OPERATION,
DC24V(C)
DC GND(DA)
TB0 R S T TAB1 LOAD
[×10h] AUTO
REMOVE TWO SHORT CIRCUIT WIRES
MONITOR
(G) R1 S1 T1 TAB2 FUNC SHUTDOWN START FROM EITHER OF THE TWO UNITS.
MENU RESET
LCD SELECT
+/− REMOTE /WIDE START STOP TB3 TB3
CN7 UP/ (MASTER) (SLAVE)
POWER DOWN STR 1 2 C C
1 DA DA
(K)
2 SET D1 D1
(L) 1 9 1 13
CN10 CN9 CN8 PWB2 CN1 CN2 D2 D2
CT
3 2 1 1 2 3 1 5 D3 D3
D4 D4
D5 D5
D6 D6
(+) 24V
to RS+
AVR1 (–) 24E RS485(+)
RS−
RS485(−)
(+) C
WIRING BETWEEN EACH UNIT
SHALL BE SHIELD CABLE.
to
AVR2 (–) DA
CLASS 1 CONTROL CIRCUIT
D1 D2 D3 D4 D5 D6
1 2 3 1 2 3 1 2 3 4 1 9 1 13 1 5 1 2 3 4 5 6 7 8
CN18 CN17 CN25 CN19 CN20 CN23 CN21
485DP 485EX 485FC OPE2 OPE1 DUAL
SYMBOL PARTS NAME
PWB1 CONTROL PC BOARD PWB1 PID OUTPUT(0-5V)
PWB2 DISPLAY PC BOARD OPERATION INPUT (DC24V)
LCD LCD MONITOR LOAD/UNLOAD INPUT (DC24V)
PS4 PRESSURE SENSOR (OIL) OPERATION OUTPUT (TR OUT)
TH4 THERMISTOR (1ST DIS.) LOAD/UNLOAD OUTPUT (TR OUT)
TH5 THERMISTOR (OIL)
TB0 TERMINAL BROCK
7.4.5 Wiring Connection Diagram 2 (400V Class, Inverter Staring (1/2))
55
7. WIRING [Wiring Connection Diagram]
56
BOTH MAIN DISCONNECT MEANS AND BRANCH CIRCUIT
PROTECTION SHALL BE PROVIDED BY THE CUSTOMER.
IN ADDITION,MAIN DISCONNECT MEANS SHALL BE PROVIDED to to to to to C
LCD CN9 TB3 PWB2 CN1 PWB2 CN2 TB3
ON THE LINE SIDE OF THE BRANCH CIRCUIT PROTECTION. CN
3φ FOR USE ON A SOLIDLY GROUNDED WYE SOURCE ONLY. USP 4 3 2 1
1 2
AC460V 60Hz YZ A B
RP 460V 115V SP1 5A CE CE R2
R S T
RS
CE CE S2
SP TR S2 46
(G) T2 1 2 3 1 2 3 1 2 3 4 1 9 1 13 1 5
1kVA LF SUCF 32
DS1-1 A CN18 CN17 CN25 CN19 CN20 CN23 CN21 DUAL 1
Y52A
46 1 OPE2 OPE1 DC24V(+)
R2 2 CN24 2 33 SHORT CIRCUIT
63SV DS1-2 B CHG DC24V INPUT CN12 3
A K DURING REMOTE OPERATION,
R4 (R) TR OUT 4 D1
T1A 1 PS2 REMOTE SETTING REMOVE SHORT CIRCUIT WIRES.
(W) PWB1(HC55) 5
C 2 CN16 DC24V
S2 R4 R2
PS2
R S T TB0 3 SW2 SW1 EXTERNAL LOAD/UNLOAD 24L 1 REMOTE STOP
(B) 500ms OR MORE
ES 4 STOP 2
TBG CB2 5A REMOTE OPERATION ONE-SHOT INPUT
TB2 (R) START 3 REMOTE START
T1 1 PS1
S1 (W) DRYER ANSWER COM1 4 TB2
(G) 2 CN11
Y1 5 Y1 OPERATION DRY "a" CONTACT(0.5A)
PS1
R1 3
(B) OPERATION ANSWER COM2 6 C
4 CAUTION DRY "a" CONTACT(0.5A)
30W 60W 90W Y2 7 Y2 DA1 UNLOAD
TH3 1 TH3 OVER LOAD Y3 8 Y3 SHUTDOWN DRY "a" CONTACT(0.5A) DA STOP
2
CN13
CT AVR3 AVR2 AVR1 UNL 9 EXTERNAL LOAD/UNLOAD : "a" CONTACT(0.5A) S2
(K) (G) (G) OVER LOAD
(G) (G) TH2 REM 10 REMOTE SETTING : "a" CONTACT(0.5A) R4
(+) (−) (+) (−) (+) (−) 1 TH2 ES
(L) CB1 2 CN10 TB1 R2
15A P11 P21 C Y52A
E TH1 41 41
DCL C1 DA1 R 1 CN9
F 2 Y52C CN15 CE 42 42 C
Y42 Y42α Y21 S2 CE
R S T
20UM
Y52 Y6 Y20 1 S2
PD REVERSE
3 T2
1 PHASE CE Y52A 43 43
INV (G) 24V1 5 R2
2 C 44 44 D
P
to PWB2 TAB1
to PWB2 TAB2
U V W 3 7 X
20A
C DA ANS DSA
Y OVLD DA DA
4
7. WIRING [Wiring Connection Diagram]
C 88F1
5 24V2 (G) 45 45
CN6 CN8 CN4 CN7 CN5 CN3
24V 24E C1 46 46
C 4 3 2 1 4 3 2 1 5 3 1 3 1 7 5 3 1 5 3 1 5 3 1 3 1 Y
20W
49M1 CN1 DA
1.1A CN14 CN2 DA1
DA Y52A
U V W R4
47 34 8 S3 S3
C to TB3 48 17 37 CE
1 2 31 S3
IM2 CE
0.4kW CM2 88F 52X S
U1 V1 W1 to X RUN RY21X K
C 460V/1.0A LCD CN7 CE
160kW 460V/275A
IM1 240kW 460V/399A CE CE
U2 W2
SP Y 52X RY
V2
SN 21X
Z 390Ω S S
K K
NOTES: (G)
CE CE
1. SIZING OF ELECTRICAL COMPONENTS NOT SUPPLIED BY HITACHI IS THE RESPONSIBILITY
OF THE CUSTOMER. FM
CLASS 2 CONTROL CIRCUIT
CM1 CE CE CE
2. RATED DRY CONTACT IS AC110V 0.5A (MAX) SP RP
3. SIGNAL INPUT FOR REMOTE OPERATION IS DC24V (+) SN SN PLC CE CE CE TB2
(−) P24
37
S3
S1
S2
S2
R3V
R3V
R3D
4. BRANCH CIRCUIT PROTECTION SHALL BE 460V/550A (160kW) MAX, 460V/700A (240kW) MAX.
FW
UL LISTED DUAL ELEMENT TIME DELAY BRANCH CIRCUIT TYPE FUSES. 8
5. FIELD WIRING CONDUCTOR SHALL BE 3/0MCM×2 (160kW) 300MCM×2 (240kW). CN39 CN43 CN42 CN38 CE C
INV H
6. USE LISTED PRESSURE TERMINAL CONDUCTORS SUCH AS A RING TYPE. 0 CE
0 A
7. CONNECT MAXIMUM 3 FIELD WIRING CONDUCTOR TO ONE CONDUIT. OI 2 1 2 1 2 1 2 1
L S2 R3D
L B
SYMBOL PARTS NAME SYMBOL PARTS NAME CM2 49M1
S2 R3D
12 CE CE CE CE CE CE CE CE
IM1 MAIN MOTOR DSA LIGHTNING ARRESTER 14 S2 R3V
(RUN)11 S3 37 S3 37 S2 R3V
IM2 FAN MOTOR R RESISTANCE AL2 R3V S2
52 MAIN ELECTROMAGNETIC CONTACTOR SW1,2 DIP SWITCH AL1
AL0 (G) FM4 FM3 FM2 FM1 S 88F 52X S CE CE CE CE CE CE CE CE CE CE CE CE CE CE
42 ELCTROMAGNETIC CONTACTOR FOR FAN FOR △ CHG CHARGE LAMP K K
6 ELCTROMAGNETIC CONTACTOR FOR FAN FOR Y SK SURGE ABSORBER CE CE
88F ELCTROMAGNETIC CONTACTOR FOR FAN 46 REVERSE PHASE RELAY 20V1B 20V1A 20V2C 20V2B 20V2A 20D1 20D2
49M1 THERMAL RELAY FOR FAN MOTOR CB1-3 CIRCUIT BREAKER RELAY OUTPUT
PWB1 CONTROL PC BOARD SP1 SUPPLEMENTARY PROTECTOR SYMBOL DESCRIPTION ACTION
PWB2 DISPLAY PC BOARD ES EMERGENCY STOP ON AT OPERATION
Y1 OPERATION RELAY REFERENCE:
LCD LCD MONITOR CN CONNECTOR (LOAD/UNLOAD/AUTO STOP)
20V1A SOLENOID VALVE DS PLUG IN CONNECTOR C REFER TO THE INSIDE OF THE AIR D REFER TO CONPONENTS THAT ARE
Y2 CAUTION OUTPUT ON AT CAUTION COMPRESSOR, BUT NOT IN THE EXTERNAL TO THE AIR COMPRESSOR
7.4.6 Wiring Connection Diagram 2 (400V Class, Inverter Staring (2/2))
57
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil Flow]
58
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil Flow]
Flow Diagram
3 5
Capacity Control & Blowoff Air Flow
21 Air Intake Filter
38 4 6
22 Suction Throttle Valve
33 23 Blowoff Valve
12 13 14 24 Blowoff Silencer
2 15 25 Blowoff air cooler
36
35
Oil Flow[→]
34
31 Oil Strainer
38 32 Oil Pump
PS1 TH2 PS4 TH3 TH5
33 Relief Valve
34 Oil Filter
35 Oil Cooler
36 Oil Temperature Control Valve
37 Gear Case Vent Pipe
Cooling Water Flow 38 Oil Drain Valve
1st-Stage Air-End Blowoff air cooler Aftercooler Cooling Air Flow and Enclosure
Suction 51 Ventilating Fan
52 Enclosure
53 Air Intake Duct
59
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil Flow]
1st-Stage Air-End Blowoff air cooler Aftercooler Cooling Air Flow and Enclosure
Suction 51 Ventilating Fan
52 Enclosure
53 Air Intake Duct
Drain Valve
Cooling Water
Outlet
60
8. STANDARD COMPONENTS AND SUBSYSTEMS [Cooling Water]
61
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
START button ON Discharge pipe pressure rises Discharge pipe pressure drops 3-way solenoid valve (20Ux)
switched over to pressurize
Airend starts rotation to Pressure sensor (PS) operates Pressure sensor (PS) operates Chamber (A)
compress minor amounts of air
3-way solenoid valve (20Ux) 3-way solenoid valve (20Ux) Suction throttle valve
Starts in no load switched over to pressurize switched over to pressurize (STV) closes
Chamber (A) Chamber (B)
△ switch (Reactor short) Blowoff valve opens
Suction throttle valve Suction throttle valve
(STV) closes (STV) opens
3-way solenoid valve (20Ux) Internal air in discharge pipe
switched over to connect
Blowoff valve opens Blowoff valve closes is exhausted to atmosphere
Chamber (A) & Chamber (C)
Suction throttle valve (STV) opens Internal air in discharge pipe Loading Compressor stops
is exhausted to atmosphere
Loading
NO 3-Way Solenoid
Suction Throttle Valve Air Exhaust Valve 20U2 Valve (4)
20U3 3-Way Solenoid
To the
Intercooler
Blowoff air cooler
Orifice
Pressure Sensor
Check Valve
Check Valve PS
Aftercooler
62
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
110
94
Pressure
psi
Air End Outlet Pressure
Time
110
Air Receiver Pressure Indications on LCD
however, the motor must keep operating for
more than 30 minutes after restarting.
Air End
psi Outlet
Pressure
Time
IMPORTANT
If the fixed speed machine is continuously loaded for a long period of time, condensate drain in blowoff air pipe may blowout from
blowoff silencer when unload start. To prevent blowout, air compressor unloads 0.5 second every 30 min when loading continue.
63
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
2nd-Stage
Blowoff
Blowoff Solenoid Valve (2)
Silencer
Intercooler
Pressure
Sensor
PS2
2nd-Stage
Air End Aftercooler
Air
Discharge
Check Valve
8.4.4 Relation between Air Consumption Rate and Capacity Control System
※ Figure in
〔 〕are for 0.93MPa models.
Air Operating Pressure Settings (MPa)
SW3
Consumption Frequency Capacity Control System Setting Lower
Factory Settings
(%) (Hz) Items Example
160VWN 160VWN
AUTO ON
100 to 60 40 to 60
(INVA)
[100 to 70] 〔40 to 54〕 ① 0.75 0.65
Standard or
240VWN 240VWN CPCS Motor Speed Control 〔0.93〕 〔0.83〕
AUTO OFF
100 to 55 35 to 60
(INVB)
[100 to 60] 〔35 to 53〕
160VWN
Upper 0.77 0.75 AUTO ON
60 to 5
② (purge start) 〔0.95〕 〔0.93〕 (INVA)
[70 to 5] 24
Two-Step Purge or
240VWN 〔24〕
Start/Stop Control Lower 0.72 0.65 AUTO OFF
55 to 5
(purge stop) 〔0.90〕 〔0.83〕 (INVB)
[60 to 5]
③
Motor Lower 0.72 0.65 AUTO ON
5 to 0 Motor Stop/Restart Control
stopped (motor restart) 〔0.90〕 〔0.83〕 (INVA)
(AUTO operation)
The DSP supports the 3 capacity control systems as above.
Depending on the varying air consumption, an appropriate system is automatically selected.
For more information, read the following page.
IMPORTANT
64
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
I: integral
Pressure Sensor
D: differential
(240VWN Models)
protection, the motor can only be stopped once every N>1 Number of
Motor Stopping N
180 operating minutes. When the pressure detected by (for 180 minutes)
the pressure sensor drops to a lower (purge-stop) pres- N≦1
① ② ③
sure point, the system will automatically restart the
CPCS Motor Two-Step Purge Motor Stop/Restart
motor, returning the system control to CPCS Motor Speed Control Start/Stop Control Control
Speed Control.
IMPORTANT
Air Consumption
100
(1) Once the motor has stopped, it cannot restart for 15 ①
Q (%)
seconds. ② ② ②
(2) The plant’s system pressure may drop drastically before ③ ③
0 Time
the motor will restart, 15 seconds later. To avoid such
problems, install an air receiver tank of volume larger
than the prescribed one.
65
8. STANDARD COMPONENTS AND SUBSYSTEMS [Outline of Oil Mist Remover Subsystem]
CAUTION
The oil mist remover reduces oil consumption to almost zero. However, The oil should still be replaced
bi-annually.
66
9. MAINTAINING THE DSP
CAUTION
● Before you service the DSP, carefully read pages 2 through 5, Chapter 1 “SAFETY.”
● Before you service the DSP, disconnect the power; otherwise you may receive an electric shock.
● Before you remove or disassemble a bolt, pipe, or any other part of the DSP, stop it, disconnect the
power, and make sure that the internal pressure has dropped to an atmospheric pressure. Otherwise
the compressed air may gush out of the DSP.
3 Overhauling
Overhauling consists changing the existing air end
with a new replacement air end.
Overhaul the DSP at 6 yearly.
67
9. MAINTAINING THE DSP [Standard Maintenance Schedule]
Intercooler
Enclosure
Ventilating Fan
Oil Pump
Instrument Panel
Main Motor
Common Base
68
9. MAINTAINING THE DSP [Standard Maintenance Schedule]
69
9. MAINTAINING THE DSP [Standard Maintenance Schedule]
Classification
Description Maintenance Model/Type Remarks
Daily 3-Months
LCD (Indications) Check △ Fixed/VSD Fill in the OPERATION RECORD LOGBOOK
Oil Level Check △ Fixed/VSD Add as required
Aftercooler Drain - Condensate Drain △ Fixed/VSD
Intercooler Drain - Condensate Drain △ Fixed/VSD
Control Air Pipe Filter Drain - Condensate Drain △ Fixed Speed only
Motor Grease Greasing △ Fixed/VSD
Intercooler
Enclosure
Ventilating Fan
Oil Pump
Instrument Panel
Main Motor
Common Base
70
9. MAINTAINING THE DSP [Standard Maintenance Schedule]
71
9. MAINTAINING THE DSP [Oil Mist Remover Maintenance]
2 years 3 years
Part or Item Daily Bi-Annually Annually (8,000Hr (4,000Hr
6 Years Remark
/years) /years)
Regulator - Settings △
Vacuum Indicator △
Safety Relief Valve △
Regulator - Performance △
Float Trap - Nozzle ▲ Disassemble and clean, if necessary.
Vacuum Indicator ▲ Disassemble and clean, if necessary.
Air Filter - Element ▲ Disassemble and clean, if necessary.
Remover - Element ●
Air Filter - Element ●
Safety Relief Valve - Sheet & Spring ●
Vacuum Indicator ●
Disassemble and clean.
Ejector ▲
Replace if it is too dirty.
Disassemble and clean.
Solenoid Valve ▲
Replace as required.
Regulator ● ● Change the assembly whole.
Ejector Assembly ●
Solenoid Valve - Coil Assembly ●
Float Trap-Nozzle Assembly ●
Pressure gauge ●
CAUTION
The oil mist remover reduces oil consumption to almost zero. However, The oil should still be replaced
bi-annually.
72
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
The maintenance intervals shown refer to the standard Maintenance Schedule (A).
CAUTION
If the air intake filter is clogged with dust/dirt particles, less air is taken in and discharge air temperature
rises. If the compressor room environment is dusty or dirty, service the air intake filter more frequently
than instructed on the Maintenance Schedule.
73
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
[Valve condition during conventional operation] ■ Cleaning the strainer element while the
Solenoid valve for drain compressor is running
Aftercooler side
If the strainer needs to be cleaned while the compres-
sor is running, consult with your dealer or Hitachi
Bypass Valve pipe
Service Station. Under ordinary circumstances, pres-
sure is applied to the strainer while the compressor is
Ⓔ running. You should therefore exercise maximum cau-
Orifice tion when removing the strainer.
Strauner
Ⓒ (1) Intercooler side
2-way valve B 2-way valve A ① Switch 3-way changeover valve I on the intercool-
Solenoid valve for drain er side from the “A” side to the “B” side.
Intercooler side
② Remove the element. Pressure is applied to the
Ⓐ strainer, so be extremely careful when opening the
Bypass Valve pipe cover of the strainer.
③ Clean the element and mount it by performing the
procedure in reverse order.
Orifice ④ Switch 3-way changeover valve I on the intercool-
3-way changeover Strauner er side from the “B” side to the “A” side.
valve I
(2) After cooler side
[Procedure for disassembling the strainer ① Switch 2-way valve A on the after cooler side from
element during operation] the “C” side to the “D” side.
② Make sure 2-way valve B is fully closed (“E” side).
Aftercooler side
In this state, strainer side pressure is drained.
③ Remove the strainer element. If 2-way valves A
and/or B are opened even the slightest amount,
Ⓕ Ⓔ
pressure is applied to the strainer. You should
therefore make certain that the valves are fully
closed.
2-way valve B
Ⓒ
2-way valve A ④ If 2-way valve B is opened to the “F” side in this
Ⓓ state, condensate can be drained while cleaning
Intercooler side
the strainer element.
Ⓐ ⑤ Place the cleaned element in its former position in
Ⓑ
the strainer and mount by performing the proce-
dure in reverse order.
⑥ Switch 2-way valve A on the after cooler side from
the “D” side to the “C” side. Also make sure
3-way changeover
valve I 2-way valve B is fully closed.
74
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
■ Orifice cleaning
[Orifice cleaning] Inspect and clean the orifices annually. Be sure to turn
the compressor off before inspecting and/or cleaning
the orifices.
Orifices
CAUTION
● Make sure a minute quantity of condensate
drains from the intercooler discharge port
every 20 seconds when loading the com-
pressor.
● If no condensate comes out, clean the
strainer element and orifices.
● If the compressor is operated with no con-
densate being discharged, it could cause
the inside of the compressor to rust and
could result in a serious accident.
75
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
WARNING
During inspection of the operation of the safety
relief valve, use the appropriate facial protec-
tion. High pressure air containing dust particles
can cause severe injury.
4 Oil - (replace every 8,000 operating hour or 2-year, whichever comes earlier)
① Place a oil receiver under the oil-draining valves
(1, 2), remove the oil.
② Replace the lubricating oil twice a year and clean the
bottom of the oil casing once a year. Wipe away the
sludge that builds up on the bottom of the oil pan of
the oil casing with a sponge and replace with new oil.
③ Remove the oil filling port plug, and fill the oil until
the oil reaches the upper red line of the oil level
gauge.
④ Check the Filling port and oil-draining valves (1, 2)
are surely seated.
76
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
IMPORTANT
IMPORTANT
77
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
3 Disassembling
① Disconnect the discharge pipe from the check valve
cover, and remove it.
Check valve cover ② Remove the fastening bolts of the check valve cover.
③ Remove the check valve cover, the gasket check valve
and gasket, in that order.
78
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
9 Clean Coolers
● Oil Cooler
Scale Removal
Remove the oil cooler water chamber cover. Flush
with Rydlymeand use a brass wire brush to remove
Wire-Brush the scale from the inner surfaces of the oil cooler
tube nest.
Oil Cooler
● Aftercooler/Intercooler
If scale build up occurs often, contact the local
Hitachi distributor for scale removal.
79
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
10 Battery replacement
80
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
11 Motor - (Servicing)
① Checking the operating temperature ③ Disassembling
The motor coil has a specified maximum allowable In a severe environment (dirty, corrosive, high dust or
temperature rise of 100℃ (212℉), based on an ambi- high powder), disassemble and service the motor
ent temperature off 40℃ (104℉). every two years. In a normal environment, disassem-
If the motor is unusually hot during normal operation, ble and service the motor every four years. For
regardless of the specified temperature rise, investi- the most common motor problems, see the Motor
gate the cause of the excessive heat utilizing the Diagnostic and Troubleshooting chart below.
Motor Diagnostics and Troubleshooting chart If the problem cannot be solved with the chart, con-
below. sult the local Hitachi distributor.
② Cleaning
Clean the motor periodically to prevent dust particles
from accumulating inside and outside of the motor.
When servicing the DSP, measure the insulation
resistance of the motor coil with a 500V megohmme-
ter and verify that the insulation resistance is 1MΩ
or more.
Heated
Excessive Rotation
Excessive Sound
breaker Tripped
Corrective Action
Electric Leak
Bearing
Frame
Cause
Installation
NOTE 3
Inadequate breaker capacity ○ ◎ Replace with properly specified capacity breaker.
Broken wires ○ Install new wires.
NOTE 3
Failed starter and switch contact ○ ○ Check the contacts and replace if necessary.
Dust accumulation reduced cooling performance Properly clean motor.
Load Power Supply Environment
○
Excessive ambient operating temperature ◎ ○ ◎ Improve the room ventilation or contact the local Hitachi distributor.
High humidity ◎ Contact the local Hitachi distributor.
Large external vibration/shock ◎ Take vibration and shock measurements.
Phase-lacking operation ◎ ◎ ○ ◎ ◎ ○ Check the wire thickness and length and contact the
Widely dropped voltage ○ ○ ◎ ◎ local power utilities company.
Fluctuating voltage ○ ○ ○ ○ Contact the local power utilities company.
Overload ○ ◎ ◎ ○ Check the DSP capacity control system.
Thrust force by the machine ○ ○ ◎ Center the shaft.
Excessive bearing noise NOTE 2 ◎ ◎ ◎ ○ Contact the local Hitachi distributor.
Burnt motor coil NOTE 2 ○ ○ ○ ◎ ◎ ◎ ○ Contact the local Hitachi distributor.
NOTES:
1. ◎ : Close relationship between the cause and type of problem, ○ : relationship between the cause and type of problem.
2. Detect the fundamental cause of the problem and take corrective action.
3. Breaker, switch and starter are hot.
81
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
IMPORTANT
● Grease gun example
● Contact your local authorized distributor or master Lever-type grease gun made by Yamada Corporation
dealer for the purchase of approved Hitachi grease. (CH-400 Micro-hose [pin type SPK-1C])
● Main motor is to be greased only when it is operating.
● Grease pan should only be cleaned when the com-
pressor is not operatong.
CAUTION
The proper amount of grease must be applied to the main motor to ensure that there is no leakage and/
or overheating of the bearings. Ensure that the main motor is properly greased during the commission-
ing of the start-up of the compressor. If the compressor has not been operational for (3) months grease
when restarting. Following "9.1 Air Compressor Maintenance" on page 67 and "9.2 Standard
Maintenance Schedule (A)(B)" on page 68 to 71, replace the main motor bearings periodically.
82
9. MAINTAINING THE DSP [How to Service the DSP Air Compressor]
② Remove the nut and the cover. Then, remove the ele-
4. Vacuum Indicator (Clean Bi-Annually and
ment.
Replace Annually)
③ Install a new element. Carefully seat the upper and
lower rubber gaskets on the element without allowing ① A dirty vacuum indicator may malfunction. Clean
any gaps. Bi-annually and replace annually.
Nut ② Hold up and pull down the locked pipe joint. Pull down
④ Grease the O-ring, φ8
Rubber Packing
Locked Joint
Pull down
3/8 φ12
Set Screw
Relief Valve Vacuum Indicator
Element
Cover
Baffle
Nut
83
10. PRECAUTIONS WHEN THE COMPRESSOR IS TO BE IDLE FOR AN EXTENDED PERIOD OF TIME
① If the compressor is not to be used for a week or
more, be sure to press the UNLOAD STOP button on
the instrument panel. 運転管理 運転状況
RUNNING CONTROL RUNNING MODE
モニタ 警 報 遠 方 電 源
REMOTE
are dry.
+/− SHUTDOWN
UP/
DOWN
表示切替/
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
設 定 STR 1 2
SET
MONITOR
IMPORTANT
UNLOAD STOP
CAUTION
● Failure to take measures to prevent rust could result in rusting due to humidity in the atmosphere or
lack of oil film in the bearings, and could cause the compressor to freeze up or could result in
damage to the bearings when operation is restarted.
● The UNLOAD STOP button is not only used when the compressor is to be idle for an extended period
of time; it is also effective way to prevent the inside of the compressor from rusting during routine
operation as well.
84
11. PARTS LIST
85
11. PARTS LIST
2 Motor Assembly
401
453
454
455
370
419
393
391
457
460
461 F72
306
415
421
426
F72 429
425
Ref.
No. Description
306 Pinion Gear, oil pump
370 O-Ring
391 Shaft Seal
393 Packing, shaft seal
401 Motor
415 Packing, motor
419 Cover, shaft seal
421 Base, air end
425 Vibration Isolation Rubber
426 Support Bolt (1), gear case
429 Support Bolt (2), gear case
453 Bearing (Load-side)
454 Bearing (Anti-Load side)
455 Grease
457 Pull Gear, motor
460 Gear Stud, oil pump
461 Gear Shaft, oil pump
F72 Grease Pan
86
11. PARTS LIST
D
537
532
528
509 534
517
518 508
507
541 506
535
536
525
503
504 519 521
522 549 552 C
D
504 519 521
522 549 552 B 509 541 518 517
515 521
542 526 528 537
A
514
529 A
530
521 526
569
B C
501
511
549 521 519 504 522 552 552 522 504 519 521 549
554
Ref. Ref.
No. Description No. Description
500 Suction Throttle Valve Assembly 528 Baffle Plate
501 Air Cylinder Assembly 529 Spring Washer (SUS)
555 502 Body, STV 530 Nut
503 Tube, air cylinder 532 Body, blowoff valve
502
513 504 Cover, air cylinder 534 Seal Washer, air cylinder
506 Piston, blowoff valve 535 Nut
507 Valve Sheet, blowoff valve piston 536 Wave Spring
512 508 Plate 537 Gasket, air cylinder piston
509 Spindle, air cylinder 541 Holder, piston
559 511 Packing, air cylinder 542 Spacer
512 Packing, air end air intake 549 Flange, o-ring
513 Packing, STV cover 551 Set of Air Cylinder Consumable Parts
F44 514 Valve Plate (A), STV 552 O-ring, air cylinder
558 515 Valve Plate (B), STV 554 Cover, STV
517 Piston, air cylinder 555 Cover Packing, STV
518 Seal Packing (3) 558 Adjusting Bolt, suction bypass valve
F46
519 Seal Packing (4) 559 Seal Washer, suction bypass valve
521 Seal Packing (5) 569 Grease, air cylinder
522 Bush, air cylinder F44 Piston, STV
525 Tie Rod, air cylinder F46 O-ring
526 Cover, air cylinder ー ー
87
11. PARTS LIST
555
502
513
512
559
F44
558
F46
88
11. PARTS LIST
629
637
404
610 614
615
611
613 628
612 616
E35
E39
89
11. PARTS LIST
6 Oil Pump
Ref.
No. Description
300 Set of Oil Pump Consumable Parts
327 Oil Pump Assembly
328 Bearing
345 329 Oil Seal
356 342 Body
343 Housing, oil pump bearing
342
345 Key
354 353 Inner Rotor
354 Outer Rotor
355 Shaft
362 356 Key
362 Snap Ring
329
328 363 O-Ring
378 Bush Bearing
355
353
363
378
343
7 Instrument Panel
Ref.
No. Description
719 719 Digital Panel
744
744 Lithium Battery
746 Control PCB
748 Seat, instrument panel
749 Display Unit
757 Screw
749
746
748
757
90
11. PARTS LIST
745 G17
D73
C95
D08 D12
D07 G16
E50 G04
G80 G05
704
D06
G06
G07
702
B72
708
729
709 701
929
F81 G04
G05
743
929
931
B44
931
935
C97
E48
E49
91
11. PARTS LIST
G81 E02
G20
G19 E03
G18
704
G04 745
G05
E10
D73
G80 E07
D08 E50 D12
D07
D06
G17 G02
D75 G03
G15
B46
G06 708
G07
G16
709 F81 C96
E50 D12 C95
G04
G05
929
931
C97
B44
935
753
931
B72 E48
E49
92
11. PARTS LIST
10 Air Piping
874
875
865
865 036
H41 F06 026
H32
868
875
H32
865
044 870
026
H41 036
044 871
F04 870
870
871
870 001
035
010 D72
002 F03
024 035 010 865
002
035 025
035 001
039 035
023 029
F07 D71
035
D70 865
035
034
H32
H32
F66
033 F02
H34
Ref. Ref.
No. Description No. Description
001 Aftercooler Header 870 Gasket
002 Gasket, aftercooler header 871 Check Valve
003 Condensate Separator 874 Discharge Piping
004 Gasket, condensate separator 875 Safety Valve
010 Gasket, intercooler header D70 Thermistor (1)
021 Demister D71 Thermistor (2)
022 Air Piping (1) D72 Thermistor (3)
023 Air Piping (2) F02 Air Piping (7)
024 Air Piping (3) F03 Air Piping (8)
025 Air Piping (4) F04 Air Piping (9)
026 Air Piping (5) F06 Air Piping (10)
029 Air Piping (6) F07 Air Piping (11)
033 Gasket (1), discharge piping F65 Seat, condensate separator
034 Gasket, 1st-stage air end discharge flange F66 Seat Gasket, condensate separator
035 Gasket, 1st-stage H31 Cooler Header (1)
036 Gasket, 2nd-stage H32 O-Ring, cooler header
039 Gasket, 2nd-stage air end discharge flange H33 O-Ring, demister box
044 Intercooler Header H34 Demister Box
865 Gasket (2), discharge piping H41 Cooler Header (2)
868 Cover, check valve − −
93
11. PARTS LIST
F32
F40
F35
F31
880
D34
F37
887
882
F12
94
11. PARTS LIST
D81
773
D35
D81
D35
D35
774
D35
888
95
11. PARTS LIST
B40
009
009
018
B41
011
F47
F36
D36 096
F36 017
D36
96
11. PARTS LIST
14 Condensate Piping
Ref.
No. Description
006 Y-type strainer
007 Gasket, y-type strainer
043 Check Valve
045 Orifice, condensate piping
047 Y-type strainer Element
876 Stop Valve
F67 3 way Switching Valve
F69 Support, drain piping
F48 Vibration Isolation Rubber
H36 Drain Solenoid Valve (2)
F69
876
H36
045
006
047 876 043
F67
007
F48 H36
045
006
047
007 F69
F48
E93 Ref.
Only 200W, 240W No. Description
E79 036 Gasket, 2nd-stage
900 Blowoff Silencer (1)
E69 901 Seat (1), blowoff silencer
E96 036 902 Cover (1), blowoff silencer
E94 E07 Cover (2), blowoff silencer
E07
E69 Seat (2), blowoff silencer
901 E79 Blowoff Silencer (2)
036
E93 Purge air cooler
036
E94 Blowoff Air Piping (1)
900 E95 036 E95 Blowoff Air Piping (2)
E96 Blowoff Air Piping (3)
E94
902
97
11. PARTS LIST
E22
E23
036
036
E21
E68
902
E21
900
901
901
900
D29
902 E68
98
11. PARTS LIST
899 D79
898
F79
F48
019
892
085
799
A80
A82 D26
(Discharge pressure)
046
D99
(Interstage pressure)
A82 D26
(Oil supply pressure)
A81
Ref.
No. Description
019 Check Valve
046 Orifice
085 O-ring, control line filter
799 Element, control line filter
892 Support plate, solenoid valve
898 Pressure Differential Indicator
899 Solenoid Valve Manifold
A80 Transparent Hose
A81 Hose Connector
A82 Wire Clamp
D26 Pressure Sensor
D79 Filter Nipple
D99 Interstage Pressure Sensor
F48 Vibration Isolation Rubber
F79 Air Exhaust Valve
99
11. PARTS LIST
D79
898
D26
(Discharge pressure)
D99
(Interstage pressure)
D26
(Oil supply pressure)
Ref.
No. Description
898 Pressure Differential Indicator
D26 Pressure Sensor
D79 Filter Nipple
D99 Interstage Pressure Sensor
100
11. PARTS LIST
19 Enclosure
951
915
941 914
956 938
913
E71
940
938
984
911 E12
949 977 D85
E76
926 E73
922 933
908
E74
932
984
903 978
937 E65 H60
A71 H68
E72
975
942 955
951 H68
954
H70 945
H68
906
H68 D25
938 958
953
H59
D14
923 959 D14 983
952
D90
D25 904
943 944
960
982
985 905
912
981
101
11. PARTS LIST
D38 O-Ring
D39 Solenoid Valve
D37 D40 Pressure Gauge
D41 Ejector
D44
D42 Vacuum Indicator
D43 Valve Sheet
D43
D44 Valve Spring
D38 D45 Air Filter/Air Pressure Regulator
D46 Diaphragm, air pressure regulator
D47 Valve Stem, air pressure regulator
D48 Element, air filter
D49 Float Trap
D78 Packing
3/8
φ12
D42
D41
φ8
1/4
1/8
φ6
φ12 3/8
1/8
φ6
D40
D78
D39
D49
φ8 D45
D46
D47
1/4
φ8
D48
D78
102
12. WARRANTY, AFTER-SALES AND SERVICE
■ Warranty
For information regarding warranty, refer to the HITACHI DSP-Series Warranty Policy.
■ After-Sales Service
If you have a problem when using the product, read the section 4, “TROUBLESHOOTING,” carefully and examine the
problem by yourself. If you still cannot find the answer, contact your distributor and declare the following information:
● Model (TYPE)
● Serial Number (MFG. NO.) }
Check the nameplate on the product
103
13. OPERATION RECORD LOGBOOK
1st-Stage Air 2nd-Stage
Motor Daily Control Remarks
End Air End 2nd-Stage Ambient
Oil Oil Load Quantity of Power Total Oil
Suction Air Temperature Temperature Pressure Ratio Cooling Operation Added
Date Time Voltage Current Temperature Pressure Temperature Pressure Temperature Water Hours
MPa kW
Control Oil
MPa ℓ ℓ Intercooler Aftercooler (Parts Change etc.)
℃ (℉) ℃ (℉) ℃ (℉) (psi) % (us gallon) (HP) h (us gallon)
Line Filter Level
V A ℃ (℉) MPa (psi) ℃ (℉) (psi)
Loading :
[0.75 (110), 0.86 (125)]:
0.17 to 0.27 (24 to 39) 0.75/0.86/1.0, 63 40 63 0.12 (17) Inspect
Benchmarks 210 Condensate Condensate Condensate
[1.0 (145)] : 0.17 (110/125/145) (145) (104) (145) to drained drained drained
oil level
(Fixed speed) (410) to 0.3 (24 to 43) gauge
Unloading :
or less or less or less or less 0.18 (26)
-0.08 to 0 (-12 to 0)
Loading :
[0.75 (110), 0.86 (125)]: 0.08 (12) to
0.17 to 0.30 (24 to 43) 0.75/0.86/1.0, 63 40 63 Inspect
Benchmarks 210 0.18 (26) Condensate Condensate
[1.0 (145)] : 0.17 (110/125/145) (145) (104) (145) drained drained
− oil level
(VSD) (410) to 0.3 (24 to 43) 0.04 (6) to gauge
or less or less or less or less
Unloading : 0.16 (23)※
0.02 to 0.10 (3 to 15)
NOTES: 1. The □ marked items as well as the number of loading times are indicated on the LCD.
2. Regarding ※ mark, upper figure is for 45Hz driving frequency, lower figure in ( ) is for less than 45Hz driving frequency.
104
14. STANDARD SPECIFICATIONS
■ DSP-132WN, 145WN, 160WN
Type − PN-404-04H
Voltage V 460 460 460
Current A 1.0 1.0 1.0
Frequency Hz 60 60 60
Number of Pole − 4-Pole
Insulation Class − Class E
Oil Cooler − Water-Cooled Horizontal Shell-and-Tube Type (Water: inside, Oil: outside)
Intercooler − Water-Cooled Horizontal Shell-and-Tube Type (Water: outside, Air: inside)
Other
105
14. STANDARD SPECIFICATIONS
■ DSP-200WN, 240WN
Type − PN-404-04H
Voltage V 460 460
Current A 1.0 1.0
Frequency Hz 60 60
Number of Pole − 4-Pole
Insulation Class − Class E
Oil Cooler − Water-Cooled Horizontal Shell-and-Tube Type (Water: inside, Oil: outside)
Intercooler − Water-Cooled Horizontal Shell-and-Tube Type (Water: outside, Air: inside)
Other
106
14. STANDARD SPECIFICATIONS
■ DSP-160VWN, 240WN
Voltage V 460
Maximum current A 275 399
Frequency Hz 60
Number of Pole − 4-Pole
Insulation Class − Class F
Nominal Output kW (HP) 0.4 (0.54)
Cooling Fan Motor
Type − PN-404-04H
Voltage V 460
Current A 1.0
Frequency Hz 60
Number of Pole − 4-Pole
Insulation Class − Class E
Oil Cooler − Water-Cooled Horizontal Shell-and-Tube Type (Water: inside, Oil: outside)
Intercooler − Water-Cooled Horizontal Shell-and-Tube Type (Water: outside, Air: inside)
Other
107
Note the Compressor’s Specifications for future reference on the table in section 11.
DSA-586A 2013.1
Printed in Japan