CLIENT

ELECTRICAL SPECIFICATIONS GENERAL ELECTRICAL NOTES POWER ABBREVIATIONS


- A -
SPECIAL PURPOSE OUTLET MOUNTED IN FLUSH WALL BOX.
PART I - GENERAL 1. ALL SYMBOLS ARE NOT NECESSARILY USED IN THIS PROJECT.
A
LETTER INDICATES TYPE.
A
AFF
AMPERE
ABOVE FINISHED FLOOR
2. IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO ESTABLISH A STANDARD OF QUALITY. THE A - NEMA TYPE 14-20R (125/250V, 3 POLE, AF ARC FAULT,
A. CONDITIONS D. PANEL BOARDS
ENGINEER RESERVES THE RIGHT TO ALLOW OTHER METHODS AND MATERIALS NOT REFLECTED HEREIN. THE 4 WIRE, GROUNDING, 20 AMP) AMP FUSE
1. FURNISH AND INSTALL A COMPLETELY WIRED AND OPERATIONAL ELECTRICAL SYSTEM 1. CIRCUIT BREAKER TYPE AS INDICATED ON DRAWINGS. UNLESS INDICATED OTHERWISE, ALL PANELS CONTRACTOR SHALL BE RESPONSIBLE TO REQUEST THE ENGINEER WAIVE THE STANDARDS TO ALLOW ALTERNATE B - NEMA TYPE 6-20R (250V, 2 POLE, 3 WIRE, AFG ABOVE FINISHED GRADE
AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN, INCLUDING BUT NOT LIMITED SHALL HAVE PANEL BOARD TYPE CONSTRUCTION WITH BOLT-ON CIRCUIT BREAKERS MEANS AND METHODS PRIOR TO BEGINNING THE PROJECT. CONTRACT DOCUMENT REVISIONS TO ACCOMMODATE GROUNDING, 20 AMP) AIC AMPERE INTERRUPTING CAPACITY AL ALUMINUM
TO, THESE MAJOR ITEMS. FOR 3∅ PANELS. MANUFACTURERS SHALL BE GENERAL ELECTRIC, SQUARE INSTALLED CONDITIONS, WITHOUT PRIOR APPROVAL, WILL RESULT IN ADDITIONAL DESIGN CHARGES TO THE C - NEMA TYPE 6-30R (250V, 2 POLE, 3 WIRE, ARCH'L ARCHITECTURAL AS AMP SWITCH
A. ELECTRICAL PANELS, SERVICE, CONDUIT, WIRING, ETC., FOR ALL OUTLETS AND D, SIEMENS, CUTLER-HAMMER OR EQUAL WITH VOLTAGE, SIZES, AND RATINGS AS INDICATED ON CONTRACTOR. GROUNDING, 30 AMP) AWG AMERICAN WIRE GAUGE
EQUIPMENT. DRAWINGS. D - NEMA TYPE 14-50R (125/250V, 3 POLE,
- B -
B. TELEPHONE OUTLETS AND CONDUIT AS INDICATED. 3. ELECTRICAL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN ACCORDANCE WITH THE NECA 4 WIRE, GROUNDING, 50 AMP) BC BARE COPPER
2. THE CIRCUIT BREAKERS SHALL BE OPERABLE IN ANY POSITION AND BE REMOVABLE FROM THE INSTALLATION STANDARDS TO THE SATISFACTION OF THE ARCHITECT, ENGINEER AND LGBO. E - NEMA TYPE 5-30R (125V, 2 POLE, 3 WIRE,
B. RELATED WORK BY OTHERS BLDG BUILDING BLDG
FRONT OF THE PANEL BOARD WITHOUT DISTURBING THE ADJACENT UNITS. BRANCH BREAKERS GROUNDING, 30 AMP) - C -
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, TRENCH, AND BACKFILL FOR SHALL BE OF SUCH DESIGN THAT COMBINATION OF SINGLE-POLE, DOUBLE-POLE, AND THREE-POLE 4. ALL WORK, MATERIALS AND EQUIPMENT SHALL CONFORM TO THE CURRENTLY ACCEPTED EDITION OF ALL F - NEMA TYPE 15-30R (250V, 3 PHASE, 3 POLE C CONDUIT
ELECTRICAL SERVICE ENTRANCE FROM THE MAIN SERVICE TO UTILITY POINT OF BREAKERS CAN BE ASSEMBLED ON THE SAME PANEL. EACH BRANCH CIRCUIT SHALL BE CLEARLY APPLICABLE NATIONAL, STATE AND CITY CODES AND ORDINANCES. 4 WIRE, GROUNDING, 30 AMP) CAB CABINET
ELECTRICAL SERVICE. ELECTRICAL CONTRACTOR SHALL COORDINATE THE NUMBERED. BRANCH AND MAIN TERMINALS SHALL BE OF THE SOLDERLESS TYPE. HANDLE TIES TO G - NEMA TYPE 15-60R (250V, 3 PHASE, 3 POLE, CAT CATALOG/CATEGORY
INSTALLATION OF THE ELECTRICAL SERVICE ENTRANCE WITH SERVING UTILITY FORM MULTI-POLE BREAKERS NOT ACCEPTABLE. 5. ALL ELECTRICAL SYSTEM COMPONENTS SHALL BE LISTED OR LABELED BY UL OR OTHER RECOGNIZED TESTING 4 WIRE, GROUNDING, 60 AMP) C/B CIRCUIT BREAKER
COMPANY. FACILITY AS ALLOWED BY AUTHORITY HAVING JURISDICTION. H - NEMA TYPE L5-20R (125 V, 1 PHASE, 2 POLE, CKT CIRCUIT
C. CODES, REGULATIONS, AND STANDARDS 3. WIRE TERMINATION FOR PANEL BOARDS AND CIRCUIT BREAKERS SHALL BE LISTED AS SUITABLE FOR 3 WIRE, GROUNDING, 20 AMP, TWIST LOCK) CLG CEILING

1. THE INSTALLATION SHALL COMPLY WITH APPLICABLE LOCAL AND STATE CODES AND
75 DEGREES C. 6. WHERE AN APPARENT DISCREPANCY EXISTS BETWEEN THE REQUIREMENTS OF THE GENERAL NOTES AND
INFORMATION PORTRAYED IN THE ELECTRICAL DRAWINGS, THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST
K - NEMA TYPE 15-60R (250 V, 3 PHASE, 3 POLE, CO
CC
CONDUIT ONLY
COMM COMMUNICATION
7822 WALKER STREET
4 WIRE, GROUNDING, 60 AMP)
ORDINANCES, WITH THE REGULATIONS OF THE CURRENTLY ACCEPTED EDITION OF THE 4. PROVIDE A TYPEWRITTEN CIRCUIT INDEX BEHIND CLEAR PLASTIC COVER ON INSIDE OF DOOR. OF THE GREATER QUALITY OR QUANTITY. M - NEMA TYPE 10-20R (125/250 VOLT, 1 PHASE,
CU COPPER LA PALMA, CA 90623
CALIFORNIA ELECTRIC CODE AND WITH THE REQUIREMENTS OF THE POWER, INFORMATION SHALL INCLUDE ROOM AND TYPE LOAD SERVED. ALL CIRCUIT BREAKERS SHALL BE - D -
3 POLE, 3 WIRE, UNGROUNDED, 20 AMP) DEMO DEMOLITION/DEMOLISH
TELEPHONE, AND CATV COMPANIES FURNISHING SERVICES TO THIS INSTALLATION. IDENTIFIED, INCLUDING SPARES. INDEX CARD FRAME SHALL BE METAL, SECURED TO DOOR. 7. CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID AND VERIFY EXISTING CONDITIONS. CONTRACTOR SHALL N - NEMA TYPE L6-20R (250 VOLT, 1 PHASE, 2 DISC. DISCONNECT PROJECT NAME
INCLUDE IN BASE BID ALL COSTS REQUIRED FOR PERMITS AND INSPECTIONS.
POLE, 3 WIRE, GROUNDING, 20 AMP TWIST LOCK) DN DOWN
2. THE FOLLOWING INDUSTRY STANDARDS, SPECIFICATIONS, AND CODES ARE MINIMUM 5. WHERE PANEL BOARDS ARE INSTALLED FLUSH WITH THE WALLS, EXTEND EMPTY CONDUITS FORM
REQUIREMENTS: THE PANEL BOARD TO AN ACCESSIBLE SPACE ABOVE OR BELOW. PROVIDE 3/4" (MINIMUM SIZE)
CONDUIT FOR EVERY THREE SINGLE SPARE CIRCUIT BREAKERS OR SPACE OR EQUIVALENT
8. CONTRACTOR SHALL VERIFY, WITH OWNER'S REPRESENTATIVE PRIOR TO SUBMITTING BID, ALLOWABLE WORKING
HOURS, EMPLOYEE PARKING AREAS, MATERIAL DELIVERY, STORAGE REQUIREMENTS, DEMOLITION AND REMOVAL
P - NEMA TYPE 5-20R (120 VOLT, 1 PHASE, 2
POLE, 3 WIRE, GROUNDING, SINGLE, 20 AMP)
DWG DRAWING
- E - CITY HALL
EA EACH
A. THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION STANDARDS. MULTI-POLE ARRANGEMENT, OR FRACTION THEREOF, BUT NOT LESS THAN TWO CONDUITS FOR EACH OF CONSTRUCTION DEBRIS, AS WELL AS DAILY CLEAN UP REQUIREMENTS. INCLUDE ALL COSTS IN BID FOR DUST SINGLE GROUNDING TYPE RECEPTACLE 20AMP, 125VOLT, 2POLE,
B.
C.
THE CALIFORNIA ELECTRICAL CODE, INCLUDING LOCAL AMENDMENTS.
UNDERWRITER LABORATORIES INCORPORATED STANDARDS.
PANEL. BARRIERS, DUMPSTER'S ETC. AS REQUIRED FOR THE DURATION OF THE PROJECT. PERFORM ALL WORK AS
DIRECTED BY OWNER'S REPRESENTATIVE AND ARCHITECT.
3WIRE.
SINGLE GROUNDING TYPE RECEPTACLE 20AMP, 125VOLT, 2POLE, 3WIRE, CONNECTED
ELEC.
ELEV
ELECTRICAL
ELEVATOR HVAC REPLACEMENT
TO EMERGENCY CIRCUIT. EM EMERGENCY
D. AMERICAN NATIONAL STANDARDS INSTITUTE. 6. PANEL BOARDS TO BE PROVIDED WITH COPPER BUSSING ONLY. EMT ELECTRICAL METALLIC TUBING

D. INSPECTION OF SITE 7. LOAD CENTERS SHALL NOT BE ALLOWED UNLESS NOTED OTHERWISE.
9. ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE,
CONTRACTOR SHALL MAKE ALL NECESSARY CORRECTIONS AT NO ADDITIONAL COST TO OWNER.
DUPLEX GROUNDING TYPE RECEPTACLE, 20 AMP, 125 VOLT, 2 POLE, 3 WIRE EQUIP
(E)
EQUIPMENT
EXISTING TO REMAIN
PROJECT
CONNECTED TO EMERGENCY CIRCUIT.
- F -
1. PRIOR TO SUBMITTING A BID FOR ELECTRICAL WORK, THE CONTRACTOR SHALL VISIT THE SITE 8. ALL NEW PANELBOARDS SHALL COMPLY WITH NEC ARTICLE 110.16. EQUIPMENT MANUFACTURERS 10. CONTRACTOR SHALL GUARANTEE ALL WORK AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY DUPLEX RECEPTACLE, NEMA 5-20R, 20A, 125V FBO FURNISHED BY OTHERS
OF THE PROPOSED CONSTRUCTION AND SHALL THOROUGHLY ACQUAINT HIMSELF WITH SHALL PROVIDE WARNING LABELS FOR ALL PANELBOARDS, GENERATORS, AUTOMATIC TRANSFER OCCUR UNDER NORMAL USE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. ALL DEFECTS SHALL BE FF FINISHED FLOOR
EXISTING UTILITIES, AND WORKING CONDITIONS TO BE ENCOUNTERED, ETC. ALLOWANCE WILL SWITCHES, ETC TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE PROMPTLY CORRECTED BY CONTRACTOR WITHOUT ADDITIONAL CHARGE TO OWNER. DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, 20A, 125V FIXT FIXTURE
NOT BE MADE FOR NONCOMPLIANCE WITH THIS CONDITION AFTER BIDDING. MARKING SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE FLEX FLEXIBLE METALLIC CONDUIT(STEEL)
EXAMINATION, ADJUSTMENT, SERVICE, OR MAINTENANCE OF THE EQUIPMENT. 11. PROVIDE AS-BUILT DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ACCURATE CONDUIT AND DEVICE DUPLEX GROUND FAULT CIRCUIT INTERRUPTING TYPE RECEPTACLE, 20 AMP, 125 FLOR FLUORESCENT
2. ELECTRICAL INSTALLATION SHALL MEET THE EXISTING CONDITIONS. E. WIRES LOCATIONS DIMENSIONED FROM PERMANENT LANDMARKS SUCH AS BUILDING WALLS. VOLT, 2 POLE, 3 WIRE CONNECTED TO EMERGENCY CIRCUIT. FT FEET OR FOOT
1. CONDUCTOR SIZES SHOWN ON THE DRAWINGS ARE BASED ON COPPER WIRE. UNLESS OTHERWISE - G -
DUPLEX GROUND FAULT CIRCUIT INTERRUPTING TYPE RECEPTACLE, 20 AMP, 125
E. STORAGE AND HANDLING OF MATERIAL SPECIFIED, ALL WIRE SHALL BE TYPE XHHW FOR FEEDERS OR BRANCH CIRCUITS LARGER THAN 4 AWG, 12. DO NOT SCALE ELECTRICAL DRAWINGS. VERIFY EXACT LOCATION OF ALL DEVICES, JUNCTION BOXES, LIGHTING
VOLT, 2 POLE, 3 WIRE
GFA GROUND FAULT ALARM
TYPE THHN/THWN INSULATION FOR FEEDERS AND BRANCH CIRCUITS 4 AWG AND SMALLER. ALL FIXTURES, ETC. WITH ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO INSTALLATION. CONTRACTOR GFCI GROUND FAULT CIRCUIT INTERRUPTER
1. DELIVER MATERIALS AND EQUIPMENT TO THE PROJECT IN THE MANUFACTURER'S ORIGINAL, SHALL VERIFY THE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT AND OTHER EQUIPMENT REQUIRING GND GROUND 7822 Walker Street
BRANCH CIRCUIT WIRING SHALL BE COPPER. SERVICE AND PANEL FEEDERS #1/0 AND LARGER MAY BE TWO DUPLEX GROUNDING TYPE RECEPTACLES IN 4S BOX, 20 AMP, 125 VOLT, 2
UNOPENED, LABELED CONTAINERS. PROTECT AGAINST MOISTURE, TAMPERING, OR DAMAGE ELECTRICAL CONNECTION PRIOR TO ROUGH-IN. EVERY OUTLET HEIGHT SHALL BE VERIFIED ON EACH WALL WITH - H - La Palma, CA 90623
ALUMINUM, PROVIDED THE CONDUCTOR SIZES ARE INCREASED FOR EQUAL OR GREATER AMPACITY POLE, 3 WIRE CONNECTED TO EMERGENCY CIRCUIT. HP HORSEPOWER
FROM IMPROPER HANDLING OR STORAGE. CONTRACTOR SHALL PROTECT AND BE RESPONSIBLE AND EQUAL OR LESS EQUIVALENT VOLTAGE DROP. INCREASE CONDUIT SIZE AS REQUIRED. THE WIRES THE INTERIOR PLANNING AND DESIGN DRAWINGS. COORDINATE WITH CABINET SHOP DRAWINGS TO ENSURE
FOR ANY DAMAGE TO WORK OR MATERIALS UNTIL FINAL ACCEPTANCE BY THE OWNER, AND HVAC HEATING, VENTILATING & AIR CONDITIONING
SHALL BE MARKED WITH COLOR TO SIMPLIFY CIRCUIT IDENTIFICATION. UNLESS OTHERWISE PROPER HEIGHT AND LOCATION WITH RESPECT TO MILLWORK, EQUIPMENT, ETC. FLOOR OUTLET w/ DEVICE AS INDICATED
SHALL MAKE GOOD WITHOUT COST TO THE OWNER, ANY DAMAGE OR LOSS THAT MAY OCCUR REQUIRED BY LOCAL ORDINANCES GROUND WIRES SHALL BE GREEN, NEUTRAL WIRES SHALL BE 120V- - I - CITY PROJECT NO. 17-BLDG-02
DURING THIS PERIOD. 13. THESE DRAWINGS INDICATE THE FINISHED REQUIREMENTS FOR THE ELECTRICAL SYSTEMS, EQUIPMENT, LIGHTING IBC INTERNATIONAL BUILDING CODE
WHITE, 277V- GRAY, AND LIVE WIRES 208Y/120V AND 120/240 SHALL BE BLACK (PHASE A), RED (PHASE
FIXTURES, OUTLETS AND DEVICES. DUE TO STRUCTURAL CONDITIONS, MECHANICAL DUCT, PIPING CONFLICTS, OR JUNCTION BOX IMC INTERMEDIATE METAL CONDUIT
B), AND BLUE (PHASE C). FOR 480Y/277V CIRCUITS, THE COLOR CODE SHALL BE BROWN (PHASE A),
2. ARRANGE FOR TIMELY DELIVERY OF MATERIALS AND EQUIPMENT TO THE JOB SITE IN IN INCH(ES) ENGINEER/ARCHITECT
ORANGE (PHASE B), AND YELLOW (PHASE C). THE WIRE SHALL BE 12 AWG UNLESS OTHERWISE OTHER LEGITIMATE REASONS, THE CONTRACTOR MAY DESIRE TO INSTALL THE WORK INDICATED IN A MANNER
ORDER TO MINIMIZE THE LENGTH OF TIME BETWEEN DELIVERY AND INSTALLATION. JUNCTION BOX - WALL MOUNT IRC INTERNATIONAL RESIDENTIAL CODE
INDICATED. CIRCUIT SHALL BE LABELED IN EACH J-BOX. DIFFERENT FROM THAT SHOWN. SUCH CHANGES SHALL BE PRESENTED TO THE OWNER'S REPRESENTATIVE FOR
ISC SHORT CIRCUIT AMPERES
REVIEW AND APPROVAL PRIOR TO PROCEEDING. UPON APPROVAL, THE WORK SHALL BE PERFORMED AND THE - J -
3. COVER AND PROTECT ANY MATERIAL WHICH MAY BE AFFECTED BY THE WEATHER MULTI-OUTLET SURFACE RACEWAY w/ NEMA 5-20R, 20A, 125V AT 12" ON CENTER.,

IDS
2. WHERE COOPER WIRE IS USED, COOPER CONDUCTOR MATERIAL SHALL COMPLY WITH N.E.C. 310-14 AS-BUILT DRAWINGS SHALL BE REVISED TO ACCURATELY REFLECT THE WORK AS ACTUALLY INSTALLED. JB, J-BOX JUNCTION BOX
WHILE IN TRANSIT OR STORED AT THE PROJECT SITE. ANY MATERIAL FOUND DEFECTIVE AND ALL CONNECTIONS AND TERMINATIONS SHALL BE MACHINE COMPRESSION TYPE EQUAL TO U.N.O.
- K -
OR NOT INSTALLED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS MAY BE PULLBOX - EXTERIOR OR INTERIOR AS INDICATED
BURNDY "HI PLUG" OR "MACADAPT", NO EXCEPTIONS. 14. RACEWAY SYSTEMS ARE SHOWN DIAGRAMMATICALLY. ACTUAL LOCATION AND ROUTING OF ALL, SHALL BE KCMIL,MCMTHOUSAND CIRCULAR MILS
REJECTED BY THE ENGINEER. DETERMINED BY CONTRACTOR TO SUIT FIELD CONDITIONS. KVA KILOVOLT AMPERE
3. NO WIRE SHALL BE INSTALLED IN THE CONDUIT SYSTEM UNTIL THE CONDUIT SYSTEM IS COMPLETE. TELEPHONE TERMINAL CABINET AT +72" TO TOP KW KILOWATT
F. CLEANUP
USE MINERALAC NO. 100 OR EQUIVALENT AS A LUBRICANT TO FACILITATE THE INSTALLATION OF 15. PROVIDE DEDICATED NEUTRAL FOR EACH NEW CIRCUIT. HOME RUN CONDUCTORS MAY BE COMBINED INTO ONE - L -
1. KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS, OR RUBBISH THE CONDUCTORS IN THE CONDUIT SYSTEM. CONDUIT. NO RACEWAY OR CABLE SHALL CONTAIN MORE THAN NINE (9) CURRENT CARRYING CONDUCTORS. PANELBOARD - SURFACE MOUNT LTG LIGHTING
- M -
IDS GROUP
CAUSED BY EMPLOYEES OR WORK UNDER THIS DIVISION OF THE SPECIFICATIONS. AT WHERE MULTIPLE CONDUCTORS IN EXCESS OF THREE (3) ARE INDICATED ON THESE DRAWINGS, THEY HAVE BEEN
THE COMPLETION OF THE WORK REMOVE ALL SURPLUS MATERIALS, TOOLS, ETC., AND 4. SPLICES IN EXTERIOR PULL BOXES AND MANHOLES SHALL BE WEATHERPROOF USING DE-RATED AS REQUIRED BY NEC ARTICLE 310 REQUIREMENTS. PANELBOARD - FLUSH MOUNT MAX. MAXIMUM
LEAVE THE PREMISES BROOM-CLEAN. "SCOTCHCAST" SPLICE KIT OR APPROVED EQUAL. SEAL ENDS OF CONDUITS AND DUCTS WITH MCB MAIN CIRCUIT BREAKER 1 PETERS CANYON ROAD, SUITE 130
"DUCTSEAL" OR APPROVED EQUAL. 16. PLASTIC CABLE TIES SHALL NOT BE USED AS A MEANS OF SUPPORT FOR MC CABLE. USE ONLY APPROVED CABLE SWITCHBOARD OR DISTRIBUTION BOARD MECH. MECHANICAL IRVINE, CA. 92606
MIN. MINIMUM TEL: 949-387-8500, FAX: 949-387-0800
G. DRAWINGS SUPPORTS PER CABLE MANUFACTURER'S INSTALLATION REQUIREMENTS.
MLO MAIN LUGS ONLY
5. PROVIDE SOLID CONDUCTOR FOR 12 AWG AND SMALLER. OR T TRANSFORMER, RATINGS AS NOTED ON THE
1. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT AND LOCATIONS OF THE ELECTRICAL WORK DATA DRAWINGS. MTD MOUNTED
F. SYSTEM GROUNDING 17. RACEWAYS SHALL BE INSTALLED CONCEALED (IN CMU OR OTHER WALL) WHENEVER POSSIBLE. RACEWAYS
PRESENTED ON THESE DRAWINGS ARE AS ACCURATE AS PLANNING CAN DETERMINE, BUT FIELD INSTALLED EXPOSED SHALL BE ROUTED OUT OF PUBLIC VIEW AS MUCH AS POSSIBLE. RACEWAYS SHALL BE RUN - N -
F FUSED DISCONNECT SWITCH - HP RATED WITH FUSES SIZED PER
VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC., TO SUIT FIELD CONDITIONS IS REQUIRED. 1. GROUNDING SHALL COMPLY WITH REQUIREMENTS OF ARTICLE 250. ALL EXPOSED NONCURRENT PARALLEL WITH, OR AT RIGHT ANGLE TO WALLS. EQUIPMENT MANUFACTURER. NC NORMALLY CLOSED
REVIEW ALL ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND ADJUST ALL WORK TO CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC RACEWAY SYSTEMS, METALLIC NEC NATIONAL ELECTRICAL CODE
MEET THE REQUIREMENTS OF CONDITIONS SHOWN. THE ARCHITECTURAL DRAWINGS SHALL TAKE SD SMOKE DETECTOR-120V WITH BATTERY AND STAMP
CABLE ARMOR, GROUNDING CONDUCTOR OF NONMETALLIC SHEATHED CABLES, GROUNDING 18. PROVIDE APPROVED EXPANSION FITTINGS WHERE RACEWAYS CROSS BUILDING EXPANSION JOINTS. PROVIDE NECA NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION
PRECEDENCE OVER ALL OTHER DRAWINGS. DISCREPANCIES BETWEEN DIFFERENT PLANS, OR BETWEEN CONDUCTOR IN NONMETALLIC RACEWAYS, AND GROUNDED CONDUCTORS OF THE WIRING SYSTEM BONDING JUMPER(S) SIZED PER CODE WHERE REQUIRED. PROVIDE ALL FITTINGS REQUIRED FOR A COMPLETE INTERCONNECTION TO OTHER SD IN UNIT NEMA NATIONAL ELECTRICAL MANUFACTURERS
DRAWINGS AND SPECIFICATIONS, OR REGULATIONS AND CODES GOVERNING THE INSTALLATION SHALL BE SHALL BE GROUNDED. INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR EXPANSION JOINT LOCATION(S). ASSOCIATION
BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE THE DATE OF BID OPENING. IF MOTOR RATED SWITCH
NEUT NEUTRAL
DISCREPANCIES ARE NOT REPORTED, THE CONTRACTOR SHALL BID THE GREATER QUANTITY OR BETTER 2. GROUNDING CONDUCTOR (NEUTRAL) OF THE WIRING SYSTEM SHALL BE CONNECTED TO THE SYSTEM 19. MINIMUM RACEWAY SIZE SHALL BE 1/2". MINIMUM HOMERUN SIZE SHALL BE 3/4". MINIMUM CONDUCTOR SIZE SHALL NFC NATIONAL FIRE CODE
QUALITY, AND APPROPRIATE ADJUSTMENTS WILL BE MADE AFTER CONTRACT AWARD. CONTRACTOR GROUNDING CONDUCTOR AT A SINGLE PLACE IN EACH SYSTEM BY REMOVABLE BONDING JUMPERS, BE #12 AWG U.N.O. TYPICAL. ALL POWER RELATED CONDUITS SHALL HAVE A CODE SIZE GROUND WIRE INSTALLED NF NON-FUSIBLE
SHALL BE RESPONSIBLE TO FIELD MEASURE AND CONFIRM MOUNTING HEIGHTS AND LOCATION OF
ELECTRICAL EQUIPMENT WITH RESPECT TO COUNTERS, RADIATION, ETC. DO NOT SCALE DISTANCES OFF
SIZED ACCORDING TO THE APPLICABLE PROVISIONS OF THE NATIONAL ELECTRICAL CODE. THE
GROUNDED CONDUCTOR (NEUTRAL) TO THE GROUNDING CONDUCTOR CONNECTION SHALL BE
IN EACH RUN.
SINGLE LINE NIC
NL
NO
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
THE ELECTRICAL DRAWINGS, USE ACTUAL BUILDING DIMENSIONS. LOCATED IN THE ENCLOSURE FOR THE SYSTEM'S OVERCURRENT PROTECTION OR WHERE OTHERWISE 20. CONTRACTOR SHALL PROVIDE PULL CORDS IN ALL EMPTY CONDUITS. WHERE MORE THAN ONE CONDUIT
TERMINATES IN A JUNCTION BOX, THE CONTRACTOR SHALL IDENTIFY EACH CONDUIT AND JUNCTION BOX IN A NPCO NEVADA POWER COMPANY
INDICATED ON THE PLANS OR SPECIFICATIONS.
NTS NOT TO SCALE
MANNER ALLOWING IDENTIFICATION AFTER ALL WALL FINISHES HAVE BEEN APPLIED. CIRCUIT BREAKER
H. EXCAVATION, CUTTING, AND FITTING 3. A GROUND BUS SEPARATE FROM THE NEUTRAL BUS SHALL BE PROVIDED IN ALL SWITCHBOARDS AND - O -
PANELBOARDS. GROUND BUS SHALL BE RETORQUED (CHECKED) PRIOR TO ENERGIZING EQUIPMENT 21. CONTRACTOR SHALL PROVIDE ALL RACEWAY SYSTEMS INDICATED ON THE DRAWING PER NEC REQUIREMENTS SERVICE CABLE TERMINATION OCP OVERCURRENT PROTECTION
1. PERFORM THE EXCAVATION, CUTTING, FITTING, REPAIRING, AND FINISHING OF THE WORK NECESSARY
PER MANUFACTURER'S RECOMMENDATIONS. AND GENERAL NOTES. ANY DEVIATION FROM THE WIRING METHODS INDICATED SHALL BE ALLOWED ONLY BY - P - STAMP
FOR THE INSTALLATION OF THE EQUIPMENT OF THIS SECTION. HOWEVER, NO CUTTING OF THE WORK OF SPECIFIC WRITTEN APPROVAL FROM EITHER THE ARCHITECT, ENGINEER OR OWNER. CONTRACTOR'S BID SHALL
OTHER TRADES OR OF ANY STRUCTURAL MEMBERS SHALL BE DONE WITHOUT THE CONSENT OF THE CURRENT TRANSFORMER P POLE
FE SSION
ARCHITECT.
4. GROUND BUSES AND NEUTRAL BUSES IN ALL DISTRIBUTION PANELS, SWITCHBOARDS, PANELBOARDS, INCLUDE ALL COSTS FOR RACEWAY SYSTEMS AS SPECIFIED UNLESS SPECIFIC WRITTEN APPROVAL FOR AN PH PHASE PR O A
D Z. O'
AND THOSE PROVIDED IN ANY EQUIPMENT SHALL BE ISOLATED EXCEPT WHERE REQUIRED TO BE ALTERNATIVE WIRING METHOD IS OBTAINED FROM EITHER THE ARCHITECT, ENGINEER OR OWNER AND IS PNL PANEL

LE
IN

RE
POTENTIAL TRANSFORMER B N

NG
R EG I S T E
CONNECTED AS SPECIFIED ABOVE FOR THE SERVICE ENTRANCE AND IN TRANSFORMER TERMINAL SUBMITTED AS PART OF CONTRACTOR'S FORMAL BID PROPOSAL. PV PV PHOTOVOLTAIC
I. COOPERATION WITH OTHER CONTRACTORS

EI
RO

I N EE R
COMPARTMENTS. PVC POLYVINYL CHLORIDE

L
GROUNDING ELECTRODE E 18557
22. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECT SIZE AND INSTALLATION OF ALL OUTLET, PULL AND PWR POWER Exp. 12-31-20
1. COOPERATE WITH THE OTHER TRADES SO THAT THE INSTALLATION OF THE ELECTRICAL OUTLETS AND - Q -
5. WHEN INDICATED ON THE DRAWINGS, EQUIPMENT GROUNDING CONDUCTORS SHALL BE EXTENDED JUNCTION BOXES IN ACCORDANCE WITH NEC 314-16. ALL BOXES SHALL BE MINIMUM 4" SQUARE BY 1-1/2" DEEP OR
EQUIPMENT WILL BE PROPERLY COORDINATED. CONDUIT, LIGHTING FIXTURES, AND OTHER EQUIPMENT L

L
SINGLE PHASE FRACTIONAL OR INTEGRAL HORSE POWER

E
AS INDICATED ON THE DRAWINGS. ALL BOXES SHALL BE RECESSED WITH COVER PLATE TO SUIT THE INTENDED QTY QUANTITY AT E C T R I C
A

ST
FROM THE GROUND BUS IN THE DISTRIBUTION EQUIPMENT TO THE RECEPTACLE, FIXTURE OR DEVICE

A
NI
LOCATIONS SHALL BE CHECKED WITH OTHER TRADES TO AVOID CONFLICT WITH THE PIPING, MOTOR EO R
LUGS WHERE THEY ARE PROVIDED. WHERE LUGS ARE NOT PROVIDED, EQUIPMENT GROUNDING APPLICATION. - R - F C A LI F O
DUCTWORK, STEEL, BEAMS, OR OTHER OBSTRUCTIONS. G GENERATOR (R) REMOVE
CONDUCTORS SHALL BE CONNECTED TO EQUIPMENT ENCLOSURES. THE CONNECTIONS SHALL BE
ARRANGED SUCH THAT REMOVAL OF THE RECEPTACLE, EQUIPMENT GROUND CONDUCTORS, OR 23. PRIOR TO INSTALLATION, CONTRACTOR SHALL REVIEW THE COMPLETE SET OF CONSTRUCTION DOCUMENTS FOR RECEP RECEPTACLE
2. COORDINATE THE LOCATION OF THE TRENCHES AND CONDUITS FOR ELECTRICAL AND ST SHUNT TRIP REQ'D REQUIRED
GROUND JUMPERS FROM GROUND BUSING SHALL NOT AFFECT THE GROUND SYSTEM. CONFLICTS WITH OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL WORK WITH OTHER
TELEPHONE UTILITY SERVICES WITH THE GENERAL CONTRACTOR. RSC RIGID STEEL CONDUIT
TRADES TO AVOID CONFLICT DURING INSTALLATION. CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS IN
GFI GROUND FAULT INTERRUPTER - S - ISSUE
6. RACEWAYS MAY NOT BE USED AS A GROUNDING CONDUCTOR FOR POWER AND LIGHTING CIRCUITS. EQUIPMENT LOCATION AND ROUTING AS NECESSARY AT NO ADDITIONAL COST TO THE OWNER.
3. COORDINATE HVAC EQUIPMENT CONNECTION REQUIREMENTS WITH HVAC SCHED SCHEDULE
ALL CONDUIT SHALL HAVE SEPARATE CODE SIZED GREEN GROUND WIRE INSTALLED IN THE CONDUIT
CONTRACTOR.
TO INSURE A CONTINUOUS GROUNDING PATH. 24. CONTRACTOR SHALL BE RESPONSIBLE TO PROPERLY CUT AND PATCH EXISTING CONSTRUCTION AS REQUIRED TO SECT SECTION REV. DESCRIPTION DATE
CAREFULLY CHECK THE LOCATIONS OF THE OUTLET BOXES AND DETERMINE THAT TRANSFER SWITCH
INSTALL NEW ELECTRICAL WORK ALL PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS SP SINGLE POLE
THEY HAVE NOT BEEN DISTURBED DURING THE INSTALLATION OF MATERIALS OF OTHER THE EXISTING WORK AND SHALL ACCURATELY MATCH ALL SURROUNDING WORK TO THE SATISFACTION OF THE SN SOLID NEUTRAL DD SUBMITTAL 6/28/2018
7. IN INACCESSIBLE LOCATIONS, MAKE CONNECTIONS BY EXOTHERMIC WELD PROCESS. CONTACT (NORMALLY OPEN)
TRADES. SPEC SPECIFICATION
ARCHITECT.
SW SWITCH
8. IN ACCESSIBLE LOCATIONS, CONNECTIONS SHALL BE MADE WITH BOLTED THROUGH, APPROVED CONTACT (NORMALLY CLOSED) CITY SUBMITTAL 3/16/2020
PART II - PRODUCTS AND EXECUTION SOLDERLESS BRONZE GROUNDING DEVICES. 25. ALL ELECTRICAL EQUIPMENT SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO ACCOMMODATE QUANTITY
SWBD
SWGR
SWITCHBOARD
SWITCH GEAR
AND SIZE OF CONDUCTORS REQUIRED. CONTRACTORS SHALL PROVIDE EQUIPMENT WITH OVERSIZED TIME SWITCH SYS SYSTEM
A. MATERIALS 9. BOND TOGETHER METAL SIDING NOT ATTACHED TO GROUNDED STRUCTURE BOND TO GROUND. ENCLOSURES WHERE REQUIRED.
1. ALL MATERIALS SHALL BE NEW AND OF QUALITY AS SPECIFIED ON THE PLANS OR CONTROL SWITCH - T -
26. ALL NEW PANELBOARDS AND SWITCHBOARDS SHALL BE OF THE SAME MANUFACTURER AND HAVE LOCKING DOORS TEMP TEMPORARY
SPECIFICATIONS AND MUST CARRY THE UNDERWRITER'S LABORATORIES APPROVAL
AND BE KEYED THE SAME U.N.O. ST SHUNT TRIP TELE TELEPHONE
COVERING THE PURPOSE FOR WHICH THEY ARE USED, IN ADDITION TO MEETING ALL G. GUARANTEE T-STAT THERMOSTAT
REQUIREMENTS OF THE CURRENT APPLICABLE CODES AND REGULATIONS. TTB TELEPHONE TERMINAL BACKBOARD
GUARANTEE ALL MATERIAL FURNISHED AND ALL WORKMANSHIP PERFORMED FOR A PERIOD OF 27. PROVIDE TYPE WRITTEN UPDATED PANEL DIRECTORY TO BE MOUNTED ON INSIDE OF ALL PANEL DOOR COVERS. 70AMP FUSE AND 100AMP SWITCH, FUSE TYPE AS SPECIFIED
1. ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF WORK. ANY DEFECTS DEVELOPING WITHIN THIS DIRECTORY SHALL REFLECT ALL ADDITIONS OR MODIFICATIONS TO EXISTING PANELS AND SHALL REFLECT ACTUAL TTB TELEPHONE TERMINAL CABINET
B. CONDUIT 70AF/100AS TYP. TYPICAL
PERIOD, TRACEABLE TO MATERIAL FURNISHED AS A PART OF THIS SECTION OR WORKMANSHIP "AS-BUILT" CONDITIONS.
PERFORMED HEREUNDER, SHALL BE MADE GOOD AT NO EXPENSE TO THE OWNER.
1. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC CONDUIT EXCEPT AS PERMITTED BELOW. RGS, THREE PHASE FRACTIONAL OR INTEGRAL HORSEPOWER - U -
28. VERIFY DEVICE COLOR AND MOUNTING ORIENTATION (VERTICAL OR HORIZONTAL) WITH ARCHITECTURAL AND M
WITH A 20 MIL PVC COATING WILL BE USED WHEN IN CONTACT WITH EARTH. IMC MAY BE USED IN INDOOR MOTOR. NUMERAL IN PLACE OF "M" INDICATES UBC UNIFORM BUILDING CODE
LOCATIONS NOT IN CONTACT WITH THE EARTH. EMT MAY BE USED IN INDOOR LOCATIONS NOT IN H. SHOP DRAWINGS AND APPROVALS INTERIOR DESIGN DRAWINGS PRIOR TO ORDERING ANY EQUIPMENT AND PROVIDE DEVICES AS REQUIRED. UNLESS
HORSEPOWER. UL UNDERWRITERS LABORATORY
NOTED OTHERWISE, DEVICES AND DEVICE PLATES SHALL BE WHITE IN COLOR. U.N.O. UNLESS NOTED OTHERWISE
CONTACT WITH EARTH, NOT IN CONCRETE SLABS OR WALLS AND NOT SUBJECT TO DAMAGE. PVC MAY BE VOLTAGE TRANSFORMER. FLOOR MOUNTD, COPPER WOUND,
1. THE ITEMS SPECIFIED AND SHOWN HEREIN AND ON DRAWINGS ARE USED AS A STANDARD OF
USED IN OR BELOW CONCRETE AND DIRECT BURIED IN EARTH. FLEXIBLE STEEL CONDUIT SHALL BE USED DRY TYPE UNLESS SPECIFIED OTHERWISE.
QUALITY. ANY MATERIALS OF EQUAL QUALITY AND AESTHETIC VALUE WILL BE GIVEN 29. WHERE MOTORS ARE INSTALLED IN SUSPENDED CEILINGS, CONTRACTOR SHALL PROVIDE DISCONNECT SWITCH IN - V -
FOR INDOOR FINAL CONNECTIONS TO EQUIPMENT IN LENGTHS NOT TO EXCEED 72". LIQUID-TIGHT
CONSIDERATION AS A SUBSTITUTE FOR THE MATERIALS SPECIFIED. NO APPROVAL WILL BE GIVEN SUSPENDED CEILING WITHIN REACH FROM ACCESS POINT. V VOLT OR VOLTAGE
FLEXIBLE STEEL CONDUIT SHALL BE FOR OUTDOOR FINAL CONNECTIONS TO EQUIPMENT NOT TO EXCEED PM ELECTRONIC POWER METER WITH C.T.s, ETC., SEE
TO A SPECIFIC CATALOG NUMBER, MODEL, OR TYPE OF EQUIPMENT, PRIOR TO BIDDING. AFTER VA VOLT AMPERE
36". SPECIFICATIONS
BIDDING, THE DECISION OF THE ARCHITECT AND/OR LEGO AND ENGINEER DETERMINING EQUAL 30. SIZING OF MOTOR-RELATED ELECTRICAL COMPONENTS, INCLUDING FEEDER AND/ OR BRANCH CIRCUITS (WIRE AND VD VOLTAGE DROP
MATERIALS WILL BE FINAL. CONDUIT) AND OVERCURRENT PROTECTION (BREAKER AND/ OR FUSES) IS BASED ON RATINGS INDICATED IN THE M UTILITY METER SOCKET, WITH C.T.s, CLIPS, ETC., PER SERVING UTILITY VP VAPOR PROOF
2. WHERE CONDUIT ENTERS OUTLET BOXES, FIXTURES OR CABINETS, FIRMLY FASTEN WITH STEEL SET
SCREW, COMPRESSION CONNECTORS, OR DOUBLE LOCKNUTS FOR GRC. ALL CONNECTIONS SHALL HAVE CONTRACT DOCUMENTS AS WELL AS NEC APPROXIMATED LOADS FOR A GIVEN MOTOR HORSEPOWER, VOLTAGE COMPANY.
2. THE CONTRACTOR SHALL SUBMIT SEVEN (7) IDENTICAL BOUND SETS OF SHOP DRAWINGS ON THE - W -
BUSHINGS OR INSULATED THROAT CONNECTORS. FIRMLY FASTEN CONDUIT TO THE BUILDING AND PHASE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY ACTUAL MOTOR AND APPLIANCE RATING AND W WATT, WIRE KEY PLAN
FOLLOWING ITEMS: GROUND, "GRD".
CONSTRUCTION. RUN EXPOSED CONDUIT PARALLEL TO THE BUILDING LINES, SUPPORTED BY LOADS. CONTRACTOR TO PROVIDE CORRECTLY SIZED MOTOR OVERLOAD ELECTRICAL COMPONENTS BASED ON WCR WITHSTAND CURRENT RATING UL LISTED
APPROPRIATE HANGERS (UNISTRUT, T & B OR APPLETON, OR EQUAL). NAMEPLATE RATING. REFLECT ALL CHANGES IN THE AS-BUILT DRAWINGS. GFCI WP WEATHERPROOF, NEMA 3R
a. SHOP DRAWINGS OF GENERATOR AND FUEL TANK INCLUDING ASSOCIATED PIPING. "GROUND FAULT CIRCUIT INTERRUPTER"
b. OUTLINE DRAWINGS AND DATA SHEETS OF EACH PANELBOARD AND SWITCHBOARD. 31. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ARCHITECT FOR REVIEW OF THE FOLLOWING EQUIPMENT: GFP GROUND FAULT PROTECTION DEVICE. - X -
3. COVER METALLIC CONDUIT IN CONTACT WITH EARTH WITH POLYETHYLENE TAPED SPIRAL WRAPPED, 1/2
c. OUTLINE DRAWINGS OF ALL EQUIPMENT. XFMR TRANSFORMER
LAPPED TO PROVIDE 20 MIL. THICKNESS. TAPE SHALL BE SCOTCH NO. 50 TAPE. CONDUIT AND DUCTS NOT GROUND FAULT SENSOR.
UNDER BUILDINGS AND FEEDER DUCTS SHALL BE INSTALLED PER N.E.C. 300-5. MAKE JOINTS WITH a. ELECTRICAL SWITCHGEAR: SWITCHBOARDS, WITH PANELS, MOTOR CONTROL CENTERS AND SAFETY GFS
3. SUBMIT ITEMS AT ONE TIME IN A NEAT AND ORDERLY MANNER WITHIN 15 DAYS OF AWARD OF DEVICES.
COMPOUND TO BE WATERTIGHT. AMMETER SWITCH, FOUR POSITION "PHASE A", "PHASE B", "PHASE C", AND
CONTRACT. PARTIAL SUBMITTALS WILL NOT BE ACCEPTABLE. AS
OFF.
4. FITTINGS AND CONDUIT BODIES SHALL BE STEEL. NO DIECAST FITTINGS. b. OVERCURRENT DEVICES: CIRCUIT BREAKERS AND FUSES INCLUDING TIME/CURRENT TRIP CURVES.
I. RECORD AND AS-BUILT DRAWINGS VOLTMETER SWITCH, SEVEN POSITION "PHASE A-N", "PHASE
VS B-N", "PHASE C-N", "PHASE AB", "PHASE BC", "PHASE CA", AND
5. CONDUIT SIZES SHALL BE AS REQUIRED BY CODE AND AS INDICATED OR SPECIFIED. c. AUTOMATIC TRANSFER SWITCH.
1. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE JOB SITE FOR THE OFF.
EXCLUSIVE PURPOSE OF MAINTAINING A RECORD OF ALL WORK INSTALLED AND TO SHOW ANY 33. ALL PENETRATIONS OF FIRE RESISTIVE FLOORS OR WALLS SHALL BE PROTECTED BY MATERIALS AND A AMMETER.
6. ALL EMPTY CONDUIT SYSTEMS SHALL HAVE A NYLON PULL STRING TO FACILITATE INSTALLATION
DEVIATIONS FROM THE WORK INDICATED ON THE DRAWINGS. INSTALLATION DIAGRAMS THAT CONFORM TO UL LISTING FOR "THROUGH-PENETRATION FIRE STOP SYSTEMS".
OF FUTURE WIRE. V VOLTMETER.
7. SCHEDULE 40 PVC CONDUIT SHALL BE PERMITTED UNDERGROUND WITH PROPER FITTINGS, 2. AT THE COMPLETION OF THE PROJECT, ONE SET OF REPRODUCIBLE DRAWINGS, SHOWING ALL 34. ALL EQUIPMENT ELECTRICAL TERMINATIONS TO UNDERGO A TORQUE TEST. ELECTRICAL CONTRACTOR IS
AS-BUILT CONDITIONS, SHALL BE DELIVERED TO THE OWNER FOR ACCEPTANCE PRIOR TO FINAL RESPONSIBLE FOR MANUFACTURER'S RECOMMENDED TORQUE DOCUMENTATION AND TOOLS TO PERFORM
KWH USAGE (KILOWATT HOUR) METER.
ALL UL APPROVED AND CEMENTED JOINTS. PENETRATIONS THROUGH FLOOR SLABS AND
BENDS GREATER THAN 22° SHALL BE WRAPPED RIGID GALVANIZED STEEL ELBOWS. PAYMENT. TORQUE TEST. KW DEMAND (KILOWATT) METER.

8. CONDUITS AND OUTLETS SHALL BE CONCEALED WITH THE BUILDING STRUCTURE, EXCEPT THAT 35. FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE MOUNTED ON A 4" HIGH CONCRETE PAD.
CERTAIN MOTOR AND LIGHTING FEEDER CONDUITS MAY BE RUN EXPOSED IN CERTAIN AREAS AS
INDICATED ON THE DRAWINGS. CONDUIT SHOWN TO BE INSTALLED IN CABINETS, COUNTERS, AND
CASEWORK SHALL BE RUN AS DIRECTED BY THE ARCHITECT.
36. PROVIDE 10 AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 75' AND 8 AWG
CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 120'. PROVIDE 10 AWG CONDUCTORS FOR 20 WIRING SCOPE OF WORK PROJECT NO. 17X115.00
AMPERE, 277V BRANCH CIRCUITS LONGER THAN 200'.
9. ALL CONDUIT SYSTEMS SHALL HAVE A CODE SIZED COPPER GROUND CONDUCTOR E (E) CONDUIT TO REMAIN
INCREASE CONDUIT SIZE AS REQUIRED. F FIRE ALARM SYSTEM REPLACEMENT OF EXISTING HVAC SYSTEM PRINT DATE 3/16/2020
10. CONDUIT PENETRATION THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK
TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT.
CONDUIT ROUTED UNDERFLOOR / UNDERGROUND
WITH NEW. DRAWN BY TP
RACEWAY CONDUIT RUN, CONCEALED IN CEILING, WALLS OR UNDERFLOOR,
11. CONDUITS SHALL BE ROUTED SURFACE ON THE STRUCTURE, PARALLEL AND DRAWING LIST APPLICABLE CODES HATCH MARKS INDICATE NUMBER OF WIRES INCLUDING GROUND CHECKED BY RO
PERPENDICULAR TO THE STRUCTURE. RACEWAY TURNED UP
ALL MECHANICAL EQUIPMENT, MATERIAL, TESTING AND DETAILS OF INSTALLATION EX EXISTING CONDUIT RUN TO BE REWIRED SHEET TITLE
C. OUTLET, PULL, AND JUNCTION BOXES E0.1 ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS
SHALL CONFORM TO THE MECHANICAL REQUIREMENTS AND REGULATIONS
E0.2 SINGLE LINE DIAGRAM & PANELBOARD SCHEDULES ENFORCED BY THE STATE OF CALIFORNIA UTILIZING THE FOLLOWING CODES & NFPA RACEWAY TURNED DOWN
1. EACH SWITCH, LIGHT. RECEPTACLE OR OTHER OUTLET SHALL BE PROVIDED WITH A CODE GAUGE,

ELECTRICAL NOTES,
GALVANIZED STEEL OUTLET BOX. JUNCTION AND PULL BOXES SHALL BE CODE GAUGE, GALVANIZED STEEL. STANDARDS:
E1.0 ELECTRICAL SITE PLAN HOMERUN TO PANELBOARD 1/2"C
OUTLET BOXES SHALL BE OF THE ONE PIECE, KNOCKOUT TYPE, IN GENERAL 4" SQUARE WITH PLASTER E1.2 ELECTRICAL DEMOLITION ROOF PLAN APPLICABLE CODES HATCH MARKS INDICATE NUMBER OF WIRES INCLUDING GROUND

LEGEND AND
RING. PLASTER RINGS SHALL BE SET TO PROVIDE NOT MORE THAN 1/8" FROM WALL SURFACE TO RING. IN
NO CASE SHALL PLASTER RING PROJECT BEYOND SURFACE OF WALL. SINGLE GANG RINGS SIMILAR TO E2.0 NEW HVAC FLOOR PLAN 2019 CALIFORNIA ADMINISTRATIVE CODE. PART 1. T-24, CALIFORNIA CODE CONDUIT CAP-OFF
OF REGULATION (CCR)
ABBREVIATIONS
STEEL CITY 52050 SHALL BE USED FOR 4" BOXES IN UNFINISHED BRICK NUMBER 180 BOXES MAY BE USED
FOR UNFINISHED MASONRY FLUSH WALL OUTLETS. CENTER ALL OUTLET BOXES IN BLOCK COURSE. E3.0 NEW HVAC ROOF PLAN RxE "X" INDICATES APPROXIMATE POINT OF INTERCEPTION OF EXISTING
2019 CALIFORNIA BUILDING CODE, PART 2, T-24, CCR CONDUIT RUN. CONDUIT TO BE REMOVED AT "R" SIDE OF "X". EXACT
2019 CALIFORNIA ELECTRICAL CODE, PART 3, T-24, CCR LOCATION OF ALL CONDUITS SHALL BE FIELD VERIFIED. EXTEND
2. BOXES INSTALLED IN POURED CEMENT FLOORS SHALL BE FLUSH TYPE CAST IRON OR STEEL WITH CONDUIT AS INDICATED ON PLANS, PROVIDE PULLBOX/JUNCTION
WATERTIGHT GASKETED COVERS. WHERE BOXES ARE INSTALLED IN FLOORS WITH TILE OR CARPET 2019 CALIFORNIA FIRE CODE, PART 9, T-24, CCR BOX SIZE AS PER NEC. SHEET NUMBER

E0.1
FLOOR COVERING, COVERS SHALL BE OF THE RECESSED TYPE TO ACCOMMODATE THE FLOOR
2019 CALIFORNIA ENERGY CODE, PART 6, T-24, CCR
COVERING.
2019 CALIFORNIA GREEN BUILDING STANDARD CODE, PART II
3. BOXES FOR TELEPHONE, COMPUTER, T.V., FIRE ALARM, SECURITY, AND SIMILAR SYSTEMS
SHALL BE MINIMUM 4" SQUARE AND 2-1/8" DEEP.
CLIENT
GENERAL NOTES
EXIST. SCE INTERCEPT PULL BOX

EXIST. 5"C.O.
ALL SHOWN EQUIPMENT IS EXISTING UNLESS NOTED 'NEW'
1. ALL EXISTING EQUIPMENT SHOWN WITH LIGHT LINES ARE EXISTING EQUIPMENT.
EXIST. EXIST. 12KV FEEDER BY SCE
TO EXIST. SCE PROPOSED 2. ALL EQUIPMENT SHOWN IN BOLD LINE ARE EXIST. EQUIPMENT. (REFER TO GENERAL NOTES ON SHEET
EXIST.
SCE PB EMERGENCY E0.3 FOR OTHER REQUIREMENTS FOR EXIST. EQUIPMENT).
UTILITY DIESEL
POLE GENERATOR
EXIST. SCE FUTURE
TRANSFORMER IN
8'x10' PULL BOX

EXIST. 4"C, 4#500


KCMIL, 1#2
GROUND
EXIST. (4) 4"C, 4#600 KCMIL, 1#250 KCMIL GROUND

EXIST. SCE SLAB BOX TO REMAIN


LOCATED AT OUTDOOR POLICE
EXIST. UGPS EXIST. MAIN / METER SECTION DEPARTMENT KEY NOTES 7822 WALKER STREET
EXIST. DISTRIBUTION SECTION "DLA" LA PALMA, CA 90623
120/208,3Ø, 4W,NEMA-3R E
N NEW BREAKER TO MATCH EXISTING AIC RATING.
M 1600A BUS 1
PROJECT NAME
AIC=65 kA
EXIST. ASC=27,140A 2-4"C 2 EXIST. CONDUCTORS BACK IN EXISTING CONDUIT. EXTEND EXISTING CONDUIT AS NECESSARY.
2000A
3P
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1-1"C CITY HALL
3 PROVIDE HACR CIRCUIT BREAKER FOR HVAC UNITS.

N
EXIST.
600A
EXIST.
175A
EXIST.
175A
EXIST.
50A
EXIST.
100A
EXIST.
50A
EXIST.
100A
EXIST.
200A
EXIST.
100A
EXIST.
50A
EXIST.
50A
EXIST.
90A
EXIST.
60A
EXIST.
20A
EXIST.
200A
EXIST.
200A HVAC REPLACEMENT
3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P 3P
GRD SPARE SPARE PROJECT
EXIST. ATS
2000A
4P

(2) 4"C, 4#600 KCMIL, 1#1 GND

EXIST. 2 1/2"C-, 4#4/0, 1#4 GND

EXIST. 2 1/2C-, 4#4/0, 1#4 GND

EXIST. 1 1/2"C-, 3#4, 1#8 GND


EXIST. 1"C-, 3#8, 1#10 GND

EXIST. 1"C-, 3#8, 1#10 GND


EXIST. (4) 4" C.O.

4 #3/0 HARD USAGE,


TEMPORARY CABLE
7822 Walker Street
La Palma, CA 90623

CITY PROJECT NO. 17-BLDG-02

ENGINEER/ARCHITECT
200A
3P

EXIST. 4"C, 4#500


KCMIL, 1#2 GROUND
EXIST. DISTRIBUTION
SECTION "DLA"
CONVERTED TO PULL
BOX.
X X X X X X
EXIST. 60 kW,120/208V,
3-PHASE, 4W
EMERGENCY DIESEL
GENERATOR
EXIST. IDS
IDS GROUP
1 1/2"C- 3#3/0

1 PETERS CANYON ROAD, SUITE 130


EXIST. IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
LOCATED AT OUTDOOR POLICE
DEPARTMENT

EXIST. 3 #4, 1 #8 GND


EXIST.-(2) 4 #600 KCMIL,

EXIST. 4 #4/0, 1 #4

EXIST. 4 #4/0, 1 #4
EXIST. AUTOMATIC TRANSFER EXIST. EMERGENCY

EXIST. 3 #8, 1 #10

EXIST. 3 #8, 1 #10


SWITCH DISTRIBUTION PANEL ,NEMA-3R STAMP
225A BUS, 120/208V, 3-PHASE, 4W

EXIST. 11 4"C.
EXIST. 3"C.

EXIST. 3"C.

EXIST. 1"C.

EXIST. 1"C.
EXIST. 2 - 4"C.

1 2 3
1 #1 GND

GND

GND

GND

GND
(R) (R) (R) (R) (R) (R)
100A 50A 50A 90A 40A 20A
NEW NEW 3P 3P 3P 3P 3P 2P
WP WP WP
PANEL PANEL
CP CP CP SPARE
EXIST. (5 TON) (7 TON) (5 TON)
A B
PB EXIST.
EXIST.
1 1/4"C- 4#6 1 1/4"C- 4#6 1"C- 4#8 STAMP

FE SSION
EXIST. 4"C, 4#500 PR O AL
D Z. O'
KCMIL, 1#2 GROUND IN

RE
N

EN L
B

REG I STE

GIN E
EI
RO
AT CITY HALL TO EXIST. E 18557

ER
EXIST. EXIST. EXIST.
AT LIBRARY BUILDING EXIST. DISTRIBUTION PANEL "DA" PANEL AT EXISTING Exp. 12-31-20
120/208,3Ø, 4W EVIDENCE LOAD LE

L
EXIST. A

ST

IA
EXIST. MAIN SWITCHBOARD 600A BUS ROOM AT C T RIC
M 600A EO RN
120/208,3Ø, 4W AIC=42kA F C A LI F O
400A BUS EXIST. 3P ASC=14,187A
300A EXIST. EXIST. EXIST.
1 2 3 4 5 6 7
3P
1 2 3 4 5 6
EXIST. EXIST. EXIST. EXIST. EXIST. NEW. EXIST. ISSUE
PANEL PANEL PANEL
150A 225A 150A 100A 90A 60A 40A 1"C- 4#8
EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. REV. DESCRIPTION DATE
3P 3P 3P 3P 3P 3P 3P 1E 2E 3E
20A 50A 30A 50A 100A 100A
1 3
3P 3P 3P 3P 3P 3P DD SUBMITTAL 6/28/2018
POLICE FIRE CITY EXIST.
DEPARTMENT DEPARTMENT HALL
NEW (3) #6 CU, (1) #10 CU GND
NEW (3) #2 CU, (1) #8 CU GND

NEW (3) #2 CU, (1) #8 CU GND


EXIST. 4 #4/0, 1 #4 GND

EXIST. 4 #1/0, 1 #6 GND

3/16/2020
EXIST. 4 #/0, 1 #6 GND

CITY SUBMITTAL
EXIST.
L ~ 30 FT, VD ~ 0.24%

L ~ 40 FT, VD ~ 0.27%

2 2 2 L ~ 25 FT, VD ~ 0.17%
EXIST. 1 1/4"C.

EXIST1 1/4"C.

EXIST. 3/4"C.

EXIST. EXIST.
EXIST. EXIST. EXIST. EXIST. EXIST. EXIST.
PANEL PB
2"C.

2"C.
3"C.

4E
EXIST. EXIST. F EXIST. F EXIST.
WP WP WP EXIST. EXIST. EXIST. EXIST. NEW
LOAD
PANEL PANEL PANEL PANEL PANEL SCOPE OF WORK
NEW FLA = 451.7
F G H C D NEW NEW WP
F 60/3/60AF
WP WP
100/3/NF 100/3/NF VFD
FLA = 69 FLA = 135 FLA = 83

NEW NEW NEW


CU-1 CU-2 DOAS
(ON ROOF)
FLA = 61
(ON ROOF)
FLA = 52
(ON ROOF)
FLA = 51.7
*
KEY PLAN

EXIST. LOADS EXIST. LOADS EXIST. LOADS EXIST. LOADS

PROJECT NO. 17X115.00

PRINT DATE 3/16/2020

* DRAWN BY TP
* * * * CHECKED BY RO
* * SCOPE OF WORK

* * * SHEET TITLE

SINGLE LINE
* * DIAGRAM &
PANELBOARD
SCHEDULES
SHEET NUMBER

E0.2
* = NEW BREAKER * = NEW BREAKER
CLIENT
GENERAL NOTES
1. ALL NEW EQUIPMENT SHALL BE UL LISTED.

2. CONTRACTOR SHALL REPAIR ALL EXISTING DISTURBED SURFACES


TO MATCH EXISTING CONDITIONS

7822 WALKER STREET


LA PALMA, CA 90623
PROJECT NAME

CITY HALL
HVAC REPLACEMENT
PROJECT

7822 Walker Street


La Palma, CA 90623

CITY PROJECT NO. 17-BLDG-02

ENGINEER/ARCHITECT
EXISTING
POLICE/FIRE
DEPARTMENTS

T
IDS
IDS GROUP
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800

STAMP

STAMP

FE SSION
PR O A
D Z. O'

LE
IN

RE
N
EXISTING CITY

NG
R E G I ST E

EI
RO

IN EE R
HALL

L
E 18557
Exp. 12-31-20
1 1 1
L

L
A
AT E C T R I C

ST

IA
E1.2 E2.0 E3.0
EO RN
F C A LI F O

ISSUE

REV. DESCRIPTION DATE

DD SUBMITTAL 6/28/2018

CITY SUBMITTAL 3/16/2020

KEY PLAN

EXISTING
LIBRARY BLDG.
(NOT IN SCOPE)

PROJECT NO. 17X115.00

PRINT DATE 3/16/2020

DRAWN BY TP

CHECKED BY RO

SHEET TITLE

ELECTRICAL
SITE PLAN
N

W E SHEET NUMBER

S E1.0
ELECTRICAL SITE PLAN 1"=20'-0" 1
CLIENT
GENERAL NOTES

1. ELECTRICAL CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS


PRIOR TO START OF WORK.

2. COORDINATE EXTENT OF WORK WITH OWNER.

3. EXISTING EQUIPMENT WERE TAKEN FROM EXISTING CONDITION OF


THE BUILDING. THE ELECTRICAL CONTRACTOR TO FIELD VERIFY
EXACT LOCATION OF EXISTING CIRCUIT NUMBER; ADJUST AND
1.0 3.1 4.0 UPDATE PANEL SCHEDULE.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND


REMOVING DEVICES, CONDUIT AND WIRE NOT BEING USED WITHIN
REMODEL AREAS. TURN UNUSED BREAKERS TO THE 'OFF' POSITION
AND UPDATE PANEL SCHEDULES AS REQUIRED.

5. REMOVE CONTROL DEVICES OF EXISTING HVAC UNITS, UNLESS


OTHERWISE NOTED.

6. EQUIPMENT TO BE REMOVED SHALL INCLUDE CONDUIT WIRING AND 7822 WALKER STREET
APPURTENANCES BACK TO THE PANEL BOARD OR EXISTING DEVICE
OR FIXTURE TO REMAIN. LA PALMA, CA 90623
7. MAINTAIN CIRCUITS TO THE AREAS DURING CONSTRUCTION.
PROJECT NAME

CITY HALL
A A
HVAC REPLACEMENT
KEY NOTES
PROJECT
1 REMOVE EXISTING DISCONNECT WITH ALL ASSOCIATED CONDUCTORS
ALL THE WAY BACK TO SOURCE. SECURE CONDUIT FOR FUTURE USE
THIS PROJECT.

2 REMOVE EXISTING DISCONNECT WITH ALL ASSOCIATED CONDUCTORS


ALL THE WAY BACK TO SOURCE. ABANDON CONDUIT IN PLACE.

7822 Walker Street


La Palma, CA 90623

CITY PROJECT NO. 17-BLDG-02

ENGINEER/ARCHITECT

A.3 IDS
IDS GROUP
A.4
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800

STAMP

AC
2B
1

AC
2C
1
EF
4
1 STAMP

FE SSION
PR O A
D Z. O'

LE
IN

RE
N

NG
R E G I ST E

EI
RO

IN EE R
L
E 18557
Exp. 12-31-20
L

L
A
AT E C T R I C

ST

IA
AC EO RN
F C A LI F O
2A
1

ISSUE

REV. DESCRIPTION DATE


A.9
DD SUBMITTAL 6/28/2018

CITY SUBMITTAL 3/16/2020


AC
2D
2 B
EF
5
1

B.4
KEY PLAN

B.6

C C
PROJECT NO. 17X115.00

PRINT DATE 3/16/2020

DRAWN BY TP

CHECKED BY RO

SHEET TITLE
1.0 2.0 3.0 4.0
ELECTRICAL
DEMOLITION ROOF PLAN
N

W E SHEET NUMBER

S E1.2
ELECTRICAL DEMOLITION ROOF PLAN 1/4" = 1'-0" 1
CLIENT
GENERAL NOTES
1. NEW EQUIPMENT SHALL BE UL LISTED.

2. CONTRACTOR SHALL REPAIR EXISTING DISTURBED SURFACES TO


MATCH EXISTING CONDITIONS

1.0 3.1 4.0

7822 WALKER STREET


LA PALMA, CA 90623
PROJECT NAME

CITY HALL
A A
HVAC REPLACEMENT
OFFICE OFFICE OFFICE
TOILET STORAGE KEY NOTES
PROJECT
1 3/4" CO TO CEILING SPACE.

FC FC FC FC
CONFERENCE 2 3 4 5 ENTRANCE CONFERENCE 2 3/4" CO TO FIRE ALARM PANEL.
ROOM ROOM
SM SM SM SM
SM

SUPPLIES FC
J J J J J J 7822 Walker Street
T 7
1
CLERICAL/ SM T 1 La Palma, CA 90623
CHAMBERS
FC
1 1 1
6 CITY PROJECT NO. 17-BLDG-02

J T T T ENGINEER/ARCHITECT
FC
1 CORRIDOR 1 T
SM J

IDS
219
SM

J A.3
BC
2 FC
15 EXIST. PANEL 'D' 1 T IDS GROUP
1 T
1 OS T CO2 2
A.4
H-36/38
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
D-31/33 TEL: 949-387-8500, FAX: 949-387-0800
BREAK 1
ROOM J

COPY FC
SM FC SM
ROOM 8 STAMP
20
J J J
H-39/41 EF
S

3
FC SM
1 J FC
14 H-34 19 ENTRANCE
1 T T T 1
J H-35/37 SM
SM

COUNCIL STAMP
CHAMBERS
FE SSION
PR O A
1 D Z. O'
UTILITY'S

LE
IN

RE
N

NG
R E G I ST E

B
TELE./EQUIP. FC

EI
RO

IN EE R
L
& ARCHIVE RM. 18 E 18557
T Exp. 12-31-20
L

L
A
AT E C T R I C

ST

IA
EO RN
NIC F C A LI F O
PUBLIC
LOBBY J
NIC
CORRIDOR SM FC ISSUE
9
REV. DESCRIPTION DATE
A.9
EXIST. PANEL 'C'
DD SUBMITTAL 6/28/2018
EXIST. PANEL '3E' 1
EXIST. PANEL 'H' CITY SUBMITTAL 3/16/2020
EXIST. PANEL 'DA'
H-32 1 OS T CO2 2
H-40/42
1 B
D-35/37
H-36/38
SM MEN'S
DSP

T CO2 TOILET
STORAGE J
J J J
FC J
J
22 SM FC SM SM
SM 17

FC FC
BC 21 16
1 T
1
1 1
STORAGE
1 WORK
T
CUBICLES
B.4 T T

KEY PLAN
RESTROOM
VESTIBULE
OFFICE B.6
FC FC
FC 12 10
1 T FC
T
23 11
SM 1 1
1 SM T T SM
OFFICE

J J J J J
FC SM
WOMEN'S OFFICE WOMEN'S
13 SM
TOILET TOILET
JANITOR'S
CLOSET

C C
PROJECT NO. 17X115.00

PRINT DATE 3/16/2020

DRAWN BY TP

CHECKED BY RO

SHEET TITLE
1.0 2.0 3.0 4.0
HVAC FLOOR
PLAN
N

W E SHEET NUMBER

S E2.0
ELECTRICAL NEW FLOOR PLAN 1/4"=1'-0" 1
CLIENT
GENERAL NOTES
1. ELECTRICAL CONTRACTOR SHALL REFER TO MECHANICAL/PLUMBING AND ARCHITECTURAL
DRAWINGS FOR EXACT LOCATIONS AND CHARACTERISTICS OF EQUIPMENT LISTED IN
SCHEDULE. ANY MODIFICATIONS AND/OR ADDITIONAL WORK NECESSARY SHALL BE
INCLUDED IN THE BASE BID.

2. TEMPERATURE CONTROL AND INTERLOCK CONDUIT AND WIRING SHALL BE BY ELECTRICAL


CONTRACTOR, U.N.O. SEE MECH/PLUMB'G DRAWINGS FOR ALL INFORMATION.

1.0 3.1 4.0 3. ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF CONNECTION POINTS
W/ THE EQUIPMENT INSTALLER PRIOR TO ROUGH-IN.

4. ELECTRICAL CONTRACTOR SHALL PROVIDE LOCAL REMOTE DISCONNECTING MEANS FOR


ELECTRIC HEATING EQUIPMENT IF REQUIRED BY THE LOCAL ELECTRICAL CODE.

5. ELECTRICAL CONTRACTOR SHALL COORDINATE THE ROUTING OF POWER WIRING TO


ROOF-MOUNTED EQUIPMENT WITHIN MECHANICAL PIPE CURB ASSEMBLY. NO SEPARATE
ROOF PENETRATIONS WILL BE PERMITTED. WIRING SHALL BE BELOW THE ROOF IN AN
ACCESSIBLE CEILING SPACE LOCATION.

6. PROVIDE W.P. J-BOX AND SWITCH (ONE SWITCH PER CIRCUIT INDICATED) AND CONNECT TO 7822 WALKER STREET
BUILDING MOUNTED SIGN. VERIFY EXACT LOCATION AND REQUIREMENTS W/ SIGN
CONTRACTOR.
LA PALMA, CA 90623
7. ROOF MOUNTED ELECTRICAL EQUIPMENT SHALL BE NEMA 3R RATED. PROJECT NAME

8. DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED IN ACCORDANCE W/ NEC 430.


CITY HALL
A A
HVAC REPLACEMENT
PROJECT

7822 Walker Street


KEY NOTES
La Palma, CA 90623

1 INSTALL NEW CONDUCTORS IN EXISTING CONDUIT. EXTEND CITY PROJECT NO. 17-BLDG-02
EXISTING CONDUIT TO ACCOMMODATE NEW EQUIPMENT LOCATION
AND POINT OF CONNECTION AS NECESSARY.
ENGINEER/ARCHITECT

NEW
EXHAUST FAN
A.3 IDS
EXIST. PANEL 'D' LOCATED IN 1ST FLR IDS GROUP
A.4
1 PETERS CANYON ROAD, SUITE 130
WP IRVINE, CA. 92606
SM TEL: 949-387-8500, FAX: 949-387-0800
J

100/3/NF
WP STAMP
CU TO DISTRIBUTION PANEL 'DA'
02 SEE SHEET E0.2

STAMP

FE SSION
PR O A
D Z. O'

LE
IN

RE
N

NG
R EG I S T E

EI
RO

I N EE R
L
E 18557
EXIST. PANEL 'DA' LOCATED IN 1ST FLR WP Exp. 12-31-20
EXIST. PANEL 'H' LOCATED IN 1ST FLR L

L
E
H-31 AT E C T R I C
A

ST

A
NI
DOAS EO R
F C A LI F O
1
DOAS
1 WP TO DISTRIBUTION PANEL 'DA'
F

SEE SHEET E0.2


60/3/60AF ISSUE
1
H-33
REV. DESCRIPTION DATE
A.9 D-32 D-30

DD SUBMITTAL 6/28/2018
J
CU
EF SM 01
1
TO DISTRIBUTION PANEL 'DA' WP WP CITY SUBMITTAL 3/16/2020
SEE SHEET E0.2 SM
1 WP WP

100/3/NF
1 B
EF
2

B.4
KEY PLAN

B.6

C C
PROJECT NO. 17X115.00

PRINT DATE 3/16/2020

DRAWN BY TP

CHECKED BY RO

SHEET TITLE
1.0 2.0 3.0 4.0
ELECTRICAL
ROOF PLAN
N

W E SHEET NUMBER

S E3.0
ELECTRICAL ROOF PLAN 1/4"=1'-0" 1