XG3900W 200
XG3900W-200 XG3900W 200H
XG3900W-200H XG3900W-200GH
XG3900W 200GH
SPECIFICATIONS
CONTENTS
〔CONTENTS〕
CONTENTS …… 1
Product Specifications …… 2
Installation Conditions …… 5
Precautions for Piping …… 9
Electric Power Facilities …… 11
Cooling water system …… 14
Lubricating Oil …… 16
Warranty Conditions …… 17
Indemnity …… 17
〔Attached Drawing〕
( ) ITCS Controller
(1) …… 18
(2) External Dimensions …… 20
(3) Foundation Drawing …… 21
(4) System Diagram …… 22
(5) Wiring Diagram …… 24
Wiring for Automatic
(6) …… 25
Alternate Operation
WARNING
RESPIRATORY
RESPIRATORYDISORDER
DISORDER
PRODUCTS SPECIFICATIONS
◆ XG39000W-200
Types
XG3900W-200 XG3900W-200H XG3900W-200GH
Items
Frequency (Hz) 50
Power supply voltage (V) 380/415 3-phase 3-wire type
3
Air discharge volume (m /min) 39 36.6 35.3
Specified pressure (MPa) 0.7 0.8 1.0
Suction Pressure Atmospheric pressure (1 bar)
condition Temperature (℃(゚F)) 2~40(36~104)
Pressure (MPa) 07
0.7 08
0.8 10
1.0
Discharge
Max. discharge pressure (Mpa) 0.75 0.85 1.0
condition
Temperature (℃) Cooling water inlet temperature below +10℃
Output (kW) 200
Type 3-phase cage induction totally enclosed
Voltage (V) 380/415
in motor
Number of poles 4P
Main
Protection IP55
Cooling system Air cooling
Starter system Star-Delta
Insulation class F
Output (kW) 0.55
Fan motor
◆ XG4730W-250
Types
XG4730W-250 XG4730W-250H XG4730W-250GH
Items
Frequency (Hz) 50
Power supply voltage (V) 380/415 3-phase 3-wire type
3
Air discharge volume (m /min) 47.3 44.1 40.7
Specified pressure (MPa) 0.7 0.8 1.0
Suction Pressure Atmospheric pressure (1 bar)
condition Temperature (℃(゚F)) 2~40(36~104)
Pressure (MPa) 07
0.7 08
0.8 10
1.0
Discharge
Max. discharge pressure (Mpa) 0.75 0.85 1.0
condition
Temperature (℃(゚F)) Cooling water inlet temperature below +10℃
Output (kW) 250
Type 3-phase cage induction totally enclosed
Voltage (V) 380/415
in motor
Number of poles 4P
Main
Protection IP55
Cooling system Air cooling
Starter system Direct Starting
Insulation class F
Output (kW) 0.55
Fan motor
NOTES:
(1)Measurement method of Air discharge volume( volumetric flow ) based on GB/T3853(Is equivalent
ISO1217 Appendix C). Suction condition : 20℃ {68゜F} 1bar 0%RH
(2)The discharge pressure gauge indicates a package outlet pressure.
(3)Lubricating oil is filled in a compressor at the factory.
Be sure to use『KOBELCO GENUINE SCREW OIL』at the time of the exchange.
(4)The noise data is measured at a point of an anechoic room, which is 1.0 meter height from the floor and 1.5
meter length from all directions of the unit.
(5)The compressed air must not be used for respiratory equipment from which aspiration is directly made.
(6)As for the guaranteed values, consult with us separately.
(※1) When the water inlet/outlet of total head over 15m condition,it will take oversize velocity flow of cooling water.
then the heat exchange pipe maybe generate corrosion.When total head over 15m,please adjust supply valve
to less than 15m.
P4
■ Fan properties
FAN AND FAN MOTOR
Type
It
Items
XG3900W XG4730W
Frequency (Hz) 50
Voltage (V) 3-phase 380/415
Output (kW) 0.55
Input air 4750m3/h@60Pa
Fan blade diameter (mm) 550
■ In different cooling water temperature ,each models required cooling water flow.
Flow rate 15℃ 25℃ 35℃
Type L/min m³/h
m /h L/min m³/h
m /h L/min m³/h
m /h
XG3900W-200
209 12.5 244 14.6 280 16.8
XG3900W-200H
XG3900W-200GH
XG4730-250
278 16.7 314 18.8 350 21.0
XG4730-250H
XG4730-250GH
P5
Installation Conditions
■ INSTALLATION SPACE
○ Allow a space of 800mm for the left side, 1500mm for the right side, 1000mm for the front,
800mm for the back and 1000mm for the top against the body.
○ Secure an appropriate space for the normal operation around the air inlet on the right
and left side and exhaust outlet on the top the unit.
○ Enough front space is required to open/close the doors and maintain the compressor.
○ Install the machine on the horizontal
floor.
1000mm
80
0m
m
m
0m
80
mm
00 15
维护所需空间 10 00
mm
P6
EXHAUST
OPENING
■ INSTALLING A VENTILATING DUCT Install a
ventillating fan
○ Provide a fresh air inlet and an exhaust outlet
installed with a ventilating fan to use the
machine in a closed room.
○ Provide the size of the air intake so as not to
produce negative pressure in the room.
○ Select the ventilating fan bigger than the
Air supply
following table.
○ B
Be careful
f l because
b the
th exhaust
h t heat
h t is
i going
i tot circulate
i l t att the
th air
i intake
i t k ,
and the ambient temperature is higher if the ceiling is lower.
○ The machine is tripped at the room temperature of 40℃ (104゚F) or higher.
C
Compressor cooling
li air
i Mi i
Minimum ventilation
til ti capacity(※2)
it ( 2)
Items
Generated Allowable Entire ventilation Ventilatin
Exhaust Local Ventilating
calories pressure loss g
air volume ventilation duct & fan
in exhaust duct duct
(※1)
Model
(MJ/h) (kcal/h) (m3/min) Pa(mmH2O) (m3/min) [m3/min] (m3/min) (m3/min)
XG3900W-200 234 125 23 89
84 20,101
XG3900W 200H
XG3900W-200H or more or more or more or more
XG3900W-200GH
66 50 (5)
XG4730W-250 273 138 27 93
98 23,520
XG4730W-250H or more or more or more or more
XG4730W-250GH
*1: Local ventilation is a method to exhaust air by directly exhausting one third to a half
of compressor-exhausted air using a ventilating fan installed near the compressor exhaust outlet.
*2: Ventilation capacity indicates the value at the allowable room temperature of 5℃ {9゜F}
higher than the ambient temperature.
P7
CAUTION
■ Piping
・An unsupported long piping may cause for vibration and, as a result, the devices to
which such piping is connected may be damaged.
The piping must be properly supported (using hangers, fasteners, columns, etc.).
・When more than two units of compressors are installed and their discharge piping are
connected to the same discharge main piping, be sure to provide the stop valves before
the discharge main piping so that they can be closed when the operations of the
compressors are stopped.
・Slope the main piping in the discharge air flow direction so that condensate does not
gather in the middle of piping.
・Provide a drainage at the bottom part of pipe if there is concave or riser piping.
・To prevent condensate reverse flow connect a discharge piping at the top of the main
piping.
When connecting to the main
piping, connect the discharge
i i from
piping f th above.
the b
Work to be executed
by the customer. Main piping
Emergency valve
Discharge air
(If you increase
Remarks the compressor)
Main piping
Hanger
T
To preventt th
the reverse
flow such as drain.
Model Air tank capacity (m3) Model Air tank capacity (m3)
Note)This is the capacity of the case of load rate 50%, difference of upper and lower limit
pressure 0.1 MPa and a cycle time (load → unload → load) 30seconds.
PH
VR :Air tank capacity(m3)
t1 :Unload time(min)
t2 :Load time(min)
Remove the front cover and introduce the power cable through the opening on the left side,
then connect each cable correctly to the terminal panel in the starter box. For normal
operation, a suitable power source is required. Secure less than ±5 % of rated voltage
during operation. In order to suppress the imbalance of current, imbalance of the voltage
between phases as less than 2 % is required.
In order to suppress the imbalance of current, imbalance of the voltage between phases
as less than 2 % is required.
Recommended
Starting current
Maximum Inrush current breaker model
Model rated current (rms value) Reference
Star-Delta
MITSUBISHI
380V 415V 380V 415V 380V 415V 380V 415V
XG3900W-200 NV800-SEW-3P-
438A 401A 2012A 1740A 8030A 7352A
XG3900W-200H 700A
XG4730W-250 NV800-SEW-3P-
XG4730W-250H 526.4A 482A 2418A 2092A 9651A 8837A 800A
XG4730W-250GH
* To prevent unexpected functions during start-up, use earth leakage breakers with
current sensitivity of 200mA.
P12
XG4730W-250H
XG4730W-250GH
NOTE: 20 m or longer cables must have a sectional size more than those listed above.
Use a relay terminal so that the cable size on the local side will be as specified above.
XG3900W-200 XG4730W-250
450kV or more
XG3900W-200H XG4730W-250H 560kV or more
XG3900W-200GH 560kV or more XG4730W-250GH
5. Cable Connection
○
Connection the power cable to compressor in accordance with following drawing.
○
Case of 380V/415V
Open the starting panel cover and removed the
cotrol panel. Connertion the power cable
and control signal harness to the control panel's
terminal blocks(R/L1,S/L2,T/L3).
1
TB-3
TB-2 TYPE:
SP
2
CP
3
SER N O :
4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CP1
5
POWER:
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
OL1
88A NF
NPC
TR
31 32 33 34 35
THF
PE
TB-3
3
4
TB-2
5
6
CP TYPE:
7
CP1 KA
8
POWER:
11
12
13
CT2
14
15
16
T/L3
17
CT1
18
19
S/L2
20
21
22
MD MC
23
24
2
MS R/L1
25
TB-1
26
27
28
29
30
31
32
TB-1 PE 88A
33
NPC
34
NF SP
35
1 2 3 1
TR
36
37
R/L1 T/L3
S/L2 PE
38
39
V2 W2 U2 U1 V1 W1
40
THF
41
42
PE
1
PE
2
PE
(客先配線)
R/L1 S/L2 T/L3 E
(connected by customer)
(connected
(客先配線by )
P14
To keep the pressure difference of cooling water 's inlet/outlet port less than 1 bar.
The design pressure of cooling water system is 5 bar.Thus to keep the pressure of
water inlet less than 5 bar.
NOTES)
If the temperature condition is ( ),should to ensure the flow rate of ( ).
※ When the water inlet/outlet of total head over 15m condition,the heat exchange pipe maybe
generate corrosion.
This time,please adjust supply valve to lower pressure.
When choose water pump ,should to consider the loss pressure of pipeline.
CAUTION
When installation in winter ,should be install discharge valve at the water inlet and instal
l the draw off valve at the water outlet.It will be easier to drain the water in pipeline.
When compressor stopped,should to drain cooling water complete so as to prevent iced up .
P16
LUBRICATING OIL
Supply grease
Model
capacity (g)
XG3900W-200
45
XG3900W-200H
XG3900W-200GH
XG4730W 250
XG4730W-250
60
XG4730W-250H
XG4730W-250GH
○ Never mix different brands of grease. (Sold separately)
P17
WARRANTY CONDITIONS
1. WARRANTY CONDITIONS
The warranty period of this machine shall be 12 months from a date of completion of
the test run or 18 months from the date of shipment, whichever comes earlier.
Note) “After completion of the test run” shall mean
[At the time when the test run ( procedure and activities of receiving materials
test ) is completed after installation at site.]
2. CONTENTS OF WARRANTY
In case a trouble should occur during the warranty period and when it is determined
that the trouble is caused clearly by our defective design, manufacture and or
execution of work, we repair or replace the parts free of change without delay.
cases:
· Trouble caused by a repair or modification conducted by you without notifying us of the fact.
INDEMNITY
Under no circumstances shall, including any illegality, Kobe Steel, Ltd. be liable for
special, indirect, incidental, or consequential damages, including, but not limited to,
loss of production, loss of anticipated profits, loss of operational profits, loss of material
CY STOP
◎ Dryer failure
EMERGENC
◎ Discharge air temperature is high
After oil separator
◎ temperature is high ◎ Emergency stop
ON
CAUTIO
◎ Ambient temperature is high
① LCD SCREEN LIQUID CRYSTAL DISPLAY SCREEN ⑧ ARROW KEY 「↑」「↓」「→」「←」 ◎ Oil separator element clogged
Operation state(discharge pressure, discharge air temperature, 「↑」「↓」「→」and「←」 are movement of cursor, and also are used ◎ Motor coil temperature is high
ambient temperature, operation time, and load rate), condition to increase or decrease values of settings. ◎ Sensor error
setup( keep pressure, auto stop pressure, auto start pressure, ⑨ 「Enter」KEY ◎ Inverter alarm
PID setting·maintenance time and, contents and ・A setting value will be decided if the key "Enter" is pressed
management for machine error are displayed. ・If the "Enter" key is pressed by the specified item (item which ◎ Suction filter change
② Power LAMP(GREEN) cursor blinks), it jumps on the screen of the item. ◎ Oil filter change
It is shown that controller is in a turning-on-electricity state. ⑩ 「Reset」KEY ◎ Oil change
③ Load LAMP(GREEN) ・Change to "setting value change mode" to the item of the present ◎ Oil separator element change
MAINTENANCE
E
It is shown that compressor is under operation. cursor position. ◎ Cooler inspection
④ Auto Start LAMP(GREEN) ・Reset Emergency, Caution and a maintenance. ◎ Motor greasing
It is shown that it is in the state of operation standby. ⑪ 「Remote/Local」KEY ◎ Monitor battery change
⑤ Emergency LAMP(RED) It changes whether starting and a stop of compressor are performed ◎ Maintenance sensor change
It is shown in a compressor that Emergency occurred and stopped. Remote or Local. In a remote case, the orange lamp of "Remote"lights ◎ Pressure loss is high
⑥ Caution LAMP(ORANGE) up, and, in a local case, the green lamp of "Local" lights up. ◎ Lamp test
It is shown in a compressor that the Caution occurred. ⑫ 「Start」KEY
⑦ Maintenance LAMP(YELLOW) A compressor starts and the green lamp lights up.
It is shown in a compressor that the Maintenance occurred and it ⑬ 「Stop」KEY
needs maintenance. A compressor stops and the red lamp lights up. ISSUE
KOBELCO COMPRESSORS (SHANGHAI) CORPORATION DRAWING No. 4V51ZS1008P1 01
P19
ITCS CONTROLLER(XG)【The
( ) description of the loading
g function】
ITCS's main functions of indication are as follows.
◆Indication of compressor
compressor's
s operating condition ◆Emergency, Caution, and Maintenance Indications
The compressor's operating condition is indicated on In case of an emergency or caution, the screen shows
what happens and how to deal with it, in addition to its causes.
tthe screen,
e sc ee , including
c ud g running
u gppressure,
essu e, te
temperature,
pe atu e,
Maintenance indication comes out on the screen
current, loading condition, running hour,
automatically when maintenance is required and also shows
running count, load hour and load count. when the next maintenance time comes by indicating the
elapsed time
time.
◆Graph Indication
AUTO ○ - - ○
Pow
er c
abl
e in
let
Controller
Air inlet
et
No 10kV inl
specification
cable
er t
inle
Pow cable Oil cooler oil exit
er
Pow After Cooler
drain exit Oil separator oil exit
Base hole
Oil supply
A ir feed
Compressor
Pl f
Planform
Maintenance space Unit mm
ISSUE
FOUNDATION DRAWING
(XG3900W,4730W)
NOTE:
1 F
1、Foundation
d i should
h ld to furished
f i h d with
i h steell rods.
d
2、Foundation required to be strong the weight.
3、Horizontal level should be ±1/100.
Unit
MARK NAME
PD1 SUCTION PRESSURE DIFFERENCE SWITC H
P1 PRESSURE SENSOR (INSIDE OIL SEPARATOR )
P2 PRESSURE SENSOR (AFTER OIL SEPARATOR )
P3 PRESSURE SENSOR (AIR FEED PRESSURE )
Ai fifter
Air fif
T1 TEMPERATURE SENSOR (ENVIRONMENT TEMPERATURE )
T2 THERMOCOUPLE(MAIN MOTOR COIL TEMPERATURE )
T3 TEMPERATURE SENSOR (INSIDE OIL SEPARATOR )
T5 TEMPERATURE SENSOR (AFTER OIL SEPARATOR )
FS1 WATER FLOW SWITC H
Suction regulating valve OL1 MAIN MOTOR OVERCURRENT RELA Y
Cooling air
Spherical valve
Flange connection
Lathedog connection
P
Pressure l ti valve
regulating l
Safety valve
Compressor
Flex master
After cooler
Air inlet
Oil cooler
ISSUE
Pressure sensor
(Air discharge pressure)
Surrounding temperature sensor
Pressure sensor
SUCTION FIFTER PRESSURE DIFFERENCE SWITCH (After oil separator ) Temperature sensor (Main motor coil)
WATER FLOW
RATA SWITCH
LOAD/UNLOAD
SOLENOID VALVE
PW Y1A Y1B Y2
C t ll
Controller
25
CUSTOMER’S WIRING
ISSUE
KOBELCO COMPRESSORS (SHANGHAI) CORPORATION DRAWING No. 4V51ZS1062P1 02
P24
CONTROLLER
PT1 PT 2 PT 3 PT4 PT 5 TE1 TE2 TE 3 TE4 TE 5 TE 6
P1-
P2-
P3-
P4-
P5-
T1-
T2-
T4-
P1+
P2+
P3+
P4+
P5+
T1+
T2+
T3+
T3-
T4+
T5+
T5-
380・
USER
415V/220V
50Hz
Load/unload Electromagnetic
Loa
・ Emergency stop (Terminal
stop (Terminal Y0 - COM6 → Closed
Closed:Emergency
Emergency stop)
・ Caution (Terminal Y1 - COM6 → Closed:Caution) COMPRESSOR
ctromagnetic valve
・ Maintenance (Terminal Y2 - COM6 → Closed:Maintenance)
・ Remote (Terminal Y3 - COM6 → Closed:Remote)
・ Running (Terminal Y4 - COM6 → Closed:Running)
(1)Input signals to the compressor should be no-voltage contact
input.Electric current of DC24V is supplied between the
COM2-XA, X8, X9 terminals from the controller side.
Voltage could damage the controller.
(2)The rated load to use the output signals from the compressor should be (4)The terminal X9-COM2 has been short-circuited at the factory.
(5)If the panel lamp of the controller is blinking (100 consecut
AC250V 2A or DC 30V 2A at maximum. Remove this terminal in the remote control mode. hours have passed since the Maintenance LED came
(3)Th tterminal
(3)The i l COM2,
COM2 COM6
COM6, XA
XA-X9
X9 andd Y0-Y4
Y0 Y4 for
f remoteness
t is
i preparedd Remote
R t (input
(i t signal
i l to
t controller)
t ll ) should
h ld be
b input
i t by with
t the
hith
b one shot th lamp,
l but
b t continue
ti to
t be
b sent.
t
in the starting panel terminal block TB2. at 500 ms or more.
When you connect with the terminal block TB2, attach a surge killer shorter pulse signals may not be recognized.
*Any modification without prior permission of KOBE STEEL may
and set the line noise at less than 800V.
invalidate the warranty even within the warranty period.
ISSUE
Wiring, setup and starting of a compressor are as follows. PRESSURE SWITCH LOC PRESSURE SWITCH LOC
1.Wiring of a compresso(The terminals within the starting boards of two compressor are wired mutually as follows.) UNLOADING PRESSURE 0.68 MPa UNLOADING PRESSURE 0.68 MPa
X8 Y3 AUTO START PRESSURE 0.60 MPa AUTO START PRESSURE 0.60 MPa
COM6 COM2 Setup 3 GROUP CONTROL YES Setup 3 GROUP CONTROL YES
The above serves as signals only for automatic alternate operation, and it differs from the usual. START SELECT MASTER START SELECT MASTER
SLAVE DIFF PRESSURE 0.03 Mpa SLAVE DIFF PRESSURE 0.03 Mpa
3. STARTING OF A COMPRESSOR
3 LOAD / UNLOAD ● LOADING PRESSURE -------
+ SLAVE DIFF
Automatic alternate operation starts by pushing the "Start" button of one of compressors. SLAVE DIFF PRESSURE ↑ PRESSURE
COM6
CCOM2
CCOM2
XG XG
COM2
COM2
COM6
COM6
Y3
Y3
XG XG
Y4
Y4
XA
XA
X8
X8
Terminal Panel D
Model Terminal Panel Manufacture ◇ XG performs unloading by the pressure of the sum of UNLOADING PRESSURE and DIFF.
Y4
Y4
Y3
Y3
XA
XA
X8
X8
XG D KOBE STEEL LTD Please set the pressure sum of UNLOADING PRESSURE and SLAVE DIFF
PRESSURE
lower than the highest discharge pressure.
*There
There is no function which changes MASTER by a timer
timer. ISSUE
KOBELCO COMPRESSORS MANUFACTURING (SHANGHAI) CORPORATION DRAWING No. 4V51ZS1024P1 01
P26
WIRING FOR AUTOMATIC OPERATION
By wiring for XG and VS, XG will serve as a backup machine of VS.If pressure becomes lower than AUTO (XG+VS)
(XG VS)
START PRESSURE in the state where VS is operating
operating, it will start automatically
automatically. And if pressure becomes higher ・THE SETTING POINTS
than UNLOADING PRESSURE, it will stop. <The example of a setting>
When XG unloads once, the unloading drive is continued until the LOADING CONDITION of VS becomes 90%
or more, and the DISCHARGE PRESSURE becomes below the AUTO START PRESSURE besides. VS XG
Setup 1 KEEP PRESSURE 0.65 MPa Setup 1 OPERATION MODE AUTO
Wiring, setup and starting of a compressor are as follows. AUTO STOP PRESSURE 0.70 MPa PRESSURE SWITCH LOC
1.Wiring of a compressor AUTO START PRESSURE 0.60 MPa UNLOADING PRESSURE 0.68 MPa
The terminals within the starting boards of two compressor are wired mutually as follows. LOADING PRESSURE 0.64 MPa
COM2 COM6 Setup 3 GROUP CONTROL YES Setup 3 GROUP CONTROL YES
2.SETTING OF A COMPRESSOR SLAVE DIFF PRESSURE 0.02 Mpa SLAVE DIFF PRESSURE 0.00 MPa
XG compressor is made the following setup. INITIAL CHARGE 5 min. INITIAL CHARGE 5 min.
(1)In the screen of COMPRESSOR SETTING 3, while setting of [GROUP CONTROL] as [YES],
an ititem off [START SELECT] also
l sets
t as [SLAVE]
[SLAVE].。 ◇ Withi
Within iinitial
iti l charging
h i time,
ti SLAVE may nott carry outt continuation
ti ti starting
t ti after
ft
(2)By key of Remote/local, set in Local mode. However, it does not start in the Remote mode. an automatic operation start.
(Please check that the lamp of Local is on.) ◇ Please set SLAVE DIFF PRESSURE setting to 0.00MPa when you connect XG with the VS.
(3) Please set SLAVE DIFF PRESSURE setting to 0.00MPa.
(4) Please set to become a relation between the following.
The relation between KEEP PRESSURE of VS and LOADING PRESSURE of XG
and UNLOADING PRESSURE of XG: ----------------- ● AUTO STOP PRESSURE
LOADING PRESSURE (XG) < KEEP PRESSURE (VS) < UNLOADING PRESSURE (XG)
------------------------------- ● UNLOADING
O G PRESSURE
SS -----------
3.STARTING OF A COMPRESSOR
Automatic operation starts by pushing the "Start" button of VS.
Starting standby is carried out when initial charging or pressure is higher than START PRESSURE. ----------------- ● KEEP PRESSURE LOAD / UNLOAD
「The
The wiring for automatic operation」
----------- ● AUTO START PRESSURE ---- ● AUTO START PRESSURE -----------
M3 SCREW M3 SCREW M3 SCREW
XA
X8
Y4
Y3
X8
XA
Y3
Y4
XG VS
Y4
M2 XA
Y3
X8
Y4
X8
XA
Y3
COM2
M6
COM6
M6
COM6
Model Manufacture
※When the unloading continues for 3 minutes with XG starts,and the inting proof timer passed,
Terminal Panel
COM2
COM6