Professional Documents
Culture Documents
Air-cooled
DSP-37A5N DSP-37AR5N
DSP-37A6N DSP-37AR6N
DSP-55A5N DSP-55AR5N
DSP-55A6N DSP-55AR6N
DSP-37VA5N DSP-37VAR5N
DSP-37VA6N DSP-37VAR6N
DSP-55VA5N DSP-55VAR5N
● This INSTRUCTION MANUAL explains in detail
DSP-55VA6N DSP-55VAR6N the important items that require attention;
[Without dryer type] [Built-in dryer type] observed as the following:
● Always observe instructions of WARNING,
Water-cooled CAUTION and IMPORTANT, as they indicate
considerable risks to safety.
DSP-37W5N
GRAPHIC DESCRIPTIONS:
DSP-37W6N
DSP-55W5N WARNING : Indicates warnings. If handled improp-
erly, death or severe injury could
DSP-55W6N result.
WARNING
Never remove a protective device from the air compressor or modify
the air compressor.
It is imperative to install an earth leakage (ground) circuit breaker on
the power cable. This prevents a ground fault accident.
DSP air compressors are not designed, intended or approved for
breathing air applications. Hitachi does not approve specialized
equipment for breathing air applications and assumes no responsibility
or liability for compressors used for breathing air services.
■ Model Code
D S P - 37 V A R 5 N
Dry or oil-free rotary NEXTseries
As the unit of pressure, the International System of Units (SI) is used throughout this manual.
For conversion from the conventional unit, see [Example].
[Example] Discharge pressure 0.70 MPa = Conventional unit: 7.14 kgf/cm2 (corresponding
value: 1 kgf/cm2 ≒ 0.098 MPa)
● For improvement of the product, contents in this manual are subject to change without notice. Please be forewarned.
● The product drawing in this manual shows DSP-55VAN as a typical example.
Contents
1. SAFETY PRECAUTIONS ………………………………………………………………………………………… 2
2. GENERAL DESCRIPTION 2.1 Appearance ………………………………………………………………………… 6
2.2 Components ………………………………………………………………………… 9
2.3 Daily Operating Components …………………………………………………… 12
3. OPERATION PROCEDURE 3.1 Instrument Panel …………………………………………………………………… 14
3.2 Start/Stop Operation ……………………………………………………………… 16
3.3 How to Use the Liquid Crystal Display (LCD) ………………………………… 17
3.4 How to Use the Digital Monitor ………………………………………………… 27
3.5 Daily Operation of Air Compressor ……………………………………………… 35
3.6 Daily Operation of Oil Mist Remover …………………………………………… 37
3.7 Adjustment Procedure …………………………………………………………… 37
4. TROUBLESHOOTING 4.1 Protective Device …………………………………………………………………… 38
4.2 Troubleshooting of Air Compressor …………………………………………… 44
4.3 Troubleshooting of Oil Mist Remover …………………………………………… 45
5. INSTALLING AND 5.1 Unpacking the Air Compressor …………………………………………………… 46
PIPING THE DSP 5.2 Conveying the DSP Air Compressor …………………………………………… 46
5.3 Installing the DSP Air Compressor ……………………………………………… 47
5.4 Piping the DSP Air Compressor ………………………………………………… 48
5.5 Ventilation of Air Compressor Room …………………………………………… 51
6. STARTUP OPERATION 6.1 Startup Operation of the Air Compressor ……………………………………… 53
6.2 Initial Setting of OMR Regulator ………………………………………………… 56
7. WIRING 7.1 Power Supply Equipment ………………………………………………………… 57
7.2 Connecting the Power Cable ……………………………………………………… 57
7.3 Wiring Diagram ……………………………………………………………………… 59
7.4 Control panel/LCD Monitor Specifications……………………………………… 60
8. STANDARD COMPONENTS 8.1 Standard Components …………………………………………………………… 81
AND SUBSYSTEMS 8.2 Air/Oil/Water Flow ………………………………………………………………… 82
8.3 Cooling Water ……………………………………………………………………… 87
8.4 Capacity Control System ………………………………………………………… 88
8.5 Dryer System ………………………………………………………………………… 94
8.6 Oil Mist Remover System ………………………………………………………… 95
9. MAINTENANCE 9.1 Periodical Maintenance of Air Compressor …………………………………… 96
9.2 Standard Maintenance Schedule ………………………………………………… 97
9.3 Maintenance Schedule for Dryer ……………………………………………… 101
9.4 Maintenance Schedule for Oil Mist Remover ……………………………… 101
9.5 How to Service the Air Compressor ………………………………………… 102
10. CAUTIONS FOR A LONG TERM OPERATION SUSPENSION …………………………………………… 117
11. PARTS LIST ……………………………………………………………………………………… 118
12. WARRANTY AND 12.1 Warranty …………………………………………………………………………… 135
AFTER-SALES SERVICE 12.2 After-Sales Service ……………………………………………………………… 135
13. RELOCATION AND 13.1 Relocation ………………………………………………………………………… 147
DISPOSAL 13.2 Disposal …………………………………………………………………………… 147
13.3 Recovery of Fluorocarbons …………………………………………………… 147
14. OPERATION RECORD LOGBOOK ……………………………………………………………………………… 148
15. STANDARD SPECIFICATIONS …………………………………………………………………………………… 150
1
1. SAFETY PRECAUTIONS
To ensure safe and proper operation of the air compressor, it is indispensable to carefully
read and understand the following warnings and instructions detailed below. These
warnings and instructions are attached to the air compressor as shown in the figure
below.
Air-Cooled DSP-37/55A(R)N
DSP-37/55VA(R)N
WARNING
Rotating Parts!
● Keep your hands and
rods etc. away from the
rotating parts (pulleys,
belts, couplings,
cooling fans, etc.).
●Do not start the air
compressor without
you returning the belt
cover to its original
place.
V pulley
Rotating V belt
Direction
of
V-Belts
M sheave
● Vtype
Air End WARNING
Electric Shock Hazard!
Discharge ● 10 minutes before servicing or wiring the air
Air Pipe compressor, disconnect the power. This will prevent
anyone from turning on the power and causing an
electric shock that could lead to severe injury or death.
● Do not allow any unlicensed person to wire the air
Heated!! compressor. Always use a licensed electrician.
● Ground the air compressor.
2
1. SAFETY PRECAUTIONS
WARNING
Rotating Parts!
When the air compressor is operating, do not
remove the protective cover; otherwise you may
be drawn in the rotating parts
WARNING WARNING
WARNING
WARNING
3
1. SAFETY PRECAUTIONS
Water-Cooled DSP-37/55WN
DSP-37/55VWN
WARNING
Rotating Parts!
● Keep your hands and
rods etc. away from the
rotating parts (pulleys,
belts, couplings,
cooling fans, etc.).
●Do not start the air
compressor without
you returning the belt
Hot Surface!
Do not directly touch the air V pulley
end, discharge air pipe, check
valve, and aftercooler header
when the air compressor is
operating and immediately Rotating V belt
after it has stopped, because Direction
these parts are heated then. of
V-Belts
M sheave
Discharge
Heated!! Air Pipe
WARNING
Hot Surface!
● Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
● Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
Air End
Discharge
Air Pipe
Heated!!
WARNING WARNING
Electric Shock Hazard! Electric Shock Hazard!
● Before servicing or wiring the air compressor, ● 10 minutes before servicing or wiring the air
disconnect the power. This will prevent anyone compressor, disconnect the power. This will prevent
from turning on the power and causing an electric anyone from turning on the power and causing an
shock that could lead to severe injury or death. electric shock that could lead to severe injury or death.
● Do not allow any unlicensed person to wire the air ● Do not allow any unlicensed person to wire the air
compressor. Always use a licensed electrician. compressor. Always use a licensed electrician.
● Ground the air compressor. ● Ground the air compressor.
4
1. SAFETY PRECAUTIONS
WARNING
Rotating Parts!
When the air compressor is operating, do not
remove the protective cover; otherwise you may
be drawn in the rotating parts
WARNING WARNING
WARNING
WARNING
5
2. GENERAL DESCRIPTION
2.1 Appearance
This section illustrates and describes the major components of the DSP air compressor. Be familiar with the name,
location and function of each component before using the DSP air compressor.
Air-Cooled DSP-37/55AN
DSP-37/55VAN
[Front View]
Air Intake
(Air for Package) Air Intake
Coolant Filling Port
[Rear View] Use the port to fill the
coolant reservoir with
coolant.
Coolant Filling Port Air Exhaust
Use the port to fill the
coolant cooler with
OMR
coolant.
See page 95 for the
details
Air Intake
(air compressor)
Coolant Level Gauge
Sling Fitting
Air Intake Use the sling fitting
(Air compresser Package) when moving and
installing the DSP air
Power Supply Port compressor.
Check the
specifications, power
supply and voltage External Pressure
before connecting the
Detecting Port
power supply. Air Intake
Air Intake Connect with
secondary side of
Compressor Air Discharge automatic valve after
discharge.
6
2. GENERAL DESCRIPTION [Appearance]
Air-Cooled DSP-37/55ARN
DSP-37/55VARN
Dryer air outlet
[Built-in dryer type]
[Front View]
Instrument Panel
Air Exhaust Air Exhaust See page pp. 14-15,
(Air Compressor Package) Air Exhaust chapter 3, for details.
This panel discharges
the hot air generated
in the air compressor. Plate of Operating/
Servicing Instructions
Enclosure Read carefully the
plate before operating
Enclosure panels
lower the sound level and servicing the DSP.
of the air compressor
package.
Oil Filling Port
Use the port to fill the
Compressed Air Discharge gear case with oil.
Sling Fitting
Oil Level Gauge Use the sling fitting
This indicates the when moving and
quantity of the oil in installing the DSP air
the gear case. Check compressor.
the oil level before
starting the DSP and
when operating it. Maintenance Door
Open the left door only
when servicing the
Air Intake DSP air compressor.
(Air for Package) Keep it closed when
operating the DSP air
compressor.
[Rear View]
Air Exhaust
Coolant Filling Port
Use the port to fill the
Dryer air inlet Air Exhaust coolant cooler with
coolant.
OMR
See page 95 for the
Air Intake details
(Air compresser Package)
Drain Trap
Air Intake Air Intake
Automatically drain the
condensate. (air compressor)
7
2. GENERAL DESCRIPTION [Appearance]
Water-Cooled DSP-37/55WN
DSP-37/55VWN
[Front View]
Plate of Operating/
Enclosure Servicing Instructions
Enclosure panels Read carefully the
lower the sound level plate before operating
of the air compressor
and servicing the DSP.
package.
Air Intake
(Air for Package) Air Intake
Air Intake
[Rear View]
Air Exhaust OMR
See page 95 for the
details
External Pressure
Detecting Port
Power Supply Port
Connect with
Check the secondary side of
specifications, power automatic valve after
supply and voltage discharge.
before connecting the
power supply. Air Intake
Compressed Air Discharge
8
2. GENERAL DESCRIPTION [Components]
2.2 Components
Air-Cooled DSP-37/55AN
DSP-37/55VAN
[Front View] Cooling fan Enclosure
Cooler
Precooler
Instrument panel
Control panel
Coolant Pump
Main motor
Oil level gauge
[Rear View]
Oil filter
V-Belt
9
2. GENERAL DESCRIPTION [Components]
Air-Cooled DSP-37/55ARN
DSP-37/55VARN
[Built-in dryer type]
[Front View] Discharge pipe Dryer
Dryer
(Compressed air discharge) Enclosure
Cooling fan
Cooler
Precooler
Instrument panel
Control panel
Coolant Pump
Common base
Airend
Main motor
Oil level gauge
[Rear View]
Oil filter
V-Belt
Check valve
10
2. GENERAL DESCRIPTION [Components]
Water-Cooled DSP-37/55WN
DSP-37/55VWN
Precooler
Control panel
Aftercooler
Main motor
Oil level gauge
[Rear View]
Oil filter
V-Belt
Check valve
11
2. GENERAL DESCRIPTION [Daily Operating Components]
運転管理 運転状況
RUNNING CONTROL RUNNING MODE
自 動
AUTO
モニタ 警 報 遠 方 電 源
REMOTE
MONITOR
POWER
ALARM
メニュー 負 荷
[× 10h] LOAD
MENU
機 能 リセット 起動待ち
FUNC RESET 故 障 AUTO START
+/− SHUTDOWN
UP/
DOWN
表示切替/
遠 方 ワイドモード ドライヤ 運 転 停 止
REMOTE SELECT/WIDE DRYER START STOP
記 憶
設 定 STR 1 2
SET
MONITOR
Oil level
アンロード停止
gauge
② When adding the coolant, use either of the two ② Use the following lubricating oil for the air
coolant filling ports; one for the coolant reservoir and compressor
another for the coolant cooler. To access the former,
open the rear door of the enclosure. To access the
latter, remove the cover for the pressure cap. Manufacturer Description
Cover Coolant filling
(pressure cap) port IDEMITSU DAPHNE NEW ROTARY
Pressure cap
Coolant KOSAN COMPRESSOR OIL A
Reservoir
COSMO OIL
COSMO SCREW 32X
LUBRICANTS
Rear Cover
SHOWA SHELL
Shell Corena S2 RJ 32
SEKIYU
JX NIPPON OIL
FAIRCOL RA32
& ENERGY
12
2. GENERAL DESCRIPTION [Daily Operating Components]
Aftercooler
drain port
Sight Glass
Control line filter
drain port
(fixed-speed type only)
① Keep the pet cock of drain trap “Crack open” and ① Stop the cooling water flow when the DSP has
verify the slight amount of air is discharged. stopped running.
② Verify the condensate is discharged every day. ② Open the water relief pet cock and the water drain
valve at the water drain port to remove the cooling
③ If condensate is not discharged properly, clean the
water from the system.
drain trap. ( page 116)
③ Take care to completely drain the cooling water
during the winter season to prevent freezing in the
cooling water pipes ( For more information,
see page 87).
Ball valve
Pet cock
Drain port
13
3. OPERATION PROCEDURE
3.1 Instrument Panel
自 動
AUTO
モニタ
MENU button MONITOR
設 定
SET
MONITOR
14
3. OPERATION PROCEDURE [Instrument Panel]
R GE NC
警 報 遠 方 電 源 ME
E
REMOTE
Y
POWER
ALARM
負 荷
[× 10h] LOAD
機 能 リセット 起動待ち
FUNC RESET 故 障 AUTO START STOP
SHUTDOWN
表示切替/
遠 方 ワイドモード ドライヤ 運 転 停 止 START button
REMOTE SELECT/WIDE DRYER START STOP Starts the air compressor.
記 憶 The START light turns ON while
STR 1 2 air compressor is running.
15
3. OPERATION PROCEDURE [Start/Stop Operation]
IMPORTANT
5 seconds
(1) The air compressor does not start for 10 second after
㻞 㻜 㻝 㻝 䠋 㻝 㻝 䠋 㻜 㻝 㻝 㻥 䠖 㻜 㻞 power on to secure the safety.
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 For , if the START button is pressed within 10 to
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻢 㻜 㻹 䠬 䠽 15 seconds after power-on, the AUTO START light will
blink up to 10 seconds for operation preparation and
㻾 㼁 㻺 㻌㻴 㻻 㼁 㻾 䠖 㻝 㻞 㻞 䡄
then the compressor starts running.
㻸 㻻 㻭 㻰 㻌 㻴 㻻 㼁 㻾 䠖 㻡 㻠 䡄
㻸 㻻 㻭 㻰 㼀 㻵 㻹 㻱 㻿 䠖 㻝 㻞 㻟 (2) Make sure that the door is closed before starting the
㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻝 㻝 䠂 air compressor.
㻸 㻻 㻭 㻰 㼀 㻵 㻹 㻱 䠖 㻞 㻠 䡏 (3) Buttons, such as START/STOP/RESET function shall
㼁 㻺 㻸 㻻 㻭 㻰 㻌 㼀 㻵 㻹 㻱 䠖 㻝 䡏 be pressed for more than 0.3 seconds.
㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻡 㻜 䠝
㻲 㻾 㻱 㻽 㼁 㻱 㻺 㻯 㼅 䠖 㻜 㻜 㻚 㻜 䠤 䡖
㻻 㼁 㼀 㻼 㼁 㼀 䠖 㻖 㻖 㻚 㻖 䡇 䠳
3.2.3 Emergency Stop (Option)
※ The asterisk blinks when the clock and total running Pressing EMERGENCY STOP button, the DSP
hours are active. compressor immediately stops.
This switch should only be pressed in emergency.
If phase is reversed, “Connection Error: Reverse The compressor can not be restarted until the switch is
Phase” will be displayed on the LCD monitor as a manually reset.
setting/connection check message. In this case, Turn the switch knob clockwise and press the RESET
exchange 2 out of the 3 main power cables. If the air button to reset.
compressor has control transformer in the control
panel, Open Phase is indicated as Reverse Phase. So
check the power cable connection of T Phase.
In case of open phase, “Connection Error: Open
Phase” will be displayed on the LCD monitor. In this
case, check the power cables.
16
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
㻿 㻱 㼀 䠖 㻻 㻼 㻱 㻺 㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
モニタ
Monitor display 2 MONITOR
㻞 㻜 㻝 㻝 䠋 㻝 㻝 䠋 㻜 㻝 㻝 㻥 䠖 㻜 㻞
㻼 㻾 㻱 㻿 㻿 㼁 㻾 㻱
㻵 㻺 㼀 㻿 㼀 㻳 䠊 㻼 䠖 㻖 䠊 㻖 㻖 㻹 䠬 䠽
㻻 㻵 㻸 㻌 㻼 㻾 㻱 㻿 䠖 㻜 䠊 㻜 㻜 㻹 䠬 䠽
㻯 㻸 㼀 䠊 㻼 㻾 㻱 㻿 䠖 㻜 䠊 㻜 㻜 㻹 䠬 䠽
㼀 㻱 㻹 㻼 㻱 㻾 㻭 㼀 㼁 㻾 㻱
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻝 䠖 㻖 㻖 㻖 䉝 IMPORTANT
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻞 䠖 㻖 㻖 㻖 䉝
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 䠖 㻌 㻞 㻡 䉝
㻯
㻞
㻸
㻺 㻰
㼀 䠊
㻌 㻿
㼀 㻱
㼁
㻹
㻯
㻼
㼀
䠖
䠊 㼀 䠊 䠖
㻌
㻖
㻞
㻖
㻡
㻖
䉝
䉝
About the LCD Backlight
㻹 㻭 㻵 㻺 㼀 㻱 㻺 㻭 㻺 㻯 㻱 (1) In the event that no button has been used for 10
㻴 㻾 䠊 㼀 㻻 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻢 㻜 㻜 㻜 䡄
㻺 㻱 㼄 㼀 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻖 㻖 㻖 㻖 minutes, the LCD backlight automatically turns OFF
for protection to the display panel. It comes ON
モニタ
MONITOR
again if any button is pressed, other than the START
and STOP buttons.
(2) If an event happens while the LCD backlight is off,
the backlight automatically turns ON and stays ON
as long as the event exists. Remote and instant stop
mode can't be set by the LCD monitor. Set after
■ Message Screen ( page 19) referring to “3.4 How to Use the Digital Monitor.”
Monitor display 3 ( page 27)
㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㼀 㼁
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽
䠘 㻿 㻴 㼁 㼀 㻰 㻻 㼃 㻺 䠚 ■ Message Display
㻯 㻻 㻻 㻸 㻭 㻺 㼀 䠖
㻻 㻵 㻸 䠖 Automatic restart/stop messages after shutdown or
㻞 䠪 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 㻱 㻹 㻼
㻴
㻯
㻵
㻻
㻳
㻺
㻴
㼀 㻭
㻌㻰
㻯
㻵
㼀
㻿
㻻
䠊 㼀 㻱 㻹
㻾 㻌㻱 㻾
㻼 䠖
㻾 䠖
warning occurrence and inspection/maintenance
モニタ
MONITOR
㻻
㻸
㼂
㻻
㻱
㼃
㻾
㻌
㻸
㼃
㻻
䠊
㻭 㻰 䠖
㻵 㻺 㼀 㻿 㼀 㻳 㻌 㻼 䠊
messages is preferentially displayed in the Monitor
㻰 㻾 㼅 㻱 㻾 㻌㻌㻌㻌 㼃 䠋 㻻 㻌 㻿 㻱 㻼 䠊
㻱 㻸 㻱 㻹 㻱 㻺 㼀 Display 3.
㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㻌 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊
By pressing the MONITOR button here, the display
can be switched but is back to the Monitor Display 3
after approximately 10 seconds.
17
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
Monitor Display 1
VSDA * SAVE
㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻜 㻞 㻖 (1)
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 (2)
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻜 㻜 㻹 䠬 䠽 (3)
Indicates ECOMODE is activated for
㻾 㼁 㻺 㻌㻴 㻻 㼁 㻾 䠖 㻝 㻞 㻞 䡄 㻖 fixed speed type.
㻸 㻻 㻭 㻰 㻌 㻴 㻻 㼁 㻾 䠖 㻡 㻠 䡄 (4) ( page 34)
㻸 㻻 㻭 㻰 㼀 㻵 㻹 㻱 㻿 䠖 㻝 㻞 㻟
㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻝 㻝 䠂
㻸 㻻 㻭 㻰 㼀 㻵 㻹 㻱 䠖 㻞 㻠 䡏 (5)
㼁 㻺 㻸 㻻 㻭 㻰 㻌 㼀 㻵 㻹 㻱 䠖 㻝 䡏
㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻥 㻞 䠝 (6)
㻲 㻾 㻱 㻽 㼁 㻱 㻺 㻯 㼅 䠖 㻟 㻜 㻚 㻡 䠤 䡖 (7)
㻻 㼁 㼀 㻼 㼁 㼀 䠖 㻖 㻖 㻚 㻖 䡇 䠳 (8) Displayed when stop is limited for AUTO
㻹 㻭 㻿 㼀 㻱 㻾 (9) operation (Standard: no symbol)
Monitor Display 2
INTE : Indicates fixed speed type used the standard, 2-step
㻞 㻜 㻝 㻝 䠋 㻝 㻝 䠋 㻜 㻝 㻝 㻥 䠖 㻜 㻞 䠆 control system.
㻼 㻾 㻱 㻿 㻿 㼁 㻾 㻱
㻵 㻺 㼀 㻿 㼀 㻳 䠊 㻼 䠖 㻖 䠊 㻖 㻖 㻹 䠬 䠽 AUTO : Indicates fixed speed type used the automatic motor
㻻 㻵 㻸 㻌 㻼 㻾 㻱 㻿 䠖 㻜 䠊 㻝 㻡 㻹 䠬 䠽 stop/restart capacity control system.
㻯 㻸 㼀 䠊 㻼 㻾 㻱 㻿 䠖 㻜 䠊 㻞 㻝 㻹 䠬 䠽
㼀 㻱 㻹 㻼 㻱 㻾 㻭 㼀 㼁 㻾 㻱
(*OPTION)
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻝 䠖 㻟 㻠 㻜 䉝 (10)
VSDB : Indicates Vtype without the AUTO capacity control.
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻞 䠖 㻖 㻖 㻖 䉝
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 䠖 㻌 㻡 㻡 䉝
VSDA : Indicates Vtype with the AUTO capacity control
㻯 㻸 㼀 䠊 㼀 㻱 㻹 㻼 䠖 㻌 㻠 㻞 䉝
㻞 㻺 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 䠊 䠖 㻖 㻖 㻖 䉝 (standard setting for Vtype).
㻹 㻭 㻵 㻺 㼀 㻱 㻺 㻭 㻺 㻯 㻱
㻴 㻾 䠊 㼀 㻻 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻜 㻜 㻜 㻜 䡄
EXIT : Indicated the external capacity control is used.
(11)
㻺 㻱 㼄 㼀 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻖 㻖 㻖 㻖
MR : Indicates multi unit control system through the
communication is used
IMPORTANT
(1) Indicates current time. An asterisk blinks. (6) Indicates the amperage current of the package
input (CURRENT).
(2) Indicates the control state.
(7) Indicates the operating frequency of the main
(3) Indicates a discharge pressure (DIS.PRESS)
motor (FREQUENCY).
(4) Indicates total running hours (RUN HOUR), total
(8) Indicates “***” for this air compressor.
loaded hours (LOAD HOUR), and total number of
loads (LOAD TIMES). (9) Indicates (MASTER), when the air compressor is
Blinking asterisk means counting the running master in lead-lag operation.
hours.
(10) Indicates each pressure and temperature. “***”
(5) Indicates a percentage of load to unload of the DSP indicates not in use.
air compressor (LOAD RATE).
(11) Indicates the number of hours until the next
For Vtype, the rate is calculated based on only
maintenance ser vice (HR. TO MAINT), and the
frequency. Indicates “***”, if PQ wide mode is
next maintenance type (NEXT MAINT).
selected.
18
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖 㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㼀 㼁 㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㻌 㻌 㻌 㻌 㻌
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽 㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽
䠘 㻿 㻴 㼁 㼀 㻰 㻻 㼃 㻺 䠚 䠘 㻲 㻭 㻵 㻸 㼁 㻾 㻱 䠚
㻯 㻻 㻻 㻸 㻭 㻺 㼀 䠖
㻻 㻵 㻸 䠖
㻞 䠪 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 㻱 㻹 㻼 㻌 㻿 㼅 㻿 㼀 㻱 㻹 㻱 㻾 㻾 䠖
㻴 㻵 㻳 㻴 㻌㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 䠖 㻿 㼅 㻿 㼀 㻱 㻹 㻌 㻾 㻱 㼀 㻾 㼅
㻯 㻻 㻺 㼀 㻭 㻯 㼀 㻻 㻾 㻌㻱 㻾 㻾 䠖 㻼 㻯 㻮 㻌 㻱 㻾 㻾 䠖
㻻 㼂 㻱 㻾 㻸 㻻 㻭 㻰 䠖 㻹 㻭 㻵 㻺 㻼 㻾 㻱 㻿 㻿 䠊 㻿 㻺 㻿 㻾 㻌 㻱 㻾 㻾 䠖
㻸 㻻 㼃 㻌 㼃 䠊 㻵 㻺 㼀 㻿 㼀 㻳 㻌 㻼 䠊 㼀 㻱 㻹 㻼 䠊 㻿 㻺 㻿 㻾 㻱 㻾 㻾 䠖 㻝
㻰 㻾 㼅 㻱 㻾 㻌㻌㻌㻌 㼃 䠋 㻻 㻌 㻿 㻱 㻼 䠊 㻰 䡅 㼟 㼏 㼛 㼚 㼚 㼑 㼏 㼠 㼜 㼛 㼣 㼑 㼞
㻱 㻸 㻱 㻹 㻱 㻺 㼀 㼟 㼚 㼐 㼏 㼛 㼚 㼠 㼍 㼏 㼠
㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㻌 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊 㼐 㼕 㼟 㼠 㼞 䡅 㼎 㼡 㼠 㼛 㼞
(Example) (Example)
When the air compressor stops running with blinking When the air compressor stops running with blinking FAILURE
SHUTDOWN and OVERLOAD, it indicates the thermal relay and TEMP.SNSR ERR, the temperature sensor 1 is
trip by overload. disconnected
② Take the proper corrective action, and press the RESET button.
For further information, see pages 38 and 39.
NOTE) SHUTDOWN of DRYER is available for only built-in dryer types. SHUTDOWN of LOW W., INTSTG P., W/O
SEP. and ELEMEMT is not available.
■ Alarm Messages
① When the alarm occurs for the air compressor occurs for the compressor, the ALARM light and contents / details
displayed on alarm screen on the LCD monitor blink and operation continues. There are 2 types of alarm
screens: ALARM and PROBLEM.
㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖 㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㻌 㻌 㻌 㻌 㻌 㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㻌 㻌 㻌 㻌 㻌
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽 㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽
䠘 㻭 㻸 㻭 㻾 㻹 䠚 䠘 㻼 㻾 㻻 㻮 㻸 㻱 㻹 䠚
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 䠖 䠄 㻌 㻌 㻌 䠅 㻖 㻖 㻖 䉝
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 䠖 㻖 㻖 㻖 䉝 㻯 㻻 㻺 㻺 㻱 㻯 㼀 㻵 㻻 㻺 㻌 㻱 㻾 㻾 䠖 㻌 㻌 㻌
㻸 㻻 㼃 㻌 㻻 䠊 㻼 䠊 䠖 㻖 䠊 㻖 㻖 㻹 㻼 㼍 㻾 㼑 㼏 㼛 㼚 㼚 㼑 㼏 㼠 㻌 㼜 㼛 㼣 㼑 㼞 䠊
㻯 㻸 㼀 䠊 㼀 㻱 㻹 㻼 䠊 䠖 㻖 㻖 㻖 䉝 㻹 㼁 㻸 㼀 䠥 㻙 㼁 㻿 㻱 㼀 㻱 㻾 㻾
㻸 㻻 㼃 㻌 㻯 㻸 㼀 䠊 㻼
㻖 䠊 䠖 㻖 㻖 㻹 㻼 㼍 㻿 㻯 㻴 㻱 㻰 㼁 㻸 㻱 㻌 㻿 㻱 㼀 㻌 㻱 㻾 㻾
㻞 䠪 㻰 㻙 㻿 䠊 㼀 㻱 㻹
㻲 㻵 㻼 㻌 㻺 㻙 㼀 㻯 㻻 㻹 䠊 㻱 㻾 㻾 㻌 㻿 㼀 㻻 㻼 䠖 㻌 㻌 㻌 㻌 㻌
㻸 㻻 㼃 㻌 㼃 䠊 㻸 㻻 㼃 㻌 㻻 㻵 㻸 㻯 㻻 㻹 䠊 㻱 㻾 㻾 㻌 㻭 㻸 㻹 䠖 㻌 㻌 㻌 㻌 㻌
㻰 㻾 㼅 㻱 㻾 㻭 㻵 㻾 㻌㻲 㻵 㻸 㼀 㻱 㻾 㻮 㻭 㼀 㼀 㻱 㻾 㼅 㻌㻻 㼁 㼀
㻸 䠊 㻯 㻻 㼁 㻺 㼀 㻌 㻻 㼂 㻱 㻾 㻌 㼃 䠋 㻻 㻌 㻿 䠊
㻼 㼞 㼑 㼟 䡏 㻾 㻱 㻿 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊 㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㼍 㼒 㼠 㼑 㼞 㻯 㻴 㻷 䠊
(Example) (Example)
When the ALARM and AIR FILTER blink, it indicates air When the PROBLEM and BATTERY OUT blink, it indicates
intake filter clogs. the battery replacement period.
② Take the proper corrective action, and press the RESET button.
For further information, see pages 38 and 39.
NOTE) ALARM of DRYER is available for only built-in dryer types. ALAEM of 2ND-S.TEMP, FIN-T, LOW-W, LOW
OIL and W/O S. are not available.
19
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
20
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
CAUTION
If a message of maintenance notice is displayed, carefully read it and service the air compressor as
instructed by this manual. After servicing the air compressor, press the SET button and hold it down for
more than seven (7) seconds; the MAINT. COMPLETED message appears. After one (1) minute, the
monitor display appears.
Note:
1. MAINTenance can be reset, if the servicing is done earlier than expected and if the remaining operating time to next maintenance is
less than 2,000h in the case of A, 1,000h in the case of B.
2. On the contrary, if the servicing is done after the maintenance notice has appeared, the remaining operating hours to the next
maintenance has been zero until the maintenance is done. After maintenance and resetting the counter, new counting time starts
just after the maintenance notice message has appeared on the display.
21
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
④
㻝 㻹 㻻 㻰 㻱 䠖 㻿 㻺 㻳 㻸 㻝 㻹 㻻 㻰 㻱 䠖 㻿 㻺 㻳 㻸
㻞 䠊 㻰 㼁 㻭 㻸 㻌 㼀 㻵 㻹 㻱 䠖 㻌 㻡 䠊 㻜 㼔 㻞 䠊 㻰 㼁 㻭 㻸 㻌 㼀 㻵 㻹 㻱 䠖 㻌 㻡 䠊 㻜 㼔
㻟 䠊 㻹 㻱 㼀 㻴 㻻 㻰 䠖 㻻 㼂 㻾 㻾 㻸 㻭 㻼 㻟 䠊 㻹 㻱 㼀 㻴 㻻 㻰 䠖 㻻 㼂 㻾 㻾 㻸 㻭 㻼
㻠 䠊 㻿 㼃 㻵 㼀 㻯 㻴 㻻 㼂 㻱 㻾 䠖 㻜 㻝 㻡 㼟 ⑤ 㻠 䠊 㻿 㼃 㻵 㼀 㻯 㻴 㻻 㼂 㻱 㻾 䠖 㻜 㻝 㻡 㼟
22
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
23
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
3 Capacity control
This function sets the pressures and times for capacity 8. TIME: ⑥ Can set the time to use pressure setting 2.
control. Two different combinations (P1 and P2) of When set the value properly, ② is indicated in “ S-A”. If
pressures can be used. Item number with dot “ . ” can the start and stop time is set at same value, pressure
be select from LCD monitor. Item number with a dash “ setting 2 is not in use and ② is indicated in S-1. And
- “ can be selected from digital monitor. See 3.4 How pressure setting 1 and 2 can be change by external
to Use the Digital Monitor for the detail. switch. Set the F018 on digital monitor “2”. Refer to
page 29 and 34 for more detail.
① ② ③
㼇 㻯 㻻 㻺 㼀 㻾 㻻 㻸 㻿 㻱 㼀 㼀 㻵 㻺 㻳 㼉 IMPORTANT
㻝 䠊 㼀 㼅 㻼 㻱 䠖 㼂 㻭 㻿 㻙 㻝 㻺 㼁 㻸
㻞 䠊 䠬 㻸 㻻 㻿 㻿 䠖 㻖 䠊 㻖 㻖 㻹 䠬 䠽 The settings can be memorized while the air compressor
㻟 䠊 䠬 㻵 㻯 㻭 䠖 㻖 㻖 㻖 㻖 㻖 䠊 㻖 䡉 㻟 is stopped.
䠄 㻯 㻻 㻺 㼀 㻾 㻻 㻸 䠋 㻯 㼁 㼀 㻙 㻵 㻺 㻕
㻠 㻼 㻝 䠖 㻜 䠊 㻣 㻜 䠋 㻜 䠊 㻢 㻜 㻹 䠬 䠽
㻡 㻼 㻞 䠖 㻜 䠊 㻣 㻜 䠋 㻜 䠊 㻢 㻜 㻹 䠬 䠽
䠄 㼀 㻭 㻾 㻳 㻱 㼀 㻌 㻼 㻝 䠋 㻼 㻞 㻕 ④
㻢 㼀 㻭 㻾 㻳 㻱 㼀 䠖 4 Scheduled Operation
㻜 䠊 㻢 㻤 䠋 㻜 䠊 㻢 㻤 㻹 䠬 䠽
㻣 㼀
㻵 㻹 㻱 㻌 㻸 㻵 㻹 㻵 㼀 䠖 㻜 㻟 㻜 㼟 ⑤ Allows a standard daily scheduling operation.
䠄 㻼 㻞 㻱 㻲 㻲 㻱 㻯 㼀 㻵 㼂 㻱 㻕
㻤 䠊 㼀 㻵 㻹 㻱 䠖 㻝 㻤 䠖 㻜 㻜 㻞 㻞 䠖 㻜 㻜 ⑥
㻿 㻱 㼀 䠖 㻿 㼀 㻻 㻾 㻱 㻌 㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷 㼇 㻿 㻯 㻴 㻱 㻰 㼁 㻸 㻱 㻌 㻿 㻱 㼀 㼀 㻵 㻺 㻳 㼉
㻝 㻥 䠖 㻜 㻣
1. Type: Indicates the setting data for capacity control 㻝 䠊 㻹 㻻 㻰 㻱 䠖 㻿 㻯 㻴 㻱 㻰 㼁 㻸 㻱
① Type of capacity control (Cannot be changed from LCD 㻿 㼀 㻭 㻾 㼀 㻿 㼀 㻻 㻼
䠄 㻝 䠅 㻜 㻣 䠖 㻜 㻜 㻌 㼅 㻞 㻜 䠖 㻜 㻜 㻌 㼅
monitor) 䠄 㻞 䠅 㻜 㻜 䠖 㻜 㻜 㻌 㻺 㻜 㻜 䠖 㻜 㻜 㻌 㻺
Fixed speed type 䠄 㻟 䠅 㻜 㻜 䠖 㻜 㻜 㻌 㻺 㻜 㻜 䠖 㻜 㻜 㻌 㻺
䠄 㻠 䠅 㻜 㻜 䠖 㻜 㻜 㻌 㻺 㻜 㻜 䠖 㻜 㻜 㻌 㻺
I: Indicates the standard, 2-step control. 䠄 㻡 䠅 㻜 㻜 䠖 㻜 㻜 㻌 㻺 㻜 㻜 䠖 㻜 㻜 㻌 㻺
IP: Indicates the optional motor stop/restar t
㻞 䠊 㻾 㻱 㻯 㻻 㻾 㻰 㻝 䠖 㻝 㻜 䠖 㻜 㻜
capacity control to “I”. 㻟 䠊 㻾 㻱 㻯 㻻 㻾 㻰 㻞 䠖 㻝 㻥 䠖 㻜 㻜
Vtype
㻿 㻱 㼀 䠖 㻿 㼀 㻻 㻾 㻱 㻌 㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
VA: Indicates motor stop/restart capacity control is
This illustration indicates a scheduling operation from 7:00 to
effective. 20:00. TIME field indicates a current time of 19:07.
VB: Indicates motor stop/restart capacity control is
canceled. 1. MODE:
② Pressure setting (Cannot be changed from LCD
OFF Operates without a schedule.
monitor)
S-1: Indicates pressure setting 1 Schedule Operates according to a daily 24- hour calendar.
24
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
㼇 㻻 㻼 㻱 㻾 㻭 㼀 㻵 㻻 㻺 㻰 㻭 㼀 㻭 㼉 㼇 㻭 㻸 㻭 㻾 㻹 㻴 㻵 㻿 㼀 㻻 㻾 㼅 㼉
㻝 䠊 㻝 㻝 䠋 㻜 㻝 㻝 㻜 䠖 㻜 㻜 㻝 䠊 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍 㼍
㻯 㻻 㻰 㻱 䠖 㻞 㻝 㻸 㻺 㻻 㻿 䠊 䠖 㻌 㻝 ①
㻼 䠖 㻜 㻠 㻢 䚸 㻖 㻖 㻖 䚸 㻜 㻝 㻢 䚸 㻜 㻞 㻝
㻜 㻣 䠋 㻜 㻤 䠋 㻜 㻝 㻝 㻥 䠖 㻞 㻢
㻯 䠖 㻞 㻜 㻜
㻞 䠊 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖
㼀 䠖 㻟 㻠 㻜 䚸 㻝 㻤 㻜 䚸 㻡 㻜 䚸 㻠 㻞 䚸 㻖 㻖
㻯 㻻 㻰 㻱 䠖 㻖 㻖 㻖 㻺 㻻 㻿 䠊 䠖 㻖 㻖
㻸 䠖 㻡 㻥 䚸 㻖 㻖 㻖 㻌
㻖 㻖 䠋 㻖 㻖 䠋 㻖 㻖 㻖 㻖 䠖 㻖 㻖
㻞 䠊 㼍 㼍 䠋 㼎 㼎 㼏 㼏 䠖 㼐 㼐 㻟 䠊 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖 㻖
㻼 䠖 㻖 㻖 㻖 䚸 㻖 㻖 㻖 䚸 㻖 㻖 㻖 䚸 㻖 㻖 㻖 㻯 㻻 㻰 㻱 䠖 㻖 㻖 㻖 㻺 㻻 㻿 䠊 䠖 㻖 㻖
㻯 䠖 㻖 㻖 㻖 㻖 㻖 䠋 㻖 㻖 䠋 㻖 㻖 㻖 㻖 䠖 㻖 㻖
㼀 䠖 㻖 㻖 㻖 䚸 㻖 㻖 㻖 䚸 㻖 㻖 䚸 㻖 㻖 䚸 㻖 㻖
㻸 䠖 㻌 㻣 㻡 䚸 㻖 㻖 㻖 㻖 㻖
㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
Data can be recorded for a maximum of twelve (12) This display shows a maximum of 6 alarms and
times. The 13th recorded data is automatically deleted displays the following information as such: type of
and the 1st recorded data is added. The most recent alarm, the number of times, and the date and time. If
data is arranged at the top of the display. If a change to the same alarm occurs in a short period of time, the
these settings is desired, the sampled data before the older data is deleted and the more recent data is stored,
settings change will be left as is and the new recorded and alarm NOS. is updated. The most recent data is
data will applied after the change. arranged at the top of the display. Press the △ or
Press the △ or ▽ button to move within the display. ▽ button to move within the display.
1. and 2. : Indicates the MONTH / DAY HOUR: MINUTE.
① Indicates operating condition.
P - Represents a pressure (MPa) and indicates from
L: When loading, U: When unloading, S: When Stopped
left to right: Discharge air pressure, ***, Oil
pressure, Coolant pressure
C - Represents an amperage current (A) 8 Shutdown History
T - Represents a temperature (℃) and indicates from left
to right: 1st stage discharge air temperature, ***, 㼇 㻲 㼁 㻺 㻯 㼀 㻵 㻻 㻺 㻹 㻱 㻺 㼁 㼉
㻝 䠊 㻜 㻤 䠋 㻜 㻝 㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷
㻭 㼂 㻳 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻡 㻞 㻹 䠬 䠽
㻭 㼂 㻳 䠊 㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻜 㻠 㻜 䠝
㻭 㼂 㻳 䠊 㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻜 㻢 㻡 䠂 This display shows a maximum of 6 shutdowns and
㻭 㼂 㻳 䠊 㻼 䠫 䠳 䠡 䠮 䠖 㻖 㻖 㻖 㻚 㻖 㼗 㼃 displays the following information as such: type of
㻞 䠊 㻜 㻝 䠋 㻜 㻝
㻭 㼂 㻳 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻡 㻞 㻹 䠬 䠽 shutdown, the number of times the air compressor has
㻭 㼂 㻳 䠊 㻯 㼁 㻾 㻾 㻱 㻺 㼀 䠖 㻜 㻠 㻜 䠝
㻭 㼂 㻳 䠊 㻸 㻻 㻭 㻰 㻾 㻭 㼀 㻱 䠖 㻜 㻢 㻡 䠂
shutdown, and the date and time of the shutdown. The
㻭 㼂 㻳 䠊 㻼 䠫 䠳 䠡 䠮 䠖 㻖 㻖 㻖 㻚 㻖 㼗 㼃 shutdown history display also shows the operation data
㻹 㻻 㻺 䠖 㻮 㻭 㻯 㻷 (pressure, temperature, current) sampled at the time of
shutdown.
This display shows the averaged load data per day. Data
To view the operation data sampled when the shutdown
can be recorded for a maximum of 6 days; the 7th day
occurred; in the shutdown history display, move to the
of averaged load data is automatically deleted and the
item number of the targeted shutdown to view. Press
1st or most recent averaged data is added. The most
the SET button to open the [DETAILS] display.
recent data is arranged at the top of the display. Press
● How to clear the all alarm and shutdown histories.
the △ or ▽ button to move within the display.
Set the F041 on digital monitor “1”. See page 29 and
Data is averaged from start to stop every day. If 24h
34 for more detail.
operation is done, data is averaged at AM0:00.
25
3. OPERATION PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
26
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
(1) How to Display the Operation Status When the power is turned on, discharge pressure is displayed
on the screen of the digital monitor. Use the following
P: Discharge pressure (MPa)
procedure to switch the digital monitor to other display.
SELECT/WIDE 1 Press ① Press the SELECT/WIDE button. Operation time is
Blinks when operation time is added. displayed on the screen.
Total running hour (×10)
② Press the SELECT/WIDE button. Interstage pressure is
displayed on the screen with “b.”
SELECT/WIDE 1 b: Not in use (display only)
Press once to go to ③ Press the SELECT/WIDE button. 1st-stage air end outlet
the next item.
2 C: Air end outlet temp (℃) temperature is displayed on the screen with “C.”
(360℃)
Press once to go to ④ Press the SELECT/WIDE button. Load rate is displayed on
the previous item.
L: Vtype: Not in use the screen with “L.”
RESET Fixed speed type: Load ratio (%)
Return to discharge ⑤ Press the SELECT/WIDE button. Load count is displayed
pressure display on the screen in units of 10,000 times with “U.”
U: Load count (×10,000 times)
⑥ Press the SELECT/WIDE button. Main motor operation
H: Vtype: Main motor operating frequency(Hz) frequency is displayed on the monitor with “H.”
Fixed speed type: Not in use(display only)
⑦ Press the SELECT/WIDE button. Operation frequency of
the fan motor is displayed on the screen with “d.”
d: Not in use (display only)
27
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
IMPORTANT
(3) How to Display Various Settings (Perform operation only when confirmation is
necessary.)
Use the following procedure to display capacity control type
Dis. pres. display and pressure setting values for confirmation.
SELECT/WIDE
No.0 : Control status
1
A : Capacity Ctrl system ① Press the SELECT/WIDE button 16 times. “0.A **” is
Press 16 times.
displayed on the screen. The content of “**” varies
No.1 : Cut-out pressure 1
070 : 0.7 MPa depending on specifications. “A” may be “L” or “U”
SELECT/WIDE 1
No.2 : Cut-in pressure 1
depending on capacity control specifications.
Press once to go to 060 : 0.6 MPa
the next item. ② Consists of items 0 - 9. Pressure setting status and
2
No.3 : Pres. diff. 1 optional pressure setting 2 can be confirmed each time the
005 : 0.05 MPa
Press once to go to SELECT/WIDE button is pressed.
the previous item. No.4 : ECOMODE
Cycle time ③ Press the RESET button. The screen is return to the
RESET 30 second
usual discharge pressure display.
Return to discharge No.5 : Cut-out pressure 2
pressure display. 070 : 0.7 MPa
28
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
■ Various settings (instantaneous power interruption (IPI), remote operation, dryer setting,
capacity control setting, pressure setting, etc.)
Switches the display from monitor mode to setting mode (F mode).
RESET
Displays 000th item of F mode.
SELECT/WIDE 1
Hold down the RESET FUNC Switches each time FUNC is pressed.
button and press the
SELECT/WIDE button
for 3 seconds or Displays setting value.
more to change to
the F mode. Perform F000: (0: Sets Stand alone operation.)
same operation to
return.
See the F mode table for more detail.
1 Forward Use 1 2 buttons to change the value.
2 Back ( page 29, 30)
Back
Setting can be changed and memorized from the digital monitor without opening the control panel.
■ F Mode table
7 segment Precision/
Function Item Range Default Remarks
display unit
0: Stand alone operation,
Multiple unit control
F000 Control setting 0-1 1 0 1: Multiple unit control
setting
(communication supported)
Instantaneous power
F002 0-1 1 0 0: Valid, 1: Invalid
interruption (IPI) setting
Instantaneous power When the IPI function is available,
interruption (IPI) Instantaneous power instantaneous power interruption is
restart setting F003 interruption (IPI) 1-5 1 sec 1 detected between 20 ms and the
detection period setting setting detection period set here, and
air compressor restarts. (see page 25).
0: REMOTE button,
Remote control switch
F005 0-3 1 0 1: Local, 2: Remote,
method
3: Selectable by external contact
Remote operation
Remote operation
setting F006 0-1 1 0 0: Pulse input, 1: Level input
method
Remote shutdown
F007 0-1 1 0 0: Invalid, 1: Valid
recovery
0: Operation, 1: Stop, 2: Link,
F008 Dryer operation type 0-3 1 2
3: Panel
Dryer operation
F009 Dryer prestart 0-1 1 0 0: Invalid, 1: Valid
setting
AUTO setting (*2) F011 AUTO operation enabled 0-1 1 0 0: Valid, 1: Invalid
29
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
7 segment Precision/
Function Item Range Default Remarks
display unit
0.70
F022 Control pressor 1 0.4 [0.5] - 0.70 0.01 MPa
(0.30)
Pressure 0.72
combination 1 F023 Cut-out pressure 1 0.42 [0.52] - 0.72 0.01 MPa
(0.32)
Rated pressure: 0.70 (0.3) MPa
※
0.67
F024 Cut-in pressure 1 0.38 [0.48] - 0.68 0.01 MPa
(*3) (0.27)
0.67
F025 (*2) Restart pressure 1 0.38 [0.48] - 0.68 0.01 MPa ※ Setting can be altered at any time.
(0.27)
Vtype (In the 0.3 MPa type, do not
0.70 change the setting)
F031 Control pressor 2 0.4 [0.5] - 0.70 0.01 MPa
(0.30)
Pressure 0.72
combination 2 F032 Cut-out pressure 2 0.42 [0.52] - 0.72 0.01 MPa
(0.32)
※
0.67
F033 Cut-in pressure 2 0.38 [0.48] - 0.68 0.01 MPa
(*3) (0.27)
0.67
F034 (*2) Restart pressure 2 0.38 [0.48] - 0.68 0.01 MPa
(0.27)
0.70
F023 Cut-out pressure 1 0.4 [0.5] - 0.70 0.01 MPa
(0.40)
Rated pressure: 0.70 (0.4) MPa
Pressure
combination 1 0.60
F024 Cut-in pressure 1 0.3 [0.4] - 0.60 0.01 MPa
※ (0.30)
(*3) 0.60
Fixed F025 (*2) Restart pressure 1 0.3 [0.4] - 0.60 0.01 MPa ※ Setting can be altered at any time.
(0.30)
speed (In the 0.4 MPa type, do not
type 0.70 change the setting)
F032 Cut-out pressure 2 0.4 [0.5] - 0.70 0.01 MPa
Pressure (0.40)
combination 2 0.60
F033 Cut-in pressure 2 0.3 [0.4] - 0.60 0.01 MPa
※ (0.30)
(*3) 0.60
F034 (*2) Restart pressure 2 0.3 [0.4] - 0.60 0.01 MPa
(0.30)
Clear shutdown history F041 (*1) Clear history data 0-1 1 0 0: Confirmed, 1: Clear history data
Note:
※ Setting of the items without ※ in remarks can be memorized while the air compressor is stopped.
*1: When set to “1”, history is cleared. After clearing, the value is automatically reset to “0”.
*2: Only the V type is equipped with AUTO function. The AUTO function is available as an option for the Fixed speed type.
*3: Refer to the below table about the Capacity control pressure setting conditions.
Do not change the setting of F items that are not specified in the table above.
The value in the [ ] is for built-in dryer type.
Fixed-speed ① F023 shall be set F024 + 0.02 or higher, and F025 + 0.02 or higher.
IMPORTANT
1. Pressure setting when minimum air receiver tank is installed ( page 49)
Vtype : Pressure differential between cut-out and cut-in shall be 0.05MPa or more, and pressure differential between cut-out
and target shall be 0.02MPa or more.
Fixed speed type : Pressure differential between cut-out and cut-in shall be 0.1MPa or more.
2. External selection of Cut-in/Cut-out pressure combination 1 or 2 is an option. (F018-2)
30
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
3.4.3 Change of Pressure Setting Use the following procedure to change the pressure
setting of the capacity control system.
3.4.4 Change of Capacity Control Type AUTO (automatic motor stop/restart function) can be
selected properly.
3.4.5 Restart for Instantaneous Power In item F018, pressure setting 1 and 2 can be switched.
Interruption ① This function is available for IPI between 20 ms and
the set value (F003: 1 to 5 sec).
② When IPI occurs , the air compressor stops and the
運転状況
RUNNING MODE START light turns off.
遠 方
③ After power recovers within F003 set condition, the
電 源
AUTO light blinks and the START light turns ON
REMOTE
POWER
負 荷
LOAD
起動待ち
(growing) to inform that the air compressor is
故 障 ③
SHUTDOWN
AUTO START
waiting for restarting from IPI.
ドライヤ 運 転 停 止
DRYER START STOP ④ The air compressor restarts 15 seconds after power
2
recovers.
IMPORTANT
(1) IPI means that the power voltage drops to zero (0)
instantaneously.
UNLOAD STOP (2) For the IPI time of less than 20 ms, the air compressor
continues to run.
②③ (3) For the IPI time of more than the setting, the air
compressor judges it as a power failure; the air
IPI is standard function. IPI can be canceled by F002. compressor stops but does not restart automatically.
refer to the page 29. Press the START button to restart the air compressor.
31
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
1
Alter
values.
(3) To change the Local or remote operation by
2
external contact.
(Contact the local HITACHI distributor/master
dealer or representative office.)
IMPORTANT
32
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
起動待ち
during dryer START light turning on (blinking). After three (3)
故 障 AUTO START
prestart operation.
minutes, the air compressor star t with AUTO
SHUTDOWN
ドライヤ
START light turning off.
運 転 停 止
DRYER START STOP
Dryer
operation
2
light
IMPORTANT
When the dryer is operated from the
When the air compressor restart for IPI, the air compressor
instrument panel, press the DRYER
button for more than 4 seconds and starts with the built –in dryer.
confirm the dryer operation light turns on
(growing).
33
3. OPERATION PROCEDURE [How to Use the Digital Monitor]
Line pressure
can be set for a certain time ( See 3.3.5 and 3.4.2
Cut-in
for the detail) press.1
Load Unload
Cut-in
Load light turns on (growing) during load and turns off press. 2
during unload when pressure combination 1 is Grow OFF Grow OFF Grow OFF Blink OFF
Load light
selected. Load light turns on (blinking) during load and Blink Blink
turns off during unload when pressure combination 2 is External contact (option) OFF ON
表示切替/
longer than the set interval. If the cycling interval 遠 方
REMOTE
ワイドモード
SELECT/WIDE
記 憶
SELECT/WIDE
time is longer than set interval, the system reduces STR 1
Press the button for 7 seconds
the cut-out pressure to a target so as to make the or more to set.
cycling interval closer to the set value. Minimum
cut-out pressure is cut-in pressure + 0.05MPa.
Minimum cycle time is 30 seconds.
Cut-out is
If the cycle time is 30 seconds or more, SELECT/ Energy Saving Effect automatically
WIDE light tur ns on (blinking) to indicate reduced.
Cut-out
ECOMODE is effective. By setting the ECOMODE pressure
Line pressure
34
3. OPERATION PROCEDURE [Daily Operation of Air Compressor]
CAUTION
● When using the air compressor, do not raise the discharge pressure excessively. Operating the air
compressor over the rated pressure can result in main motor overload, shutdown of the airend and/or
damage of parts.
● If the air relief valve has blown or a protective device has shutdown the air compressor, investigate
the cause of and take corrective action. If there are any questions or comments in taking these
actions, contact the local HITACHI distributor/master dealer or representative office.
負 荷
LOAD
機 能
FUNC
リセット
RESET
故 障
SHUTDOWN
起動待ち
AUTO START
⑤ Close the petcock and water relief valve.
表示切替/
Water-Cooled
遠 方 ワイドモード 運 転 停 止
REMOTE SELECT/WIDE START STOP
記 憶
STR 1 2
⑥ Open the cooling water valve.
③ Verify that the oil stays between the upper and lower red
lines of the oil level gauge while air compressor is
running. Since the oil comes back to the oil case after the
air compressor stops, the oil level during air compressor
running is lower than during air compressor stopping.
3.5.2 Starting the air compressor ① Open the discharge stop valve.
② Press the START button.
運転管理 運転状況
RUNNING CONTROL RUNNING MODE
- If the oil pressure does not rise over 0.09 MPa, the air
③④ 警 報
ALARM
遠 方
REMOTE
負 荷
電 源
POWER
compressor is shutdown.
LOAD
- If the coolant pressure does not rise over 0.11 MPa, the
DIS. PRESS: 0.70MPa 遠 方
表示切替/
ワイドモード 運 転 停 止
Air-Cooled
DSP is shut down.
REMOTE SELECT/WIDE START STOP
記 憶
OIL PRESS: 0.15MPa - The compressor switches to full load operation within 15
CLT. PRESS: 0.15MPa
seconds for the Fixed speed type and within 10 seconds for
UNLOAD STOP
the V type.
②
See page 33 for the detail of dryer operation.
③ Check the LCD monitor, and verify that:
① - the oil pressure is 0.09 MPa or more.
メニュー
ALARM
REMOTE
負 荷
POWER PRES), coolant pressure (CLT PRES), discharge air
[× 10h] LOAD
MENU
機 能 リセット 起動待ち
+/-
UP/
DOWN
FUNC RESET
表示切替/
故 障
SHUTDOWN
AUTO START
temperature (DIS. TEMP 1), oil temperature (OIL TEMP)
遠 方 ワイドモード ドライヤ 運 転 停 止
REMOTE SELECT/WIDE DRYER START STOP
設 定
SET
記 憶
STR 1 2
and coolant temperature (CLT TEMP) stays within the
MONITOR
normal range. ( page 55)
UNLOAD STOP
② Verify that the intercooler/aftercooler condensate
㻞 㻜 㻝 㻝 䠋 㻝 㻝 䠋 㻜 㻝 㻝 㻥 䠖 㻜 㻞 drain is discharged intermittently when the air
㻼 㻾 㻱 㻿 㻿 㼁 㻾 㻱
㻵 㻺 㼀 㻿 㼀 㻳 䠊 㻼 䠖 㻖 䠊 㻖 㻖 㻹 䠬 䠽
compressor is loading.
㻻 㻵 㻸 㻌 㻼 㻾 㻱 㻿 䠖 㻜 䠊 㻝 㻡 㻹 䠬 䠽 Automatic drain Automatic drain
㻯 㻸 㼀 䠊 㻼 㻾 㻱 㻿 䠖 㻜 䠊 㻞 㻝 㻹 䠬 䠽 Model
㼀 㻱 㻹 㻼 㻱 㻾 㻭 㼀 㼁 㻾 㻱
valve: Open valve: Closed
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻝 䠖 㻟 㻠 㻜 䉝 37/55 kW 2 sec 45 sec
㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 㻞 䠖 㻖 㻖 㻖 䉝
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 䠖 㻡 㻡 䉝
㻯 㻸 㼀 䠊 㼀 㻱 㻹 㻼 䠖 㻌 㻠 㻞 䉝 ③ When the air compressor r unning, verify the
㻞 㻺 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 䠊 䠖 㻖 㻖 㻖 䉝
㻹 㻭 㻵 㻺 㼀 㻱 㻺 㻭 㻺 㻯 㻱 condensate is discharged from drain trap for dryer.
㻴 㻾 䠊 㼀 㻻 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻜 㻜 㻜 㻜 䡄
㻺 㻱 㼄 㼀 㻌 㻹 㻭 㻵 㻺 㼀 䠖 㻖 㻖 㻖 㻖 (Discharging cycle depends on the ambient and air
compressor operating condition.) ( page 13)
負 荷
LOAD
② 機 能
FUNC
リセット
RESET
故 障
SHUTDOWN
起動待ち
AUTO START
36
3. OPERATION PROCEDURE [Daily Operation of Oil Mist Remover, Adjustment Procedure]
3.6 Daily Operation of Oil Mist Remover ② The first steps to resolve the lower suction vacuum
pressure are as following.If the unloaded discharge
3.6.1 When Setting air temperature rises and high discharge air
temperature alarm occurs,
A) Clean or replace the air intake filter.
B) Clean the suction throttle valve’s plate.
③ If the compressor cannot be shutdown to clean these
Pressure gauge (MPa) parts, turn the adjusting bolt (the suction throttle
0.25 to 0.28
bypass valve ) ounterclockwise to open and regulate
Make sure that the pressure gauge
reads as above. the discharge air temperature.
④ Replace the consumable parts in the air intake filter
and suction throttle valve with new consumable
par ts in accor dance with the appr opriate
maintenance schedule. For the detail refer to
Make sure that the
condensate is not
the section 9, Maintenance the air compressor.
collected in the
filter bowl.
If the condensate is
collected, push up
3.7.2 Regulating the Oil Pressure
the cock to drain
the condensate. The illustration below is an example of water cooler.
Make sure that the vacuum
indicator does not show a
red mark.
Condensate Drain Cock
37
4. TROUBLESHOOTING
CAUTION
If a shutdown, alarm, problem or failure occurs, investigate the cause and take proper corrective action
before restarting. If there is any questions or comments, contact the local HITACHI distributor/master
dealer or representative office.
■ During Operation
LCD Indication Failure How to History Error
What and How to Detect Detector Shutdown What Actions to Take
Heading Trouble Description Light Reset code code
● For working pressure of 0.70
Discharge air temperature MPa: About 398 ℃ or higher SHUTDOWN Press RESET
Thermistor Yes See page 44. 18 E0.18
[Fixed speed type] ● For working pressure of 0.40 Blinks button.
MPa: About 340 ℃ or higher
● For working pressure of 0.70
Discharge air temperature MPa: About 398 ℃ or higher SHUTDOWN Press RESET
● For working pressure of 0.30
Thermistor Yes See page 44. 18 E0.18
[Vtype] Blinks button.
MPa: About 340 ℃ or higher
SHUTDOWN Press RESET
Coolant temperature 70℃ or higher Thermistor Yes See page 44. 5A E0.5A
Blinks button.
SHUTDOWN Pressure Press RESET
Coolant pressure 0.10 MPa or lower Yes See page 44. 5D E0.5D
Blinks sensor button.
Oil temperature SHUTDOWN Press RESET
70℃ or higher Thermistor Yes See page 44. 58 E0.58
(OIL HIGH TEMP) Blinks button.
Oil pressure
SHUTDOWN Pressure Press RESET
(OIL LOW PRESS) 0.08 MPa or lower Yes See page 44. 5C E0.5C
Blinks sensor button.
[Fixed speed type]
0.08MPa or lower
Oil pressure
(operating Freq. 45Hz or higher) SHUTDOWN Pressure Press RESET
SHUTDOWN (OIL LOW PRESS) Yes See page 44. 5C E0.5C
0.04MPa or lower Blinks sensor button.
[Vtype]
(operating Freq. Less than 45Hz)
Overloading (Main motor) Detected during SHUTDOWN Thermal Press RESET
Yes See page 44. 17 E0.17
(OVERLOAD: MAIN) operation Blinks relay button.
Overloading (Fan motor) Detected during SHUTDOWN Thermal Press RESET
Yes See page 44. 53 E0.53
(OVERLOAD: SUB) operation Blinks relay button.
Answer error of 52
Detected during operation SHUTDOWN Disconnect the power. Check the 52 for Press RESET
(CONTACTOR ERR: 52) CPU Yes 51 E0.51
or Emergency stop in Y. Blinks proper operation and the wires for tightness . button.
[Fixed speed type]
Answer error of 42
Detected during operation SHUTDOWN Disconnect the power. Check the 6 and 42 for Press RESET
(CONTACTOR ERR: 52) CPU Yes 16 E0.16
or emergency stop in Δ Blinks proper operation and the wires for tightness. button.
[Fixed speed type]
When set the
[Built-in dryer type] SHUTDOWN Press RESET
SHUTDOWN for the dryer CPU Yes See page 42, 43. 19 E0.19
(DRYER) Blinks button.
failure. See page 33
Water flow Cooling water Differential
SHUTDOWN Press RESET
(LOW WATER FLOW) puressure differential pressure Yes See page 44. 44 E0.44
Blinks button.
[Water-cooled type] 0.034 MPa or lower switch
38
4. TROUBLESHOOTING [Protective Device]
■ During Operation
LCD Indication Failure How to History Error
What and How to Detect Detector Shutdown What Actions to Take
Heading Trouble Description Light Reset code code
[Vtype] Inverter trip
Failure signal from SHUTDOWN Press RESET
FAILURE Inverter tripping or main motor CPU Yes See page 44. 44 E0.44
inverter Blinks button.
overloading with automatic retrials.
Clogging of air intake filter Pressure
Pressure differential of ALARM Press RESET
differential No See page 102. 21 E0.21
(AIR FILTER) -4.98 kPa or more Blinks button.
sensor
● For working pressure of 0.70MPa:
Discharge air temperature About 388℃ or higher ALARM Automatically
Thermistor No See page 44. 25 E0.25
[Fixed speed type] ● For working pressure of 0.40MPa: Blinks reset.
About 330℃ or higher
● For working pressure of 0.70MPa:
Discharge air temperature About 388℃ or higher ALARM Automatically
Thermistor No See page 44. 25 E0.25
[Vtype] ● For working pressure of 0.30MPa: Blinks reset.
About 330℃ or higher
ALARM Automatically
Coolant temperature 63℃ or higher Thermistor No See page 44. 2A E0.2A
Blinks reset.
ALARM
ALARM Automatically
Coolant pressure 0.12 MPa or lower Thermistor No See page 44. 2D E0.2D
Blinks reset.
Oil temperature ALARM Automatically
63℃ or higher Thermistor No See page 44. 28 E0.28
(OIL TEMP) Blinks reset.
[Fixed Speed type] ALARM Pressure Automatically
0.10MPa or lower No See page 44. 2C E0.2C
Oil pressure (LOW O.P.) Blinks sensor reset.
each
[Built-in dryer type] When set the ALARM for the ALARM Press RESET
protective Yes See page 42, 43. 2E E0.2E
(DRYER) dryer failure. See page 33. Blinks button.
device
Hold down the
Load/unload cycle time over ALARM Replace consumable parts of suction REMOTE and press the
1,000,000 cycles CPU No 59 E0.59
(L COUNT OVER) Blinks throttle valve and blowoff valve. SELECT/WIDE button
for 7 seconds or more.
■ Other
LCD Indication Failure How to History Error
What and How to Detect Detector Shutdown What Actions to Take
Heading Trouble Description Light Reset code code
Battery out ALARM Disconnect the power and replace the Press RESET
Battery voltage low CPU No 64 E0.64
(BATTERY OUT) Blinks battery with a new one. See page 103. button.
Scheduling operation error Start/stop time not set ALARM Press RESET
CPU No See page 24. 62 E0.62
(SCHEDULE SET ERR) yet Blinks button.
Lead/lag operation error Wiring connection or ALARM Check the wire and the operation Press RESET
PROBLEM CPU No 61 E0.61
(MULTI-U SET ERR) setting error Blinks setting on the instrument panel. button.
RS-485 port error Wiring connection or SHUTDOWN Press RESET E0.65,
CPU Yes (Note 3) 65, 67
(COM.ERR STOP) setting error Blinks button. 67
RS-485 port error Wiring connection or ALARM Press RESET E0.63X,
CPU Yes (Note 3) 63X, 68X
(COM.ERR ALM) setting error Blinks button. 68X
[Vtype] ALARM Press RESET
Inverter error CPU Yes See page 40 13 E0.13
Control device error (SYSTEM ERR) Blinks button.
(ROM1)(RAM1) main 43 E0.43
board memory error Disconnect the power and then
PCB error SHUTDOWN Press RESET 47, 48 47, 48
CPU Retry reconnect the power. If problem is
(PCB ERR) (ROM2)(RAM2) LCD Blinks button. 41 E0.41
persists, change the PCB.
board memory error 42, 46 42, 46
Discharge pressure sensor error SHUTDOWN Press RESET
PS2 disconnected CPU Retry 34 E0.34
(PRESS.SNSR ERR 2) Blinks button.
FAILURE Coolant pressure sensor error
SHUTDOWN Disconnect the power and check the Press RESET
(PRESS.SNSR ERR 3) PS3 disconnected CPU Retry 38 E0.38
Blinks pressure sensor wire for tightness. button.
[Air-cooled type]
Oil pressure sensor error SHUTDOWN Press RESET
PS4 disconnected CPU Yes 39 E0.39
(PRESS.SNSR ERR 4) Blinks button.
Coolant temperature sensor error
SHUTDOWN Press RESET
(TEMP.SNSR ERR 1) TH1 disconnected CPU Yes Disconnect the power and check the 31 E0.31
Blinks button.
[Air-cooled type] thermistor sensor wire for tightness.
Oil temperature sensor error SHUTDOWN (Note 4) Press RESET
TH5 disconnected CPU Yes 37 E0.37
(TEMP.SNSR ERR 5) Blinks button.
Notes
(1) Depends on the specification, reverse phase relay is used.
(2) The air compressor using reverse phase relay, such as for 380-415V/50Hz, 440V/60Hz, indicates a phase-lacking connection as reversal phase.
(3) Communication error details:
Port 1(65) =Main circuit communication (Vtype), Port 3 (67)= LCD communication, Port 4 (68)= Multiple unit control communication,
Port 5 (63)= External communication
(4) If the thermistor is disconnected, override operation is not available. Contact the local HITACHI distributor/master dealer or representative
office.
(5) The phase-lucking connection indication is only for T phase. In case of R and S phase, LCD monitor is disappeared or LCD monitor indication
becomes unstable.
39
4. TROUBLESHOOTING [Protective Device]
■ How to Identify the Failure Cause of E0.13 (Inverter Error) and Check the History
SELECT/WIDE
IMPORTANT
1
Press once to go to
the next item.
RESET 1. If the shutdown code “XX” is “ ,” it indicates that
Not used there is no shutdown history. Also, when anything
Return to discharge (display only)
pressure display.
other than shutdown history is displayed without
b shutdown resetting, the display is return to the latest
2 shutdown history in 3 minutes.
Press once to go to 2. For the shutdown history of Inverter, only the most
the previous item. To display of various settings recent shutdown is recorded. Shutdown history is
displayed in shutdown codes.
( See the shutdown code list in this page.)
40
4. TROUBLESHOOTING [Protective Device]
41
4. TROUBLESHOOTING [Protective Device]
WARNING
The dryer uses non-flammable, non-toxic, and odorless refrigerant (chlorofluorocarbon R-410A). However,
if chlorofluorocarbon leaks from the product and contacts fire, toxic gas is generated and causes irritation
to the eye and the throat. In addition, chlorofluorocarbon, being heavier than air, may accumulate over the
floor, which may lead to oxygen deficiency. Therefore if chlorofluorocarbon leaks, extinguish fire and
ventilate the room as sweeping the floor. After that, contact the local HITACHI distributor/master dealer or
representative office.
42
4. TROUBLESHOOTING [Protective Device]
1 Dryer Failure
If a shutdown occurs to the dryer, the following display display mode depending on the dryer shutdown setting
is appeared on the LCD monitor. There are 2 types of ( pages 30 and 33).
For the cause and actions to be taken, see page 42.
㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖 㻞 㻜 㻝 㻝 䠋 㻜 㻝 䠋 㻝 㻝 㻝 㻥 䠖 㻝 㻥 㻖
㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㼀 㼁 㼀 㼅 㻼 㻱 䠖 㼂 㻿 㻰 㻭 㻌 㼀 㼁 㻌 㻌 㻌
㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽 㻰 㻵 㻿 䠊 㻼 㻾 㻱 㻿 㻿 䠖 㻜 䠊 㻠 㻢 㻹 䠬 䠽
䠘 㻿 㻴 㼁 㼀 㻰 㻻 㼃 㻺 䠚 䠘 㻲 㻭 㻵 㻸 㼁 㻾 㻱 䠚
㻯 㻻 㻻 㻸 㻭 㻺 㼀 䠖 㻰㻌㻵㻌㻿㻌㻚㻌㼀㻌㻱㻌㻹㻌㻼㻌㻦 㻖 㻖 㻖 䉝
㻻 㻵 㻸 䠖 㻻㻌㻵㻌㻸㻌㻌㼀㻌㻱㻌㻹㻌㻼㻌㻦 㻖 㻖 㻖 䉝
㻞 䠪 㻰 㻌 㻿 㼁 㻯 㼀 䠊 㼀 㻱 㻹 㻼 㻌 㻻㻌㻵㻌㻸㻌㻌㻼㻌㻾㻌㻱㻌㻿㻌㻌㻸㻌㻻㻌㼃㻌㻦 㻖 㻚 㻖 㻖 㻹 㻼 㼍
㻴 㻵 㻳 㻴 㻌㻰 㻵 㻿 䠊 㼀 㻱 㻹 㻼 䠖 㻯㻌㻻㻌㻻㻌㻸㻌㻭㻌㻺㻌㼀㻌㻌㼀㻌㻱㻌㻹㻌㻼㻌㻦 㻖 㻖 㻖 䉝
㻯 㻻 㻺 㼀 㻭 㻯 㼀 㻻 㻾 㻌㻱 㻾 㻾 䠖 㻯㻌㻻㻌㻻㻌㻸㻌㻭㻌㻺㻌㼀㻌㻌㻼㻌㻾㻌㻱㻌㻿㻌㻚㻌㻌㻸㻌㻻㻌㼃㻌㻦 㻖 㻚 㻖 㻖 㻹 㻼 㼍
㻻 㼂 㻱 㻾 㻸 㻻 㻭 㻰 䠖 㻵㻌㻺㻌㼀㻌㻚㻌㻌㻌㻯㻌㻚㻌㻌㻹㻌㻭㻌㻸㻌㻲㻌㼁㻌㻺㻌㻯㻌㼀㻌㻵㻌㻻㻌㻺 㻲 㻵 㻺 㻌 㼀 㻱 㻹 㻼 㻚 㻌 㻴 㻵 㻳 㻴
㻸 㻻 㼃 㻌 㼃 䠊 㻵 㻺 㼀 㻿 㼀 㻳 㻌 㻼 䠊 㼃㻌㻭㻌㼀㻌㻱㻌㻾㻌㻌㻿㻌㼀㻌㻻㻌㻼 㻻㻵㻸㻚㻌㻸㼂㻸㻚㻌㻸㻻㼃
㻰 㻾 㼅 㻱 㻾 㻌㻌㻌㻌 㼃 䠋 㻻 㻌 㻿 㻱 㻼 䠊 㻰㻌㻾㻌㼅㻌㻱㻌㻾 㻭㻵㻾㻌㻵㻺㼀㻭㻷㻱㻌㻲㻵㻸㼀㻱㻾
㻱 㻸 㻱 㻹 㻱 㻺 㼀 㻸㻌㻚㻌㻯㻌㻻㻌㼁㻌㻺㻌㼀㻌㻌㻻㻌㼂㻌㻱㻌㻾 㻻㻵㻸㻛㼃㼀㻾㻌㻿㻱㻼㻭㻾㻭㼀㻚㻌㻲㻚
㻼 㼞 㼑 㼟 㼟 㻾 㻱 㻿 㻌 㼍 㼒 㼠 㼑 㼞 㻌 㻯 㻴 㻷 䠊 㻼㻌㻾㻌㻱㻌㻿㻌㻿㻌㻌㻾㻌㻱㻌㻿㻌㻌㻭㻌㻲㻌㼀㻌㻱㻌㻾㻌㻌㻯㻌㻴㻌㻷㻌䠊
Hexagon
until the pressure is stabilized.
cap nut
Note) Before turning the adjusting screw, mark the cap and
Adjusting
screw adjusting bolt in advance so that the factory setting
position is indicated. After pressure adjustment, be sure
to tighten the hexagon cap nut back to its original state.
Tightening torque: approx. 196N・cm.
43
4. TROUBLESHOOTING [Troubleshooting of Air Compressor]
Shutdown - 1. 1st-stage AIR END air intake 1. Clean or change the air intake filter
Discharge air <S H U T D O W N> efficiency - Lowered 2. Lower the suction air temperature
temperature 2. Air intake filter - Dirty 3. Replace the check valve.
HIGH DIS. TEMP. 1:
3. Temperature of Suction Air-High 4. Check the coolant cooler. Clean it, as
Press RES after CHK. 4. Coolant temperature - High required, with a use of an air nozzle.
Shutdown – 1. Oil strainer and/or oil filter – Dirty 1. Clean the oil strainer
Oil pressure <S H U T D O W N> 2. Oil level – Low 2. Replace the oil filter.
3. Add the oil.
OIL : OIL LOW PRESS
[Air-cooled type] 1. Coolant level – Low 1. Add the coolant into the coolant
Shutdown – <S H U T D O W N> 2. Pressure cap – Loosened reservoir.
Coolant pressure 3. Coolant strainer – Clogging 2. Re-fasten the pressure cap tightly.
COOLANT : LOW PRESS
3. Clean the coolant strainer.
Press RES after CHK.
Shutdown – 1. Power supply voltage – Low 1. Rectify the power supply voltage.
Motors overload <S H U T D O W N> 2. Discharge air pressure – Too high 2. Check the suction throttle valve
[Fixed speed type]
OVERLOAD : MAIN
3. Check the capacity control system.
Press RES after CHK.
44
4. TROUBLESHOOTING [Troubleshooting of Oil Mist Remover]
② The OMR relief valve opens immediately when starting the air compressor (the control air pressure is still
low) or when the DSP has stopped. This is a normal occurrence.
YES
The OMR relief valve is dirty or stuck open by a foreign Disassemble and clean the OMR relief valve.
object. Replace if necessary.
NO
Go to the procedure ①. The vacuum indicator shows a
red mark. (Gear case has a positive internal pressure.)
NOTE:
The OMR relief valve opens immediately when starting the DSP (the control air pressure is still low) or when the DSP has
stopped. This is a normal occurrence.
③ Oil is vented through the ejector’s compressed air outlet (the separated oil is not being recovered).
Accumulated oil is visible in the tube between the YES
Clean the nozzle of the float trap.
element housing and the float trap.
NO
Upper or lower packing is not seated properly on the YES Reinstall the element, seating the packing properly for a
element ? maximum sealing performance.
NO
YES
Control air contains oil ? Check the control air for oil contents.
NO
Element may be dirty.
Inspect the element and replace if necessary.
NO
Foreign matter in float trap nozzle (Check for a large
YES Disassemble and clean the float trap nozzle and the
amount of air sucked from the oil collecting pipe to oil
float trap.
pump suction side.)
NOTE:
The oil mist remover makes the gear case internal pressure negative during operation, reducing the pressure by 0.005 to 0.01
MPa. This is not unusual; reset the oil pressure on the OMR relief valve.
45
5. INSTALLING AND PIPING THE DSP
5.1 Unpacking the Air Compressor
■ After unpacking the crate, verify that the product is in accordance with the order, by referring to section 15.
■ Verify that the product is not damaged or deformed during transportation.
Model Nameplate Standard Accessories
Foundation bracket 2 pcs
M16 × 90 bolt 2 pcs
M16 × 35 bolt 2 pcs
Output (kW) M16 nut 2 pcs
M16 washer 2 pcs
Fork slot cover 4 pcs
Model M6 × 15 bolt 8 pcs
Drain trap * 1 pc
Drain pipe (1/2B) * 1 pc
Frequency Elbow (1/2B) * 1 pc
(Hz) Nipple (1/2B) * 2 pcs
* Provided only with built-in dryer type
Ball valve (1/2B) * 1 pc
Motorized isolation valve ** 1 pc ** Provided only with .
Motorized water isolation valve *** 1 pc *** Provided only with Water-Cooled .
[fixed-speed compressor]
Model Total Mass (kg)
DSP-37A(R)N 1,020 (1,170) Lift the unit balanced.
46
5. INSTALLING AND PIPING THE DSP [Installing the DSP Air Compressor]
WARNING
1. Keep flammable solvents or any other hazardous chemicals away from the air compressor. Such
chemicals may be ingested into the air compressor and could cause an explosion during the
compression process.
2. Do not use fire near the air compressor; otherwise the sparks may enter the airend and burn it internally.
■ Install the air compressor in a bright, wide, and airy room as follows:
■ Install the air compressor in a dry and dust-free room, and avoid the following.
Raindrops, Basements, Steam Metals, Sand, Other Hard Materials Harmful Gases
Toxic gases such as chlorine gas, hydrogen
Causes electric leak, generation of Causes motor insulation failure, bearing Causes deterioration of oil, wear of cooler,
drain/rust, microcomputer malfunction. damage, microcomputer malfunction. detachment of coating from rotor surface.
■ Install the air compressor on a level floor. ■ Do not install the air compressor near a wall.
To ensure an appropriate amount of oil Do not set the air Doing this may cause the operating noise
Prohibited
To prevent noise and vibration compressor on blocks. to resonate and increase the noise levels.
CAUTION
● Install the air compressor indoors. Installing it outdoors may lead to damage of the airend due to
water vapor, dust, etc.
● The air compressor installation room should have an air intake opening, an air exhaust opening and
have good ventilation. If the room is poorly ventilated, hot air exhausted by the air compressor may
cause the room temperature to rise excessively and lead to damage of the air compressor.
47
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
Discharge valve
Stop Motorized isolation Stop valve
valve (Vtype)
Close
Approx. 500 mm or more As shown in the figure above, when one compressor is
must be maintained. operating and the other is stopped with opening the stop
valve, back pressure is applied to the aftercooler and
check valve of the stopped air compressor. This may
cause more condensate going into the air compressor
and more rusting of aftercooler and check valve.
48
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
IMPORTANT
49
5. INSTALLING AND PIPING THE DSP [Piping the DSP Air Compressor]
5.4.6 Piping Procedure Dryer Drain Trap 5.4.8 Cooling Water Piping Water-Cooled
If pipes are not connected as described above, ① The pipings for water inlet and outlet for coolers are
drain may not be properly discharged, causing required.
the drain to enter the discharge air.
② Using a union or flange joint to connect the air
compressor to the water pipings, allows for minimal
5.4.7 Drain Pipe
disassembly of the enclosure panels (customer
supplied).
Pressure gauge
To
drain pit
A
Drain pipe
Filter Regulator
50
5. INSTALLING AND PIPING THE DSP [Ventilation of Air Compressor Room]
CAUTION
Provide a ventilating system to the air compressor room in the event that the room temperature exceeds
the allowable ambient operating temperature of 40℃. Operating the air compressor at an ambient
operating temperature above 40℃ may cause a serious problem.
IMPORTANT
● Stop the ventilating fan when the air compressor has stopped.
● The ventilating fan should be running while the air compressor is operating. If the ventilating fan is not running, the loss of air
flow may reduce the performance of the cooler.
● The duct should be detachable for ease of maintenance on the air compressor.
detachable end directly in contact with the grilled air Fig. C Air intake Ventilating fan
opening Fresh See
exhaust (without dryer part) on top of the air air “Recommended
compressor. Do not install the duct for dryer exhaust. fan capacity ②” in
For the dryer ventilation, install a ventilating fan with the table.
51
5. INSTALLING AND PIPING THE DSP [Ventilation of Air Compressor Room]
Do not connect the exhaust duct directly to the dryer Technical Data for Room Ventilation
exhaust due to the low allowable pressure loss of the Model 37WN 55WN
dryer ventilation fan. Item/Unit 37VWN 55VWN
If an exhaust duct is connected to the dryer exhaust and Heat generation MJ/h 16 22
ventilation is forced with a ventilating fan, the dryer may Recommended
be excessively cooled or damaged. m3/min 45 60
fan capacity ①
Note 1) The value in the ( ) shows for built-in dryer type.
Note 2) The specified capacity is based on the allowable room
temperature rise of 5℃ and static pressure is zero (0) MPa.
Fresh
air
Fig. A
Fig. B
52
6. STARTUP OPERATION
The instructions in this chapter should be followed when starting up the air compressor for the first time or after a
long term suspension.
CAUTION
● Before connecting the power, verify that the air compressor is correctly installed, piped and wired.
● Check the power supply; verify that it is firmly grounded and that the voltage is within an allowable
range (-5% to +10%).
city water.
負 荷
LOAD
表示切替/
遠 方 ワイドモード 運 転 停 止
記 憶
STR 1 2
WARNING
Hitachi does NOT fill the air compressor with oil.
Before startup operation, fill the air compressor
with the oil. If oil is not added and the air
compressor is operated, it may burn or fail.
53
6. STARTUP OPERATION [Startup Operation of the Air Compressor]
6.1.2 Starting
② Verify that the air compressor has proper rotation.
運転管理 運転状況
RUNNING CONTROL RUNNING MODE
If rotation is not correct (phase reversal), change 2
警 報 遠 方
③④ ALARM
REMOTE
負 荷
LOAD
電 源
POWER
of the 3 wires of the power cable.
機 能 リセット 起動待ち
RESET
FUNC 故 障 AUTO START
SHUTDOWN
記 憶
表示切替/
ワイドモード
SELECT/WIDE
運 転
START
停 止
STOP
③ Verify that the oil pressure rises 0.12 MPa or greater
within ten (10) seconds after star ting the air
1 2
INTSTG. P: *. **MPa STR
Air-Cooled
① Fully open the discharge stop valve, and press the ⑥ Raise the pressure step by step as illustrated below.
START button.
0.70 Pressure Raising Pattern
Discharge pressure (MPa)
0
0.5hr 1hr 1.5hrs 2hrs
Time
モニタ
MONITOR
警 報
ALARM
遠 方
REMOTE
電
POWER
源 ② Check the LCD for operating pressures and
メニュー 負 荷
WARNING
㻰 㻵 㻿 㻚 㻌 㼀 㻱 㻹 㻼 㻚 㻌 㻞 㻦 㻖 㻖 㻖 䉝
㻻 㻵 㻸 㻌 㼀 㻱 㻹 㻼 㻦 㻡 㻡 䉝
㻯 㻸 㼀 㻚 㻌 㼀 㻱 㻹 㻼 㻦 㻌 㻠 㻞 䉝
㻞 㻺 㻰 㻌 㻿 㼁 㻯 㻚 㻌 㼀 㻚 㻦 㻖 㻖 㻖 䉝
㻹 㻭 㻵 㻺 㼀 㻱 㻹 㻭 㻹 㻯 㻱 During inspection of the operation of the air
㻴 㻾 㻚 㻌 㼀 㻻 㻌 㻹 㻭 㻵 㻺 㼀 㻦 㻜 㻜 㻜 㻜 㼔
㻺 㻱 㼄 㼀 㻌 㻹 㻭 㻵 㻺 㼀 㻦 㻖 㻖 㻖 㻖 relief valve, use the appropriate facial
protection. High pressure air containing dust
particles can cause severe injury.
54
6. STARTUP OPERATION [Startup Operation of the Air Compressor]
6.1.4 Stopping
① Press the UNLOAD STOP button to stop the air
運転管理 運転状況
compressor. Operation stops when the air end and the
RUNNING CONTROL RUNNING MODE
警 報 遠 方
REMOTE 電 源
air piping have dried for 5 minutes. To stop the
②
POWER
負 荷
LOAD
STOP button.
SHUTDOWN
記 憶
INTSTG P: *. ** MPa STR 1 2
55
6. STARTUP OPERATION [Initial Setting of OMR Regulator]
CAUTION
1. Maintain the pressure of a control air at the regulator setting value or more. If a control air pressure
of this level cannot be obtained, the ejector cannot operate and as a result, the gear case internal
pressure rises.
When the gear case internal pressure reaches approximately 20 mmH2O, the OMR relief valve opens
to atmosphere to prevent excessive rise. This results in the venting of oil fume to atmosphere.
Therefore, if a control pressure cannot be maintained at the regulator setting, value, take
precautions to keep the air compressor from inhaling the oil fume back into the air intake.
2. If two or more air compressors are in parallel, the system may force a specific unit to unload for a
long period of time. The unloaded air compressors oil mist remover ejector may seldom operate,
thus opening its OMR relief valve frequently and venting oil mists to atmosphere. To solve this
problem, connect the unloaded air compressors control air pipe to an area in the plant air piping
system where pressure is consistently available, minimizing the amount of time the OMR relief valve
opens.
3. The OMR relief valve shortly opens when the air compressor starts and stops, even when control air
pressure is high. After repeated starts and stops, the OMR relief valve may ooze a slight amount of
oil. This is not unusual.
4. The oil mist remover consumes compressed air of approximately the value indicated above table.
The exact air consumption depends on the setting of the regulator.
5. Take precautions if the air compressor is used in AUTO operation mode, as the air compressor may
not stop automatically, due to the uninterrupted consumption of the compressed air by the oil mist
remover.
56
7. WIRING
WARNING
1. Always use a licensed electrician. Do not allow an unlicensed person to wire the compressor. An
unlicensed person may wire the air compressor wrongly, and a wrong wiring may cause an electric
shock.
2. Do not remove any protective relays on the air compressor. Also, do not make a modification of the
control circuit that may result in impairing the protective relay's function. Remember that the loss of
the protective relay's function may cause serious damage to the air compressor such as a burning of
the air end. In the event that you need to modify the control circuit, consult your distributor.
3. Before opening the control panel to service or wire the air compressor, disconnect the power; otherwise
you may receive an electric shock. In addition, attach a notice on the power supply stating “Under the
maintenance work. Keep the switch off.” to prevent someone from carelessly turning the switch on.
7.2 Connecting the Power Cable ■ Usable HITACHI Earth Leakage Circuit Breakers
Model 37A(R)N 55A(R)N 37VA(R)N 55VA(R)N
① Wiring inside the air compressor is completed prior to
Item/Voltage 37WN 55WN 37VWN 55VWN
shipment by Hitachi. Refer to “7.3 Wiring Diagram”. 200 V EX400B EX600B RXK225H RX400B
Model of
② Ground resistance requirements are required when connected Hitachi class (225A) (300A) (225A) (350A)
Breakers 400 V EXK225 EXK225 RXK225-H RXK225-H
the power cable and grounding cable. The ground (HITACHI) class (150A) (200A) (150A) (175A)
resistance requirements are shown in the table below: NOTE: Use the earth leakage circuit breaker that is sensitivitycurrent-
Power supply voltage Ground resistance type Ground resistance value switchable (selectable, either 100 mA or 200 mA), and set its
earth leakage sensitivity current to 200 mA.
200 V class Type D 100 Ω or less
400 V class Type C 10 Ω or less ⑦ Disconnect the power and verify that it is safe before
③ For service accessibility to the air compressor, install 1.) Overhauling , 2.) Adding oil and/or 3.) Servicing
the power cable away from the enclosure. the control panel.
④ Install an earth leakage circuit breaker between the ■ Example of Power Cable Connection
air compressor and the power supply for protecting Earth leakage circuit breaker is used also as a disconnect.
the motor.
Earth Leakage
⑤ Use a HITACHI earth leakage circuit breaker. Circuit Breaker
⑥ When using a non-HITACHI earth leakage circuit
breaker, consult your distributor because a selection Turn off the earth leakage
circuit breaker if air
condition may be different between Hitachi and other compressor is not in use.
manufacturers. R1 S1 T1
57
7. WIRING [Connecting the Power Cable]
CAUTION
Protect the power cables with using attached
rubber bush, conduits and/or protective tubes.
An unprotected power cable can come into
direct contact with the steel plates on the
power cable holes with a slight amount of
vibration. This could damage the cover over
time and result in a short circuit accident.
CAUTION
● Install an earth leakage circuit breaker at the right primary side of the air compressor.
Do not install a disconnect switch such as a knife switch in the wiring, as it is not protect the air
compressor and may result in the burning of motors if a ground fault occurs.
● Ground the air compressor to prevent electric shock or an air compressor failure. Ground
independently and directly to the earth (Do not use the steel skeleton of the building as a ground, as it
could cause an operational failure).
58
7. WIRING [Wiring Diagram]
59
7. WIRING [Control panel/LCD Monitor Specifications]
Power of
200 V (50 Hz, 60 Hz) / 220 V (60 Hz)
control circuit
Motor Fixed-speed… - △ (three contactor)
starting method Vtype…Inverter-Controlled
Operating (1) Unload Stop (2) Restart for IPI (3) Remote Start/Stop
functions (4) Dryer prestart (5) Lead/lag (option) (6) Scheduling
(7) ECOMODE
Supported (1) POWER light (2) START light (3) SHUTDOWN light
indication (4) LOAD light (5) REMOTE light (6) AUTO light
(lights) (7) AUTO START light
Setting and (1) Capacity control setting and each function setting
indication (1) Discharge pressure (2) Operating hours (3) Discharge temperature
(4-digit digital (4) Load light (5) Alarm/shutdown code (6) Alarm/shutdown history
monitor) (7) Pressure setting
Setting and (1) Monitor display
display - Clock - Capacity control setting - Discharge pressure
(LCD) - Oil pressure - Coolant pressure - Operating hours
- Loading hours - No. of loading times - Discharge air temperature 1
- Oil temperature - Coolant temperature - Amperage Current
- Hours to a next maintenance - Next maintenance item
- Load ratio - Scheduled time
(2) Message display
- Inspection/maintenance - Under automatic stop - Restart
- ISI/retry - Unload stop - Other message
(3) Alarm/shutdown
- Alarm check - Setting/connection check - Power check
- Abnormal stop - Device shutdown
(4) Function menu
- Function setting - Operation type - Capacity control
- Scheduled operation - Operation data recording - Load date recording
- Alarm history - Shutdown history - Shutdown history details
Dry contacts (1) Operation signal output : a contact × 1
(2) Alarm signal output : a contact × 1
(3) Shutdown signal output : a contact × 1
Air compressor continues to operate.
Instantaneous Power Interruption Less than 20 ms
Air compressor stops, blows off and automatically
and Restarting For 20 ms to setting (1)
restarts in setting (2).
For setting (1) or more
Air compressor stops.
Note) Setting(1): Time selected on the instrument panel (1 - 5 sec)
Setting (2): 15 - 60 sec
Unload Stop: Operated by the Unload Stop button located lower on the operating monitor.
60
7. WIRING [Wiring Diagram]
⑶ Capacity Control System The low noise cooling fan cools the cooler, exhausts
[Fixed-speed type] the hot air within the enclosure, and exhausts the
When the demand of compressed air decreases, the inter nal compressed air that is released to
system closes the suction throttle valve and atmosphere during the unloading (purging) process.
exhausts the internal compressed air to atmosphere Water-Cooled
at the same time, thus unloading the air compressor.
The small cooling fan cools the inside of the
package, and exhausts the internal compressed air
When demand of the compressed air decreases, the that is released to atmosphere during the
system reduces the motor speed. And When unloading (purging) process.
demand of the compressed air decreases more, ※ The indication in the ( ) is for Vtype.
purges the compressed air to atmosphere.
81
8. STANDARD COMPONENTS AND SUBSYSTEMS [Standard Components, Air/Oil/Water Flow]
Water-Cooled
Air-Cooled
Coolant Flow
Coolant flows through the jacket of the air end case.
The heat-exchanged or heated coolant is cooled by the
coolant cooler and is pneumatically circulated by the
coolant pump. The cooling fan removes the heat of the
coolant cooler.
82
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil/Water Flow]
52
12
37
Air cooler
Air intake for 63SV 22 Compressed
compressed air 51
air discharge
8
11
T/C 23
Condenser
Dryer air inlet
41 34
6 9
2
32 Dryer
4 compressor Dryer
PS4 condensate
5 PS2 drain
TH5
30
31 10
16
33 3
35
TH1 PS3
14
Capacity Control & Blowoff Air Flow Air Flow and Other
21 Air Intake Filter 51 Fan Motor
22 Air Cylindera 52 Enclosure
23 Blowoff Valve 53 Air Intake Duct
24 Blowoff Silencer 54 Cooling fan
83
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil/Water Flow]
52
12
37
M
Air cooler
M
Air intake for 63SV Compressed
compressed air 51 17
air discharge
23 8 M
11
T/C Dryer air inlet
Condenser
40 34
41
M 6 9
2
32 Dryer
4 compressor
PS4 Dryer
PS2 condensate
TH5 5
drain
30
31 10
65
33 3
35
TH1 PS3
14
Capacity Control & Blowoff Air Flow Air Flow and Other
21 Air Intake Filter 51 Fan Motor
22 Blowoff Solenoid Valve (1) 52 Enclosure
23 Blowoff Solenoid Valve (2) 53 Air Intake Duct
24 Blowoff Silencer 54 Cooling fan
84
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil/Water Flow]
52
37
1 11
9
T/C 23
12
6
2
32 Compressed
4
PS4 air discharge
PS2
TH5 5
30
31
33
35 3 34
16
36 7 38 15 13
Cooling air flow Compressed air flow Lubricating oil flow Cooling water flow
85
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil/Water Flow]
37
M
Air intake for 63SV M
compressed air
10 8
23
1 11
9
T/C 17
40
M 6 12
2
32 M
4
PS4
PS2 Compressed
TH5 5 air discharge
30
31
33
35 3 34
16
36 7 38 15 13
Cooling air flow Compressed air flow Lubricating oil flow Cooling water flow
86
8. STANDARD COMPONENTS AND SUBSYSTEMS [Cooling Water]
8.3 Cooling Water Water-Cooled a) The cooling water pipe could freeze and burst in
cold temperatures.
1. Cooling Water Quality b) The airend case can be overcooled and develop
If a cooling tower (open-type circulatory cooling water moisture internally; thus leading to scaling in the
system) supplies the cooling water to the Air cooling water jackets.
compressor, problems such as corrosion, scale, and
② Clean the cooling water subsystem (cooling water
slime may be caused by:
jackets of the first- and second-stage airends,
(1) higher mineral content due to concentration,
intercooler, aftercooler, and oil cooler) periodically.
(2) contamination by foreign matter like insects, and/or
(3) production of algae or bacterium. Using the best 2. Control of Cooling Water
quality cooling water is highly recommended. The service life of the cooling water system depends on
(4) Refer to the table “Cooling Water Quality” below for water quality. If the cooling water quality is not within
the open type circulatory system. specification, the cooler pipes can corrode or scaling can
① Stop the cooling water flow, when the air compressor occur. To avoid the problem, periodically sample the
has stopped. Open the petcock and the water drain cooling water used and subject it to a quality inspection.
valve to drain the cooling water (see Figure 1 below). 3. Quantity and Pressure of Cooling Water
Failure to perform step 1, can lead to the following: Refer to the table “Quantity and Pressure of Cooling
Water” below.
CAUTION
Performance of the coolers varies depending
Water drain pet cock
on the extent of throttling the stop valves at
the cooling water inlet and outlet.
To control the cooling water flow rate, throttle
the stop valve at the outlet and leave the stop
Water drain port
valve at the inlet opened completely.
Water drain port
Cooling water discharge valve
87
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
START button ON Discharge pipe pressure rises Discharge pipe pressure drops 3-way solenoid valve (20Ux)
switched over to pressurize
Airend starts rotation to Pressure sensor (PS) operates Pressure sensor (PS) operates Chamber (A)
compress minor amounts of air
3-way solenoid valve (20Ux) 3-way solenoid valve (20Ux) Suction throttle valve
Starts in no load switched over to pressurize switched over to pressurize (STV) closes
Chamber (A) Chamber (B)
Changes to full voltage delta connection Blowoff valve opens
Suction throttle valve Suction throttle valve
3-way solenoid valve (20Ux) (STV) closes (STV) opens
switched over to connect Internal air in discharge pipe
Chamber (A) & Chamber (C) Blowoff valve opens Blowoff valve closes is exhausted to atmosphere
Airend
Control Line Filter
Pressure sensor
Compressed
Air Discharge
88
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
START button ON Discharge pipe pressure rises Discharge pipe pressure drops 3-way solenoid valve (20Ux)
switched over to pressurize Load-Unload Operation
Chamber (A)
Airend starts rotation to Pressure sensor (PS) operates Pressure sensor (PS) operates
compress minor amounts of air
Suction throttle valve
3-way solenoid valve (20Ux) 3-way solenoid valve (20Ux) (STV) closes
Starts in no load switched over to pressurize switched over to pressurize
Chamber (A) Chamber (B)
Changes to full voltage Blowoff valve opens
delta connection Suction throttle valve Suction throttle valve
(STV) closes (STV) opens Internal air in discharge
3-way solenoid valve (20Ux) pipe is exhausted to
switched over to connect atmosphere
Chamber (A) & Chamber (C) Blowoffvalve opens Blowoff valve closes
30% or more
Load ratio ?
89
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
0.70
0.60
Pressure
MPa
Air discharge pressure
after aftercooler
0.10
Time
minutes or more has passed after
Air Receiver Pressure Indications on LCD the first stop, the motor continues
0.70
to operate for 20 minutes after
restart of the air compressor, and
0.60
then return to the initial cycle.
Pressure
0.70
* 0.62(minimum)
0.60 (Note)
Pressure
Time
90
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
Airend
Pressure sensor
Blowoff
Precooler silencer
Check valve Aftercooler
Air
discharge
8.4.5 Relationship between Air Consumption Rate and Capacity Control System
Rated Air Pressure setting (MPa)
Operating Capacity
Model pressure consumption Capacity control system Example control type
(%) frequency (Hz) Initial
(MPa) of Lower
37kW 100 - 70 60 - 42
0.70 0.70 0.60 AUTO ON
55kW 100 - 56 60 - 34 ① CPCS motor Control (VSDA)
or
37kW 100 - 56 60 - 34 speed control pressure
AUTO OFF
0.30 0.30 − (VSDB)
55kW 100 - 48 60 - 29
37kW 70 - 4 24 Cut-out
pressure 0.72 0.70
0.70 AUTO ON
Cut-in 0.67 0.60
55kW 56 - 4 19 pressure (VSDA)
② Two-step purge
or
control Cut-out
37kW 56 - 4 19 AUTO OFF
pressure 0.32 (VSDB)
0.30 −
Cut-in 0.27
55kW 48 - 4 16 pressure
All 0.70 Main motor ③ Motor stop/ Cut-in 0.67 0.60 AUTO ON
4-0
model 0.30 stop restart control pressure 0.27 − (VSDA)
The air compressor supports the three (3) capacity control systems as shown above.
Depending on the varying air consumption, an appropriate system is automatically selected. For more information, see
the following page. Operation frequency is shown by Digital monitor. LCD monitor displays up to first figure after
decimal place.
IMPORTANT
91
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
I : integral
Pressure sensor
D: differential
IMPORTANT
100
①
seconds.
Q (%)
② ② ②
(2) The plant’s system pressure may drop drastically before
the motor restarts, 15 seconds later. To avoid such 0
③ ③
problems, install an air receiver tank of 1.24 m3 or larger. The values are for air-cooled, 37 kW, 0.7 MPa type.
92
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
Pa ① ②
7M
0.
90 Pa
6M ②
0.
a
MP 100
Pa
5M
80 0.
a
MP
80 90 100 110 0.4
Air consumption (%)
70
This figure is intended for 0.7 MPa type.
① By reducing the operating pressure from 0.7MPa to 90 100 110 120 130
0.6MPa, the maximum consumption power is
Air consumption (%)
automatically limited to approximately 92% of the
consumption power at 0.7MPa. ① By reducing the operating pressure from 0.70 MPa
to 0.50 MPa, the power consumption is reduced to
② By reducing the operating pressure further down to
85%, and further reduced to 79% at 0.40 MPa.
0.5MPa, the consumption power is reduced to
approximately 85%. The consumption power at 0.4 ② By reducing the operating pressure from 0.70 MPa
MPa is approximately 79%. to 0.50MPa, PQ-Wide Mode utilizes the surplus
power from the reduction in pressure to increase the
If reducing the power is desired; the “PQ Wide Mode:
capacity up to approximately 118% of the rated
OFF” is recommended.
capacity, and further increased to 126% at 0.40MPa.
表示切替/
遠 方 ワイドモード
REMOTE SELECT/WIDE
記 憶
表示切替/ワイドモード
STR 1
Set by button
93
8. STANDARD COMPONENTS AND SUBSYSTEMS [Dryer System]
: Refrigerant flow
Precooler Ⓐ
Air cooler Ⓑ
Refrigerant
evaporating Heat exchanger
pressure gauge
P Automatic drain
trap Ⓒ
Ejector Ⓗ Fan Ⓕ
Charge valve
High pressure switch
PS1
PS2
Fan control switch
Accumulator Ⓘ
Refrigeration
compressor
Ⓓ
Vacuum Indicator
Air End
Indicates that the ejec-
tor is operating properly
and that the gear case
internal pressure is
negative.
Oil Pump
Air Source
Gear Case
When the compressor starts running, The incorporated ejector uses the compressed air to
oil mist is vented from the vent pipe. generate a vacuum pressure, which maintains a
negative pressure on the oil mist remover subsystem.
This prevents the gear case internal pressure from
When the line pressure rises,
the ejector actuates. rising due to a resistance of the element.
By installing the oil mist remover:
Negative pressure is maintained in There is no need to extend a gear case vent pipe
the oil mist remover. ① outdoors, avoiding any type of trouble that may be caused
by incorrect installation of the gear case vent pipe.
Without increase of gear case internal pressure, Oil mists are prevented from venting from the gear
the high-performance remover element removes ② case to atmosphere, keeping the compressor room/
oil mist. area clean.
CAUTION
The oil mist remover reduces oil consumption to almost zero. However, the oil should still be replaced
bi-annually.
95
9. MAINTENANCE
CAUTION
● Before servicing the air compressor, carefully read “SAFETY PRECAUTIONS” ( page 2 - 5).
● Before servicing , disconnect the power to prevent an electric shock.
● Before removing or disassembling any parts on the air compressor, stop it, disconnect the power and
make sure that the internal pressure of the air compressor has dropped to atmospheric pressure to
prevent high pressure air from blowing off and causing injury. Special attention must be paid to the
piping between the compressor check valve and stop valve located in the air discharge piping.
3 Overhauling
Overhauling consists of changing the existing
airend with a new replacement airend.
Overhaul the air compressor at 6 years.
96
9. MAINTENANCE [Standard Maintenance Schedule]
97
9. MAINTENANCE [Standard Maintenance Schedule]
Category
Part or Item Action Type Remarks
1-year Every 3-year
Protection, Safety Device Check ▲ Fixed/V A/W Change any operating parts in need of replacement.
Motors Check & Clean ▲ Fixed/V A/W Clean and measure the insulation for any resistance.
Coolant pump Check ▲ Fixed/V A
Pressure cap Check ▲ Fixed/V A Clean and replace as required.
Coolant strainer Replace ▲ Fixed/V A
Gasket, coolant strainer Replace ● Fixed/V A
Oil filter (secondary) Replace ● Fixed/V A/W
Consumable parts - Suction throttle valve Replace ● Fixed A/W Replace the gaskets, etc together.
Seal washer - Suction throttle valve Replace ● Fixed A/W
Relay (Drain solenoid valve) Replace ● Fixed/V A/W
98
9. MAINTENANCE [Standard Maintenance Schedule]
99
9. MAINTENANCE [Standard Maintenance Schedule]
100
9. MAINTENANCE [Maintenance Schedule for Dryer and Oil Mist Remover]
CAUTION
The oil mist remover reduces oil consumption to almost zero. However, the oil should still be replaced
biannually.
101
9. MAINTENANCE [How to Service the Air Compressor]
CAUTION ④ Loosen the wing nut and remove the air intake filter.
Make sure the contamination and/or dust doesn’t
If the air intake filter is clogged with dust/dirt enter the airend side.
particles; Differential pressure (resistance of
flow) across the air intake filter increases, ⑤ Tap the air intake filter to remove large particles.
which results in decreased air intake to the Then blow air to clean the surface of filter.
airend and a rise in discharge air temperature.
⑥ In the case of oily or carbon dust, dip the element
To avoid a problem, service the air intake filter
into neutral detergent and water solution for about
regularly. If the compressor room environment
30 minutes. Rinse the element several times with
is dusty or dirty, service the air intake filter
clean water (water pressure is less than 0.27MPa)
more frequently than instructed on the
Maintenance Schedule. and air-dr y it. Confirm the element is dried
completely.
102
9. MAINTENANCE [How to Service the Air Compressor]
Ⓐ Ⓑ ① Stop the air compressor and turn off the main power.
Two-way
will be released without passing through the
Ⓐ change valve condensate drain solenoid valve.
103
9. MAINTENANCE [How to Service the Air Compressor]
◆ Cleaning of strainer
■ Cleaning of strainer element
Y-type Strainer Assembly ① Discharge the compressed air in the procedure in
page 103.
② Remove the cover of the strainer.
Element ③ Remove the element from inside the strainer and
Strainer wash with water.
Gasket
④ Replace the cleaned element in its original position
Plug and set the O-ring or gasket, and plug properly.
Tighten
■ Cleaning of orifice
Loosen
Inspect and clean the orifices annually. Be sure to
stop the air compressor before inspecting and/or
◆ Cleaning of orifice cleaning the orifices.
Strainer CAUTION
● Check that a slight amount of condensate is
drained every 45 seconds through the drain
port of the aftercooler while the air
compressor is in loading process.
Orifice
104
9. MAINTENANCE [How to Service the Air Compressor]
Cover ② Place oil pans under the oil drain ports. The dimension
of oil pan is approximately 75 × 250 × 300mm.
Prepare the oil jug of 18 liters or more for air-cooled
type, and 14 liters or more for watercooled type.
Oil filling ③ Remove the plugs of oil drain port. Then connect
port plug copper pipes to the ports. The dimensions of the
copper pipes is 1/2B × 50 to 100 mm. After that,
open the oil drain valve to drain lubricating oil.
Oil drain valve
④ Replace all lubricating oil bi-annually. Also once a year,
(Gear case)
Oil level gauge remove the oil port cover and wipe the sludge off of
Oil drain port (with plug)
the bottom of the gear case with a sponge and clean.
⑤ Close oil drain valve. Tighten removed plugs with
Air-Cooled [Rear View]
seal tape to oil drain port.
■ Oil filling
⑥ Remove the oil filling port plug, and fill the oil until the
oil reaches the upper red line of the oil level gauge.
■ Check/refilling
⑦ Turn on the power, press the START button and
press the STOP button after 5 – 6 seconds running.
⑧ Check the oil level on the oil level gauge. The oil
level drops because lubricating oil flows to the
piping, oil cooler and so on.
⑨ Disconnect the power and add the oil until upper red
Oil drain valve Oil drain port
(Oil cooler) (with plug) line.
⑩ After refilling is complete, plug tightly.
⑪ Turn the power on, press the START button and
Water-Cooled [Rear View]
make sure the oil level is between the upper and
lower red lines of the oil level gauge.
⑫ Make sure no oil leaks from the oil drain valve and
plugs.
WARNING
● Change the oil regularly, as instructed in the
standard maintenance schedule ( page
97 to 100). Neglecting to change the oil
Oil drain port
causes oil deterioration that could result in
(with plug) clogging of the oil strainer and a fire.
Oil drain valve
● Be sure to use the recommended lubricating
(Oil cooler)
oil on page 12. Absolutely DO NOT mix
different types of lubricating oil.
● Overfilling with lubricating oil may increase
shaft power and result in rise in oil temperature.
105
9. MAINTENANCE [How to Service the Air Compressor]
IMPORTANT
Clogging of the oil strainer drops the oil pressure of the air
compressor.
● Vtype
If the oil pressure sensor detects an oil pressure as low
as 0.08MPa or lower for operation frequency 45 Hz or
higher, or 0.04 MPa for operation frequency less than
Cover 45 Hz, the air compressor automatically shutdowns.
● Fixed-speed type
Oil Strainer If oil pressure sensor detects an oil pressure as low as
0.08MPa or lower, the air compressor automatically
shutdowns.
Pan
(Prepare a pan with a size of IMPORTANT
approx. 20 x 100 x 250 mm)
Clogging of the oil filter drops the oil pressure of the air
compressor.
● Vtype
If oil pressure sensor detects an oil pressure as low as
0.08MPa or lower for operation frequency 45 Hz or
higher, or 0.04 MPa for operation frequency less than
45 Hz, the air compressor automatically shutdowns.
● Fixed-speed type
If oil pressure sensor detects oil pressure as low as
0.08MPa or lower, the air compressor automatically
shutdowns.
106
9. MAINTENANCE [How to Service the Air Compressor]
WARNING
During inspection of the operation of the air
relief valve, use the appropriate facial
protection. High pressure air containing dust
particles can cause severe injury.
107
9. MAINTENANCE [How to Service the Air Compressor]
Air-Cooled
108
9. MAINTENANCE []
Water-Cooled
109
9. MAINTENANCE [How to Service the Air Compressor]
Packing
IMPORTANT
Coolant Pump
When the coolant pressure sensor detects the coolant
pressure as low as 0.10 MPa (due to the clogging of the
coolant strainer), the DSP shuts down automatically.
Coolant Pump
Header
110
9. MAINTENANCE [How to Service the Air Compressor]
V-Belt ing L
oad WARNING
Press
V-Belt ( k g )
P Before you check the V-belts, stop the DSP and
Motor
disconnect the power.
Sheave Keep your hands and rods etc. away from the
rotating parts during operation; otherwise you
may be seriously injured.
Flat Bar 1 Visually checking the V-belts, pulley, and motor sheave
(about 700 mm)
① Spotlight the V-belts contacting surfaces, and verify
that the ribs are not chipped or cracked.
Likewise verify that the pulley and motor sheave are
Pressing Load Flexure not abraded abnormally or chipped.
Item V-Belt
P δ
Type× ② Verify that the V-belts are not generating abnormal
MPa kgf N mm
Model Quantity
DSP-37A(R)5N, 37W5N 10.2∼11.8 100∼116 10.6
slipping sound (squeaking or creaking noise).
DSP-37A(R)6N, 37W6N
DSP-37VA(R)N, 37VWN
9.9∼11.5 97∼113 10.9 2 Checking the V-belts tension
0.7
DSP-55A(R)5N, 55W5N 12.5∼14.4 123∼141 10.3 ① Prepare a 700-mm flat bar.
DSP-55A(R)6N, 55W6N
12.3∼14.2 121∼139 10.7
DSP-55VA(R)N, 55VWN ② Press the bar onto the belt span surface of the pulley
12PK×2
DSP-37A(R)5N, 37W5N 9.2∼10.6 90∼104 10.7
and motor sheave. Use a spring balance to apply the
DSP-37A(R)6N, 37W6N 9.1∼10.4 89∼102 10.6
0.4 pressing load kg (see the table) onto the belts at the
DSP-55A(R)5N, 55W5N 11.6∼13.4 114∼131 10.0
DSP-55A(R)6N, 55W6N 11.4∼13.1 112∼128 10.0 span center, and measure the flexure mm.
DSP-37VA(R)N, 37VWN 9.1∼10.5 89∼103 10.7 See the table for an allowable flexure range. If the
0.3
DSP-55VA(R)N, 55VWN 11.2∼12.9 110∼126 10.7 flexure is within the range, you do not need to
readjust the belt tension. If the flexure is not within
the range, contact your distributor for a tension
Item Span Mass Tension
readjustment.
MPa m kg/m kgf N
Model ③ Alternately you can measure a belt tension directly
DSP-37A(R)5N, 37W5N 0.663 164∼189 1608∼1853
by using a special tension meter. For more information
DSP-37A(R)6N, 37W6N
0.680 159∼183 1559∼1794
DSP-37VA(R)N, 37VWN about the tension meter, contact your distributor.
0.7
DSP-55A(R)5N, 55W5N 0.642 200∼230 1961∼2255
DSP-55A(R)6N, 55W6N
0.666 196∼226 1922∼2216
DSP-55VA(R)N, 55VWN
DSP-37A(R)5N, 37W5N 0.669 0.228 146∼169 1432∼1657 CAUTION
DSP-37A(R)6N, 37W6N 0.663 144∼166 1412∼1628
0.4
DSP-55A(R)5N, 55W5N 0.623 186∼214 1824∼2098 ● Low-tensed V-belts may slip and may be
DSP-55A(R)6N, 55W6N 0.626 182∼210 1785∼2059 drastically low in a service life.
DSP-37VA(R)N, 37VWN 0.666 146∼168 1432∼1647
0.3 ● Wrong centering during a belt tension
DSP-55VA(R)N, 55VWN 0.669 179∼206 1755∼2020
adjustment may cause a larger misalignment
and reduce a service life.
111
9. MAINTENANCE [How to Service the Air Compressor]
Check valve Remove the enclosure panels such as rear cover [Ref.
No. 911].
Gasket
3 Disassembly
① Loosen and remove the bolts tightened to the check
Check valve valve cover (upper).
cover (lower)
② Remove the check valve cover, gasket, check valve,
Flow direction (arrow direction)
and gasket.
Gasket
112
9. MAINTENANCE [How to Service the Air Compressor]
Battery
④ The battery is mounted on the back of the LCD
⑤ unit. Unplug the battery connector. The battery
is held by double-sided adhesive tape.
113
9. MAINTENANCE [How to Service the Air Compressor]
Heated
Excessive Sound
Breaker Tripped
Electric Leak
Corrective Action
Bearing
Frame
Cause
Installation
○ ◎
Broken wires ○ Install new wires.
Note 3
Failed breaker, controller or contactor ○ ○ Check the contacts and replace if necessary.
Dust accumulation reduced cooling
○ Properly clean motor.
Environment
performance
Excessive ambient operating Improve the room ventilation or contact the local
◎ ○ ◎
temperature Hitachi distributor.
High humidity ◎ Contact the local Hitachi distributor.
Large external vibration/shock ◎ Take vibration and shock measurements.
Load Power Supply
114
9. MAINTENANCE [How to Service the Air Compressor]
the O-ring, replace Cover ② Pull down the indicator while pushing up the locked
Rubber packing pipe joint at the top.
the housing, and
Remover
tighten set screws element Nut Spring
(A) diagonally and Plate Valve seat
O-ring
evenly.
Rubber packing
Locked joint
3/8 φ12
Pull
(A)
Fig. A Fig. B
Cover
Baffle
Nut A
115
9. MAINTENANCE [How to Service the Air Compressor]
Drain Cock
CAUTION
● Use household neutral detergent to clean
the bowl. Other solvents will crack the
bowl.
116
10. CAUTIONS FOR A LONG TERM OPERATION SUSPENSION
① If the air compressor is not operated for a week or
more, use the UNLOAD STOP function when the
air compressor is stopped. The air compressor 運転管理
RUNNING CONTROL
運転状況
RUNNING MODE
自 動
AUTO
メニュー 負 荷
[× 10h] LOAD
IMPORTANT
SET
MONITOR
CAUTION
● If the air compressor is stops for a week or more without taking action described in this page, serious
damage for the airend may occur due to the lack of lubrication or airend internal rusting.
● Use unload stop button not only for long operation suspension but also for daily operation to prevent
the airend from the rusting.
● If the air compressor can’t be operated weekly, rust prevented action and periodical inspection is
required. Contact the local HITACHI distributor/master dealer or representative office for the detail.
117
11. PARTS LIST
118
11. PARTS LIST
3 Motor Assembly
Ref.
405 No. Description
330 V-Pulley
331 Stopper
401 Motor
403
403 Motor Sheave
331 405 VR Belt
409 Base, motor
421 Base, air end
424 Vibration Isolation Rubber (1)
425 Vibration Isolation Rubber (2)
401 427 Bolt
453 435 Motor Terminal Cover
454 436 Motor Rubber Plate (1)
437 Motor Rubber Plate (2)
330 437 453 Bearing (Load-side)
436 454 Bearing (Anti-Load-side)
435 D88 Angle Washer
421
427
D88
409
424
425
119
11. PARTS LIST
4 Suction
[Fixed-speed compressor] Ref.
Description
No.
556 532 500 Suction Throttle Valve Assembly
534
508 501 Air Cylinder Assembly
507 502 Body, STV
506 503 Tube, air cylinder
504 557
533 504 Cover (1)
521
519 540 506 Piston, blowoff valve
522 507 Valve Sheet, blowoff valve piston
520
508 Plate
503
509 Spindle, air cylinder
520
518 535 510 Distance Piece
537
536
511 Gasket, air cylinder
539
517 516 512 Gasket (1), air end air intake
525 515 513 Gasket, STV cover
514 Valve Plate, STV
528
515 Seal Gasket (1)
538
527 516 Seal Gasket (2)
515 509 517 Piston, air cylinder
541
526 518 Seal Gasket (3)
522 519 Seal Gasket (4)
514
520 O-Ring, air cylinder
542
567 521 Seal Gasket (5)
504 522 Bush, air cylinder
511 525 Tying Rod, air cylinder
502 540
526 Cover, air cylinder
500 Suction Throttle Valve
Assembly 527 Spacer
510 501 Air Cylinder Assembly 528 Baffle Plate
555
529 529 Spring Washer (SUS)
E15
530 530 Rod Nut
513 559 532 Body, blowoff valve
558 ※569
533 Guide RIng
534 Seal Washer, air cylinder
535 Nut
536 Wave Spring
537 O-Ring (piston)
※551 538 O-Ring (spacer)
512 539 O-Ring (needle)
540 O-Ring, air cylinder
541 Holder, piston
502 542 Spacer
551 Set of Air Cylinder Consumable Parts
513 555 Gasket, unloader cover
556 Spacer (2)
557 O-Ring
558 Adjusting Bolt, suction bypass valve
559 Seal Washer, suction bypass valve
567 Valve Plate (2), STV
569 Grease, air cylinder
E15 Seat, STV
※ Does not come with the
product.
Ref.
No. Description
502 Body, STV
512 Gasket (1), air end air intake
513 Gasket, STV cover
512
120
11. PARTS LIST
638
E50
E66 629
670
628 D03
D05 E48
689
694 692
634
E48 693
F42
600
E48 E32
692
E48
E28 D04 D04
E52
121
11. PARTS LIST
J45
J42
E18
404
404 C84
C84
J44
55KW
E18
680 977
[Fixed-speed compressor]
37kW
122
11. PARTS LIST
6 Oil Pump
Ref.
No. Description
300 Consumable Parts Kit, oil pump
327 Oil Pump Assembly
328 Bearing
362 329 Oil Seal
329 342 Oil Pump body
346
329 ※300
328 343 Housing, oil pump bearing
327 344 Cover, oil pump
355
345 356 345 Key
346 Backup Ring
347 Backup Ring
349 Packing, oil pump cover
342
350 Case
353
354 351 Support
363 353 Inner Rotor
350 354 Outer Rotor
363 355 Shaft
360 343 356 Key
328 357 Pipe Knock
358 Ring
382 360 Bolt
362 Snap Ring
363 O-Ring
381 Packing, oil pump support
382 Seal Washer
351 ※ Does not come with the
381 347 product.
357
358
349
344
7 Coolant Pump
Ref.
No. Description
825 826 802 Case
D98 803 Cover
804 Impeller
805 Shaft
810 ※994 808 Mechanical Seal
810 Key
812 Rubber Deflector
815 Packing, case cover
825 Motor, coolant pump
826 Packing, header
994 Consumable Parts Kit, coolant pump
D31 Nut
D97 O-Ring
D98 Bearing
804
805 ※ Does not come with the
D31 product.
812
815
803
802
808
D97
123
11. PARTS LIST
8 Instrument Panel
Ref.
No. Description
H79 719 Digital Panel
719 744 Lithium Battery
744
746 Control PCB
Display unit assembly
(included in #745 Starter board 748 Seat, instrument panel
PCB assembly) 755 Display Unit
(included in #700 Control Panel) G57 E-Stop (Option)
H39 PCB Cover
H43 UNLOAD STOP Button
H79 Switch Guard
H80 OPE Code Pipe
H81 OPE Code (1)
H82 OPE Code (2)
H99 Unload Stop Nameplate
755
746
H81
748
H82 G57
H99
H39
H80
124
11. PARTS LIST
9 Control Panel
[Fixed-speed compressor]
H38 740
Air-Cooled
D12
745 D10
D75
752
D73
706, 737
※A18
939
B44
E47
E46 938
Ref. Ref.
No. Description No. Description
700 Control Panel 929 Rubber Bush
701 Electromagnetic Contactor (42) 938 Handle
702 Electromagnetic Contactor (6) 939 Rubber Bush
704 Electromagnetic switch, fan A10 Electromagnetic switch, dryer
705 Electromagnetic switch, C pump A18 Electromagnetic Contactor
706 Fuse B44 Cover
708 Current Transformer D06 Terminal Block
709 Terminal Block (1) D07 Auxiliary Relay (1)
710 Terminal Block (2) D08 Auxiliary Relay (2)
711 Temperature control switch D10 Line Filter
720 Transformer D12 Fan, control panel
729 Electromagnetic switch, 52 D73 Relay (only 400V class)
737 Fuse Holder D75 Transformer (only 400V class)
740 Expansion Unit E46 Rubber Bush
745 PC Board E47 Rubber Bush
752 Fuse (400V class only) H38 AVR
※ Built-in dryer type only.
125
11. PARTS LIST
9 Control Panel
Air-Cooled Ref.
Description
No.
700 Control Panel
37kW E03 704 Electromagnetic switch, fan
D10
705 Electromagnetic switch, C pump
745
706 Fuse (2)
J48 708 Current Transformer
J49 709 Terminal Block (1)
706, D12 710 Terminal Block (2)
737 711 Temperature control switch
D10 D08 700 720 Transformer
709 E05
740 737 Fuse Holder (1)
740 Expansion Unit
704 D07
745 PC Board
E06
708 753 DC Reactor (1)
705
929 Rubber Bush
D06 E19 938 Handle
939 Rubber Bush
※A10 ※A18 E07 A10 Electromagnetic switch, dryer
753 E47 929
720 A18 Electromagnetic Contactor
E17 B44 Cover
939
D06 Terminal Block
711 D07 Auxiliary Relay (1)
H38 740 E47
D08 Auxiliary Relay (2)
D10 Line Filter
D12 Fan, control panel
938
E03 Inverter cooling fan
710
706, 737 E05 Main PCB
938 E06 Power PCB
E46 E07 Smoothing Condenser
E17 Inverter
B44 E19 Digital operator
E46 Rubber Bush
55kW E47 Rubber Bush
D10
745 E87 Support
H38 AVR
J48 Support (1)
D12 J49 Support (2)
706,
※ Built-in dryer type only.
737
D10 709 D08 E05 700
740
E03
704 D07
E87
708 E06
705
D06 E19
※A10 ※A18
753 E07 E47 929
720
E87 E17
939
711
H38 740 E47
938
710
706, 737
938
E46
B44
126
11. PARTS LIST
9 Control Panel
[Fixed-speed compressor]
H38 740
Water-Cooled
D12
745 D10
D75
752
D73
706, 737
D10 D08
D06 D07 700
729
704
701 720
708
709 E47
929
702
711
939
B44
E47
E46 938
Ref. Ref.
No. Description No. Description
700 Control Panel 929 Rubber Bush
701 Electromagnetic Contactor (42) 938 Handle
702 Electromagnetic Contactor (6) 939 Rubber Bush
704 Electromagnetic switch, fan B44 Cover
706 Fuse D06 Terminal Block
708 Current Transformer D07 Auxiliary Relay (1)
709 Terminal Block (1) D08 Auxiliary Relay (2)
710 Terminal Block (2) D10 Line Filter
711 Temperature control switch D12 Fan, control panel
720 Transformer D73 Relay (only 400V class)
729 Electromagnetic switch, 52 D75 Transformer (only 400V class)
737 Fuse Holder E46 Rubber Bush
740 Expansion Unit E47 Rubber Bush
745 PC Board H38 AVR
752 Fuse (400V class only)
127
11. PARTS LIST
9 Control Panel
Ref.
Water-Cooled No. Description
700 Control Panel
704 Electromagnetic switch, fan
37kW D10 E03
706 Fuse
745 708 Current Transformer
709 Terminal Block (1)
J48 710 Terminal Block (2)
J49 711 Temperature control switch
706, D12
720 Transformer
737
737 Fuse Holder (1)
D10 D08
700 740 Expansion Unit
740 709 E05
745 PC Board
D07 753 DC Reactor (1)
704
E06 929 Rubber Bush
708 938 Handle
939 Rubber Bush
D06 E19 B44 Cover
D06 Terminal Block (3)
E07
753 E47 929 D07 Auxiliary Relay (1)
720 D08 Auxiliary Relay (2)
E17
939 D10 Line Filter
D12 Fan, Control panel
711 E47 E03 Inverter cooling fan
H38 740
E05 Main PCB
E06 Power PCB
938 E07 Smoothing Condenser
710 E17 Inverter
706, 737 E19 Digital operator
938 E46 Rubber Bush
E46
E47 Rubber Bush
E87 Support (3)
B44
H38 AVR
55kW J48 Support (1)
D10 J49 Support (2)
745
706, D12
737
D10 709 D08 E05 700
740
E03
D07
704 E87
708 E06
D06 E19
753
E07 E47 929
720
E87 E17
939
711
E47
H38 740
938
710
706,737
938
E46
B44
128
11. PARTS LIST
10 Air Pipe
Ref.
Air-Cooled No. Description
022 Air Piping (1)
024 023 Air Piping (2)
024 Air Piping (3)
025 Air Piping (4)
868 026 Air Piping (5)
870 027 Air Piping (6)
058 Support, discharge piping
871 865 Gasket (2)
870 866 Discharge piping
868 Cover, check valve
868 870 Gasket
871 Check Valve
873 Thermocouple, discharge air
875 Air Relief Valve
C07 Motorized Isolation Valve
D19 Gasket, flange
J73 Air Piping (7)
D19 D19 J74 Air Piping (8)
023
J73
058
875
D19
865 J74
022
873
875
027
D19
025
866
058
[Fixed-speed compressor]
129
11. PARTS LIST
10 Air Pipe
D19
Water-Cooled 024
868
870
871
875
870
868
001
002 866
D19
003
025
Ref.
No. Description
001 Aftercooler Header
002 Gasket, aftercooler header
003 Condensate Separator
023 Air Piping (2)
024 Air Piping (3)
025 Air Piping (4)
865 Gasket (2)
866 Discharge piping
868 Cover, check valve
870 Gasket
871 Check Valve
865 873 Thermocouple, discharge air
875 Air Relief Valve
D19 Gasket, flange
023 873
130
11. PARTS LIST
11 Drain Pipe
Ref.
No. Description
006 IC Strainer Assy
007 Gasket, IC strainer
047 IC Strainer Element
052 Orifice, condensate piping (AC)
F68 Support (1), condensate piping
F69 Support (2), condensate piping
F80 Condensate Solenoid Valve
H75 2 way Valve (2)
Air-Cooled
006
007
047
F80
052
F68
H75
F69
Water-Cooled
131
11. PARTS LIST
12 Oil Piping
[Fixed-speed compressor] Ref.
Description
No.
773 Drain pipe
880 Oil Strainer
881 Oil Filter Element
Air-Cooled Water-Cooled 887 Valve
888 Thermistor
D34 O-Ring
H53 Float Cover
887
887
H53
888
881
880
887
773
D34
D34
132
11. PARTS LIST
12 Oil Piping
Ref.
No. Description
773 Drain pipe
880 Oil Strainer
Air-Cooled Water-Cooled
881 Oil Filter Element
887 Valve
888 Thermistor
D34 O-Ring
E24 Oil Flow Solenoid Valve
H53 Float Cover
887
887
H53
888
881
880
887
773 E24
D34 D34
133
11. PARTS LIST
13 Coolant Piping
854
836
Ref.
845 No. Description
D18
800 Pan
801 Coolant Pump
828 Coolant Orifice
829 Support, coolant reservoir
833 Coolant Strainer
837 835 Thermistor
836 Pressure Cap
848
837 Reservoir tank
845 845 Wire Clamp
846 Hose Nozzle
847 Transparent Hose
848 Coolant drain valve
847 854 Pressure Cap Assembly
860 Header, coolant pump
829 861 Gasket, strainer
999 DSP coolant
846 D17 Support, coolant pump
※999 D18 Seat, pressure cap
835
※ Does not come with the
833 product.
861
845
801
828
860
800
D17
14 Water Piping
Ref.
Description
Water-Cooled No.
017 008 Piping (1)
013 018 009 Piping (2)
011 Pet Cock
013 Piping (3)
017 Stop Valve, for a water flow control
018 Seat, cooling water piping
064 Water Drain Valve, precooler
009 859 Support, pressure switch
879 Pressure Differential Relay
D33 Support, water piping
008
D33
879
859
011
064
134
11. PARTS LIST
15 Blowoff Piping
[Fixed-speed compressor] Ref.
Description
No.
900 Blowoff Silencer
902
901 Seat, blowoff silencer
Air-Cooled Water-Cooled 902 Cover, blowoff silencer
900
901
135
11. PARTS LIST
15 Blowoff Piping
Ref.
No. Description
900 Blowoff Silencer
901 Seat, blowoff silencer
Air-Cooled 902 Cover, blowoff silencer
E21 Blowoff Solenoid Valve (1)
E22 Blowoff Solenoid Valve (2)
E23 Seat, blowoff solenoid valve
E80 Support, silencer cover
E23
E21
901
E80
E22
900
902
Water-Cooled
E23
E21
901
E22
E80
900
902
136
11. PARTS LIST
D28
H83
A92 896
D27 899
H84
D79 A92
844
D26
898
A92
A92
847
897
085
799 844
137
11. PARTS LIST
H84
H83
A92 E83
A92
D26
D79 A92
898
A92
138
11. PARTS LIST
A92 896
899
D27
H83
D79
844
D26
898
A92
A92
847
897
085
799 844
139
11. PARTS LIST
H83
A92
D26
A92
D79
898
A92
A92
140
11. PARTS LIST
17 Enclosure (1)
966
A36
J31
H59 914
915
A52
945 J30
970 A53
943
A71
D25 942
H97 910 [Fixed-speed D55
compressor]
A71
909
D14 909
A53 A33
H98
A52
141
11. PARTS LIST
17 Enclosure (1)
J31
914
Water-Cooled H59
915
D23 912
916 [Fixed-speed D59 911
966 compressor]
H60
J34
945
970
943
J33 A71
942
910
D25
909
H97
A71
A53
D14
A52
H98
J28
944 E47
904 924 929 939
905
Ref. Ref.
No. Description No. Description
904 Front Door (1) 970 Rear Frame (2)
905 Front Door (2) A52 Cover (1), discharge air pipe
909 Right Panel A53 Cover (2), discharge air pipe
910 Left Panel A71 Fork Slot Cover
911 Rear Panel (1) D14 Magnet
912 Rear Panel (2) D23 OMR cover (1)
914 Top Panel (1) D25 Chain
915 Top Panel (2) D59 OMR cover (2)
916 Cover, air intake filter E47 Rubber Bush
924 Cover, power cord H59 Left-Corner Cap
929 Rubber Bush H60 Right-Corner Cap
939 Rubber Bush H97 Name plate for model
942 Common Base H98 Name plate for NEXT
943 Front Frame (1) J28 Drain maintenance cover
944 Front Frame (2) J31 OMR cover
945 Front Frame (3) J33 Cover (1), Water Piping
966 Top Frame J34 Cover (2), Water Piping
142
11. PARTS LIST
16 Enclosure (2)
Ref.
No. Description
Air-Cooled Water-Cooled 917 Duct, air intake (1)
918 Cover, air intake
921 D22 921 Cover, air intake filter duct
932 922 Air Intake Filter
922 932 Wing Nut
933 933 Stud Bolt
949 948 Support, Control Panel
949 Duct, suction filer
D22 Cover (1), air intake duct
J35 Support, Duct (1)
J36 Support, Duct (2)
J37 Support, Duct (3)
J38 Support, Duct (4)
J39 Support, cover (1)
[Fixed-speed compressor] J40 Support, cover (2)
J41 Support, Control Panel
918
J35
J38
948
J41
J37
J40
J39
J36
917
143
11. PARTS LIST
D38
Details of A
D45
D46
D40
H18
OUT IN
H77
E62
D49
H17
D39
D48
D78
A
144
11. PARTS LIST
19 Dryer
Ref.
No. Description
A00 Air Dryer Assembly
A37 J32 A34 A01 Refrigerant Compressor
A02 Plate Type Heat Exchanger
A00 A03 Condenser
A02 A04 Fan
A05 Fan motor
A04 A06 High pressure switch
A07 Fan control switch
A05
A08 Discharge Switch Assembly
A15 A15 Refrigerant Pressure Gauge
A20 Hot Gas Bypass Valve
A34 Duct, dryer
A03
A37 Bracket, dryer
A45 Ball Valve
A47 Connecter, drain pipe
A48 Piping, Dryer Condensate Water (2)
A20
A50 Condensate Drain Trap Assembly
A06 A51 O-Ring, condensate drain trap
A07 A58 Panel, Dryer (1)
A08 A01 A59 Panel, Dryer (2)
A61 Support Plate, fan (1)
A62 Support Plate, fan (2)
A63 Support Plate, fan (3)
J32 Support Plate, cover
J75 Panel, Dryer (3)
A37 A47
A48
A45
A50
A51
A58
A62
A61 A63
A59
J75
145
12. WARRANTY AND AFTER-SALES SERVICE
12.1 Warranty
This Limited Warranty applies to products manufactured by Hitachi Industrial Equipment Systems Co., Ltd. (as
HIES hereinafter).
Warranty Period
The warranty period is 12 (twelve) calendar months after the date of the product delivery or 18 (eighteen)
calendar months after the date of the product shipping (as indicated by the bill of lading), whichever passes
earlier.
HIES shall not liable for any indirect or consequential damages caused by the failed product, including any lost
production or sales.
Contact your distributor to obtain warranty services if necessary.
● Model (TYPE)
● Serial Number (MFG. NO.) } Check the nameplate on the product
146
13. RELOCATION AND DISPOSAL
13.1 Relocation
To relocate the product, contact the local HITACHI distributor/master dealer or representative office. Note in
particular that you need to replace the parts to relocate the air compressor from a 50 Hz area to a 60 Hz area, and vice
versa. Otherwise, the air compressor cannot be operated at the relocation site. Operating the air compressor without
parts replacement may cause failure of the air compressor.
13.2 Disposal
To dispose of the air compressor after long use, be sure to drain lubricating oil. It is dangerous if lubricating oil leaks
to the outside for some reason from a disposed air compressor. Contact the local HITACHI distributor/master dealer
or representative office.
147
Date Motor Discharge Air Suction Oil Coolant Oil Coolant Load Loading Cooling Total Daily inspection item Remarks
148
temp. temp. temp. pressure pressure ratio count water operating
Time Control Auto
Voltage Current Temp. Pressure qty hour After- Coolant Parts replacement,
air pipe drain trap Oil level
Year V A ℃ MPa ℃ ℃ ℃ MPa MPa % ℓ h cooler level other notes
filter (dryer)
387 or 0.7 or Drain
Air-Cooled 0.7MPa
lower lower 0.11 - Drain discharge
Control criteria Within
330 or 0.4 or 0.18 discharge
(fixed-speed type) 0.4MPa - Within the
lower lower 40 or 62 or 62 or 0.13 - Drain
the coolant
387 or 0.7 or lower lower lower 0.27 discharge Drain gauge
Air-Cooled 0.7MPa 0.09 - 0.18 - level
lower lower discharge
Control criteria [0.05 - 0.16] gauge
330 or 0.3 or (※1)
(Vtype) 0.3MPa - -
lower lower
387 or 0.7 or Drain
Water-Cooled 0.7MPa
lower lower 0.11 - Drain discharge
Control criteria
330 or 0.4 or 0.18 discharge
(fixed-speed type) 0.4MPa - Within
lower lower 40 or 62 or Drain
- - the -
387 or 0.7 or lower lower discharge Drain gauge
Water-Cooled 0.7MPa 0.09 - 0.18 -
lower lower discharge
Control criteria [0.05 - 0.16]
330 or 0.3 or (※1)
(Vtype) 0.3MPa - -
lower lower
14. OPERATION RECORD LOGBOOK
Notes) 1. Total operating hour, loading count, current value, discharge pressure, oil pressure, Coolant pressure, discharge temp., oil temp., Coolant temp., and load rate are displayed on the LCD monitor.
2. The figures with the “※1” mark are the values for operating frequency of 45 Hz or higher and the figures (in the brackets) are the values for operating frequency below 45 Hz.
Date Motor Discharge Air Suction Oil Coolant Oil Coolant Load Loading Cooling Total Daily inspection item Remarks
temp. temp. temp. pressure pressure ratio count water operating
Time Control Auto
Voltage Current Temp. Pressure qty hour After- Coolant Parts replacement,
air pipe drain trap Oil level
Year V A ℃ MPa ℃ ℃ ℃ MPa MPa % ℓ h cooler level other notes
filter (dryer)
387 or 0.7 or Drain
Air-Cooled 0.7MPa
lower lower 0.11 - Drain discharge
Control criteria Within
330 or 0.4 or 0.18 discharge
(fixed-speed type) 0.4MPa - Within the
lower lower 40 or 62 or 62 or 0.13 - Drain
the coolant
387 or 0.7 or lower lower lower 0.27 discharge Drain gauge
Air-Cooled 0.7MPa 0.09 - 0.18 - level
lower lower discharge
Control criteria [0.05 - 0.16] gauge
330 or 0.3 or (※1)
(Vtype) 0.3MPa - -
lower lower
387 or 0.7 or Drain
Water-Cooled 0.7MPa
lower lower 0.11 - Drain discharge
Control criteria
330 or 0.4 or 0.18 discharge
(fixed-speed type) 0.4MPa - Within
lower lower 40 or 62 or Drain
- - the -
387 or 0.7 or lower lower discharge Drain
Water-Cooled 0.7MPa 0.09 - 0.18 - gauge
lower lower discharge
Control criteria [0.05 - 0.16]
330 or 0.3 or
(Vtype) 0.3MPa (※1) - -
lower lower
Notes) 1. Total operating hour, loading count, current value, discharge pressure, oil pressure, Coolant pressure, discharge temp., oil temp., Coolant temp., and load rate are displayed on the LCD monitor.
149
14. OPERATION RECORD LOGBOOK
2. The figures with the “※1” mark are the values for operating frequency of 45 Hz or higher and the figures (in the brackets) are the values for operating frequency below 45 Hz.
15. STANDARD SPECIFICATIONS
Air-Cooled
■ Standard Specifications
Model DSP-37A[R]5N DSP-55A[R]5N DSP-37VA[R]5N DSP-55VA[R]5N
Item DSP-37A[R]6N DSP-55A[R]6N DSP-37VA[R]6N DSP-55VA[R]6N
Discharge pressure MPa 0.7 0.4 0.7 0.4 0.7 0.3 0.7 0.3
Capacity @rated pressure 50/60Hz m3/min 5.0 5.9 6.4 8.0 5.0 6.7 6.4 8.5
Capacity @PQ WIDEMODE ON, 0.6MPa m3/min - - - - 5.5 - 7.0 -
Capacity @PQ WIDEMODE ON, 0.5MPa m3/min - - - - 6.0 - 7.6 -
Capacity @PQ WIDEMODE ON, 0.4MPa m3/min - - - - 6.4 - 8.2 -
PQ WIDEMODE range MPa - 0.4∼0.7 [0.5∼0.7] - 0.4∼0.7 [0.5∼0.7] -
Intake air Press./Temp. ℃ Atmospheric Pressure / 0 to 40 [5 to 40]
Compressor
150
15. STANDARD SPECIFICATIONS
Notes (1) Capacity is measured according to ISO 1217, Third Edition, Annex C.
(2) P.D.P is measured at 30 degree C of intake air temperature and rated discharge pressure.
P.D.P might be much worth at 0.4MPa or less of discharge pressure.
P.D.P might be 13 degree C at PQ WIDEMODE ON and 0.6MPa of discharge pressure.
(3) Capacity after built-in dryer is decreased due to the condensate by maximum 3% .
(4) Earth leakage circuit breaker is out of scope of supply from Hitachi.
(5) DSP series air compressors are not designed, intended or approved for breathing air applications.
(6) Pressures are indicated as the gauge pressure.
(7) Install the air compressor indoors and avoid flammable and corrosive environment, moisture and dust.
(8) Hitachi may make improvements and/or changes in the appearance and/or specifications described in this publication at anytime
without notice.
(9) The value in the [ ] is for built-in dryer type.
151
15. STANDARD SPECIFICATIONS
Water-Cooled
■ Standard Specifications
Model DSP-37W5N DSP-55W5N
DSP-37VWN DSP-55VWN
Item DSP-37W6N DSP-55W6N
Discharge pressure MPa 0.7 0.4 0.7 0.4 0.7 0.3 0.7 0.3
Capacity @rated pressure 50/60Hz
m3/min 5.0 5.9 6.4 8.0 5.0 6.7 6.4 8.5
Capacity @PQ WIDEMODE ON, 0.6MPa
m3/min - - - - 5.5 - 7.0 -
Capacity @PQ WIDEMODE ON, 0.5MPa
m3/min - - - - 6.0 - 7.6 -
Capacity @PQ WIDEMODE ON, 0.4MPa
m /min
3
- - - - 6.4 - 8.2 -
PQ WIDEMODE range MPa - 0.4∼0.7 - 0.4∼0.7 -
Intake air Press./Temp. ℃ Atmospheric Pressure / 0 to 40
Type of compressed gas - Air
Maximum shaft power kW 42.6 60.5 42.6 60.5
Compressor
152
15. STANDARD SPECIFICATIONS
Notes (1) Capacity is measured according to ISO 1217, Third Edition, Annex C.
(2) P.D.P is measured at 30 degree C of intake air temperature and rated discharge pressure.
P.D.P might be much worth at 0.4MPa or less of discharge pressure.
P.D.P might be 13 degree C at PQ WIDEMODE ON and 0.6MPa of discharge pressure.
(3) Earth leakage circuit breaker is out of scope of supply from Hitachi.
(4) DSP series air compressors are not designed, intended or approved for breathing air applications.
(5) Pressures are indicated as the gauge pressure.
(6) Install the air compressor indoors and avoid flammable and corrosive environment, moisture and dust.
(7) Hitachi may make improvements and/or changes in the appearance and/or specifications described in this publication at anytime
without notice.
153
Note the Air Compressor’s Specifications below for future reference.
Model DSP- kW Hz
DSA-599C 2015.7
Printed in Japan