SECTION - A

PLAN AT BEAM TOP LEVEL

TYPICAL LONGITUDINAL SECTION


PLAN

TYPICAL CROSS SECTION AT OPNING TYPICAL CROSS SECTION

6. LAP REINFORCEMENT BARS SHALL BE AVOIDED AS FAR AS POSSIBLE.


LAPS MAY BE PROVIDED, IF UNAVOIDABLE. HOWEVER IN SUCH CASES
A) BASIC LENGTH AS PER CLAUSE 15.2.4 OF IRC: 112-2011, FOR Fe 500
REINFORCEMENT AND CONCRETE OF M40 DESIGN MIX
2
1 1
DIA OF BAR (MM) LAP LENGTH (MM)
8 280
10 340
12 410
16 550
20 680

* FOR UNFAVORABLE BOND CONDITIONS THE ABOVE VALUES MUST BE


2 MULTIPLIED BY 1.43
TYP. CONSTRUCTION JOINT
B) FOR INCREASE IN PERCENTAGE OF LAPPED BARS RELATIVE TO TOTAL
CROSS SECTIONAL AREA OF THE ABOVE VALUES SHOULD BE FURTHER
TYPICAL SIDE WALL ANCHORING DETAILS SECTION 1-1 TYPICAL TOP SLAB ANCHORING DETAILS OF MULTIPLIED BY COEFFICIENT MENTIONED BELOW.
OF 150 x 10 MS FLAT 150 x 10 MS FLAT PERCENTAGE OF LAPPED BARS
RELATIVE TO TOTAL CROSS <25% 33% 50%
SECTIONAL AREAS

COEFFICIENT 1 1.15 1.4

C) NOT MORE THAN 50% OF REINFORCING BARS SHALL BE LAPPED AT


ANY SECTION
7. SOFT AND LOOSE PATCHES IN THE BEARING AREA ARE TO BE REPLACED
BY COMPACTED GRANULAR FILLS WITH LAYERS NOT EXCEEDING 500.
NOTES :
8. BACK FILLING BEHIND WALLS SHALL BE DONE SIMULTANEOUSLY ON EITHER
1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN METERS, SIDE OF THE STRUCTURE WITH HEIGHT DIFFERENCE NOT MORE THAN 1.0 m.
UNLESS OTHERWISE SPECIFIED.
9. ANY DISCREPANCY NOTED SHOULD BE REPORTED TO THE DESIGN
2. DIMENSIONS ARE NOT TO BE SCALED. ONLY WRITTEN DIMENSIONS ENGINEER IMMEDIATELY.
SHALL BE FOLLOWED. 10. CLEAR COVERS: FOR EARTHFACE REINFORCEMENT - 45 mm
3. GRADE OF CONCRETE SHALL BE AS FOLLOWS:- FOR NON EARTHFACE REINFORCEMENT- 45 mm
LEVELLING COURSE ------------------ M15 11. THE INSERT PLATES SHOULD BE FLUSHED WITH RCC WALL.
RCC DUCT ------------------ M40 12. ALL ANCHORING BARS OF INSERT PLATES SHOULD BE TIED TO INNER
SECTION 2-2
DISTRIBUTION.
ETAILS OF 4. REINFORCEMENT SHALL BE HYSD BARS OF GRADE DESIGNATION Fe500
TYPICAL DETAILS OF GRATING @DRAIN TOP CONFORMING TO IS: 1786. 13. DESIGN CRITERIA HAS BEEN FROM THE FOLLOWING CODES
A) IRC 6 - 2016 B) IS 3370 - 2009 C) IS 456.
5. THE PROPERTIES OF THE MATERIALS USED FOR BACKFILLING BEHIND
SIDE WALL SHALL CONFIRM TO THE FOLLOWING, Ø>=30° & Ƴsat=20 kN/m3 14. SBC SHOULD BE ENSURED BEFORE THE CONSTRUCTION.

CLIENT PROOF CONSULTANT Contract No. 14/CE/2017-18, Dt:24.11.2017 TITLE:


Andhra Pradesh Tender No. 14/CE/ADC/ENGG/2017-18, ELECTRICAL RCC POWER DUCT AIR INTAKE OF SIZES REV. R0
Dt:05.09.2017 (1.5x2.5), (2.5x2.8), (3.4x3.15), (4.28x3.15), (4.28x4.0) &
AMARAVATI DEVELOPMENT (4.28x4.4) NUMERATION & REINFORCEMENT DETAILS OF
CORPORATION LIMITED EPC CONTRACTOR & DESIGN CONSULTANT 33 & 220 KV FOR E7, E9, E11, N3A & N3B ROADS IN PKG-XII SIZE: A1

PROJECT SENIOR INFRA ENGINEER HOD / IPD CE / ADCL DRAWING NO


R0 07.03.18 FOR APPROVAL RVR RST RVR ISK Investigation, Detail Design and Construction of smart trunk infrastructure with Roads,
Storm Water Drains, Water Supply Network, Sewerage Network, Utility ducts for
M/S MEGHA ENGINEERING & M E I L - A D C - XII - S T - D W G - 7 9 5 0 - 0 0 1
REV DATE REVISION DESCRIPTION DSGD DRWN CHKD APPD Power & ICT, Reuse water line, Pedestrian tracks, Cycle tracks, Avenue Plantation & Street INFRASTRUCTURES LIMITED
Furniture etc. in E7, E9, E11 , N3A & N3B Roads in Amaravati Capatial City, Andhra Pradesh S-2 TECHNOCRAT INDUSTRIAL ESTATE,
RELEASED FOR Preliminary/Information Approval Construction As Built on EPC Basis. (Package - XII) BALANAGAR, HYDERABAD-500 037 SCALE: AS SHOWN
4NO'S OF 4NO'S OF NOTES :
Y12 BARS Y12 BARS
1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN METERS,
Y8@150 c/c Y8@150 c/c
STRPS. STRPS. UNLESS OTHERWISE SPECIFIED.
BEAM
2. DIMENSIONS ARE NOT TO BE SCALED. ONLY WRITTEN DIMENSIONS
SHALL BE FOLLOWED.
TYPICAL BEAM TYPICAL COLUMN 3. GRADE OF CONCRETE SHALL BE AS FOLLOWS:-
CROSS SECTION R/F CROSS SECTION R/F LEVELLING COURSE ------------------ M15
SCHEDULE OF REINFORCEMENT RCC DUCT ------------------ M40

SW6 SW6 4. REINFORCEMENT SHALL BE HYSD BARS OF GRADE DESIGNATION Fe500


Bar Mkd. Shape of bar
Bar Mkd. Shape of bar CONFORMING TO IS: 1786.
SW6' SW6'

TS1 TS2 5. THE PROPERTIES OF THE MATERIALS USED FOR BACKFILLING BEHIND
SW5' SW5'
SIDE WALL SHALL CONFIRM TO THE FOLLOWING, Ø>=30° &Ƴsat=20 kN/m
SW5 SW5
TS4
TS1a
6. LAP REINFORCEMENT BARS SHALL BE AVOIDED AS FAR AS POSSIBLE.
TS2
SW2 TS2 TS2 SW2 SW2 SW1 TS1 SW1 SW2 LAPS MAY BE PROVIDED, IF UNAVOIDABLE. HOWEVER IN SUCH CASES
SW3
TS3a TS3 TS3
TS3a
TS3 A) BASIC LENGTH AS PER CLAUSE 15.2.4 OF IRC: 112-2011, FOR Fe 500
SW4
REINFORCEMENT AND CONCRETE OF M40 DESIGN MIX

SW1 + TS1a
SW1 + TS1a

TS4 TS6 TS3 + TS6 TS4

SW1 + TS1
SW1 + TS1
TS3a
SW5' DIA OF BAR (MM) LAP LENGTH (MM)
8 280
TS6
10 340
TS1a TS1a TS1 TS1 SW6'
12 410
SW1 16 550
SW1 BS2
20 680
SW1
BS3 * FOR UNFAVORABLE BOND CONDITIONS THE ABOVE VALUES MUST BE
SW4 MULTIPLIED BY 1.43
SW2
SW2 SW2 SW4 SW2 SW2 SW4 B) FOR INCREASE IN PERCENTAGE OF LAPPED BARS RELATIVE TO TOTAL
SW1
SW1 BS3'
SW4 CROSS SECTIONAL AREA OF THE ABOVE VALUES SHOULD BE FURTHER
SW3 SW3 SW3 SW3
BS3 BS3 BS3 BS3 MULTIPLIED BY COEFFICIENT MENTIONED BELOW.
SW5
BS4
BS1 BS1 BS1 BS1
PERCENTAGE OF LAPPED BARS
BS6 BS1 + BS6 BS6 BS6 BS1 + BS6 BS6 SW6 RELATIVE TO TOTAL CROSS <25% 33% 50%
BS2 BS2
SW1 + BS3

SECTIONAL AREAS

SW1 + BS3
SW1 + BS3

SW1 + BS3
EBS1 (BS1 + BS6) EBS1 (BS1 + BS6)

BS1 COEFFICIENT 1 1.15 1.4


SW2 SW1 SW1 SW2
BS3 SW2 SW1 SW1 SW2
BS3
BS3'
BS3'
C) NOT MORE THAN 50% OF REINFORCING BARS SHALL BE LAPPED AT
BS4 EBS1
BS4 ANY SECTION.
BS6 7. SOFT AND LOOSE PATCHES IN THE BEARING AREA ARE TO BE REPLACED
TYPICAL R/F CROSS SECTION AT OPNING TYPICAL R/F CROSS SECTION BY COMPACTED GRANULAR FILLS WITH LAYERS NOT EXCEEDING 500.

8. BACK FILLING BEHIND WALLS SHALL BE DONE SIMULTANEOUSLY ON EITHER


SIDE OF THE STRUCTURE WITH HEIGHT DIFFERENCE NOT MORE THAN 1.0 m.

9. ANY DISCREPANCY NOTED SHOULD BE REPORTED TO THE DESIGN


ENGINEER IMMEDIATELY.

10. CLEAR COVERS: FOR EARTHFACE REINFORCEMENT - 45 mm


FOR NON EARTHFACE REINFORCEMENT- 45 mm

11. THE INSERT PLATES SHOULD BE FLUSHED WITH RCC WALL.


12. ALL ANCHORING BARS OF INSERT PLATES SHOULD BE TIED TO INNER
DISTRIBUTION.
13. DESIGN CRITERIA HAS BEEN FROM THE FOLLOWING CODES
A) IRC 6 - 2016 B) IS 3370 - 2009 C) IS 456.
14. SBC SHOULD BE ENSURED BEFORE THE CONSTRUCTION.

CLIENT PROOF CONSULTANT Contract No. 14/CE/2017-18, Dt:24.11.2017 TITLE:


Andhra Pradesh Tender No. 14/CE/ADC/ENGG/2017-18, ELECTRICAL RCC POWER DUCT AIR INTAKE OF SIZES REV. R0
Dt:05.09.2017 (1.5x2.5), (2.5x2.8), (3.4x3.15), (4.28x3.15), (4.28x4.0) &
AMARAVATI DEVELOPMENT (4.28x4.4) NUMERATION & REINFORCEMENT DETAILS OF
CORPORATION LIMITED EPC CONTRACTOR & DESIGN CONSULTANT 33 & 220 KV FOR E7, E9, E11, N3A & N3B ROADS IN PKG-XII SIZE: A1

PROJECT SENIOR INFRA ENGINEER HOD / IPD CE / ADCL DRAWING NO


R0 07.03.18 FOR APPROVAL RVR RST RVR ISK Investigation, Detail Design and Construction of smart trunk infrastructure with Roads,
Storm Water Drains, Water Supply Network, Sewerage Network, Utility ducts for
M/S MEGHA ENGINEERING & M E I L - A D C - XII - S T - D W G - 7 9 5 0 - 0 0 2
REV DATE REVISION DESCRIPTION DSGD DRWN CHKD APPD Power & ICT, Reuse water line, Pedestrian tracks, Cycle tracks, Avenue Plantation & Street INFRASTRUCTURES LIMITED
Furniture etc. in E7, E9, E11 , N3A & N3B Roads in Amaravati Capatial City, Andhra Pradesh S-2 TECHNOCRAT INDUSTRIAL ESTATE,
RELEASED FOR Preliminary/Information Approval Construction As Built on EPC Basis. (Package - XII) BALANAGAR, HYDERABAD-500 037 SCALE: AS SHOWN